Reference: | Requirements for standard railings and toeboards are in Railing, toeboards, and cover specifications, WAC 296-24-75011, the General Safety and Health Standards, chapter 296-24 WAC. |
(3) You must make sure the top rung or step of the ladder is level with the landing served by the ladder.
(4) You must make sure the spacing from the landing platform to the first rung below the platform of a through ladder is the same as the rung spacing of the ladder.
(5) You must make sure, if two or more separate ladders are used to reach an elevated work area, that the ladders are offset with a platform or landing between them.
EXEMPTION: | A platform or landing is not required when a portable ladder is used to reach a fixed ladder on structures such as utility towers and billboards where the bottom of the fixed ladder is elevated to limit access. |
[Statutory Authority: RCW
49.17.010,
49.17.040,
49.17.050,
49.17.060, and chapter
49.17 RCW. WSR 14-09-095, § 296-876-60060, filed 4/22/14, effective 7/1/14. Statutory Authority: RCW
49.17.010,
49.17.040,
49.17.050,
49.17.060. WSR 06-16-020, § 296-876-60060, filed 7/24/06, effective 12/1/06.]