WSR 00-16-132

PROPOSED RULES

BUILDING CODE COUNCIL


[ Filed August 2, 2000, 10:36 a.m. ]

Original Notice.

Preproposal statement of inquiry was filed as WSR 00-03-017.

Title of Rule: Amendment of chapters 51-44 and 51-45 WAC (amendment of the 1997 Edition of the Uniform Fire Code and Fire Code Standards).

Purpose: To consider whether to amend the 1997 Editions of the Uniform Fire Code and Fire Code Standards, Published by the International Fire Code Institute.

Statutory Authority for Adoption: RCW 19.27.031 and 19.27.074.

Statute Being Implemented: Chapters 19.27 and 34.05 RCW.

Summary: The proposed rules include adoption of amendments to the 1997 Uniform Fire Code and Fire Code Standards, including editorial corrections, elimination of conflicting language and improved requirements for fleet fueling and ammonia refrigeration.

Reasons Supporting Proposal: RCW 19.27.031 and 19.27.074.

Name of Agency Personnel Responsible for Drafting and Implementation: Al Rhoades, P.O. Box 48300, Olympia, WA 98504-8300, (360) 586-8999; and Enforcement: Local jurisdictions.

Name of Proponent: Washington State Building Code Council, governmental.

Agency Comments or Recommendations, if any, as to Statutory Language, Implementation, Enforcement, and Fiscal Matters: The council is seeking comments on the issues proposed in the rules shown below.

Rule is not necessitated by federal law, federal or state court decision.

Explanation of Rule, its Purpose, and Anticipated Effects: The proposed rule will amend chapters 51-44 and 51-45 WAC. Chapters 51-44 and 51-45 WAC adopt and amend the 1997 Edition of the Uniform Fire Code (UFC) and the Uniform Fire Code Standards published by the International Fire Code Institute. The purpose is to further amend the 1997 UFC to make editorial corrections and other improvements in the code language. The proposed amendments will provide greater safety and flexibility than the published version for application in Washington state.

     Regulatory Review: In compliance with Executive Order 97-02, regulatory improvement, the following criteria for regulatory review will be considered at the time of final adoption of the rule.

     1. Need. This rule is necessary to comply with the requirements of RCW 19.27.074. The council must regularly review the Uniform Fire Code and Uniform Fire Code Standards, and adopt amendments as deemed appropriate by the council. The purpose and objective of this review, as given in RCW 19.27.020, is to promote the health, safety and welfare of the occupants or users of buildings; to require minimum construction standards for the state of Washington; to permit the use of modern technical methods; to eliminate restrictive, obsolete, conflicting, duplicating and unnecessary regulations; and to provide standards to make buildings accessible to and usable by physically disabled persons. The technical advisory groups appointed by the council have identified rules that are obsolete, duplicative or ambiguous, and have proposed amendments and revisions.

     2. Effectiveness and Efficiency. The mission of the council is to adopt building codes for uniform application throughout the state. In the course of the regular rule review, the council examined regulatory alternatives and new technologies. The council has identified where alternatives can be used effectively and efficiently. The council efficiently achieves uniform state building codes by serving as the central administrative agency for state-wide adoption of building codes.

     3. Clarity. To enhance clarity, only those subsections with a state amendment will be filed under the main section number. The balance of the main section will remain as written in the national uniform code, as adopted by reference, unless otherwise noted.

     4. Intent and Statutory Authority. The proposed rule is consistent with the legislative intent of the statute, chapter 19.27 RCW. The statute gives the council sufficient authority to maintain the State Building Code, and to amend the Uniform Fire Code and Uniform Fire Code Standards.

     5. Coordination. The council rule-making process includes participation by national, state, and local building, fire, mechanical and plumbing officials, as well as state agency representatives for the Departments of Social and Health Services, Health, Labor and Industries, and the State Fire Marshal. The council actively seeks participation from other state agencies to assure that duplication and inconsistency is eliminated.

     6. Cost. The council appointed technical advisory groups and an Economic and Regulatory Assessment Committee to examine the costs and benefits associated with the revisions to the building codes.

     7. Fairness. The state amendments to the Uniform Fire Code proposed by the council are intended to mitigate disproportionate impact on the regulated community. The council is made up of representatives from the regulated community, as well as public and regulatory officials. In addition, the council enlisted the assistance of technical advisory groups, made up of individuals, organizations and businesses impacted by the building codes, to review changes and proposals.

Proposal Changes the Following Existing Rules: The proposed amendments will improve the existing rules by correcting editorial errors and updating code language to allow improved practices to be utilized. The amendments added to the 1997 UFC are as follows:

     1. Section 103.2.1.1: Editorial change to remove unnecessary duplicative language.

     2. Section 105.8: Adds permit requirement to fuel motor vehicles directly from a tank vehicle, or to operate a site where motor vehicles are fueled directly from tank vehicles.

     3. Section 207 – F: Adds definition for Family Child Day Care Home.

     4. Section 216 - O: Editorial changes to coordinate definitions with other proposed changes.

     5. Section 219 - R: Editorial changes to coordinate definitions with other proposed changes.

     6. Section 1007.2.12.10: Deletion of section to remove conflicting language regarding visual alarms.

     7. Section 1007.3.3.3.4: Editorial changes to clarify intent regarding visual alarms.

     8. Section 1102.3.1: Relocation of reference to Department of Ecology WAC for open burning.

     9. Section 1102.4.1: Relocation of reference to Department of Ecology WAC for recreational fires.

     10. Section 1109.8.3: Adds the RCW source reference for an existing amendment.

     11. Section 2501.9.3: Editorial correction of a publishing errata in the 1997 UFC.

     12. Section 2501.9.6.2: Editorial correction of a publishing errata in the 1997 UFC.

     13. Section 2501.17: Deletion of duplicative language contained in Section 1109.8.3 above.

     14. Section 5201.1: Deletes existing language and adds reference to amended Section 7904.5.4.2 below for fueling motor vehicles directly from a tank vehicle.

     15. Section 6106: Removes unnecessary language regarding gas appliances regulated by the mechanical code.

     16. Section 6307.1: When required by the chief an emergency control box for ammonia refrigeration shall be installed per IIAR-2-1992.

     17. Section 6309: Added language for ammonia refrigeration discharge, allowing the chief to require some treatment or a study to show that a hazardous condition will not occur.

     18. Section 7901.2.2: Added definitions applying to the fueling of motor vehicles directly from tank vehicles.

     19. Sections 7904.5.4.2 and 7904.5.4.2.7: Requirements for the fueling of motor vehicles directly from tank vehicles.

     20. Section 7904.5.4.2.2: Editorial changes to improve language.

     21. Section 8001.3.2: Change back to original 1997 UFC language.

     22. Sections 8102.2 and 8102.9 and Table 81-A: Removal of the requirement for small hose valves and stations.

     23. Standard 10-1: An amendment changing the frequency of required inspection and maintenance for fire extinguishers.

A small business economic impact statement has been prepared under chapter 19.85 RCW.

Small Business Economic Impact Statement
The State Building Code Council is proposing to adopt amendments to chapter 51-44 WAC, the 1997 Uniform Fire Code published by the International Fire Code Institute. The council appoints Technical Advisory Groups (TAGs) to conduct a comprehensive review of proposed code amendments. The participants on the Fire Code TAG represent architects, mechanical engineers, fire officials, insurance companies, model code organizations, homebuilders, large commercial organizations, utilities, and state agencies. The Economic and Regulatory Assessment Committee consists of council members as specified in SBCC by-laws.

