Development Classification | Minimum Fire Flow Requirement |
| |
Rural | None |
Residential | 500 gallons per minute for 30 minutes |
Commercial and multifamily structures greater than 4000 sq. ft. | 750 gallons per minute for 60 minutes** |
Industrial | 1000 gallons per minute for 60 minutes** |
* ** | Minium flows are in addition to requirements for normal domestic maximum use. Commercial and industrial buildings may be subject to higher flow requirements when evaluated on an individual basis by the local fire protection authority. |
Note: | Minimum standards in most cases require less flow than categories in the guidelines published by the Insurance Services Office (Municipal Survey Service, 160 Water Street, New York, New York 10038) and therefore may not result in lower insurance rates. |