| Aboveground | Underground |
(i) Uninsulated | 56% | 58% |
(ii) Insulated | 57% |
(iii) DOT containers must be filled according to DOT regulations.
This corresponds to 82% by volume at -28°F, 85% by volume at 5°F, 87.5% by volume at 30°F, and 90.6% by volume at 60°F.
(2) When containers are filled according to liquid level by any gauging method other than a fixed length dip tube gauge, each container must have a thermometer well so that the internal liquid temperature can be easily determined and the amount of liquid and vapor in the container corrected to a 60°F basis.