     Proposed amendments to WAC 51-44-6309, Pressure-relief Discharge of Ammonia Refrigerant, and to WAC 51-44-6307.1 Location of Emergency Control Box, have been identified by the Fire Code TAG and the Economic and Regulatory Assessment Committee as having a cost impact on businesses required to comply with the rule.

     The proposed amendment to 6309 clarifies where the local fire chief has authority to require a containment system for ammonia discharge or to require engineering analysis to show atmospheric discharge is safe. The current rule implies the jurisdiction's authority to require a containment system by reference to industry standards. The amendment gives express authority to the fire chief to determine where an atmospheric release of ammonia refrigerant may reasonably be expected to result in significant concentrations of ammonia which may be hazardous to persons or other premises.

     Cold storage industries would be impacted, where required by the local fire chief to install a containment system or complete an engineering analysis. For an ammonia refrigeration system with an overall cost of $500,000 to $750,000, the containment system would cost about $8,000 to $10,000. According to criteria established by Economic Committee, this represents more than a minor cost impact. The containment system represents between 1% and 2% of the total system cost.

     The cost of the emergency control box is estimated at between $3,000 and $4,000, again assuming an overall system cost $500,000 to $750,000. This represents between 1/2 and 3/4 of 1% of total cost. The Economic Committee criteria designates 1/4 of 1% of total cost or less as "minor cost."

     The cost of containment systems and an emergency control box are proportional to system capacity. Assuming that equivalent system capacities are capable of storing equivalent volume of product, the code amendments would not pose a disproportionate impact on small business. Further, the local fire chief must make a determination based on the industry standards, already in effect. The intent of the current code is to require an emergency control box. Atmospheric release installed according to the standards (ASHRAE 15-1994, IIAR 2-1992) is the general rule. The added costs for containment systems would apply only where a safety hazard exists.

A copy of the statement may be obtained by writing to Tim Nogler, Managing Director, Washington State Building Code Council, P.O. Box 48300, Olympia, WA 98504-8300, phone (360) 586-0486, fax (360) 586-5880.

RCW 34.05.328 does not apply to this rule adoption. The State Building Code Council is not listed in this section as one of the agencies required to comply with this regulation.

Hearing Location: Spokane City Council Chambers, West 808 Spokane Falls Boulevard, Spokane, WA on September 15, 2000, at 10:00 a.m.; and at the Radisson Hotel, 17101 International Boulevard, SeaTac, WA, on October 13, 2000, at 10:00 a.m.

Assistance for Persons with Disabilities: Contact Sue Mathers by September 1, 2000, TDD (360) 753-2200, or (360) 753-1184.

Submit Written Comments to: Judy Wilson, Chairman, State Building Code Council, P.O. Box 48300, Olympia, WA 98504-8300, fax (360) 586-5880, by October 13, 2000.

Date of Intended Adoption: November 17, 2000.

August 2, 2000

Judy Wilson

Chairman

OTS-4186.2


AMENDATORY SECTION(Amending WSR 98-02-053, filed 1/6/98, effective 7/1/98)

WAC 51-44-0103
Section 103 -- Inspection and enforcement.


103.2.1.1 General.      The chief is authorized to administer and enforce this code.      (((Exception: Medical Gas Systems, Section 7404.2.3))) Under the chief's direction, the fire department is authorized to enforce all ordinances of the jurisdiction pertaining to:


     1. The prevention of fires,


     2. The suppression or extinguishment of dangerous or hazardous fires,


     3. The storage, use and handling of hazardous materials,


     4. The installation and maintenance of automatic, manual and other private fire alarm systems and fire-extinguishing equipment,


     5. The maintenance and regulation of fire escapes,


     6. The maintenance of fire protection and the elimination of fire hazards on land and in buildings, structures and other property, including those under construction,


     7. The maintenance of means of egress, and


     8. The investigation of the cause, origin and circumstances of fire and unauthorized releases of hazardous materials.


     For authority related to control and investigation of emergency scenes, see Section 104.

[Statutory Authority: RCW 19.27.031 and 19.27.074.      98-02-053, § 51-44-0103, filed 1/6/98, effective 7/1/98.]


NEW SECTION
WAC 51-44-0105
Section 105.8 -- Permit required.


105.8 f.3 Flammable or combustible liquids. See Article 79.


     1. To use or operate, repair or modify a pipeline for the transportation of flammable or combustible liquids.


     2. To store, handle or use Class I liquids in excess of 5 gallons (18.9 L) in a building or in excess of 10 gallons (37.9 L) outside of a building, except that a permit is not required for the following:

     2.1 The storage or use of Class I liquids in the fuel tank of a motor vehicle, aircraft, motorboat, mobile power plant or mobile heating plant, unless such storage, in the opinion of the chief, would cause an unsafe condition.

     2.2 The storage or use of paints, oils, varnishes or similar flammable mixtures when such liquids are stored for maintenance, painting or similar purposes for a period of not more than 30 days.


     3. To store, handle or use Class II or Class III-A liquids in excess of 25 gallons (94.6 L) in a building or in excess of 60 gallons (227.1 L) outside a building, except for fuel oil used in connection with oil-burning equipment.


     4. To remove Class I or Class II liquids from an underground storage tank used for fueling motor vehicles by any means other than the approved, stationary on-site pumps normally used for dispensing purposes.


     5. To install, construct, alter or operate tank vehicles, equipment, tanks, plants, terminals, wells, fuel-dispensing stations, refineries, distilleries and similar facilities where flammable and combustible liquids are produced, processed, transported, stored, dispensed or used.


     6. To install, alter, remove, abandon, place temporarily out of service or otherwise dispose of a flammable or combustible liquid tank.


     7. To change the type of contents stored in a flammable or combustible liquid tank to a material other than that for which the tank was designed and constructed.


     8. To fuel motor vehicles directly from a tank vehicle, or to operate a site where motor vehicles are fueled directly from tank vehicles.

[]


AMENDATORY SECTION(Amending WSR 98-02-053, filed 1/6/98, effective 7/1/98)

WAC 51-44-0200
Article 2 -- Definitions and abbreviations.


SECTION 206 - E.


ELECTRICAL CODE is the National Electrical Code, promulgated by the National Fire Protection Association, as adopted in chapter 296-46 WAC, or the locally adopted Electrical Code.


SECTION 207 - F.


FAMILY CHILD DAY CARE HOME is a child day care facility, licensed by the state, located in the family abode of the person or persons under whose direct care and supervision the child is placed, for the care of twelve or fewer children, including children who reside at the home.


SECTION 216 - O.


Group E Occupancies:


     Group E Occupancies shall be:


     Division 1. Any building used for educational purposes through the 12th grade by 50 or more persons for more than 12 hours per week or four hours in any one day.


     Division 2. Any building used for educational purposes through the 12th grade by less than 50 persons for more than 12 hours per week or four hours in any one day.


     Division 3. Any building or portion thereof used for day-care purposes for more than six persons.


EXCEPTION: Family child day care homes ((as defined in chapter 51-40 WAC, Uniform Building Code,)) shall be considered Group R, Division 3 Occupancies.

