CHAPTER 2.2 SPECIFIC REQUIREMENTS FOR GENERAL HOSPITALS
2.2-2.2 Medical/Surgical Nursing Unit
2.2-2.2.2 Patient Room
2.2-2.2.2.1 Capacity
(1) In new construction, the maximum number of beds per room shall be two.
(2) Where renovation work is undertaken and the present capacity is more than one patient, maximum room capacity shall be no more than the present capacity with a maximum of four patients.
2.2-3.3.3.3 Control Room
2.2-3.3.3.3(2) The room shall be physically separated from the hybrid operating room with walls and a door. A door is not required when the control is built, maintained, and controlled exactly the same as the operating room.
2.2-3.3.4.2 Preoperative Patient Care Area
2.2-3.3.4.2 (2)(b)(ii) Where bays are used, an aisle with a minimum clearance of 6 feet (1.83 meters) independent of the foot clearance between patient stations or other fixed objects shall be provided.
2.2-3.3.4.3 Phase I Postanesthesia Care Unit (PACU)
2.2-3.3.4.3(b) PACU size. A minimum of 1.5 postanesthesia patient care stations or as determined by the functional program per operating room shall be provided.
2.2-3.4.2.1 CT Scanner Room
2.2-3.4.2.1 (1)(b) CT scanner room(s) shall be sized to allow a minimum clearance of 4 feet (122 centimeters) on the patient transfer and foot side of the table and 3 feet (91 centimeters) on nontransfer side of the table.
2.2-3.4.4 Magnetic Resonance Imaging (MRI) Facilities
2.2-3.4.4.2(2) The MRI scanner room(s) shall have a minimum clearance of 4 feet (122 centimeters) on the patient transfer side and foot of the table and 3 feet (91 centimeters) on nontransfer side of the table. The door swing shall not interfere with the patient transfer.
2.2-3.5.2 Interventional Imaging Procedure Room
2.2-3.5.2.2 Ceilings. Ceilings in interventional imaging procedure rooms shall be designed as semirestricted, see 2.1-7.2.3.3(3) for finishes.
2.2-4.2 Pharmacy Service
2.2-4.2.1 General: Until final adoption of USP 797 by either federal or other state programs, facilities may request plan review for conformance to USP 797 with their initial submission to the Department of Health, Construction Review Services.
CHAPTER 2.4 CRITICAL ACCESS HOSPITALS
2.4-1.1 Application
2.4-1.1 Application. Chapter 2.4 contains specific requirements for small rural hospitals. The functional program for these facilities must clearly describe a scope of services that is appropriate for chapter 2.4. For facilities with services that are not appropriately addressed in chapter 2.4, the appropriate portions of chapters 2.2, 2.3, 2.5, 2.6 and 2.7 will apply.
CHAPTER 3.1 OUTPATIENT FACILITIES
*3.1-3.2.2 General Purpose Examination/Observation Room
3.1-3.2.2.2 Space requirements
(3) Existing general purpose examination rooms under review for addition to a hospital license shall be no less than 80 gross square feet and provide a minimum 2'-6" clearance around the examination table.
3.1-3.2.3 Special Purpose Examination Room
3.1-3.2.3.2(c) A room arrangement in which an examination table, recliner, bed or chair is placed at an angle, closer to one wall than another or against a wall to accommodate the type of patient being served shall be permitted.
3.1-7.2.2 Architectural Details
3.1-7.2.2.2 Ceiling Height
3.1-7.2.2.2(2)
This subsection is not adopted.
3.1-7.2.3.1 Flooring and Wall Bases
3.1-7.2.3.1(5) The following rooms shall have floor and wall base assemblies that are monolithic and have an integral coved wall base that is carried up the wall a minimum of 6 inches (150 mm) and is tightly sealed to the wall:
(a) Operating rooms;
(b) Interventional imaging rooms, including cardiac catheterization labs;
(c) Cystoscopy, urology and minor surgical procedure rooms;
(d) Endoscopy procedure rooms;
(e) Endoscopy instrument processing rooms;
(f) IV and chemotherapy preparation rooms;
(g) Airborne infection isolation (AII) rooms;
(h) Anterooms to AII and PE rooms, where provided;
(i) Sterile processing rooms.
3.1-8.4.3 Plumbing Fixtures
3.1-8.4.3.1 General
(2) Clearances. Water spouts used in lavatories and sinks shall have clearances adequate to:
(a) avoid contaminating utensils and the contents of carafes, etc.
(b) provide a minimum clearance of 6" from the bottom of the spout to the flood rim of the sink to support proper hand washing asepsis technique without the user touching the faucet, control levers, or the basin.
Appendix Language:
A3.1-8.4.3 Aerator usage on water spouts may contribute to the enhanced growth of waterborne organisms and is not recommended.
