WSR 15-17-037 PROPOSED RULES BUILDING CODE COUNCIL [Filed August 12, 2015, 10:46 a.m.]
Original Notice.
Preproposal statement of inquiry was filed as WSR 15-10-079.
Title of Rule and Other Identifying Information: Adoption and amendment of the 2015 International Energy Conservation Code (IECC)/Washington State Energy Code (WSEC) (commercial), chapter 51-11C WAC.
Hearing Location(s): DES Presentation Room, 1500 Jefferson S.E., Olympia, WA 98504, on October 16, 2015, at 10 a.m.
Date of Intended Adoption: November 13, 2015.
Submit Written Comments to: Dave Kokot, Chair, State Building Code Council (SBCC), P.O. Box 41449, Olympia, WA 98504-1449, e-mail sbcc@ga.wa.gov, fax (360) 586-9088, by October 23, 2015.
Assistance for Persons with Disabilities: Contact Peggy Bryden by September 24, 2015, (360) 407-9280.
Purpose of the Proposal and Its Anticipated Effects, Including Any Changes in Existing Rules: The proposed rules adopt the 2015 edition of WSEC (commercial) with amendments to incorporate requirements from the 2015 IECC (commercial), and formatted to the 2015 IECC, to provided [provide] increased clarity and energy efficiency as required in RCW 19.27A.160.
Note: Sections that had no changes are not shown in this filing.
The 2015 WSEC contains several extensive reorganizational items:
Existing Buildings (2015 IECC Change). Provisions for existing buildings have been removed from Section C101.4 and elsewhere in the code and relocated to a new Chapter 5 and broken out into additions, alterations, repairs and change of use. (Proposed State Amendment.) An exception is added to Section C503.3 for air leakage testing of alteration, unless the alteration involves a change in space conditioning. Replacement exterior lighting and parking garage lighting is now addressed in the alterations Section C503.6.
Compliance Options (2015 IECC Change). Section C402.1 was extensively rewritten for the 2015 edition. The IECC added a component performance alternative, in Section C402.1.5, based on Washington's method. This new section replaces the old WSEC language. The prescriptive compliance path is now shown as a number list of items. The exception to C402.1 was moved to the list of exempt equipment buildings shown in C402.1.2. Low energy and semi-heated buildings were also moved into this section as subsections.
Refrigerated Spaces (2015 IECC Change/Proposed State Amendment). The 2015 IECC added requirements equivalent to those found in the 2012 WSEC. The 2015 WSEC relocates all of these requirements to a new Section C410. Duplicative language was removed and language was clarified. Federal efficiency tables were added. Use of the component performance method was clarified.
Economizers (2015 IECC Change/Proposed State Amendment). The 2015 IECC was reorganized to remove the division between simple systems and complex systems. All of the economizer requirements (and exceptions) were moved to C403.3. Much of C403.4 was moved into C403.3. Section C403.4.1.3 moved to C403.3.1 and was integrated into the ASHRAE 90.1 economizer control requirements. New requirements for modulating airflow units from ASHRAE are also added. Section C403.4.1.4 became Section C403.3.2. Section C403.3.1.1 became Section C403.3.3. Section C403.4.1.1 became Section C403.3.4.
Economizer Exceptions: Two new economizer exceptions were added for controlled atmosphere agricultural buildings and buildings utilizing waste heat for space heating or water heating. Exceptions for replacement equipment were moved to Chapter 5. The size limitation of the VRF exception was removed.
Lighting Controls (2015 IECC Change). The 2015 IECC reorganizes the lighting controls section significantly. It is broken into five main topics: Occupant sensors, time switches, manual control, daylight responsive controls and additional controls.
Commissioning (Proposed State Amendment). The term "certified commissioning professional" replaced most instances of "registered design professional" throughout this section. All of the documentation requirements were moved to Section C103.6. Commissioning plan was moved from Section C408.1.1 to C408.1.2 and revised to incorporate ASHRAE 202 requirements, as was the final commissioning report language. The checklist was revised to reflect the new section numbers and titles. System specific sections were revised to clarify exemptions and simplify language. The electrical section scope increased to all systems covered under Section C405.
As well as several new requirements:
DOAS (Proposed State Amendment). New Section C403.2.6.1 mandates dedicated outdoor air systems (DOAS) in certain occupancy types (office, retail, education, libraries and fire stations) to separate the ventilation system and heating/cooling system to reduce fan energy use. Section C403.2.6.1.1 allows the code official to waive this requirement if it is shown to be impractical. Section C403.2.6.1.2 sets fan control requirements for DOAS systems.
Section C406: Additional Efficiency Package Options (2015 IECC Change/Proposed State Amendment). The 2015 IECC revised the requirements for additional efficiency options, adding more options and simplifying the others provided. SBCC determined this would be an efficient, tested method of gaining energy efficiency and incorporated it into WSEC. All buildings are now required to achieve two credits from the available options. Based on the changes made to the LPA tables, the C406 LPA was reduced a further fifteen percent over the C405.2 values.
Controlled Receptacles (Proposed State Amendment). A new requirement was added in Section C405.10 for fifty percent of receptacles to be controlled by time switches or occupancy sensors.
Appendix E: Renewable Energy (Proposed State Amendment). A new appendix is included requiring commercial buildings to provide some type of renewable energy generation or energy recovery. This appendix is not adopted as a statewide requirement, but may be adopted by a local jurisdiction.
Other notable changes include:
Ventilation (Proposed State Amendment). Modification of Section C403.2.6 to limit the amount of outdoor air introduced into the building to reduce the amount of energy needed to heat/cool that air. Exceptions are provided for when needed for specific nonventilation functions, residential buildings, alterations and systems with ERV.
Table C402.1.3 (Proposed State Amendments). Two options are presented for this table. They differ only in the mass wall category. Option 1 uses the value from the 2015 IECC (and 2012 IECC) and deletes the footnote allowing uninsulated walls for some building types. Option 2 also deletes the footnote, but increases the R-value to that of the 2012 Seattle Energy Code. The other change, present in both options, is the additional column to the compliance option for continuous insulation fasteners, increasing the allowable penetrations to 0.12 percent.
Lighting Power Allowance (Proposed State Amendment). Both the building area method and space-by-space method were decreased by twenty percent over those proposed in the integrated draft.
A number of changes were made to update to new ASHRAE 90.1 requirements:
Efficiency tables C403.2.3 (1) through (10), C404.2, C405.8 (1) through (4).
C403.2.3.1, Water-cooled centrifugal chilling packages.
C403.2.3.2, Positive displacement (air- and water-cooled) chilling packages.
C403.2.4.1.3, Setpoint overlap restrictions.
C403.2.4.5, Zone isolation.
C403.2.4.6, Freeze protection systems.
C403.2.4.12, Direct digital control systems.
C403.2.7.1, Kitchen exhaust.
C403.2.11.5, Fan airflow control.
C403.4.1.1, Static pressure sensor location.
C403.4.1.2, Set points for DDC.
C403.4.2.5, Boiler turndown.
C403.4.4, Mechanical systems serving multiple zones.
C403.4.4.3, Multiple zone VAV control.
C404.7.3, Controls for hot water storage.
C405.6, Electrical transformers.
Several sections were moved to accommodate the reorganization (and thus shown as underlined text), but were not changed (or had very minor editorial changes):
Area weighted U-factors moved from C402.3.4 to C402.4.3.4.
Doors moved from C402.2.7 to C402.4.4.
Off hour controls moved from C403.2.4.3 to C403.2.4.2.
Group R-2/R-3 dwelling units moved from C403.2.4.8 to C403.2.4.10.
