| Contaminant | Primary MCLs (mg/L) |
| Antimony (Sb) | | 0.006 |
| Arsenic (As) | | 0.010* |
| Asbestos | | 7 million fibers/liter (longer than 10 microns) |
| Barium (Ba) | | 2.0 |
| Beryllium (Be) | | 0.004 |
| Cadmium (Cd) | | 0.005 |
| Chromium (Cr) | | 0.1 |
| Copper (Cu) | | ** |
| Cyanide (CN) | | 0.2 |
| Fluoride (F) | | 4.0*** |
| Lead (Pb) | | ** |
| Mercury (Hg) | | 0.002 |
| Nitrate (as N) | | 10.0 |
| Nitrite (as N) | | 1.0 |
| Selenium (Se) | | 0.05 |
| Sodium (Na) | | ** |
| Thallium (Tl) | | 0.002 |
| Contaminant | Secondary MCLs (mg/L) |
| Chloride (Cl) | | 250.0 |
| Fluoride (F) | | 2.0*** |
| Iron (Fe) | | 0.3 |
| Manganese (Mn) | | 0.05 |
| Silver (Ag) | | 0.1 |
| Sulfate (SO4) | | 250.0 |
| Zinc (Zn) | | 5.0 |
Note* | Does not apply to TNC systems. |
Note** | Although the state board of health has not established MCLs for copper, lead, and sodium, there is sufficient public health significance connected with copper, lead, and sodium levels to require inclusion in inorganic chemical and physical source monitoring. For lead and copper, the EPA has established distribution system related levels at which a system is required to consider corrosion control. These levels, called "action levels," are 0.015 mg/L for lead and 1.3 mg/L for copper and are applied to the highest concentration in ten percent of all samples collected from the distribution system. The EPA has also established a recommended level of twenty mg/L for sodium as a level of concern for those consumers that may be restricted for daily sodium intake in their diets. |
Note*** | If a water system provides community fluoridation, the level of fluoride and associated requirements are set under WAC 246-290-460. |
TABLE 6
PHYSICAL CHARACTERISTICS
Contaminant | Secondary MCLs |
Color | 15 Color Units |
Specific Conductivity | 700 umhos/cm |
Total Dissolved Solids (TDS) | 500 mg/L |
(b) Compliance with the MCLs, except for nitrate and nitrite, in this subsection is determined by a running annual average at each sampling point. The system will not be considered in violation of the MCL until it has completed one year of quarterly sampling and at least one sampling point is in violation of the MCL. If one sampling point is in violation of the MCL, the system is in violation of the MCL.
(i) If any sample will cause the running annual average to exceed the MCL at any sampling point, the system is out of compliance with the MCL immediately.
(ii) If a system fails to collect the required number of samples, compliance will be based on the total number of samples collected.
(iii) If a sample result is less than the detection limit, zero will be used to calculate the running annual average.
(c) Compliance with the MCLs for nitrate and nitrite is determined based on one sample if the levels of these contaminants are below the MCLs as determined under Table 5 of this section. If the levels of nitrate or nitrite exceed the MCLs in the initial sample, a confirmation sample is required under 40 C.F.R. 141.23 (f)(2), and compliance shall be determined based on the average of the initial and confirmation samples.
(4) Disinfection byproducts.
(a) The department shall consider standards under this subsection as primary standards. The MCLs in this subsection apply to monitoring required by WAC
246-290-300(6) and 40 C.F.R. 141.620 - 629.
(b) The MCLs for disinfection byproducts are as follows:
TABLE 7
DISINFECTION BYPRODUCTS
Disinfection Byproduct | MCL (mg/L) |
Total Trihalomethanes (TTHMs) | | 0.080 |
Haloacetic acids (five) (HAA5) | | 0.060 |
Bromate | | 0.010 |
Chlorite | | 1.0 |
(c) Whether a system has exceeded the disinfection byproduct MCLs shall be determined in accordance with 40 C.F.R. 141.133. Beginning on the dates specified for compliance in 40 C.F.R. 141.620(c), compliance with the TTHMs and HAA5 MCLs shall be based on the LRAAs as required by 40 C.F.R. 141.64 (b)(2) and 40 C.F.R. 141.620(d). Compliance with the bromate and chlorite MCL will continue to be determined in accordance with 40 C.F.R. 141.133.
(5) Disinfectant residuals.
(a) The department shall consider standards under this subsection primary standards. The MRDLs in this subsection apply to monitoring required by WAC
246-290-300(6).
