Degree of Hazard | Application Condition | Appropriate Approved Backflow Preventer |
High health cross-connection hazard | Backsiphonage or backpressure backflow | AG, RPBA, or RPDA |
Low cross-connection hazard | Backsiphonage or backpressure backflow | AG, RPBA, RPDA, DCVA, or DCDA |
(b) Premises isolation requirements.
(i) The purveyor shall ensure that an approved air gap, RPBA, or RPDA is installed for premises isolation for service connections to premises posing a high health cross-connection hazard including, but not limited to, those premises listed in Table 13 of this section, except those premises identified as severe in (b)(ii) of this subsection.
(ii) For service connections to premises posing a severe health cross-connection hazard including wastewater treatment plants, radioactive material processing plants, and nuclear reactors, the purveyor shall ensure that either an:
(A) Approved air gap is installed for premises isolation; or
(B) Approved RPBA or RPDA is installed for premises isolation in combination with an in-plant approved air gap.
(iii) If the purveyor's CCS determines that no hazard exists for a connection serving premises of the type listed in Table 13 of this section, the purveyor may grant an exception to the premises isolation requirements of (b)(i) of this subsection.
(iv) The purveyor shall document, on a case-by-case basis, the reasons for granting an exception under (b)(i) of this subsection and include the documentation in the cross-connection control program annual summary report required in subsection (8) of this section.
TABLE 13 (formerly codified as TABLE 9)
SEVERE* AND HIGH HEALTH CROSS-CONNECTION HAZARD PREMISES REQUIRING PREMISES ISOLATION BY AG OR RPBA
Agricultural (farms and dairies) |
Beverage bottling plants |
Car washes |
Chemical plants |
Commercial laundries and dry cleaners |
Premises where both reclaimed water and potable water are provided |
Film processing facilities |
Food processing plants |
Hospitals, medical centers, nursing homes, veterinary, medical and dental clinics, and blood plasma centers |
Premises with separate irrigation systems using the purveyor's water supply and with chemical addition+ |
Laboratories |
Metal plating industries |
Mortuaries |
Petroleum processing or storage plants |
Piers and docks |
Radioactive material processing plants or nuclear reactors* |
Survey access denied or restricted |
Wastewater lift stations and pumping stations |
Wastewater treatment plants* |
Premises with an unapproved auxiliary water supply interconnected with the potable water supply |
+ | For example, parks, playgrounds, golf courses, cemeteries, estates, etc. |
* | RPBAs for connections serving these premises are acceptable only when used in combination with an in-plant approved air gap; otherwise, the purveyor shall require an approved air gap at the service connection. |
(c) Backflow protection for single-family residences.
(i) For single-family residential service connections, the purveyor shall comply with the premises isolation requirements of (b) of this subsection when applicable.
(ii) If the requirements of (b) of this subsection do not apply and the requirements specified in subsection (2)(g)(ii) of this section are met, the purveyor may rely on backflow protection provided at the point of hazard in accordance with WAC
51-56-0600 of the UPC for hazards such as, but not limited to:
(A) Irrigation systems;
(B) Swimming pools or spas;
(C) Ponds; and
(D) Boilers.
For example, the purveyor may accept an approved AVB on a residential irrigation system, if the AVB is properly installed under the UPC.
(d) Backflow protection for fire protection systems.
(i) Backflow protection is not required for residential flow-through or combination fire protection systems constructed of potable water piping and materials.
(ii) For service connections with fire protection systems other than flow-through or combination systems, the purveyor shall ensure that backflow protection consistent with WAC
51-56-0600 of the UPC is installed. The UPC requires minimum protection as follows:
(A) An RPBA or RPDA for fire protection systems with chemical addition or using unapproved auxiliary water supply; and
(B) A DCVA or DCDA for all other fire protection systems.
(iii) For connections made on or after April 9, 1999, the purveyor shall ensure that backflow protection is installed before water service is provided.
(iv) For existing fire protection systems:
(A) With chemical addition or using unapproved auxiliary supplies, the purveyor shall ensure that backflow protection is installed within ninety days of the purveyor notifying the consumer of the high health cross-connection hazard or in accordance with an alternate schedule acceptable to the purveyor.
(B) Without chemical addition, without on-site storage, and using only the purveyor's water (i.e., no unapproved auxiliary supplies on or available to the premises), the purveyor shall ensure that backflow protection is installed in accordance with a schedule acceptable to the purveyor or at an earlier date if required by the code official administering the State Building Code as defined in chapter
51-04 WAC.