Group LC Occupancies:


     Group LC Occupancies shall be:

     Group LC Occupancies shall include buildings, structures, or portions thereof, used for the business of providing licensed care to clients in one of the following categories regulated by either the Washington Department of Health or the Department of Social and Health Services:

          1. ((Adult family home.

          2.)) Adult residential rehabilitation facility.

          ((3.)) 2. Alcoholism intensive inpatient treatment service.

          ((4.)) 3. Alcoholism detoxification service.

          ((5.)) 4. Alcoholism long term treatment service.

          ((6.)) 5. Alcoholism recovery house service.

          ((7.)) 6. Boarding home.

          ((8.)) 7. Group care facility.

          ((9.)) 8. Group care facility for severely and multiple handicapped children.

          ((10.)) 9. Residential treatment facility for psychiatrically impaired children and youth.


EXCEPTION: Where the care provided at an alcoholism detoxification service is acute care similar to that provided in a hospital, the facility shall be classified as a Group I, Division 1.1 hospital.

Group R Occupancies:


     Group R Occupancies shall be:


     Division 1. Hotels and apartment houses.      Congregate residences (each accommodating more than 10 persons).


     Division 2. Not used.


     Division 3. Dwellings, family child day care homes ((as defined in chapter 51-40 WAC, Uniform Building Code)), adult family homes, and lodging houses.      Congregate residences (each accommodating 10 persons or less).


OPEN BURNING is the burning of a bonfire, rubbish fire or other fire in an outdoor location where fuel being burned is not contained in an incinerator, outdoor fireplace, barbecue grill or barbecue pit.      ((See chapter 173-425 WAC.))


SECTION 219 - R.


RECREATIONAL FIRE is the burning of materials other than rubbish where fuel being burned is not contained in an incinerator, outdoor fireplace, barbecue grill or barbecue pit and with a total fuel area of 3 feet (914 mm) or less in diameter and 2 feet (610 mm) or less in height for pleasure, religious, ceremonial, cooking or similar purposes.      ((See chapter 173-425 WAC.))

[Statutory Authority: RCW 19.27.031 and 19.27.074.      98-02-053, § 51-44-0200, filed 1/6/98, effective 7/1/98.]


AMENDATORY SECTION(Amending WSR 98-02-053, filed 1/6/98, effective 7/1/98)

WAC 51-44-1007
Section 1007 -- Fire alarm systems.


1007.1.3 Where new construction or modification is to be in compliance with adopted chapter 51-40 WAC, Chapter 11, alarm modifications shall be designed to be compatible with the requirements of UFC Article 10.


((1007.2.12.10 Accessible buildings.


1007.2.12.10.1 General.
Alarm systems in buildings which are required to have accessible building facilities shall include both audible and visible alarms.      All devices shall be listed or approved.      The alarm devices shall be located in all accessible sleeping accommodations and common use areas, including toilet rooms and bathing facilities, hallways, and lobbies.


EXCEPTIONS: 1.      Alarm systems in Group I, Division 1.1 and 1.2 Occupancies may be modified to suit standard health care design practice.
2.      Visible alarms are not required in Group R, Division 1 apartment buildings.
1007.2.12.10.2 Alarms.


1007.2.12.10.2.1 Audible alarms. Audible alarms shall produce a sound in accordance with UFC Standard 10-2.      Audible alarms shall exceed the prevailing equivalent sound level in the room or space by at least 15 decibels, or shall exceed any maximum sound level with a duration of 30 seconds by 5 decibels, whichever is louder. Sound levels for alarm signals shall not exceed 120 decibels.


1007.2.12.10.2.2 Visible alarms.      Visible alarm signal appliances shall be integrated into the building or facility alarm system.      All devices shall be listed or approved.      Where single-station audible alarms are provided, single-station visible alarm signals shall be provided.


EXCEPTION: Visible alarms are not required in Group R, Division 1 apartment buildings.

     Visible alarms shall be located per nationally recognized standards.      NFPA 72, 1993 edition, and ANSI 117.1, 1992, shall be considered equivalent facilitation.


1007.2.12.10.2.3 Access to manual fire alarm systems. Manual fire alarm devices shall be mounted at least 36 inches (914.4 mm) and not more than 54 inches (1371.6 mm) above the floor where a parallel approach is provided.      Where a parallel approach cannot be provided the height shall not exceed 48 inches (1219.2 mm).
))


1007.3.3.3.4 Visual alarms. Where provided, alarm systems shall include both audible and visual alarms.      Visual alarm devices shall be located in hotel guest rooms as required by the building code (see UBC Washington State Amendments, Section 1105.4.9); assembly areas; accessible public- and common-use areas, including toilet rooms and bathing facilities; hallways; and lobbies.      (See UBC Washington State Amendments, Section 1106.15.2, for additional information about visual signals.)

[Statutory Authority: RCW 19.27.031 and 19.27.074.      98-02-053, § 51-44-1007, filed 1/6/98, effective 7/1/98.]


NEW SECTION
WAC 51-44-1102
Section 1102 -- Incineration, open burning and commercial barbecue pits.


1102.3.1 General. Open burning shall be conducted in accordance with Section 1102.3. Open burning shall also be conducted as required by other governing agencies regulating emissions. See chapter 173-425 WAC.


EXCEPTION: Recreational fires shall be in accordance with Section 1102.4.

1102.4.1 General. Recreational fires shall be in accordance with Section 1102.4. See also chapter 173-425 WAC.

[]


AMENDATORY SECTION(Amending WSR 98-02-053, filed 1/6/98, effective 7/1/98)

WAC 51-44-1109
Section 1109 -- Control of sources of ignition.


1109.8.3 Religious ceremonies.      Participants in religious ceremonies shall not be precluded from carrying hand-held candles. See RCW 19.27.031(3).

[Statutory Authority: RCW 19.27.031 and 19.27.074.      98-02-053, § 51-44-1109, filed 1/6/98, effective 7/1/98.]


AMENDATORY SECTION(Amending WSR 98-02-053, filed 1/6/98, effective 7/1/98)

WAC 51-44-2500
Article 25 -- Places of assembly.


2501.9.3 Width with Fixed Seats. Aisles in assembly occupancies with fixed seats shall comply with Section 2501.9.3.      The clear width of aisles shall be based on the number of occupants within the portion of the seating areas served by the aisle.


     The clear width of an aisle in inches shall not be less than the occupant load served by the aisle multiplied by 0.3 for aisles with slopes greater than 1 unit vertical to 8 units horizontal (12.5% slope) and not less than 0.2 for aisles with a slope of 1 unit vertical to 8 units horizontal (12.5% slope) or less.      In addition, when the rise of steps in aisles exceeds 7 inches (178 mm), the aisle clear width shall be increased by 1 1/4 inches (32 mm) for each 100 occupants or fraction thereof served for each 1/4 inch (6.35 mm) of riser height above 7 inches (178 mm).


EXCEPTION: For buildings with smoke-protected assembly seating and for which an approved life-safety evaluation is conducted, the minimum clear width of aisles and other means of egress may be in accordance with Table 2501-B.      For Table 2501-B, the number of seats specified must be within a single assembly area, and interpolation shall be permitted between the specified values shown.      If Table 2501-B is used the minimum clear widths shown shall be modified in accordance with the following:

((1.      Factor A: If risers exceed 7 inches (178 mm) in height, multiply the stair width in the tables by factor A, where:

((A

=

1 +

(riser height - 7.0 inches)

5
For SI:

A

=

1 +

(riser height - 178mm)

127))

2.      Factor B: Stairs not having a handrail within a 30-inch (760 mm) horizontal distance shall be 25 percent wider than otherwise calculated.      Multiply by factor B, where B = 1.25.
3.      Factor C: Ramps steeper than 1 unit vertical in 10 units horizontal (10% slope) where used in ascent shall be 10 percent wider than otherwise calculated.      Multiply by factor C, where C = 1.10.

