(8) Ventilation.
(a) A two-inch air space must be left around ceilings and the perimeter of floors, except in doorways;
(b) Foundation ventilators must be at least four inches by six inches;
(c) Vents in the foundation, roof, or gables must be screened and offset.
(9) Exposed metal.
(a) Sparking metal construction cannot be exposed below the tops of walls in storage facilities;
(b) All nails must be blind nailed, countersunk, or nonsparking.