CHAPTER 3.2 SPECIFIC REQUIREMENTS FOR PRIMARY CARE OUTPATIENT CENTERS
3.2-1.3 Site
3.2-1.3.2 Parking
This section is not adopted.
CHAPTER 3.5 SPECIFIC REQUIREMENTS FOR FREESTANDING URGENT CARE FACILITIES
3.5-1.1 Application
3.5-1.1 Application. This chapter applies to facilities that provide urgent care to the public but are not freestanding emergency departments. The functional program for the facilities must clearly describe a scope of services that are appropriate for urgent care, as determined by the department.
CHAPTER 3.7 SPECIFIC REQUIREMENTS FOR OUTPATIENT SURGICAL FACILITIES
3.7-1.3 Site
3.7-1.3.2 Parking
This section is not adopted.
3.7-3.6.13.1(2) Location
3.7-3.6.13.1(2) Location. The sterile processing room shall be designed to provide a one-way traffic pattern of contaminated materials/instruments to clean materials/instruments to the sterilizer equipment. Two remotely located doors shall be provided as follows:
(a) Entrance to the contaminated side of the sterile processing room shall be from the semirestricted area.
(b) Exit from the clean side of the sterile processing room to the semirestricted area or to an operating room shall be permitted.
3.7-5.1.2 On-Site Sterilization Facilities
3.7-5.1.2 On-Site Sterilization Facilities. When sterilization occurs on-site, one of the following conditions shall apply:
(1) Outpatient surgical facilities with three or fewer operating rooms where immediate use sterilization occurs on-site shall meet the requirements in Section 3.7-3.6.13 (Sterile Processing Room) or shall meet the requirements of Section 2.1-5.1.
(2) Outpatient surgical facilities with four or more operating rooms, or facilities that do not use immediate use sterilization, shall meet the requirements of Section 2.1-5.1.
CHAPTER 3.9 SPECIFIC REQUIREMENTS FOR ENDOSCOPY FACILITIES
3.9-3.3.2.2 Space Requirements
3.9-3.3.2.2 (2)(b) Where bays are used, an aisle with a minimum clearance of 6 feet (1.83 meters) independent of the foot clearance between patient stations or other fixed objects shall be provided.
CHAPTER 3.11 SPECIFIC REQUIREMENTS FOR PSYCHIATRIC OUTPATIENT CENTERS 3.11-1.3 Site
3.11-1.3.1 Parking
This section is not adopted.
CHAPTER 3.13 MOBILE, TRANSPORTABLE, AND RELOCATABLE UNITS 3.13-1.1 Application
3.13-1.1.1 Unit Types
This section applies to mobile, transportable, and modular structures as defined below. These units can increase public access to needed services.
Mobile mammography units do not require review by the Department of Health, Construction Review Services.
Appendix Language:
A3.13-1.1.1 The facility providing services, including mobile mammography, should review these requirements in consideration of the service offering and the delivery of care model.
3.13-8.6 Safety and Security Systems
3.13-8.6.1 Fire Alarm System
Fire alarm notification shall be provided to the facility while the unit is on-site.
3.13-8.6.1.2 Each mobile unit shall provide fire alarm notification by one of the following methods:
(1) Via an auto-dialer connected to the unit's smoke detectors.
(2) An audible device located on the outside of the unit.
(3) Connection to the building fire alarm system.
Part 4
ANSI/ASHRAE/ASHE Standard 170-2013: Ventilation of Health Care Facilities
Section 7.2 Additional Room Specific Requirements
7.2.3 Combination Airborne Infectious Isolation/Protective Environment (AII/PE) Room
7.2.3 (c)(2)
This section is not adopted.
7.4 Surgery Rooms
7.4.4 Sterile Processing Room. Where a sterile processing room is provided, it shall meet the following requirements:
(a) The airflow design shall provide a "clean to dirty" airflow within the space with supply air provided over the clean area and exhaust provided from the soiled area.
(b) This room shall be positive to adjacent spaces with the exception of operating rooms or positively pressurized procedure rooms.
(c) A minimum of two outside air changes and six total air changes shall be provided.
(d) Two filter banks shall be required: The primary filter shall be MERV 7, the final filter shall be MERV 14.
(e) Room air shall be exhausted to the exterior.
[Statutory Authority: RCW
70.41.030 and C.F.R. 2005, Title 42, Vol. 3, Sec. 482.41. WSR 15-14-001, § 246-320-600, filed 6/17/15, effective 7/18/15. Statutory Authority: Chapter
70.41 RCW. WSR 10-17-120, § 246-320-600, filed 8/18/10, effective 9/18/10; WSR 08-14-023, § 246-320-600, filed 6/20/08, effective 7/21/08.]