Group R-2 sleeping units moved from C403.2.4.9 to C403.2.4.11.
Occupancy sensors moved from C403.2.5.2 to C403.2.6.3.
Laboratory exhaust moved from C403.2.5.4.2 to C403.2.7.2.
Manual controls moved from C405.2.1 to C405.2.3.
Area controls moved from C405.2.5 to C405.2.8.
Many changes were minor editorial changes to correlate section references or minor language adjustments:
C101.1, C101.2, C101.3, C108, C402.1, C402.2, C402.2.6, C402.4.1.3, Table C402.4, C403.2.1, C403.2.2, C403.2.3.4, C403.2.4, C403.2.4.5, C405.1, C405.5, C409.1, C409.3.
For a more detailed description of all of the changes, please see SBCC's web site at https://fortress.wa.gov/ga/apps/SBCC/Page.aspx?cid=3119.
A more in-depth analysis can be found on our web site, www.sbcc.wa.gov, or by contacting the office (contact information is noted under the small business/cost-benefit analysis section).
Reasons Supporting Proposal: RCW 19.27.031 and 19.27.074.
Statutory Authority for Adoption: RCW 19.27A.020, 19.27A.025, 19.27A.045, 19.27A.160.
Rule is not necessitated by federal law, federal or state court decision.
Agency Comments or Recommendations, if any, as to Statutory Language, Implementation, Enforcement, and Fiscal Matters: SBCC is seeking comments on the issues proposed in the rules shown below.
Name of Proponent: SBCC, governmental.
Name of Agency Personnel Responsible for Drafting and Implementation: Krista Braaksma, 1500 Jefferson S.E., P.O. Box 41449, Olympia, WA, (360) 407-9278.
A small business economic impact statement has been prepared under chapter 19.85 RCW.
Small Business Economic Impact Statement
Description: SBCC is filing a proposed rule to adopt the updated 2015 edition of IECC with state amendments, known as the 2015 WSEC: Chapters 51-11R and 51-11C WAC. Since 1985 SBCC has been responsible to update new editions of the building code per RCW 19.27.074.
The administrative compliance requirements are under the authority of the local government. RCW 19.27.050. Enforcement activities including permit issuance, plan review and approval, and inspections occur at the local level. Requirements for construction document submittal and other reporting requirements are determined by the local jurisdiction and are consistent with previously established policies. The proposed amendments to chapter 51-51 WAC include specific technical requirements for building construction to be consistent with national standards.
WSEC is updated every three years by SBCC. The code development process conducted by the model code organization is open to all interest groups within the design and construction industry and from governmental organizations. See www.iccsafe.org for more information about the model code development process.
Professional Services: Washington has had a statewide building code in effect since 1974. The local enforcement authority having jurisdiction administers the codes through the building and/or fire departments. Administrative procedures for state building code compliance are established and will not be changed by the adoption of the update to the current building codes. Small businesses will employ the same types of professional services for the design and construction of buildings and systems to comply with the state building code.
The proposed rule updates the state building code and does not require additional equipment, supplies, labor or other services. Services needed to comply with the building code are existing within the construction industry as required by the local authority having jurisdiction.
Costs of Compliance for Businesses: SBCC accepts proposals to amend WSEC to meet the legislative goals. The statewide code amendment proposal process is defined in chapter 51-04 WAC and SBCC bylaws. Proposals must increase the energy efficiency in buildings. Each proponent must identify where a proposed amendment has an economic impact and must quantify costs. SBCC developed a specific set of forms for WSEC, so proponents could identify where a proposed amendment was editorial, technical or a policy change.
SBCC received one hundred fifty-four proposals to improve WSEC. The energy code technical advisory group (TAG) recommended approval of one hundred sixteen amendments as submitted or as modified. Of those, TAG identified twenty-one as editorial corrections, and eighty-seven as technical corrections. The remaining eight proposed amendments were identified by TAG as having a significant cost.
The energy code TAG and the SBCC economic workgroup determined there is a cost for compliance on businesses for the following proposed state amendments. SBCC recommended filing the proposed rule to allow input through the public hearing process. See the preliminary cost-benefit analysis of the 2015 WSEC for a detailed review of each of these amendments.
Loss of Sales or Revenue: The proposed rules make the state code for building construction consistent with national standards. Businesses with new products or updated test or design standards are recognized in the updated building code. For these businesses there will be a gain in sales and revenue.
The results of reduced energy use in buildings include avoiding the need for new power generation, reducing environmental impact, and providing local employment. The legislative findings state that energy efficiency is the cheapest, quickest, and cleanest way to meet rising energy needs, confront climate change, and boost our economy.
Cost of Compliance for Small Businesses: The majority of businesses affected by the updates to the building codes are small businesses; over ninety-five percent of those listed in the construction and related industries have under fifty employees. The costs per employee are comparable between the largest businesses and the majority of small businesses. The cost to comply with the updated codes is not a disproportionate impact on small business. Where SBCC found the cost of compliance for small businesses to be disproportionate, the proposed rule mitigates the cost. The proposed rules include a definition of small business and provide exceptions for compliance with the updated rule.
Small Businesses Involved in the Development of the Rule: SBCC conducted open public meetings of the energy code TAG, available via telephone conference bridge and over the internet, and allowed comment on every item on every agenda. SBCC appointed over one hundred representatives of all segments of the business and construction community to serve on the TAGs.
List of Industries: Below is a list of industries required to comply with the energy code:
Estimate of the Number of Jobs That Will Be Created or Lost: The adoption of the latest code edition is not expected to significantly impact the number of jobs in the construction industry. These rules are likely to be job neutral overall, i.e., they will not result in any job gains or losses. The scheduled effective date of the new edition is July 1, 2016. Building permits issued prior to that date will be vested under the 2012 building code. Permits issued for projects under the 2015 code edition will start with the 2017 construction season.
The construction industry has experienced growth over the period June 2014 to June 2015.
(Data from Current Employment Statistics (CES))
A copy of the statement may be obtained by contacting Tim Nogler, Washington SBCC, P.O. Box 41449, Olympia, WA 98504-1449, phone (360) 407-9280, fax (360) 586-9088, e-mail sbcc@ga.wa.gov.
A cost-benefit analysis is required under RCW 34.05.328. A preliminary cost-benefit analysis may be obtained by contacting Tim Nogler, Managing Director, Washington SBCC, P.O. Box 41449, Olympia, WA 98504-1449, phone (360) 407-9280, fax (360) 586-9088, e-mail sbcc@ga.wa.gov.
August 12, 2015
David F. Kokot
Council Chair
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-10100 Section C101—Scope and general requirements.
C101.1 Title. This code shall be known as the ((International Energy Conservation Code of [NAME OF JURISDICTION])) Washington State Energy Code, and shall be cited as such. It is referred to herein as "this code."
C101.2 Scope. This code applies to commercial buildings and the buildings sites and associated systems and equipment.
C101.3 Intent. This code shall regulate the design and construction of buildings for the ((effective)) use and conservation of energy over the ((useful)) life of each building. This code is intended to provide flexibility to permit the use of innovative approaches and techniques to achieve this objective. This code is not intended to abridge safety, health or environmental requirements contained in other applicable codes or ordinances.
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency. AMENDATORY SECTION (Amending WSR 14-24-122, filed 12/3/14, effective 1/3/15)
WAC 51-11C-10140 Section C101.4—Applicability.
C101.4 Applicability. Where, in any specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern. Where there is a conflict between a general requirement and a specific requirement, the specific requirement shall govern.
C101.4.1 ((Existing buildings. Except as specified in this chapter, this code shall not be used to require the removal, alteration or abandonment of, nor prevent the continued use and maintenance of, an existing building or building system lawfully in existence at the time of adoption of this code.
