In addition to the requirements of NEC 230.70(A), service equipment, subpanels, and similar electrical equipment must be installed so that they are readily accessible and may not be installed in clothes closets, toilet rooms, or shower rooms.
[Statutory Authority: Chapter
19.28 RCW, RCW
19.28.031 and
19.28.251. WSR 19-15-117, § 296-46B-408, filed 7/23/19, effective 8/23/19.]