     Where egress is possible in two directions, the width of such aisles shall be uniform throughout their length.


     When aisles converge to form a single path of exit travel, the aisle width shall not be less than the combined required width of the converging aisles.


In assembly rooms with fixed seats arranged in rows, the clear width of aisles shall not be less than set forth above and not less than the following:


     Forty-eight inches (1219 mm) for stairs having seating on both sides.


     Thirty-six inches (914 mm) for stairs having seating on one side.


     Twenty-three inches (584 mm) between a stair handrail and seating when the aisles are subdivided by the handrail.


     Forty-two inches (1067 mm) for level or ramped aisles having seating on both sides.


     Thirty-six inches (914 mm) for level or ramped aisles having seating on one side.


     Twenty-three inches (584 mm) between a stair handrail and seating when an aisle does not serve more than five rows on one side.
))


1.      Where risers exceed 7 inches (178 mm) in height, multiply the stairway width in the tables by factor A, where:

A

=

1 +

(riser height - 7.0 inches)

(4-1)


5

For SI:

A

=

1 +

(riser height - 178 mm)


127

Where risers do not exceed 7 inches (178 mm) in height, A = 1.

2.      Stairways not having a handrail within a 30-inch (762 mm) horizontal distance shall be 25 percent wider than otherwise calculated, i.e., multiply by B = 1.25. For all other stairs, B = 1.
3.      Ramps steeper than 1 unit vertical in 10 units horizontal (10% slope) where used in ascent shall have their width increased by 10 percent, i.e., multiply by C = 1.10. For ramps not steeper than 1 unit vertical in 10 units horizontal (10% slope), C = 1. Where fixed seats are arranged in rows, the clear width of aisles shall not be less than set forth above or less than the following minimum widths:
3.1 Forty-eight inches (1219 mm) for stairways having seating on both sides.
3.2 Thirty-six inches (914 mm) for stairways having seating on one side.
3.3 Twenty-three inches (584 mm) between a stairway handrail and seating where the aisles are subdivided by the handrail.
3.4 Forty-two inches (1067 mm) for level or ramped aisles having seating on both sides.
3.5 Thirty-six inches (914 mm) for level or ramped aisles having seating on one side.
3.6 Twenty-three inches (584 mm) between a stairway handrail and seating where an aisle does not serve more than five rows on one side.

     Where exit access is possible in two directions, the width of such aisles shall be uniform throughout their length. Where aisles converge to form a single path of exit travel, the aisle width shall not be less than the combined required width of the converging aisles.


2501.9.5 Ramp slope. The slope of ramped aisles shall not be more than 1 unit vertical in 8 units horizontal (12.5 percent slope).      Ramped aisles shall have a slip-resistant surface.


EXCEPTION: When provided with fixed seating, theaters may have a slope not steeper than 1 unit vertical to 5 units horizontal (20 percent slope).

2501.9.6.2 When required. Aisles with a slope steeper than 1 unit vertical to 8 units horizontal (12.5 percent slope) shall consist of a series of risers and treads extending across the entire width of the aisle, except as provided in subsection 2501.9.5.


     The height of risers shall not be more than ((7)) 8 inches (((178)) 203 mm) or less than 4 inches (102 mm) and the tread run shall not be less than 11 inches (279 mm).      The riser height shall be uniform within each flight and the tread run shall be uniform throughout the aisle.      Variations in run or height between adjacent treads or risers shall not exceed 3/16 inch (4.8 mm).      A contrasting marking stripe or other approved marking shall be provided on each tread at the nosing or leading edge such that the location of each tread is readily apparent when viewed in descent.      Such stripe shall be a minimum of 1 inch (25.4 mm) wide and a maximum of 2 inches (51 mm) wide.


EXCEPTION: When the slope of aisle steps and the adjoining seating area is the same, the riser heights may be increased to a maximum of 9 inches (229 mm) and may be nonuniform but only to the extent necessitated by changes in the slope of the adjoining seating area to maintain adequate sightlines.      Variations may exceed 3/16 inch (4.8 mm) between adjacent risers provided the exact location of such variations is identified with a marking stripe on each tread at the nosing or leading edge adjacent to the nonuniform riser.      The marking stripe shall be distinctively different from the contrasting marking stripe.

2501.17 Candles and other open-flame devices.      Candles and other open-flame devices shall not be used in places of assembly or in drinking or dining establishments.


EXCEPTIONS: 1.      When used in conjunction with approved heating or cooking appliances in areas not accessible to the public.
2.      When used in conformance with Section 1109.8.
3.      When used in conformance with Section 8203.2.1.8.
((4.      Hand-held candles carried by participants in religious ceremonies.      (See RCW 19.27.031(3).)))

[Statutory Authority: RCW 19.27.031 and 19.27.074.      98-02-053, § 51-44-2500, filed 1/6/98, effective 7/1/98.]


AMENDATORY SECTION(Amending WSR 98-02-053, filed 1/6/98, effective 7/1/98)

WAC 51-44-5200
Article 52 -- Motor vehicle fuel-dispensing stations.


5201.1 Scope. Automotive, marine and aircraft motor vehicle fuel-dispensing stations shall be in accordance with Article 52 and UFC Standard 52-1.      Such operations shall include both public accessible and private operations.      ((Flammable and combustible liquids and LP-gas shall also be in accordance with Articles 79 and 82.


EXCEPTION: Class II or III liquids may be transferred from tank vehicles into fuel tanks of motor vehicles when approved by the chief, and under the following conditions:
1.      Only diesel fuel will be allowed and each premises shall require a separate permit issued in accordance with Section 105,
2.      Tank vehicles shall meet the requirements of the U.S. Department of Transportation (DOT) and UFC Standard 79-4 and as approved by the chief,
3.      The tank vehicle, while in service, shall not be left unattended.      Tank vehicles with fuel in the cargo tank shall not be left unattended,
4.      A fire extinguisher with a classification of 2A-20BC shall be readily available at the fueling site,
5.      There shall be signs stating "NO SMOKING OR OPEN FLAME WITHIN 25 FEET (7620 mm)" readily visible at the fueling site,
6.      There shall be adequate lighting for night time operations,
7.      For other than marine motor vehicles, the fuel hose shall not exceed 50 feet (15 240 mm) in length,
8.      Approved automatic closing nozzles without a latch open device shall be used,
9.      Communication devices shall be available in accordance with Section 5201.6.3,
10.      Tank vehicles shall have emergency shut off valves as approved by the chief,
11.      Dispensing shall be done in accordance with Section 7903.3.3,
12.      At least 20 feet (6096 mm) from any source of ignition,
13.      The applicant shall comply with all applicable federal, state and local environmental laws and regulations as a condition of permit,
14.      The private fueling area shall be located on an area graded in a manner to direct the spill away from buildings, storage and property lines.))

For provisions relating to the transfer of flammable and combustible liquids directly from tank vehicles into the fuel tanks of motor vehicles, see Section 7904.5.4.2.