C101.4.2 Historic buildings. The building official may modify the specific requirements of this code for historic buildings and require alternate provisions which will result in a reasonable degree of energy efficiency. This modification may be allowed for those buildings or structures that are listed in the state or national register of historic places; designated as a historic property under local or state designation law or survey; certified as a contributing resource with a national register listed or locally designated historic district; or with an opinion or certification that the property is eligible to be listed on the national or state registers of historic places either individually or as a contributing building to a historic district by the state historic preservation officer or the keeper of the national register of historic places.
C101.4.3 Additions, alterations, renovations or repairs. Additions, alterations, renovations or repairs to an existing building, building system or portion thereof shall conform to the provisions of this code as they relate to new construction without requiring the unaltered portion(s) of the existing building or building system to comply with this code. Additions, alterations, renovations or repairs shall not create an unsafe or hazardous condition or overload existing building systems. An addition shall be deemed to comply with this code if the addition alone complies or if the existing building and addition comply with this code as a single building.
C101.4.3.1 Lighting and motors. Alterations that replace 60 percent or more of the luminaires in a space enclosed by walls or ceiling-height partitions shall comply with Section C405.5. Where less than 60 percent of the luminaires in a space enclosed by walls or ceiling-height partitions are new, the installed lighting wattage shall be maintained or reduced.
Alterations that replace 60 percent or more of the exterior luminaires shall comply with Section C405.6. Where less than 60 percent of the exterior luminaires are new, the installed lighting wattage shall be maintained or reduced.
Where new wiring is being installed to serve added fixtures and/or fixtures are being relocated to a new circuit, controls shall comply with Sections C405.2.1, C405.2.2.3, C405.2.3, C405.2.4, and as applicable C408.3. In addition, office areas less than 300 ft2 enclosed by walls or ceiling-height partitions, and all meeting and conference rooms, and all school classrooms, shall be equipped with occupancy sensors that comply with Section C405.2.2 and C408.3. Where a new lighting panel (or a moved lighting panel) with all new raceway and conductor wiring from the panel to the fixtures is being installed, controls shall also comply with the other requirements in Sections C405.2.2 and C408.3.
Where new walls or ceiling-height partitions are added to an existing space and create a new enclosed space, but the lighting fixtures are not being changed, other than being relocated, the new enclosed space shall have controls that comply with Sections C405.2.1, C405.2.2, C405.2.3 and C408.3.
Those motors which are altered or replaced shall comply with Section C403.2.13.
C101.4.3.2 Mechanical systems. Those parts of systems which are altered or replaced shall comply with Section C403. Additions or alterations shall not be made to an existing mechanical system that will cause the existing mechanical system to become out of compliance.
All new systems in existing buildings, including packaged unitary equipment and packaged split systems, shall comply with Section C403.
Where mechanical cooling is added to a space that was not previously cooled, the mechanical cooling system shall comply with the economizer requirements in Section C403.3.1 or C403.4.1.
Alterations to existing mechanical cooling systems shall not decrease economizer capacity unless the system complies with Section C403.3.1 or C403.4.1. In addition, for existing mechanical cooling systems that do not comply with Sections C403.3.1 or Section 403.4.1, including both the individual unit size limits and the total building capacity limits on units without economizer, other alterations shall comply with Table C101.4.3.2.
When space cooling equipment is replaced, controls shall be installed to provide for integrated operation with economizer in accordance with Section C403.3.
Existing equipment currently in use may be relocated within the same floor or same tenant space if removed and reinstalled within the same permit.
C101.4.4 Change in occupancy or use. Spaces undergoing a change in occupancy from an F, S or U occupancy to an occupancy other than F, S or U shall comply with this code. Any space that is converted to a Group R dwelling unit or portion thereof, from another use or occupancy shall comply with this code. Where the use in a space changes from one use in Table C405.5.2 (1) or (2) to another use in Table C405.5.2 (1) or (2), the installed lighting wattage shall comply with Section C405.5.
C101.4.5 Change in space conditioning. Any nonconditioned space that is altered to become conditioned space or semi-heated space shall be required to be brought into full compliance with this code. Any semi-heated space that is altered to become conditioned space shall be required to be brought into full compliance with this code.
C101.4.6)) Mixed occupancy. Where a building includes both residential and commercial occupancies, each occupancy shall be separately considered and meet the applicable provisions of ((IECC)) WSEC—Commercial Provisions or ((IECC)) WSEC—Residential Provisions.
AMENDATORY SECTION (Amending WSR 13-20-120, filed 10/1/13, effective 11/1/13)
WAC 51-11C-10143 ((Table C101.4.3.2—Economizer compliance options for mechanical alterations.)) Reserved.
((Table C101.4.3.2
Economizer Compliance Options for Mechanical Alterations
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-10150 Section C101.5—Compliance.
C101.5 Compliance. Residential buildings shall meet the provisions of ((IECC)) WSEC—Residential Provisions. Commercial buildings shall meet the provisions of ((IECC)) WSEC—Commercial Provisions.
C101.5.1 Compliance materials. The code official shall be permitted to approve specific computer software, worksheets, compliance manuals and other similar materials that meet the intent of this code.
((C101.5.2 Low energy buildings. The following buildings, or portions thereof, separated from the remainder of the building by building thermal envelope assemblies complying with this code shall be exempt from all thermal envelope provisions of this code:
1. Those that are heated and/or cooled with a peak design rate of energy usage less than 3.4 Btu/h • ft2 (10.7 W/m2) or 1.0 watt/ft2 (10.7 W/m2) of floor area for space conditioning purposes.
2. Those that do not contain conditioned space.
3. Greenhouses isolated from any conditioned space and not intended for occupancy.
C101.5.2.1 Semi-heated spaces. A semi-heated space shall meet all of the building thermal envelope requirements, except that insulation is not required for opaque wall assemblies. Component performance calculations involving semi-heated spaces shall calculate fully insulated opaque walls for the Target UA calculation, and Total Building Performance calculations involving semi-heated spaces shall calculate fully insulated opaque walls for the Standard Reference Design.))
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-10300 Section C103—Construction documents.
C103.1 General. Construction documents and other supporting data shall be submitted in one or more sets with each application for a permit. The construction documents shall be prepared by a registered design professional where required by the statutes of the jurisdiction in which the project is to be constructed. Where special conditions exist, the code official is authorized to require necessary construction documents to be prepared by a registered design professional.
C103.2 Information on construction documents. Construction documents shall be drawn to scale upon suitable material. Electronic media documents are permitted to be submitted when approved by the code official. Construction documents shall be of sufficient clarity to indicate the location, nature and extent of the work proposed, and show in sufficient detail pertinent data and features of the building, systems and equipment as herein governed. Details shall include, but are not limited to, as applicable((,)):
1. Insulation materials and their R-values((;)).
2. Fenestration U-factors and SHGCs((;)).
3. Area-weighted U-factor and SHGC calculations((;)).
4. Mechanical system design criteria((;)).
5. Mechanical and service water heating system and equipment types, sizes and efficiencies((;)).
6. Economizer description((;)).
7. Equipment and systems controls((;)).
8. Fan motor horsepower (hp) and controls((;)).
9. Duct sealing, duct and pipe insulation and location((;)).
10. Lighting fixture schedule with wattage and control narrative((; and air sealing details)).
11. Location of daylight zones on floor plan.
12. Air barrier details including all air barrier boundaries and associated square foot calculations on all six sides of the air barrier as applicable.
C103.2.1 Building thermal envelope depiction. The building's thermal envelope shall be represented on the construction documents.
