Class location | Design factor (F) |
1 | 0.72 |
2 | 0.60 |
3 | 0.50 |
4 | 0.40 |
(1) For Class 1 locations a design factor of 0.60 or less must be used in the design formula in 49 C.F.R. Section 195.106 for steel pipe in Class 1 locations that:
(a) Crosses the right of way of an unimproved public road, without a casing;
(b) Crosses without a casing, or makes a parallel encroachment on the right of way of either a hard-surfaced road, a highway, a public street, or a railroad;
(c) Is supported by a vehicular, pedestrian, railroad, or pipeline bridge; or
(d) Is used in a fabricated assembly (including mainline valve assemblies, cross-connections, and river crossing headers).
(2) For Class 2 locations, a design factor of 0.50, or less, must be used in the design formula in 49 C.F.R. Section 195.106 for uncased steel pipe that crosses the right of way of a hard-surfaced road, a highway, a public street, or a railroad.
(3) For Class 1 and Class 2 locations, a design factor of 0.50, or less, must be used in the design formula in 49 C.F.R. Section 195.106 for:
(a) Steel pipe in a pump station; and
(b) Steel pipe (including a pipe riser, on a platform located offshore or in inland navigable waters).