Note: | Discharged to a safe location could be a: |
| 1. Safe location outside the building; |
| OR |
| 2. Closed, properly vented salvage tank or tanks that can hold more than the dip tank. |
(3) The employer must make sure the bottom of the overflow pipe is at least six inches (15.2 cm) below the top of the tank.
Note: | The overflow pipe should be large enough to remove water applied to the liquid surface of the dip tank from automatic sprinklers or other sources in the event of fire. Smaller dip tanks should be equipped with overflow pipes, if practical. |
[Statutory Authority: RCW
49.17.010,
49.17.040,
49.17.050, and
49.17.060. WSR 20-21-091, § 296-307-45510, filed 10/20/20, effective 11/20/20; WSR 03-10-068, § 296-307-45510, filed 5/6/03, effective 8/1/03.]