C103.3 Examination of documents. The code official shall examine or cause to be examined the accompanying construction documents and shall ascertain whether the construction indicated and described is in accordance with the requirements of this code and other pertinent laws or ordinances.
C103.3.1 Approval of construction documents. When the code official issues a permit where construction documents are required, the construction documents shall be endorsed in writing and stamped "Reviewed for Code Compliance." Such approved construction documents shall not be changed, modified or altered without authorization from the code official. Work shall be done in accordance with the approved construction documents.
One set of construction documents so reviewed shall be retained by the code official. The other set shall be returned to the applicant, kept at the site of work and shall be open to inspection by the code official or a duly authorized representative.
C103.3.2 Previous approvals. This code shall not require changes in the construction documents, construction or designated occupancy of a structure for which a lawful permit has been heretofore issued or otherwise lawfully authorized, and the construction of which has been pursued in good faith within 180 days after the effective date of this code and has not been abandoned.
C103.3.3 Phased approval. The code official shall have the authority to issue a permit for the construction of part of an energy conservation system before the construction documents for the entire system have been submitted or approved, provided adequate information and detailed statements have been filed complying with all pertinent requirements of this code. The holders of such permit shall proceed at their own risk without assurance that the permit for the entire energy conservation system will be granted.
C103.4 Amended construction documents. Changes made during construction that are not in compliance with the approved construction documents shall be resubmitted for approval as an amended set of construction documents.
C103.5 Retention of construction documents. One set of approved construction documents shall be retained by the code official for a period of not less than 180 days from date of completion of the permitted work, or as required by state or local laws.
C103.6 Building documentation and close out submittal requirements. The construction documents shall specify that the documents described in this section be provided to the building owner or owner's authorized agent within 180 days of the date of receipt of the certificate of occupancy.
C103.6.1 Record documents. Construction documents shall be updated to convey a record of the completed work. Such updates shall include mechanical, electrical and control drawings red-lined, or redrawn if specified, that show all changes to size, type and locations of components, equipment and assemblies.
C103.6.2 Manuals. An operating and maintenance manual shall be provided for each component, device, piece of equipment, and system required to be commissioned by this code. The manual shall include all of the following:
1. Submittal data indicating all selected options for each piece of equipment.
2. Manufacturer's operation manuals and maintenance manuals for each device, piece of equipment, and system requiring maintenance, except equipment not furnished as part of the project. Required routine maintenance actions, cleaning and recommended relamping shall be clearly identified.
3. Name and address of at least one service agency.
4. Controls system inspection schedule, maintenance and calibration information, wiring diagrams, schematics, and control sequence descriptions. Desired or field-determined setpoints shall be permanently recorded on control drawings at control devices or, for digital control systems, on the graphic where settings may be changed.
C103.6.3 Compliance documentation. All energy code compliance forms and calculations shall be delivered in one document to the building owner as part of the project record documents, manuals, or as a standalone document. This document shall include the specific energy code year utilized for compliance determination for each system. NFRC certificates for the installed windows, list total area for each NFRC certificate, the interior lighting power compliance path (building area, space-by-space) used to calculate the lighting power allowance.
For projects complying with C401.2, item one the documentation shall include:
1. The envelop insulation compliance path (prescriptive or component performance).
2. All completed code compliance forms, and all compliance calculations including, but not limited to, those required by sections C402.1.5, C403.2.12.1, C405.4, and C405.5.
For projects complying with C407 the documentation shall include:
1. A list of all proposed envelop component types, areas and U-values.
2. A list of all lighting area types with areas, lighting power allowance, and installed lighting power density.
3. A list of each HVAC system modeled with the assigned and proposed system type.
4. Electronic copies of the baseline and proposed model input and output file. The input files shall be in a format suitable for rerunning the model and shall not consist solely of formatted reports of the inputs.
C103.6.4 Systems operation training. Training of the maintenance staff for equipment included in the manuals required by Section C103.6.2 shall include at a minimum:
1. Review of manuals and permanent certificate.
2. Hands-on demonstration of all normal maintenance procedures, normal operating modes, and all emergency shutdown and start-up procedures.
3. Training completion report.
AMENDATORY SECTION (Amending WSR 14-24-122, filed 12/3/14, effective 1/3/15)
WAC 51-11C-10400 Section C104—Inspections.
C104.1 General. Construction or work for which a permit is required shall be subject to inspection by the code official or his designated agent, and such construction or work shall remain accessible and exposed for inspection purposes until approved. It shall be the duty of the permit applicant to cause the work to remain accessible and exposed for inspection purposes. Neither the code official nor the jurisdiction shall be liable for expense entailed in the removal or replacement of any material, product, system or building component required to allow inspection to validate compliance with this code.
C104.2 Required ((approvals. Work shall not be done beyond the point indicated in each successive inspection without first obtaining the approval of the code official. The code official, upon notification, shall make the requested inspections and shall either indicate the portion of the construction that is satisfactory as completed, or notify the permit holder or his or her agent wherein the same fails to comply with this code. Any portions that do not comply shall be corrected and such portion shall not be covered or concealed until authorized by the code official. Where applicable, inspections shall include at least the requirements in Sections C104.2.1 through C104.2.3.2.
C104.2.1 Envelope
C104.2.1.1 Wall Insulation Inspection: To be made after all wall insulation and air vapor retarder sheet or film materials are in place, but before any wall covering is placed.
C104.2.1.2 Glazing Inspection: To be made after glazing materials are installed in the building.
C104.2.1.3 Exterior Roofing Insulation: To be made after the installation of the roof insulation, but before concealment.
C104.2.1.4 Slab/Floor Insulation: To be made after the installation of the slab/floor insulation, but before concealment.
C104.2.2 Mechanical
C104.2.2.1 Mechanical Equipment Efficiency and Economizer: To be made after all equipment and controls required by this code are installed and prior to the concealment of such equipment or controls.
C104.2.2.2 Mechanical Pipe and Duct Insulation: To be made after all pipe and duct insulation is in place, but before concealment.
C104.2.3 Lighting and motors
C104.2.3.1 Lighting Equipment and Controls: To be made after the installation of all lighting equipment and controls required by this code, but before concealment of the lighting equipment.
C104.2.3.2 Motor Inspections: To be made after installation of all equipment covered by this code, but before concealment.
C104.3)) inspections. The code official or his designated agent, upon notification, shall make the inspections set forth in Sections C104.2.1 through C104.2.6.
C104.2.1 Footing and foundation inspection. Inspections associated with footings and foundations shall verify compliance with the code as to R-value, location, thickness, depth of burial and protection of insulation as required by the code and approved plans and specifications.
C104.2.2 Insulation and fenestration inspection. Inspections shall be made before application of interior finish and shall verify compliance with the code as to types of insulation and corresponding R-values and their correct location and proper installation; fenestration properties (U-factor, SHGC and VT) and proper installation; and air leakage controls as required by the code and approved plans and specifications.
C104.2.3 Plumbing inspection. Inspections verify compliance as required by the code and approved plans and specifications as to types of insulation and corresponding R-values and protection, required controls and required heat traps.
C104.2.4 Mechanical inspection. Inspections shall verify compliance as required by the code and approved plans and specifications as to installed HVAC equipment type and size, required controls, system insulation and corresponding R-value, system and damper air leakage and required energy recovery and/or economizers.
C104.2.5 Electrical and lighting inspection. Inspections shall verify compliance as required by the code and approved plans and specifications as to installed lighting systems, components and controls; motors and installation of an electric meter for each dwelling unit.
C104.2.6 Final inspection. The building shall have a final inspection and not be occupied until approved.
((C104.4)) C104.3 Reinspection. A building shall be reinspected when determined necessary by the code official.