The storage and use of flammable and combustible liquids and LP-gas shall also be in accordance with Articles 79 and 82.

[Statutory Authority: RCW 19.27.031 and 19.27.074.      98-02-053, § 51-44-5200, filed 1/6/98, effective 7/1/98.]


AMENDATORY SECTION(Amending WSR 98-02-053, filed 1/6/98, effective 7/1/98)

WAC 51-44-6100
Article 61 -- Oil-burning equipment.


SECTION 6102 - GENERAL.


The design, construction and installation of oil-burning equipment shall be in accordance with the Mechanical Code.      Oil-burning equipment shall be of an approved type.      Tanks and piping serving oil-burning equipment which has been out of service for a period of one year shall be removed from the ground or property or abandoned in place in accordance with Section 7902.1.7 of this code.


SECTION 6103 - PERMITS.


A permit is required to remove, abandon, place temporarily out of service or otherwise dispose of a combustible liquids tank.      See Section 105.8, permit f.3.      Such a permit may be issued without an inspection of the tank or premises as otherwise required in Section 105.4.


SECTION 6106 - PORTABLE UNVENTED OIL-BURNING HEATING APPLIANCES ((AND UNVENTED DECORATIVE GAS LOGS AND FIREPLACES)).

6106.1 General.      The design, construction and use of portable unvented oil-burning heating appliances shall be in accordance with Section 6106 and other applicable provisions of this code.


6106.2 Equipment. Portable unvented oil-burning heating appliances shall be listed and shall be limited to a fuel tank capacity of 2 gallons (7.6 L).


EXCEPTION: Appliances approved for temporary use during construction processes are allowed to have a greater fuel tank capacity, provided such capacity does not exceed the terms of the listing of the appliance.

6106.3 Location. The use of listed portable unvented oil-burning heating appliances shall be limited to supplemental heating in Groups S, Divisions 3, 4, and 5 and Group U Occupancies.


EXCEPTIONS: 1. When approved, portable unvented oil-burning heating appliances may be used in any occupancy during construction processes when such use is necessary for the construction and the use does not represent a hazard to life or property.
2.      Approved, unvented portable oil-fueled heaters may be used as a supplemental heat source in any Group B, F-2, M, R or U Occupancy provided that such heaters shall not be located in any sleeping room or bathroom, and shall comply with RCW 19.27A.080, 19.27A.090, 19.27A.100, 19.27A.110, and 19.27A.120.
((3.      Approved, unvented decorative gas logs and decorative fireplaces may be installed, used, maintained and permitted to exist in any Group I or R Occupancy, except bathrooms and bedrooms.      An unvented decorative gas log is a listed natural or liquefied petroleum gas burning log with an open flame consisting of a metal frame or base supporting simulated logs which is designed so that its primary function lies in the aesthetic effect of the logs and flame.      An unvented decorative fireplace is a listed unvented gas log permanently installed in a freestanding enclosure or zero clearance enclosure designed and approved for installation in walls or other building structures.      Unvented decorative gas logs and fireplaces shall:
1.      Be equipped with an approved oxygen-depletion sensor,
2.      Be listed,
3. Not be installed in any room which does not have an alternative primary source of heat,
4.      Have free air volume of at least 50 cubic feet (1.4 m3) for each 1,000 Btu (2.2 mm2/W) of thermal output, and
5.      Be permanently installed.))

6106.4 Fuel.      The grade and type of fuel shall be in accordance with the listing for the appliance.      Storage and handling of fuel shall be in accordance with Article 79.

[Statutory Authority: RCW 19.27.031 and 19.27.074.      98-02-053, § 51-44-6100, filed 1/6/98, effective 7/1/98.]


AMENDATORY SECTION(Amending WSR 98-02-053, filed 1/6/98, effective 7/1/98)

WAC 51-44-6300
Article 63 -- Refrigeration.


SECTION 6301 - SCOPE.


6301.1 This article shall govern the design, installation, construction and repair of refrigeration systems that vaporize and liquefy a fluid during the refrigerating cycle.      Refrigerant piping design and installation, including pressure vessels and pressure relief devices, shall conform to this code.      Permanently installed refrigerant storage systems and other components shall be considered as part of the refrigeration system to which they are attached.


6301.2 Refrigeration unit and system installations having a refrigerant circuit containing more than 220 pounds (100 kg) of Group A1 or 30 pounds (13.6 kg) of any other group refrigerant shall be in accordance with Article 63 and the Mechanical Code.      See the Mechanical Code for refrigerant group descriptions.      See also Sections 8001.1.2 and 8002.


EXCEPTION: The chief is authorized to exempt temporary or portable installations.

6301.3 Refrigeration systems shall comply with the requirements of this code and, except as modified by this code, ASHRAE 15 - 1994.      Ammonia refrigerating systems shall comply with this code and, except as modified by this code, ASHRAE 15 - 1994 and IIAR 2 - 1992.


SECTION 6307 - EMERGENCY CONTROL BOX.


6307.1 Location.
When required by the chief an emergency control box shall be installed per IIAR 2 - 1992.


SECTION 6309 - AMMONIA DISCHARGE.


Ammonia refrigeration discharge systems shall be designed and installed in accordance with ASHRAE 15 - 1994 Section 9.7.8.2, Ammonia Discharge and IIAR 2 - 1992 except as noted in this section. Discharge to atmosphere is allowed unless the chief determines, upon review of the application and submittals, that the facility is located where an atmospheric release may reasonably be expected to result in significant concentrations of ammonia which may be hazardous to persons or other premises.


     The chief may require one of the following:


     1. Water tank containment system consisting of a tank containing one gallon of water for each two (2) pounds of ammonia (4 kg of water for each kilogram of ammonia) that will be released in one hour from the largest relief device connected to the discharge pipe. The water shall be prevented from freezing. The discharge pipe from the pressure-relief device shall distribute ammonia in the bottom of the tank but no lower than 33 feet (10 m) below the maximum liquid level. The tank shall contain the volume of water and ammonia without overflowing.


     2. Other treatment systems that meet the requirements of the authority having jurisdiction.


     3. For atmospheric release, an approved engineering analysis which includes the following information:


     a. The anticipated discharge rate and quantity of ammonia discharged.

     b. Assumed weather conditions, such as wind speed, wind direction, humidity, temperature, and conditions of atmospheric temperature inversion.

     c. Emergency response planning.


     d. Design benefits which would limit discharge
.


EXCEPTION: An emergency discharge is not required for ammonia-water absorption unit systems installed outdoors serving a dwelling unit provided that the discharge is shielded and dispersed.

SECTION 6310 - REFRIGERATION MACHINERY ROOMS.


6310.1 When Required.
Where required by UMC Table 1104.2(1), a machinery room shall be provided to enclose refrigeration systems located indoors.      Access to the machinery room shall be restricted to authorized personnel.      For rooms where occupational exposure could occur, see WAC 269-62-07515 and 296-62-3112.


6310.2 Dimensions. A machinery room shall be dimensioned so as to provide clearances required by UMC Chapter 3.      There shall be clear head room of not less than 7 feet 3 inches (2210 mm).


6310.3 Means of egress. Means of egress shall comply with Uniform Building Code Section 1020 - Special Hazards.

     Each machinery room shall be provided with a minimum of one exit door that opens directly to the outside.


EXCEPTION: Self-closing, tight-fitting doors opening into a vestibule leading directly outside.

