Safe working load | Proof load |
Up to 20 tons . . . . | 25 percent in excess. |
20-50 tons . . . . | 5 tons in excess. |
Over 50 tons . . . . | 10 percent in excess. |
Proof loads must be applied at the designed maximum and minimum boom angles or radii, or, if this is impracticable, as close to these as practicable. The angles or radii of test must be stated in the certificate of test. Proof loads must be swung as far as possible in both directions. The weight of all auxiliary handling devices must be considered a part of the load.
(3) After satisfactory completion of a unit proof load test the derrick and all component parts thereof must be carefully examined in accordance with the requirements of WAC
296-304-20003(4), as far as applicable.