((C104.5)) C104.4 Approved inspection agencies. The code official is authorized to accept reports of approved inspection agencies, provided such agencies satisfy the requirements as to qualifications and reliability relevant to the building components and systems they are inspecting.
((C104.6)) C104.5 Inspection requests. It shall be the duty of the holder of the permit or their duly authorized agent to notify the code official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspections of such work that are required by this code.
((C104.7)) C104.6 Reinspection and testing. Where any work or installation does not pass an initial test or inspection, the necessary corrections shall be made so as to achieve compliance with this code. The work or installation shall then be resubmitted to the code official for inspection and testing.
((C104.8)) C104.7 Approval. After the prescribed tests and inspections indicate that the work complies in all respects with this code, a notice of approval shall be issued by the code official.
((C104.8.1)) C104.7.1 Revocation. The code official is authorized to, in writing, suspend or revoke a notice of approval issued under the provisions of this code wherever the certificate is issued in error, or on the basis of incorrect information supplied, or where it is determined that the building or structure, premise, or portion thereof is in violation of any ordinance or regulation or any of the provisions of this code.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-10600 Section C106—Referenced standards.
C106.1 Referenced codes and standards. The codes and standards referenced in this code shall be those listed in Chapter 5, and such codes and standards shall be considered as part of the requirements of this code to the prescribed extent of each such reference and as further regulated in Sections C106.1.1 and C106.1.2.
C106.1.1 Conflicts. Where differences occur between provisions of this code and referenced codes and standards, the provisions of this code shall apply.
C106.1.2 Provisions in referenced codes and standards. Where the extent of the reference to a referenced code or standard includes subject matter that is within the scope of this code, the provisions of this code, as applicable, shall take precedence over the provisions in the referenced code or standard.
C106.2 ((Conflicting requirements. Where the provisions of this code and the referenced standards conflict, the provisions of this code shall take precedence.
C106.3)) Application of references. References to chapter or section numbers, or to provisions not specifically identified by number, shall be construed to refer to such chapter, section or provision of this code.
((C106.4)) C106.3 Other laws. The provisions of this code shall not be deemed to nullify any provisions of local, state or federal law. In addition to the requirements of this code, all occupancies shall conform to the provisions included in the State Building Code (chapter 19.27 RCW). In case of conflicts among the codes enumerated in RCW 19.27.031 (1) through (4) and this code, an earlier named code shall govern over those following. In the case of conflict between the duct sealing and insulation requirements of this code and the duct insulation requirements of Sections 603 and 604 of the International Mechanical Code, the duct insulation requirements of this code, or where applicable, a local jurisdiction's energy code shall govern.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-10800 Section C108—Stop work order.
C108.1 Authority. Whenever the code official finds any work regulated by this code being performed in a manner either contrary to the provisions of this code or dangerous or unsafe, the code official is authorized to issue a stop work order.
C108.2 Issuance. The stop work order shall be in writing and shall be given to the owner of the property involved, or to the owner's agent, or to the person doing the work. Upon issuance of a stop work order, the cited work shall immediately cease. The stop work order shall state the reason for the order, and the conditions under which the cited work will be permitted to resume.
C108.3 Emergencies. Where an emergency exists, the code official shall not be required to give a written notice prior to stopping the work.
C108.4 Failure to comply. Any person who shall continue any work after having been served with a stop work order, except such work as that person is directed to perform to remove a violation or unsafe condition, shall be liable to a fine ((of not less than [AMOUNT] dollars or more than [AMOUNT] dollars)) as set by the applicable governing authority.
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency. AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-20201 Section C202.1—A.
ABOVE-GRADE WALL. A wall enclosing conditioned space that is not a below-grade wall. This includes between-floor spandrels, peripheral edges of floors, roof and basement knee walls, dormer walls, gable end walls, walls enclosing a mansard roof and skylight shafts.
ACCESSIBLE. Admitting close approach as a result of not being guarded by locked doors, elevation or other effective means (see "Readily accessible").
ADDITION. An extension or increase in the conditioned space floor area or height of a building or structure.
AIR BARRIER. Material(s) assembled and joined together to provide a barrier to air leakage through the building envelope. An air barrier may be a single material or a combination of materials.
AIR CURTAIN. A device, installed at the building entrance, that generates and discharges a laminar air stream intended to prevent the infiltration of external, unconditioned air into the conditioned spaces, or the loss of interior, conditioned air to the outside.
ALTERATION. Any construction, retrofit or renovation to an existing structure other than repair or addition that requires a permit. Also, a change in a building, electrical, gas, mechanical or plumbing system that involves an extension, addition or change to the arrangement, type or purpose of the original installation that requires a permit.
APPROVED. Approval by the code official as a result of investigation and tests conducted by him or her, or by reason of accepted principles or tests by nationally recognized organizations.
APPROVED AGENCY. An established and recognized agency regularly engaged in conducting tests or furnishing inspection services, when such agency has been approved by the code official.
ATTIC AND OTHER ROOFS. All other roofs, including roofs with insulation entirely below (inside of) the roof structure (i.e., attics, cathedral ceilings, and single-rafter ceilings), roofs with insulation both above and below the roof structure, and roofs without insulation but excluding roofs with insulation entirely above deck and metal building roofs.
AUTOMATIC. Self-acting, operating by its own mechanism when actuated by some impersonal influence, as, for example, a change in current strength, pressure, temperature or mechanical configuration (see "Manual").
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-20202 Section C202.2—B.
BELOW-GRADE WALL. That portion of a wall in the building envelope that is entirely below the finish grade and in contact with the ground.
BOILER, MODULATING. A boiler that is capable of more than a single firing rate in response to a varying temperature or heating load.
BOILER SYSTEM. One or more boilers, their piping and controls that work together to supply steam or hot water to heat output devices remote from the boiler.
BUBBLE POINT. The refrigerant liquid saturation temperature at a specified pressure.
BUILDING. Any structure used or intended for supporting or sheltering any use or occupancy, including any mechanical systems, service water heating systems and electric power and lighting systems located on the building site and supporting the building.
BUILDING COMMISSIONING. A process that verifies and documents that the selected building systems have been designed, installed, and function according to the owner's project requirements and construction documents, and to minimum code requirements.
BUILDING ENTRANCE. Any door, set of doors, doorway, or other form of portal that is used to gain access to the building from the outside by the public.
BUILDING SITE. A contiguous area of land that is under the ownership or control of one entity.
BUILDING THERMAL ENVELOPE. The below-grade walls, above-grade walls, floor, roof, and any other building elements that enclose conditioned space or provides a boundary between conditioned space, semiheated space and exempt or unconditioned space.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-20203 Section C202.3—C.
-FACTOR (THERMAL CONDUCTANCE).C The coefficient of heat transmission (surface to surface) through a building component or assembly, equal to the time rate of heat flow per unit area and the unit temperature difference between the warm side and cold side surfaces (Btu/h ft2 x °F) [W/(m2 x K)].
CERTIFIED COMMISSIONING PROFESSIONAL. An individual who is certified by an ANSI/ISO/IEC 17024:2012 accredited organization to lead, plan, coordinate and manage commissioning teams and implement commissioning processes. The individual's accredited certification required by the referenced standard provides a measured level of experience and competence with the various whole building commissioning processes and ability to deliver quality service. The engineer of record for the project may be considered the certified commissioning professional if she/he is qualified to perform commissioning services for the entire process.
CIRCULATING HOT WATER SYSTEM. A specifically designed water distribution system where one or more pumps are operated in the service hot water piping to circulate heated water from the water-heating equipment to the fixture supply and back to the water-heating equipment.
