(1) Combustion.
(a) Combustion zone temperature. Whenever solid waste is being burned, the temperature of the final combustion zone shall not be below 982°C (1800°F) for a fifteen minute average nor below 871°C (1600°F) for any reading.
(b) Combustion zone residence time. The minimum combustion chamber temperature must be maintained for at least one second (1.0 second) in a zone after the last over fire air has entered the combustion chamber. If over fire air is not used, the combustion chamber shall maintain the minimum combustion temperature or greater for at least one second with all combustion gases. Procedures for determining the residence time shall be a part of the new source review.
(c) Excess air. The combustion gases leaving the final combustion zone must contain at least three percent oxygen measured on a wet basis.
(d) Combustion air distribution and control. The air distribution shall be fully controllable where pressurized air is introduced and the air flow shall be monitored and recorded.
(2) Combustion air. To minimize odor, fugitive emissions and to maintain a negative pressure in the tipping area, the combustion air shall be withdrawn from the tipping area, or shall utilize an equivalent means of odor and fugitive emission control acceptable to ecology or the authority.
(3) Particulate control device temperature. The inlet temperature of the primary particulate control device shall not exceed 177°C (350°F).
(4) Operation. At all times, the owner or operator shall, to the extent practicable, maintain and operate any incinerator facility, including associated air pollution control equipment, in a manner consistent with good air pollution control practice. This may mean that if the emissions limits are being exceeded, no more waste should be fed into the incinerator until the problem is corrected. Determination of whether acceptable operating and maintenance procedures are being used will be based on information available to ecology or the authority which may include, but is not limited to, monitoring and recording results, opacity observations, review of operating and maintenance procedures, and inspection of the source.
[Statutory Authority: RCW
70.94.331 and
70.94.510. WSR 04-01-159 (Order 02-05), § 173-434-160, filed 12/22/03, effective 1/22/04. Statutory Authority: RCW
70.94.331. WSR 90-19-062 (Order 90-10), § 173-434-160, filed 9/17/90, effective 10/18/90. Statutory Authority: Chapter
70.94 RCW. WSR 87-07-041 (Order 86-38), § 173-434-160, filed 3/16/87.]