(1) Main line disconnects and car light disconnects shall be located adjacent to the controller when not located in a dedicated machine room. When located in a dedicated room, commercial machine room requirements shall be followed. Main line disconnects shall comply with WAC
296-96-02460.
(2) Access to the motor brake shall have:
(a) A lockable door that is a minimum of 6" x 6" or 36 sq. in.
(b) A "STOP" switch shall be located within reach of the access door.
(c) A light switch and GFCI receptacle shall be located within reach of the access door.
[Statutory Authority: Chapter
70.87 RCW. WSR 21-18-096, § 296-96-02700, filed 8/31/21, effective 10/1/21.]