Note: | This requirement may be met by marking the equipment and entering the results of the tests and the dates of testing onto logs. |
Table 1 A-C Proof-Test Requirements Maximum proof-test current, mA (gloves only) | ||||||
Class of equipment | Proof-test voltage rms V | 267 mm (10.5 in.) glove | 356 mm (14 in.) glove | 406 mm (16 in.) glove | 457 mm (18 in.) glove | |
0 | 5,000 | 8 | 12 | 14 | 16 | |
1 | 10,000 | 14 | 16 | 18 | ||
2 | 20,000 | 16 | 18 | 20 | ||
3 | 30,000 | 18 | 20 | 22 | ||
4 | 40,000 | 22 | 24 |
Table 2 D-C Proof-Test Requirements | |
Class of Equipment | Proof-test voltage |
0 | 20,000 |
1 | 40,000 |
2 | 50,000 |
3 | 60,000 |
4 | 70,000 |
Note: The d-c voltages listed in this table are not appropriate for proof testing rubber insulating line hose or covers. For this equipment, d-c proof-tests must use a voltage high enough to indicate that the equipment can be safely used at the voltages listed in Table 3. See ASTM D 1050-90 and ASTM D 1049-88 for further information on proof tests for rubber insulating line hose and covers. |
Table 3 Glove Tests-Water Level1, 2 | ||||
A-C proof-test | D-C proof-test | |||
Class of glove | mm. | in. | mm. | in. |
0 | 38 | 1.5 | 38 | 1.5 |
1 | 38 | 1.5 | 51 | 2.0 |
2 | 64 | 2.5 | 76 | 3.0 |
3 | 89 | 3.5 | 102 | 4.0 |
4 | 127 | 5.0 | 153 | 6.0 |
1The water level is given as the clearance from the cuff of the glove to the water line, with a tolerance of 13 mm. (0.5 in.). | ||||
2If atmospheric conditions make the specified clearances impractical, the clearances may be increased by a maximum of 25 mm. (1 in.) |
Table 4 Rubber Insulating Equipment Voltage Requirements | |||||
Class of equipment | Maximum use voltage1 a-c-rms | Retest voltage2 a-c-rms | Retest voltage2 d-c-rms | ||
0 | 1,000 | 5,000 | 20,000 | ||
1 | 7,500 | 10,000 | 40,000 | ||
2 | 17,000 | 20,000 | 50,000 | ||
3 | 26,500 | 30,000 | 60,000 | ||
4 | 36,000 | 40,000 | 70,000 | ||
Note: Rubber gloves must only be used on voltages of 5000 volts phase to phase or less. | |||||
1The maximum use voltage is the a-c voltage (rms) classification of the protective equipment that designates the maximum nominal design/voltage of the energized system that may be safely worked. The nominal voltage design is equal to the phase-to-phase voltage on multiphase circuits. However, the phase-to-ground potential is considered to be the nominal design/voltage: | |||||
(a) If there is no multiphase exposure in a system area and if the voltage exposure is limited to the phase-to-ground potential, or | |||||
(b) If the electrical equipment and devices are insulated or isolated or both so that the multiphase exposure on a grounded wye circuit is removed. | |||||
2The proof-test voltage must be applied continuously for at least one minute, but no more than three minutes. |
Table 5 Rubber Insulating Equipment Test Intervals | |
Type of equipment | When to test |
Rubber insulating line hose | Upon indication that insulating value is suspect |
Rubber insulating covers | Upon indication that insulating value is suspect |
Rubber insulating blankets | Before first issue and every 12 months thereafter |
Rubber insulating gloves | Before first issue and every 6 months thereafter |
Rubber insulating sleeves | Before first issue and every 12 months thereafter |