6310.4 Refrigerant-vapor Alarms. Machinery rooms shall contain a refrigerant vapor detector with an audible and visual alarm.      The detector, or a sampling tube that draws air to the detector, shall be located in an area where refrigerant vapor from a leak will concentrate.      The alarm shall be actuated at a value not greater than the corresponding TLV - TWA values shown in UMC Table 1104.1.      Detectors and alarms shall be placed in approved locations.


EXCEPTION: Detectors are not required for ammonia systems complying with UMC Section 1106.8.

6310.7 Special Requirements. Open flames that use combustion air from the machinery room shall not be installed in a machinery room.


EXCEPTIONS: 1. Matches, lighters, halide leak detectors and similar devices.
2. Where the refrigerant is carbon dioxide or water.
3. Fuel burning equipment shall not be prohibited in the same machinery room with refrigerant - containing equipment where combustion air is ducted from outside the machinery room and sealed in such a manner as to prevent any refrigerant leakage from entering the combustion chamber, or where a refrigerant vapor detector is employed to automatically shut off the combustion process in the event of refrigerant leakage.
SECTION 6311 - REFRIGERATION MACHINERY ROOM VENTILATION.


6311.1 General.      Machinery rooms shall be mechanically ventilated to the outdoors.      Mechanical ventilation shall be capable of exhausting the minimum quantity of air both at the normal operating and emergency conditions.      Multiple fans or multispeed fans shall be allowed in order to produce the emergency ventilation rate to obtain a reduced airflow for normal ventilation.


EXCEPTION: Where a refrigerating system is located outdoors more than 20 feet (6096 mm) from any building opening and is enclosed by a penthouse, lean - to or other structure, natural or mechanical ventilation shall be provided in accordance with UMC Section 1105.9.

6311.2 Distribution of Ventilation.      Provisions shall be made for supply air to replace that being exhausted.      Openings for supply air shall be located to avoid intake of exhaust air.      Air supply and exhaust ducts to the machinery room shall comply with the provisions of UMC Section 1105.9.


6311.3 Intermittent Control of Ventilation Systems.      Fans providing refrigeration machinery room temperature control or automatic response to refrigerant vapor are allowed to be automatically controlled to provide intermittent ventilation as conditions require.


6311.4 Emergency Control of Ventilation Systems.      Fans providing emergency purge ventilation for refrigerant escape shall have a clearly identified switch of the break-glass type providing on-only control immediately adjacent to and outside of each refrigerant machinery room exit.      Purge fans shall also respond automatically to the refrigerant concentration detection system set to activate the ventilation system at values not greater than the corresponding TLV - TWA values shown in UMC Table 1104.1.      Ventilation equipment in ammonia machinery rooms equipped with a refrigerant vapor detector that will automatically start the ventilation system and actuate an alarm may be set at detection levels which exceed those in UMC Table 1104.1 but such detection level setting shall not exceed 1,000 ppm.      An emergency purge control shall be provided with a manual reset only.


6311.6 Ventilation Discharge.      Exhaust from mechanical ventilation systems shall be discharged 20 feet (6096 mm) or more from a property line or openings into buildings.      Also see Section 6308.


6311.7 Fans. Fans and associated equipment intended to operate the emergency purge of other than Group A1 or Group B1 refrigerants shall meet the requirements for a Class I, Division 1 hazardous location as specified in the Electrical Code.


EXCEPTION: Ammonia machinery rooms.

SECTION 6313 - DETECTION AND ALARM SYSTEMS.


6313.2.1 Alarm.
Refrigerant vapor alarms shall be activated at a value not greater than the corresponding TLV - TWA values shown in UMC Table 1104.1.


EXCEPTION: Alarms in ammonia machinery rooms may be activated by a detector setting not to exceed 1,000 ppm when the activation of the detector will automatically start the ventilation system.

6313.2.2 Automatic shutdown, is not adopted.


SECTION 6314 - REFRIGERATION MACHINERY ROOM EQUIPMENT AND CONTROLS.


6314.4 Emergency Control. A clearly identified switch of the break-glass type providing off-only control of electrically energized equipment and devices within the refrigeration machinery room shall be provided immediately adjacent to and outside of each refrigeration machinery room means of egress.


SECTION 6315 - REFRIGERANT CONTROL VALVES.


6315.2 Support.     
Stop valves installed in copper refrigerant lines of 7/8 inch (22 mm) or less outside diameter shall be securely supported independently of the tubing or piping.


SECTION 6318 - INSTRUCTIONS.


The person in charge of premises on which a refrigeration unit or system is installed shall provide an approved card located in the emergency control box designating:


     1. Instructions for suspending operation of the system in the event of an emergency,


     2. The name, address, and emergency telephone numbers to obtain emergency service,


     3. The name, address, and telephone number of the fire department with instructions to notify the fire department in the event of an emergency,


     4. The names, addresses, and telephone numbers of all corporate, local, state, and federal agencies to be contacted as required in the event of a reportable incident, and,


     5. The location and operation of emergency discharge systems when such systems are required by Article 63.

[Statutory Authority: RCW 19.27.031 and 19.27.074.      98-02-053, § 51-44-6300, filed 1/6/98, effective 7/1/98.]


AMENDATORY SECTION(Amending WSR 98-02-053, filed 1/6/98, effective 7/1/98)

WAC 51-44-7900
Article 79 -- Flammable and combustible liquids.


SECTION 7901.2.2 -- DEFINITIONS - LIMITED APPLICATION.


AUTO START AND STOP NOZZLE is an approved dispensing nozzle that is not capable of dispensing liquid unless the nozzle is in contact with the fuel fill opening of the motor vehicle. The nozzle must be incapable of dispensing liquid until the nozzle has entered the fuel fill opening of the motor vehicle fuel tank. The nozzle will automatically stop dispensing prior to full extracting the nozzle from the fuel tank opening.


MOTOR VEHICLE includes, but is not limited to, a vehicle, machine, tractor, trailer, or semi-trailer, or any combination thereof, propelled or drawn by mechanical power and used upon the highways in the transportation of passengers or property. The term "motor vehicle" also includes freight containers or cargo tanks used, or intended for use, in connection with motor vehicles. For reference, see 49 CFR Pt. 171.8 (October 1994).


REMOTE EMERGENCY SHUT-OFF DEVICE is a device capable of halting the pumping of fuel from the furthest point at which the fuel is being dispensed, but not less than 100 feet.


SECTION 7902 - STORAGE.


7902.1.7.2.4 Tanks abandoned in place.
Tanks abandoned in place shall be abandoned as follows:


     1. Flammable and combustible liquids shall be removed from the tank and connected piping,


     2. The suction, inlet, gage, vapor return and vapor lines shall be disconnected,


     3. The tank shall be filled completely with an approved, inert solid material,


EXCEPTION: Residential heating oil tanks of 1,100 gallons (4,164 L) or less, provided the fill line is permanently capped or plugged, below grade, to prevent refilling of the tank.

     4. Remaining underground piping shall be capped or plugged, and
     5. A record of the tank size, location and date of abandonment shall be retained.


7902.6.8 Leaking tanks. Leaking tanks shall be handled in accordance with WAC 173-360-325.


7902.6.10 Tank lining. Steel tanks are allowed to be lined only for the purpose of protecting the interior from corrosion or providing compatibility with a material to be stored.      Only those liquids tested for compatibility with the lining material are allowed to be stored in lined tanks.      Lining of leaking underground storage tanks shall be done in accordance with the provisions of WAC 173-360-325.