CLIMATE ZONE. A geographical region based on climatic criteria as specified in this code.
CODE OFFICIAL. The officer or other designated authority charged with the administration and enforcement of this code, or a duly authorized representative.
COEFFICIENT OF PERFORMANCE (COP) - COOLING. The ratio of the rate of heat removal to the rate of energy input, in consistent units, for a complete refrigerating system or some specific portion of that system under designated operating conditions.
COEFFICIENT OF PERFORMANCE (COP) - HEATING. The ratio of the rate of heat removal to the rate of heat delivered to the rate of energy input, in consistent units, for a complete heat pump system, including the compressor and, if applicable, auxiliary heat, under designated operating conditions.
COMMERCIAL BUILDING. For this code, all buildings that are not included in the definition of "Residential buildings."
COMPUTER ROOM. A room whose primary function is to house equipment for the processing and storage of electronic data and that has a design electronic data equipment power density exceeding 20 watts per square foot of conditioned area.
CONDENSING UNIT. A factory-made assembly of refrigeration components designed to compress and liquefy a specific refrigerant. The unit consists of one or more refrigerant compressors, refrigerant condensers (air-cooled, evaporatively cooled, or water-cooled), condenser fans and motors (where used) and factory-supplied accessories.
CONDITIONED FLOOR AREA. The horizontal projection of the floors associated with the conditioned space.
CONDITIONED SPACE. An area ((or room within a building being heated or cooled, containing uninsulated ducts, or with a fixed opening directly into an adjacent conditioned space)), room or space that is enclosed within the building thermal envelope and that is directly heated or cooled or that is indirectly heated or cooled. Spaces are indirectly heated or cooled where they communicate through openings with conditioned spaces, where they are separated from conditioned spaces by uninsulated walls, floors or ceilings, or where they contain uninsulated ducts, piping or other sources of heating or cooling.
CONTINUOUS AIR BARRIER. A combination of materials and assemblies that restrict or prevent the passage of air through the building thermal envelope.
CONTINUOUS INSULATION (CI). ((Insulation)) Insulating material that is continuous across all structural members without thermal bridges other than ((service openings and penetrations by metal fasteners with a cross-sectional area, as measured in the plane of the surface, of less than 0.04% of the opaque surface area of the assembly)) fasteners and service openings. It is installed on the interior or exterior or is integral to any opaque surface of the building envelope.
CONTROLLED PLANT GROWTH ENVIRONMENT. Group F and U buildings or spaces that are specifically controlled to facilitate and enhance plant growth and production by manipulating various indoor environment conditions. Technologies include indoor agriculture, cannabis growing, hydroponics, aquaculture and aquaponics. Controlled indoor environment variables include, but are not limited to, temperature, air quality, humidity, and carbon dioxide.
CURTAIN WALL. Fenestration products used to create an external nonload-bearing wall that is designed to separate the exterior and interior environments.
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency. Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040. AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-20204 Section C202.4—D.
DATA ACQUISITION SYSTEM. An electronic system managed by the building owner to collect, tabulate and display metering information.
DAYLIGHT RESPONSIVE CONTROL. A device or system that provides automatic control of electric light levels based on the amount of daylight in a space.
DAYLIGHT ZONE. (((See also Fig. C202.4)
1. Under skylights. The area under skylights whose horizontal dimension, in each direction, is equal to the skylight dimension in that direction plus either 70 percent of the floor-to-ceiling height or the dimension to a ceiling height opaque partition, or one-half the distance to adjacent skylights or vertical fenestration, whichever is least.
2. Adjacent to vertical fenestration. The area adjacent to vertical fenestration which receives daylight through the fenestration. For purposes of this definition and unless more detailed analysis is provided, the primary daylight zone depth is assumed to extend into the space a distance equal to the window head height and the secondary daylighted zone extends from the edge of the primary zone to a distance equal to two times the window head height or to the nearest ceiling height opaque partition, whichever is less. The daylight zone width is assumed to be the width of the window plus 2 feet (610 mm) on each side, or the window width plus the distance to an opaque partition, or the window width plus one-half the distance to adjacent skylight or vertical fenestration, whichever is least.
3. In parking garages. The area within 20 feet of any portion of a perimeter wall that has a net opening to wall ratio of at least 40 percent and no exterior obstructions within 20 feet.
4. Under atrium glazing. The area at the floor directly beneath the atrium and the top floor under the atrium whose horizontal dimension, in each direction, is equal to the distance between the floor and ceiling height. Levels below the top floor that are not directly beneath the atrium are unaffected.
Figure C202.1
The portion of the building interior floor area that is illuminated by natural daylight through sidelight and toplight fenestration.
DEMAND CONTROL VENTILATION (DCV). A ventilation system capability that provides for the automatic reduction of outdoor air intake below design rates when the actual occupancy of spaces served by the system is less than design occupancy.
DEMAND RECIRCULATION WATER SYSTEM. A water distribution system where ((pump(s))) pumps prime the service hot water piping with heated water upon demand for hot water.
DUCT. A tube or conduit utilized for conveying air. The air passages of self-contained systems are not to be construed as air ducts.
DUCT SYSTEM. A continuous passageway for the transmission of air that, in addition to ducts, includes duct fittings, dampers, plenums, fans and accessory air-handling equipment and appliances.
DWELLING UNIT. A single unit providing complete independent living facilities for one or more persons, including permanent provisions for living, sleeping, eating, cooking and sanitation.
DYNAMIC GLAZING. Any fenestration product that has the fully reversible ability to change its performance properties, including U-factor, SHGC, or VT.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-20206 Section C202.6—F.
FAN BRAKE HORSEPOWER (BHP). The horsepower delivered to the fan's shaft. Brake horsepower does not include the mechanical drive losses (belts, gears, etc.).
FAN EFFICIENCY GRADE (FEG). A numerical rating identifying the fan's aerodynamic ability to convert shaft power, or impeller power in the case of a direct-driven fan, to air power.
FAN SYSTEM BHP. The sum of the fan brake horsepower of all fans that are required to operate at fan system design conditions to supply air from the heating or cooling source to the conditioned space(s) and return it to the source or exhaust it to the outdoors.
FAN SYSTEM DESIGN CONDITIONS. Operating conditions that can be expected to occur during normal system operation that result in the highest supply fan airflow rate to conditioned spaces served by the system.
FAN SYSTEM MOTOR NAMEPLATE HP. The sum of the motor nameplate horsepower of all fans that are required to operate at design conditions to supply air from the heating or cooling source to the conditioned space(s) and return it to the source or exhaust it to the outdoors.
FENESTRATION. ((Skylights, roof windows, vertical windows (fixed or moveable), opaque doors, glazed doors, glazed block and combination opaque/glazed doors. Fenestration includes products with glass and nonglass glazing materials.)) Products classified as either vertical fenestration or skylights.
SKYLIGHT. Glass or other transparent or translucent glazing material installed at a slope of less than 60 degrees (91.05 rad) from horizontal.
VERTICAL FENESTRATION. Windows (fixed or moveable), opaque doors, glazed doors, glazed block and combination opaque/glazed doors composed of glass or other transparent or translucent glazing materials and installed at a slope of at least 60 degrees (91.05 rad) from horizontal.
CLERESTORY FENESTRATION. An upper region of vertical fenestration provided for the purpose of admitting daylight beyond the perimeter of a space. The entire clerestory fenestration assembly is installed at a height greater than 8 feet above the finished floor.
FENESTRATION AREA. Total area of the fenestration measured using the rough opening, and including the glazing, sash and frame.
