(1) Tests to an alteration design must be performed and evaluated by a professional engineer or architect licensed in Washington or by a DAPIA who approved the original design plan.
(2) Test reports must contain the following items:
(a) A description of the methods or standards that applied to the test;
(b) Drawings and a description of the item tested;
(c) A description of the test set-up;
(d) The procedure used to verify the correct load;
(e) The procedure used to measure each condition;
(f) Test data, including applicable graphs and observations of the characteristics and behavior of the item tested;
(g) Engineering data; and
(h) Analysis, comments, and conclusion.
(3) The written test procedures, results, and conclusions must reference the applicable structural alteration design plan.