913.2.1 Protection of fire pump rooms and access. Fire pumps shall be located in rooms that are separated from all other areas of the building by 2-hour fire barriers constructed in accordance with Section 707 of the International Building Code or 2-hour horizontal assemblies constructed in accordance with Section 711 of the International Building Code, or both. Fire pump rooms not directly accessible from the outside shall be accessible through an enclosed passageway from an interior exit stairway or exterior exit. The enclosed passageway shall have a fire-resistance rating not less than the fire-resistance rating of the fire pump room (see NFPA 20 Section 4.14.2.1.2).
[Statutory Authority: RCW
19.27.031 and
19.27.074. WSR 22-13-093, § 51-54A-0913, filed 6/14/22, effective 7/1/23.]