Test Results Reporting Requirements for Proprietary Treatment Products | |||
Treatment Component/Sequence Category | Testing Results Reported | ||
Category 1 Designed to treat sewage with strength typical of a residential source when septic tank effluent is anticipated to be equal to or less than treatment level E. | Report test results of influent and effluent sampling obtained throughout the testing period for evaluation of constituent reduction for the parameters: CBOD5, and TSS: | ||
□ Average | □ Standard Deviation | ||
□ Minimum | □ Maximum | ||
□ Median | □ Interquartile Range | ||
□ 30-day Average (for each month) | |||
For bacteriological reduction performance, report fecal coliform test results of influent and effluent sampling by geometric mean from samples drawn within thirty-day or monthly calendar periods, obtained from a minimum of three samples per week throughout the testing period. See WAC 246-272A-0130. Test report must also include the individual results of all samples drawn throughout the test period. | |||
Category 2 Designed to treat high-strength sewage when septic tank effluent is anticipated to be greater than treatment level E. | Report all individual test results and full test average values of influent and effluent sampling obtained throughout the testing period for: CBOD5, TSS and O&G. Establish the treatment capacity of the product tested in pounds per day for CBOD5. | ||
(Such as at restaurants, grocery stores, mini-marts, group homes, medical clinics, residences, etc.) | |||
Category 3 Black water component of residential sewage (such as composting and incinerating toilets). | Report test results on all required performance criteria according to the format prescribed in the NSF test protocol described in Table I. | ||
Total Nitrogen Reduction in Categories 1 & 2 (Above) | Report test results on all required performance criteria according to the format prescribed in the test protocol described in Table I. |
Product Performance Requirements for Proprietary Treatment Products | ||||||||
TreatmentComponent/Sequence Category | Product Performance Requirements | |||||||
Category 1 Designed to treat sewage with strength typical of a residential source when septic tank effluent is anticipated to be equal to or less than treatment level E. | Treatment System Performance Testing Levels | |||||||
Level | Parameters | |||||||
CBOD5 | TSS | O&G | FC | TN | ||||
A | 10 mg/L | 10 mg/L | —— | 200/100 ml | —— | |||
B | 15 mg/L | 15 mg/L | —— | 1,000/100 ml | —— | |||
C | 25 mg/L | 30 mg/L | —— | 50,000/100 ml | —— | |||
D | 25 mg/L | 30 mg/L | —— | —— | —— | |||
E | 125 mg/L | 80 mg/L | 20 mg/L | —— | —— | |||
N | —— | —— | —— | —— | 20 mg/L | |||
Values for Levels A - D are 30-day values (averages for CBOD5, TSS, and geometric mean for FC.) All 30-day averages throughout the test period must meet these values in order to be registered at these levels. Values for Levels E and N are derived from full test averages. | ||||||||
Category 2 Designed to treat high-strength sewage when septic tank effluent is anticipated to be greater than treatment level E. | All of the following requirements must be met: | |||||||
(1) All full test averages must meet Level E; and | ||||||||
(Such as at restaurants, grocery stores, mini-marts, group homes, medical clinics, residences, etc.) | (2) Establish the treatment capacity of the product tested in pounds per day for CBOD5. | |||||||
Category 3 Black water component of residential sewage (such as composting and incinerating toilets). | Test results must meet the performance requirements established in the NSF test protocol. | |||||||
Total Nitrogen Reduction in Categories 1 & 2 (Above) | Test results must establish product performance effluent quality meeting Level N, when presented as the full test average. |