(C) When establishing backflow protection retrofitting schedules for fire protection systems that have the characteristics listed in (d)(iv)(B) of this subsection, the purveyor may consider factors such as, but not limited to, impacts of assembly installation on sprinkler performance, costs of retrofitting, and difficulty of assembly installation.
(e) Purveyors may require approved backflow preventers commensurate with the degree of hazard as determined by the purveyor to be installed for premises isolation for connections serving premises that have characteristics such as, but not limited to, the following:
(i) Complex plumbing arrangements or plumbing potentially subject to frequent changes that make it impracticable to assess whether cross-connection hazards exist;
(ii) A repeated history of cross-connections being established or reestablished; or
(iii) Cross-connection hazards are unavoidable or not correctable, such as, but not limited to, tall buildings.
(5) Approved backflow preventers.
(a) The purveyor shall ensure that all backflow prevention assemblies relied upon by the purveyor are models included on the current list of backflow prevention assemblies approved for use in Washington state. The current approved assemblies list is available from the department upon request.
(b) The purveyor may rely on testable backflow prevention assemblies that are not currently approved by the department, if the assemblies:
(i) Were included on the department or USC list of approved backflow prevention assemblies at the time of installation;
(ii) Have been properly maintained;
(iii) Are commensurate with the purveyor's assessed degree of hazard; and
(iv) Have been inspected and tested at least annually and have successfully passed the annual tests.
(c) The purveyor shall ensure that an unlisted backflow prevention assembly is replaced by an approved assembly commensurate with the degree of hazard, when the unlisted assembly:
(i) Does not meet the conditions specified in (b)(i) through (iv) of this subsection;
(ii) Is moved; or
(iii) Cannot be repaired using spare parts from the original manufacturer.
(d) The purveyor shall ensure that AVBs meet the definition of approved atmospheric vacuum breakers as described in WAC
246-290-010.
(6) Approved backflow preventer installation.
(a) The purveyor shall ensure that approved backflow preventers are installed in the orientation for which they are approved (if applicable).
(b) The purveyor shall ensure that approved backflow preventers are installed in a manner that:
(i) Facilitates their proper operation, maintenance, inspection, in-line testing (as applicable), and repair using standard installation procedures acceptable to the department such as those in the USC Manual or PNWS-AWWA Manual;
(ii) Ensures that the assembly will not become submerged due to weather-related conditions such as flooding; and
(iii) Ensures compliance with all applicable safety regulations.
(c) The purveyor shall ensure that approved backflow assemblies for premises isolation are installed at a location adjacent to the meter or property line or an alternate location acceptable to the purveyor.
(d) When premises isolation assemblies are installed at an alternate location acceptable to the purveyor, the purveyor shall ensure that there are no connections between the point of delivery from the public water system and the approved backflow assembly, unless the installation of the connection meets the purveyor's cross-connection control requirements and is specifically approved by the purveyor.
(e) The purveyor shall ensure that approved backflow preventers are installed in accordance with the following time frames:
(i) For connections made on or after April 9, 1999, the following conditions shall be met before service is provided:
(A) The provisions of subsection (3)(d)(ii) of this section; and
(B) Satisfactory completion of the requirements of subsection (7) of this section.
(ii) For existing connections where the purveyor identifies a high health cross-connection hazard, the provisions of (3)(d)(ii) of this section shall be met:
(A) Within ninety days of the purveyor notifying the consumer of the high health cross-connection hazard; or
(B) In accordance with an alternate schedule acceptable to the purveyor.
(iii) For existing connections where the purveyor identifies a low cross-connection hazard, the provisions of subsection (3)(d)(ii) of this section shall be met in accordance with a schedule acceptable to the purveyor.
(f) The purveyor shall ensure that bypass piping installed around any approved backflow preventer is equipped with an approved backflow preventer that:
(i) Affords at least the same level of protection as the approved backflow preventer that is being bypassed; and
(ii) Complies with all applicable requirements of this section.
(7) Approved backflow preventer inspection and testing.
(a) For backflow preventers that protect the public water system, the purveyor shall ensure that:
(i) A CCS inspects backflow preventer installations so that protection is provided commensurate with the assessed degree of hazard;
(ii) Either a BAT or CCS inspects:
(A) Air gaps installed in lieu of approved backflow prevention assemblies for compliance with the approved air gap definition; and
(B) Backflow prevention assemblies for correct installation and approval status.