7902.6.15.2 Cathodic protection.      Cathodic protection systems provided for corrosion protection shall be in accordance with recognized standards.      See WAC 173-360-320.


SECTION 7903 - DISPENSING, USE, MIXING AND HANDLING.


7903.4 Solvent Distillation Units.


7903.4.1 General.      Solvent distillation units used to recycle Class I, II or III-A liquids having a distillation chamber capacity of 60 gallons (227.1 L) or less shall be listed, labeled and installed in accordance with Section 7903.4 and nationally recognized standards.      See Article 90, Standard u.1.17.


EXCEPTIONS:

1. Solvent distillation units installed in dry-cleaning plants in accordance with Section 3603.
2. Solvent distillation units used in continuous throughput industrial processes where the source of heat is remotely supplied using steam, hot water, oil or other heat-transfer fluids, the temperature of which is below the auto-ignition point of the solvent(s).
3. Approved research, testing and experimental processes.
Solvent-distillation units used to recycle Class I, II or III-A liquids, having a distillation chamber capacity exceeding 60 gallons (227.1 L) shall be used in locations that comply with the use and mixing requirements of Section 7903 and other applicable provisions in Article 79.


Classes I, II and III-A liquids also classified as unstable (reactive) shall not be processed in solvent-distillation units.


EXCEPTION: Appliances listed for the distillation of unstable (reactive) solvents.

SECTION 7904 - SPECIAL OPERATIONS.


7904.5.4.2 Destination of liquids off loaded from tank vehicles and tank cars.


7904.5.4.2.1 General.
Class I, II or III liquids shall be transferred from a tank vehicle or tank car only into an approved atmospheric tank or approved portable tank, except as provided in Sections 7904.5.4.2.2 through 7904.5.4.2.7.


7904.5.4.2.2 Marine craft and special equipment. Liquids intended for use as motor fuels are allowed to be transferred from tank vehicles into the fuel tanks of marine craft and special equipment ((under the following conditions and)) when approved, and when:


     1. The tank vehicle's specific function is that of supplying fuel to fuel tanks and each premises shall require a separate permit issued in accordance with Section 105,


     2. The operation shall be performed only where the general public has no access or where there is no unusual exposure to life and property,


     3. The dispensing line shall not exceed 50 feet (15 240 mm) in length, and


     4. The dispensing nozzle is approved.


7904.5.4.2.2.1 Vehicle fueling. When approved by the chief, dispensing of motor vehicle fuel from tank vehicles into the fuel tanks of motor vehicles is allowed in accordance with Article 52 and Sections 7904.2 and 7904.5.4.2.((2.))


7904.5.4.2.7 Fueling of motor vehicles from tank vehicles.


7904.5.4.2.7.1 General. The transfer of gasoline or other Class I flammable liquid into the fuel tank of a motor vehicle is prohibited except as provided for in Sections 7904.5.4.2.2 through 7904.5.4.2.6. The transfer of a Class II combustible liquid (e.g., diesel fuel) into the fuel tank of a motor vehicle shall be in accordance with Section 7904.5.4.2.7.


7904.5.4.2.7.2 Permits and plans. See also Section 105.8, Permit f.3. A permit is required:

     1. To transfer fuel into a motor vehicle directly from a tank vehicle.

     2. For any site where fuel is transferred into the fuel tank of a motor vehicle directly from a tank vehicle.


     The following information shall be included with any application for permit to transfer fuel into a motor vehicle from a tank vehicle:

     • License number of each fuel delivery vehicle.

     • Proof of tank vehicle compliance with 49 CFR 178 requirements and inspections. Documentation showing inspection approval of the vehicles by a USDOT registered inspector shall be proof of compliance.

     • An approved Spill Response Plan.


     The following information shall be included with any application to utilize a site for the transfer of fuel into motor vehicles from tank vehicles:


     • A site plan showing all property lines, buildings, facilities, hazardous materials, parking, lighting, fencing, openings into buildings, storm drains, unpaved areas, lanes of egress and the proposed location(s) of fueling.


7904.5.4.2.7.3 Fuel delivery vehicles.


7904.5.4.2.7.3.1 Maintenance. All required equipment, safety features and devices on the fuel delivery vehicle shall be maintained in full working order at all times.


7904.5.4.2.7.3.2 Compliance with USDOT regulations. Fuel delivery vehicles shall comply with all applicable 49 CFR 178 requirements. Documentation from a USDOT registered inspector shall be available for review by the fire department and shall be proof of compliance.


7904.5.4.2.7.3.3 Fuel dispensing hoses. The fueling hose shall not be extended beyond 50 feet.


EXCEPTION: The fueling hose may be extended up to a distance of 125 feet if the operator carries an approved remote emergency shut-off device capable of stopping the flow of fuel. The demonstrated distance by which the remote emergency shut-off reliably operates shall determine the approved hose distance or as denoted by the manufacturer, whichever distance is less. The hose shall be clearly marked at the approved distance. The approved distance marking on the hose shall consist of a band, the length of which shall be a minimum of 12 inches. The marking shall be of contrasting color to the hose.
All pressure hoses and couplings shall be inspected at intervals appropriate to the service. Any hose showing materials deterioration, signs of leakage or weakness in its carcass or at the couplings shall be withdrawn from service and repaired or discarded.

7904.5.4.2.7.3.4 Hose diameter. The inside diameter of the delivery hose shall not exceed 1-1/4 inches.


7904.5.4.2.7.3.5 Spill control equipment. Fuel delivery vehicles shall be equipped with clean-up supplies in accordance with the Department of Ecology's Storm-water Management in Washington State Volume IV Source Control Best Management Practice Number S1.11. Such supplies shall be readily available for employment by the operator at all times.


7904.5.4.2.7.3.6 Nozzle. The dispensing nozzle shall be an approved listed automatic closing type hose nozzle without a latch-open device or an approved auto start and stop nozzle with a latch-open device.


7904.5.4.2.7.3.7 Emergency shut-off valve. The fuel delivery vehicle shall have an approved emergency shut-off valve on the fuel delivery vehicle.


7904.5.4.2.7.3.8 Fire extinguisher. The fuel delivery vehicle shall have a fire extinguisher with a minimum rating of 2A 20BC located in a readily accessible location.


7904.5.4.2.7.4 Operation requirements.


7904.5.4.2.7.4.1 Training. Fuel delivery vehicle operators shall comply with current training and certification requirements in accordance with local, state and federal regulations for handling, dispensing and transporting hazardous materials.


7904.5.4.2.7.4.2 Notification of spills. The fuel delivery vehicle operator shall, without delay, directly notify the fire department via 911 when an unauthorized discharge becomes reportable under state, federal or local regulations or when any spill or accidental release is not contained by spill prevention measures.


7904.5.4.2.7.4.3 Location of attendant during dispensing. The attendant shall be located at the nozzle at all times when fuel is being dispensed.


7904.5.4.2.7.4.4 Signage. Signs stating NO SMOKING or OPEN FLAME WITHIN 25 FEET, or an approved equivalent, shall be visible and readable at the fueling site.


7904.5.4.2.7.4.5 Emergency communication. Each tanker shall have a mobile or portable phone or two-way radio to an attended base.


