This section applies to the handling, storage, and use of flammable liquids with a flash point at or below 199.4°F (93°C). This section does not apply to:
(1) Bulk transportation of flammable liquids;
(2) Storage, handling, and use of fuel oil tanks and containers connected with oil burning equipment;
(3) Storage of flammable liquids on farms.
(4) Liquids without flashpoints that may be flammable under some conditions, such as certain halogenated hydrocarbons and mixtures containing halogenated hydrocarbons;
(5) Mists, sprays, or foams, except flammable aerosols covered in WAC
296-24-33009; or
(6) Installations made in accordance with requirements of the following standards:
(a) National Fire Protection Association Standard for Drycleaning Plants, NFPA No. 32-1970;
(b) National Fire Protection Association Standard for the Manufacture of Organic Coatings, NFPA No. 35-1970;
(c) National Fire Protection Association Standard for Solvent Extraction Plants, NFPA No. 36-1967; or
(d) National Fire Protection Association Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines, NFPA No. 37-1970.
[Statutory Authority: RCW
49.17.010,
49.17.040,
49.17.050,
49.17.060 and 29 C.F.R. 1910 Subpart Z. WSR 14-07-086, § 296-24-33003, filed 3/18/14, effective 5/1/14. Statutory Authority: RCW
49.17.010, [49.17].050 and [49.17].060. WSR 95-22-015, § 296-24-33003, filed 10/20/95, effective 1/16/96. Statutory Authority: Chapter
49.17 RCW. WSR 94-06-068 (Order 93-17), § 296-24-33003, filed 3/2/94, effective 3/1/95; Order 73-5, § 296-24-33003, filed 5/9/73 and Order 73-4, § 296-24-33003, filed 5/7/73.]