(iii) A BAT tests approved backflow prevention assemblies for proper operation.
(b) The purveyor shall ensure that inspections and/or tests of approved air gaps and approved backflow assemblies that protect the public water system are conducted:
(i) When any of the following occur:
(A) Upon installation, repair, reinstallation, or relocation of an assembly;
(B) Upon installation or replumbing of an air gap;
(C) After a backflow incident involving the assembly or air gap; and
(ii) Annually thereafter, unless the purveyor requires more frequent testing for high hazard premises or for assemblies that repeatedly fail.
(c) The purveyor shall ensure that inspections of AVBs installed on irrigation systems are conducted:
(i) At the time of installation;
(ii) After a backflow incident; and
(iii) After repair, reinstallation, or relocation.
(d) The purveyor shall ensure that approved backflow prevention assemblies are tested using procedures acceptable to the department, such as those specified in the most recently published edition of the USC Manual. When circumstances, such as, but not limited to, configuration or location of the assembly, preclude the use of USC test procedures, the purveyor may allow, on a case-by-case basis, the use of alternate (non-USC) test procedures acceptable to the department.
(e) The purveyor shall ensure that results of backflow prevention assembly inspections and tests are documented and reported in a manner acceptable to the purveyor.
(f) The purveyor shall ensure that an approved backflow prevention assembly or AVB, whenever found to be improperly installed, defective, not commensurate with the degree of hazard, or failing a test (if applicable) is properly reinstalled, repaired, overhauled, or replaced.
(g) The purveyor shall ensure that an approved air gap, whenever found to be altered or improperly installed, is properly replumbed or, if commensurate with the degree of hazard, is replaced by an approved RPBA.
(8) Recordkeeping and reporting.
(a) Purveyors shall keep cross-connection control records for the following time frames:
(i) Records pertaining to the master list of service connections or consumer's premises required in subsection (3)(j)(i) of this section shall be kept as long as the premises pose a cross-connection hazard to the purveyor's distribution system;
(ii) Records regarding inventory information required in subsection (3)(j)(ii) of this section shall be kept for five years or for the life of the approved backflow preventer whichever is shorter; and
(iii) Records regarding backflow incidents and annual summary reports required in subsection (3)(j)(iii) of this section shall be kept for five years.
(b) Purveyors may maintain cross-connection control records in original form or transfer data to tabular summaries.
(c) Purveyors may maintain records or data in any media, such as paper, film, or electronic format.
(d) The purveyor shall complete the cross-connection control program summary report annually. Report forms and guidance on completing the report are available from the department.
(e) The purveyor shall make all records and reports required in subsection (3)(j) of this section available to the department or its representative upon request.
(f) The purveyor shall notify the department, authority having jurisdiction, and local health jurisdiction as soon as possible, but no later than the end of the next business day, when a backflow incident is known by the purveyor to have:
(i) Contaminated the public water system; or
(ii) Occurred within the premises of a consumer served by the purveyor.
(g) The purveyor shall:
(i) Document details of backflow incidents contaminating the public water system on a backflow incident report form available from the department; and
(ii) Include all backflow incident report(s) in the annual cross-connection program summary report referenced in (d) of this subsection, unless otherwise requested by the department.
[Statutory Authority: RCW
43.20.050,
70A.125.080, and
70A.130.010. WSR 21-23-097, § 246-290-490, filed 11/17/21, effective 1/1/22. Statutory Authority: RCW
70.119A.180 and
43.20.050. WSR 08-03-061, § 246-290-490, filed 1/14/08, effective 2/14/08. Statutory Authority: RCW
43.20.050 (2) and (3) and
70.119A.080. WSR 03-08-037, § 246-290-490, filed 3/27/03, effective 4/27/03. Statutory Authority: RCW
43.02.050 [43.20.050]. WSR 99-07-021, § 246-290-490, filed 3/9/99, effective 4/9/99. Statutory Authority: RCW
43.20.050. WSR 91-02-051 (Order 124B), recodified as § 246-290-490, filed 12/27/90, effective 1/31/91. Statutory Authority: P.L. 99-339. WSR 89-21-020 (Order 336), § 248-54-285, filed 10/10/89, effective 11/10/89. Statutory Authority: RCW
34.04.045. WSR 88-05-057 (Order 307), § 248-54-285, filed 2/17/88. Statutory Authority: RCW
43.20.050. WSR 83-19-002 (Order 266), § 248-54-285, filed 9/8/83.]