(b) The MRDL for disinfectants is as follows:
TABLE 8
DISINFECTANT RESIDUAL MRDLs
Disinfectant Residual | MRDL (mg/L) |
Chlorine | | 4.0 (as C12) |
Chloramines | | 4.0 (as C12) |
Chlorine Dioxide | | 0.8 (as C1O2) |
(c) Whether a system has exceeded MRDLs shall be determined in accordance with 40 C.F.R. 141.133.
(6) Radionuclides.
(a) The department shall consider standards under this subsection primary standards.
(b) The MCLs for radium-226 and radium-228, gross alpha particle activity, beta particle and photon radioactivity, and uranium shall be as listed in 40 C.F.R. 141.66.
(7) Organic chemicals.
(a) The department shall consider standards under this subsection primary standards.
(b) VOCs.
(i) The MCLs for VOCs are as follows:
Contaminant | Chemical Abstract Service (CAS) Number | MCL (ppb) |
Vinyl chloride | 75–01–4 | 2 |
Benzene | 71–43–2 | 5 |
Carbon tetrachloride | 56–23–5 | 5 |
1,2-Dichloroethane | 107–06–2 | 5 |
Trichloroethylene | 79–01–6 | 5 |
para-Dichlorobenzene | 106–46–7 | 75 |
1,1-Dichloroethylene | 75–35–4 | 7 |
1,1,1-Trichloroethane | 71–55–6 | 200 |
cis-1,2-Dichloroethylene | 156–59–2 | 70 |
1,2-Dichloropropane | 78–87–5 | 5 |
Ethylbenzene | 100–41–4 | 700 |
Monochlorobenzene | 108–90–7 | 100 |
o-Dichlorobenzene | 95–50–1 | 600 |
Styrene | 100–42–5 | 100 |
Trichloroethane | 127–18–4 | 5 |
Toluene | 108–88–3 | 1,000 |
trans-1,2-Dichloroethylene | 156–60–5 | 100 |
Xylenes (total) | 1330–20–7 | 10,000 |
Dichloromethane | 75–09–2 | 5 |
1,2,4-Trichlorobenzene | 120–82–1 | 70 |
1,1,2-Trichloroethane | 79–00–5 | 5 |
(ii) The department shall determine compliance with this subsection based on compliance with 40 C.F.R. 141.24(f).
(c) SOCs.
(i) MCLs for SOCs shall be as listed in 40 C.F.R. 141.61(c).
(ii) The department shall determine compliance with this subsection based on compliance with 40 C.F.R. 141.24(h).
(8) Other contaminants.
The state board of health shall determine state MCLs for any additional contaminants as described in WAC
246-290-315 (5) through (8).
[Statutory Authority: RCW
43.20.050,
70A.125.080, and
70A.130.010. WSR 21-23-097, § 246-290-310, filed 11/17/21, effective 1/1/22. Statutory Authority: RCW
43.20.050 and
70.119A.080. WSR 17-01-062, § 246-290-310, filed 12/14/16, effective 1/14/17. Statutory Authority: RCW
43.20.050. WSR 09-21-045, § 246-290-310, filed 10/13/09, effective 1/4/10. Statutory Authority: RCW
70.119A.180 and
43.20.050. WSR 08-03-061, § 246-290-310, filed 1/14/08, effective 2/14/08. Statutory Authority: RCW
43.20.050 and
70.119A.080. WSR 04-04-056, § 246-290-310, filed 1/30/04, effective 3/1/04. Statutory Authority: RCW
43.20.050 (2) and (3) and
70.119A.080. WSR 03-08-037, § 246-290-310, filed 3/27/03, effective 4/27/03. Statutory Authority: RCW
43.02.050 [43.20.050]. WSR 99-07-021, § 246-290-310, filed 3/9/99, effective 4/9/99. Statutory Authority: RCW
43.20.050. WSR 94-14-001, § 246-290-310, filed 6/22/94, effective 7/23/94; WSR 93-08-011 (Order 352B), § 246-290-310, filed 3/25/93, effective 4/25/93; WSR 92-04-070 (Order 241B), § 246-290-310, filed 2/4/92, effective 3/6/92. Statutory Authority: Chapter
43.20 RCW. WSR 91-07-031 (Order 150B), § 246-290-310, filed 3/15/91, effective 4/15/91. Statutory Authority: RCW
43.20.050. WSR 91-02-051 (Order 124B), recodified as § 246-290-310, filed 12/27/90, effective 1/31/91. Statutory Authority: P.L. 99-339. WSR 89-21-020 (Order 336), § 248-54-175, filed 10/10/89, effective 11/10/89. Statutory Authority: RCW
34.04.045. WSR 88-05-057 (Order 307), § 248-54-175, filed 2/17/88. Statutory Authority: RCW
43.20.050. WSR 83-19-002 (Order 266), § 248-54-175, filed 9/8/83.]