7904.5.4.2.7.4.6 Warning lights. The fuel delivery vehicle's parking brake and the hazard warning lights shall be activated during fueling operations.


7904.5.4.2.7.4.7 Spill prevention.


7904.5.4.2.7.4.7.1 Overfill and drip protection. Operators shall place a drip pan or absorbent, in good condition, under each fuel fill opening prior to and during all dispensing operations. Drip pans shall be liquid tight. The pan or absorbent shall have a capacity of at least 3 gallons. Spills retained in the drip pan or absorbent pillow need not be reported. Operators, when fueling, shall have on their persons an absorbent pad capable of capturing diesel foam overfills. Except during fueling, the nozzle shall face upwards and an absorbent pad shall be kept under the nozzle to prevent drips. Contaminated absorbent pads shall be disposed of regularly in accordance with local, state and federal requirements.


7904.5.4.2.7.4.7.2 Topping off. Fuel expansion space shall be provided in each motor vehicle tank to prevent overflow. Tanks shall not be topped off. The operator shall cease filling and remove the fill nozzle if the automatic shut-off engages.


7904.5.4.2.7.4.8 Lighting. The operator shall provide lighting that provides clear illumination at the point of fueling. General lighting of the fueling area shall be provided for nighttime fueling.


7904.5.4.2.7.4.9 Vehicle motor shutdown. The vehicle being fueled shall be shut off during fueling operations.


7904.5.4.2.7.4.10 Fuel hoses. At no time shall the fueling hose extend across a trafficable lane without fluorescent traffic cones conspicuously placed so that all vehicle traffic is blocked.

     The fuel hose shall be returned to its storage location on the vehicle prior to repositioning the vehicle. At no time shall the hose be allowed to drag behind the vehicle while it is in motion.


7904.5.4.2.7.5 Site requirements.


7904.5.4.2.7.5.1 Property owner's consent. All persons and parties with an interest in the property (i.e., property owner, lessor, real estate company, property manager as well as operators of the property) must give consent in writing to allow the mobile fueling to occur on the property. Managers, lessees, renters and other persons cannot solely give permission. Each person or party must indicate that they understand the risk of spills.


7904.5.4.2.7.5.2 Location of fueling. The fuel dispensing vehicle and the fueling operation shall be at least 15 feet from all property lines, streets, alleys, public ways, building openings and storm drains.


EXCEPTIONS:

1. The distance to storm drains can be eliminated if an approved storm drain cover or an approved equivalent that will prevent any fuel from reaching the drain is in place prior to fueling or hose being placed within 15 feet of the drain. When placement of a storm drain cover will cause the accumulation of excessive water or difficulty in safely conducting the fueling, it shall not be used and fueling shall not take place within 15 feet of a drain.
2. The distance to storm drains can be eliminated for drains that direct intake to approved oil-water separators.

7904.5.4.2.7.5.3 Sources of ignition. Fuel dispensing is prohibited within 15 feet of any source of ignition.


7904.5.4.2.7.5.4 Access. Mobile fueling operations shall not be performed during times when the public has access to the area unless restricted by remoteness of the property, fencing or other control measures.

[Statutory Authority: RCW 19.27.031 and 19.27.074.      98-02-053, § 51-44-7900, filed 1/6/98, effective 7/1/98.]


AMENDATORY SECTION(Amending WSR 98-02-053, filed 1/6/98, effective 7/1/98)

WAC 51-44-8000
Article 80 -- Hazardous materials.


SECTION 8001 - GENERAL.


8001.3.2 Hazardous materials management plan.      When required by the chief, each application for a permit shall include a hazardous materials management plan (HMMP).      The location of the HMMP shall be posted adjacent to permits when an HMMP is provided.      The HMMP shall include a facility site plan designating the following:


     1. Storage and use areas,


     2. Maximum amount of each material stored or used in each area,


     3. Range of container sizes,


     4. Locations of emergency isolation and mitigation valves and devices,


     5. Product conveying piping containing liquids or gases, other than utility-owned fuel gas lines and low-pressure fuel gas lines,


     6. On and off positions of valves for valves which are of the self-indicating type, and


     7. Storage plan showing the intended storage arrangement, including the location and dimensions of aisles.


     The plans shall be legible and approximately to scale.      Separate distribution systems are allowed to be shown on separate pages.


     See also Appendix II-E.


SECTION 8003 - STORAGE.


8003.3.2.3 Canopies. Portable tanks and cylinders stored outside of buildings shall be stored under a canopy of noncombustible construction.      Such storage shall not be considered indoor storage.      See also Section 8003.1.14.


EXCEPTION: Portable tanks and cylinders used for storing anhydrous ammonia (fertilizer grade).

     An automatic fire-sprinkler system shall be provided for canopies used for storage of highly toxic or toxic compressed gases.


EXCEPTION: Where water is incompatible with the hazardous material stored, the chief may approve alternate fire suppression methods to an automatic sprinkler system.

[Statutory Authority: RCW 19.27.031 and 19.27.074.      98-02-053, § 51-44-8000, filed 1/6/98, effective 7/1/98.]


NEW SECTION
WAC 51-44-8102
Section 8102 -- General fire-protection and life-safety features.


8102.2 Extent and type of protection. Fire-detection systems, smoke and heat removal, curtain boards, and fire sprinkler design densities shall extend the lesser of 15 feet (4572 mm) beyond the high-piled storage area or to a permanent partition. When portions of high-piled storage areas have different fire-protection requirements due to commodity, method of storage or storage height, the fire-protection features required by Table 81-A within this area shall be based on the most restrictive design requirements.


8102.9 Hose connections.


8102.9.1 Fire department hose connections. When exit passageways are required by the building code for egress, a Class I standpipe system shall be provided in accordance with the Building Code. See UBC Standard 9-2.

Place illustration here.

[]

OTS-4198.1


NEW SECTION
WAC 51-45-10100
Standard 10-1 -- Selection, installation, inspection, maintenance and testing of portable fire extinguishers.


4-1.2 The procedure for inspection and maintenance of fire extinguishers varies considerably. Minimal knowledge is necessary to perform a monthly "quick check" or inspection in order to follow the inspection procedure as outlined in Section 4-3. A trained person who has undergone the instructions necessary to reliably perform maintenance and has the manufacturer's service manual shall service the fire extinguishers not more than six years apart, as outlined in Section 4-4.


4-3.1* Frequency. Extinguishers shall be inspected when initially placed in service and thereafter at approximately 30-day (monthly) intervals. Extinguishers shall be inspected at more frequent intervals when circumstances require. Inspection procedures shall be performed in accordance with 4-3.2.


4-3.2 Procedures. Monthly inspection of extinguishers shall include a check of at least the following items:

     (a) Located in designated place.

     (b) No obstructions to access or visibility.

     (c) Operating instructions on nameplate legible and facing outward.

     (d) Seals and tamper indicators not broken or missing.

     (e) Determine fullness by weighing or "hefting."

     (f) Examine for obvious physical damage, corrosion, leakage, or clogged nozzle.

     (g) Pressure gage reading or indicator in the operable range or position.


4-4.1 Frequency. Extinguishers shall be subjected to maintenance not more than six years apart or when specifically indicated by an inspection. Other maintenance and testing frequencies shall be performed in accordance with 4-4 and 4-5. Maintenance procedures shall be performed in accordance with 4-4.2.

[]

© Washington State Code Reviser's Office