Exception: | Fixtures and appliances are not required to withstand the dielectric strength test. |
(2) Each commercial coach designed with a 480-volt electrical system must be subjected to a one-minute 1,275-volt dielectric strength test between current-carrying conductors and the coach ground. The test may also be performed at 1,500 volts for one second.
(3) Low-voltage circuit conductors in each commercial coach must withstand the applied potential without electrical breakdown of a one-minute, 500-volt, or a one-second, 600-volt, dielectric strength test. The potential must be applied between live and grounded conductors.
(4) The test is to be performed by the manufacturer and witnessed by the inspector.