FENESTRATION PRODUCT, FIELD-FABRICATED. A fenestration product whose frame is made at the construction site of standard dimensional lumber or other materials that were not previously cut, or otherwise formed with the specific intention of being used to fabricate a fenestration product or exterior door. Field fabricated does not include site-built fenestration.
FENESTRATION PRODUCT, SITE-BUILT. A fenestration designed to be made up of field-glazed or field-assembled units using specific factory cut or otherwise factory-formed framing and glazing units. Examples of site-built fenestration include storefront systems, curtain walls, and atrium roof systems.
-FACTOR.F The perimeter heat loss factor for slab-on-grade floors (Btu/h x ft x °F) [W/(m x K)].
FLOOR AREA, NET. The actual occupied area not including unoccupied accessory areas such as corridors, stairways, toilet rooms, mechanical rooms and closets.
FURNACE ELECTRICITY RATIO. The ratio of furnace electricity use to total furnace energy computed as ratio = (3.412 x EAE)/1000 x EF + 3.412 x EAE) where EAE (average annual auxiliary electrical consumption) and EF (average annual fuel energy consumption) are defined in Appendix N to Subpart B of Part 430 of Title 10 of the Code of Federal Regulations and EF is expressed in millions of Btus per year.
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency. Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040. AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-20207 Section C202.7—G.
GENERAL LIGHTING. Lighting that provides a substantially uniform level of illumination throughout an area. General lighting shall not include ((decorative lighting or)) lighting that provides a dissimilar level of illumination to serve a ((specialized)) specific application or decorative feature within such area.
GENERAL PURPOSE ELECTRIC MOTOR (SUBTYPE I). A motor that is designed in standard ratings with either of the following:
1. Standard operating characteristics and standard mechanical construction for use under usual service conditions, such as those specified in NEMA MG1, paragraph 14.02, "Usual Service Conditions," and without restriction to a particular application or type of application.
2. Standard operating characteristics or standard mechanical construction for use under unusual service conditions, such as those specified in NEMA MG1, paragraph 14.03, "Unusual Service Conditions," or for a particular type of application, and that can be used in most general purpose applications.
General purpose electric motors (Subtype I) are constructed in NEMA T-frame sizes or IEC metric equivalent, starting at 143T.
GENERAL PURPOSE ELECTRIC MOTOR (SUBTYPE II). A motor incorporating the design elements of a general purpose electric motor (Subtype I) that is configured as one of the following:
1. A U-frame motor.
2. A Design C motor.
3. A close-coupled pump motor.
4. A footless motor.
5. A vertical, solid-shaft, normal-thrust motor (as tested in a horizontal configuration).
6. An 8-pole motor (900 rpm).
7. A polyphase motor with voltage of not more than 600 volts (other than 230 or 460 volts).
GREENHOUSE. A permanent structure or a thermally isolated area of a building that maintains a specialized sunlit environment that is used exclusively for, and is essential to, the cultivation, protection or maintenance of plants. Greenhouses are those that are erected for a period of 180 days or more.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-20208 Section C202.8—H.
HEAT TRAP. An arrangement of piping and fittings, such as elbows, or a commercially available heat trap that prevents thermosyphoning of hot water during standby periods.
HEATED SLAB-ON-GRADE FLOOR. Slab-on-grade floor construction in which the heating elements, hydronic tubing, or hot air distribution system is in contact with, or placed within or under, the slab.
((HIGH-EFFICACY LUMINAIRES. Luminaires with compact fluorescent lamps, T-8 or smaller diameter linear fluorescent lamps, or lamps with a minimum efficacy of:
1. 60 Lumens per watt for lamps over 40 watts;
2. 50 Lumens per watt for lamps over 15 watts to 40 watts; and
3. 40 Lumens per watt for lamps 15 watts or less.))
HIGH SPEED DOOR. A nonswinging door used primarily to facilitate vehicular access or material transportation, with a minimum opening rate of 32 inches (813 mm) per second, a minimum closing rate of 24 inches (610 mm) per second and that includes an automatic-closing device.
HISTORIC BUILDINGS. Buildings that are listed in or eligible for listing in the National Register of Historic Places, or designated as historic under an appropriate state or local law.
HUMIDISTAT. A regulatory device, actuated by changes in humidity, used for automatic control of relative humidity.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-20209 Section C202.9—I.
INFILTRATION. The uncontrolled inward air leakage into a building caused by the pressure effects of wind or the effect of differences in the indoor and outdoor air density or both.
((INSULATING SHEATHING. An insulating board with a core material having a minimum R-value of R-2.))
INSULATION ENTIRELY ABOVE DECK. A roof with all insulation:
1. Installed above (outside of) the roof structure; and
2. Continuous (i.e., uninterrupted by framing members).
INTEGRATED ENERGY EFFICIENCY RATIO (IEER). A single-number figure of merit expressing cooling part-load EER efficiency for unitary air-conditioning and heat pump equipment on the basis of weighted operation at various load capacities for the equipment.
INTEGRATED PART LOAD VALUE (IPLV). A single number figure of merit based on part-load EER, COP, or kW/ton expressing part-load efficiency for air conditioning and heat pump equipment on the basis of weighted operation at various load capacities for equipment.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-20212 Section C202.12—L.
LABELED. Equipment, materials or products to which have been affixed a label, seal, symbol or other identifying mark of a nationally recognized testing laboratory, inspection agency or other organization concerned with product evaluation that maintains periodic inspection of the production of the above-labeled items and whose labeling indicates either that the equipment, material or product meets identified standards or has been tested and found suitable for a specified purpose.
LINER SYSTEM (LS). A system that includes the following:
1. A continuous vapor barrier liner membrane that is installed below the purlins and that is uninterrupted by framing members.
2. An uncompressed, unfaced insulation resting on top of the liner membrane and located between the purlins.
For multilayer installations, the last rated R-value of insulation is for unfaced insulation draped over purlins and then compressed when the metal roof panels are attached.
LISTED. Equipment, materials, products or services included in a list published by an organization acceptable to the code official and concerned with evaluation of products or services that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services and whose listing states either that the equipment, material, product or service meets identified standards or has been tested and found suitable for a specified purpose.
LOW-SLOPED ROOF. A roof having a slope less than 2 units vertical in 12 units horizontal.
LOW-VOLTAGE DRY-TYPE DISTRIBUTION TRANSFORMER. A transformer that is air-cooled, does not use oil as a coolant, has an input voltage less than or equal to 600.
LOW-VOLTAGE LIGHTING. A lighting system consisting of an isolating power supply, the low voltage luminaires, and associated equipment that are all identified for the use. The output circuits of the power supply operate at 30 volts (42.4 volts peak) or less under all load conditions.
LUMINAIRE. A complete lighting unit consisting of a lamp or lamps together with the housing designed to distribute the light, position and protect the lamps, and connect the lamps to the power supply.
LUMINAIRE-LEVEL LIGHTING CONTROL. A lighting system consisting of one or more luminaire(s) with embedded lighting control logic, occupancy and ambient light sensors, wireless networking capabilities, and local override switching capability.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-20213 Section C202.13—M.
MANUAL. Capable of being operated by personal intervention (see "Automatic").
MASS TRANSFER DECK SLAB EDGE. That portion of the above-grade wall made up of the concrete slab where it extends past the footprint of the floor above. The area of the slab edge shall be defined as the thickness of the slab multiplied by the perimeter of the edge condition. Examples of this condition include, but are not limited to, the transition from an above-grade structure to a below-grade structure or the transition from a tower to a podium.
METAL BUILDING ROOF. A roof that:
1. Is constructed with a metal, structural, weathering surface;
2. Has no ventilated cavity; and
3. Has the insulation entirely below deck (i.e., does not include composite concrete and metal deck construction nor a roof framing system that is separated from the superstructure by a wood substrate) and whose structure consists of one or more of the following configurations:
a. Metal roofing in direct contact with the steel framing members;
b. Metal roofing separated from the steel framing members by insulation;
c. Insulated metal roofing panels installed as described in a or b.
METAL BUILDING WALL. A wall whose structure consists of metal spanning members supported by steel structural members (i.e., does not include spandrel glass or metal panels in curtain wall systems).
METER. A device that measures the flow of energy.
MICROCELL. A wireless communication facility consisting of an antenna that is either: (a) Four (4) feet in height and with an area of not more than 580 square inches; or (b) if a tubular antenna, no more than four (4) inches in diameter and no more than six (6) feet in length; and the associated equipment cabinet that is six (6) feet or less in height and no more than 48 square feet in floor area.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-20215 Section C202.15—O.
OCCUPANT SENSOR CONTROL. An automatic control device or system that detects the presence or absence of people within an area and causes lighting, equipment or appliances to be regulated accordingly.
ON-SITE RENEWABLE ENERGY. Energy derived from solar radiation, wind, waves, tides, landfill gas, biomass, or the internal heat of the earth. The energy system providing on-site renewable energy shall be located on the project site.
OPAQUE DOOR. A door that is not less than 50 percent opaque in surface area.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-20216 Section C202.16—P.
PERSONAL WIRELESS SERVICE FACILITY. A wireless communication facility (WCF), including a microcell, which is a facility for the transmission and/or reception of radio frequency signals and which may include antennas, equipment shelter or cabinet, transmission cables, a support structure to achieve the necessary elevation, and reception and/or transmission devices or antennas.
POWERED ROOF/WALL VENTILATORS. A fan consisting of a centrifugal or axial impeller with an integral driver in a weather-resistant housing and with a base designed to fit, usually by means of a curb, over a wall or roof opening.
PROPOSED DESIGN. A description of the proposed building used to estimate annual energy use for determining compliance based on total building performance.
AMENDATORY SECTION (Amending WSR 14-24-054, filed 11/25/14, effective 5/1/15)
WAC 51-11C-20218 Section C202.18—R.
RADIANT HEATING SYSTEM. A heating system that transfers heat to objects and surfaces within a conditioned space, primarily by infrared radiation.
READILY ACCESSIBLE. Capable of being reached quickly for operation, renewal or inspection without requiring those to whom ready access is requisite to climb over or remove obstacles or to resort to portable ladders or access equipment (see "Accessible").
REFRIGERANT DEW POINT. The refrigerant vapor saturation temperature at a specified pressure.
REFRIGERATED WAREHOUSE COOLER. An enclosed storage space that has a total chilled storage area of 3,000 ft2 or greater and is designed to maintain a temperature of greater than 32°F but less than 55°F.
REFRIGERATED WAREHOUSE FREEZER. An enclosed storage space that has a total chilled storage area of 3,000 ft2 or greater and is designed to maintain a temperature at or below 32°F.
REFRIGERATION SYSTEM, LOW TEMPERATURE. Systems for maintaining food product in a frozen state in refrigeration applications.
REFRIGERATION SYSTEM, MEDIUM TEMPERATURE. Systems for maintaining food product above freezing in refrigeration applications.
REGISTERED DESIGN PROFESSIONAL. An individual who is registered or licensed to practice their respective design profession as defined by the statutory requirements of the professional registration laws of the state or jurisdiction in which the project is to be constructed.
REPAIR. The reconstruction or renewal of any part of an existing building.
REROOFING. The process of recovering or replacing an existing roof covering. See "Roof Recover" and "Roof Replacement."
RESIDENTIAL BUILDING. For this code, includes detached one- and two-family dwellings and multiple single-family dwellings (townhouses) as well as Group R-2, R-3 and R-4 buildings three stories or less in height above grade plane.
ROOF ASSEMBLY. A system designed to provide weather protection and resistance to design loads. The system consists of a roof covering and roof deck or a single component serving as both the roof covering and the roof deck. A roof assembly includes the roof covering, underlayment, roof deck, insulation, vapor retarder and interior finish.
ROOF RECOVER. The process of installing an additional roof covering over a prepared existing roof covering without removing the existing roof covering.
ROOF REPAIR. Reconstruction or renewal of any part of an existing roof for the purposes of its maintenance.
ROOF REPLACEMENT. The process of removing the existing roof covering, repairing any damaged substrate and installing a new roof covering.
ROOFTOP MONITOR. A raised section of a roof containing vertical fenestration along one or more sides.
-VALUE (THERMAL RESISTANCE).R The inverse of the time rate of heat flow through a body from one of its bounding surfaces to the other surface for a unit temperature difference between the two surfaces, under steady state conditions, per unit area (h • ft2 • °F/Btu) [(m2 • K)/W].
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency. Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040. AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-20219 Section C202.19—S.
SATURATED-CONDENSING TEMPERATURE. The saturation temperature corresponding to the measured refrigerant pressure at the condenser inlet for single component and azeotropic refrigerants, and the arithmetic average of the dew point and bubble point temperatures corresponding to the refrigerant pressure at the condenser entrance for zeotropic refrigerants.
SCREW LAMP HOLDERS. A lamp base that requires a screw-in-type lamp, such as a compact-fluorescent, incandescent, or tungsten-halogen bulb.
SEMI-HEATED SPACE. An enclosed space within a building, including adjacent connected spaces separated by an uninsulated component (e.g., basements, utility rooms, garages, corridors), which:
1. Is heated but not cooled, and has a maximum installed heating system output capacity of 3.4 Btu/(h-ft2) but not greater than 8 Btu/(h-ft2);
2. Is not a ((cold storage space or frozen storage space)) walk-in or warehouse cooler or freezer space.
SERVICE WATER HEATING. Heating water for domestic or commercial purposes other than space heating and process requirements.
SKYLIGHT. Glass or other transparent or translucent glazing material installed at a slope of less than 60 degrees (1.05 rad) from horizontal. Glazing material in skylights, including unit skylights, solariums, sunrooms, roofs and sloped walls is included in this definition.
SLAB BELOW GRADE. Any portion of a slab floor in contact with the ground which is more than 24 inches below the final elevation of the nearest exterior grade.
SLAB-ON-GRADE FLOOR. That portion of a slab floor of the building envelope that is in contact with the ground and that is either above grade or is less than or equal to 24 inches below the final elevation of the nearest exterior grade.
SLEEPING UNIT. A room or space in which people sleep, which can also include permanent provisions for living, eating, and either sanitation or kitchen facilities but not both. Such rooms and spaces that are also part of a dwelling unit are not sleeping units.
SMALL ELECTRIC MOTOR. A general purpose, alternating current, single speed induction motor.
SMALL BUSINESS. Any business entity (including a sole proprietorship, corporation, partnership or other legal entity) which is owned and operated independently from all other businesses, which has the purpose of making a profit, and which has fifty or fewer employees.
SOLAR HEAT GAIN COEFFICIENT (SHGC). The ratio of the solar heat gain entering the space through the fenestration assembly to the incident solar radiation. Solar heat gain includes directly transmitted solar heat and absorbed solar radiation which is then reradiated, conducted or convected into the space.
STANDARD REFERENCE DESIGN. A version of the proposed design that meets the minimum requirements of this code and is used to determine the maximum annual energy use requirement for compliance based on total building performance.
STEEL-FRAMED WALL. A wall with a cavity (insulated or otherwise) whose exterior surfaces are separated by steel framing members (i.e., typical steel stud walls and curtain wall systems).
STOREFRONT. A nonresidential system of doors and windows mulled as a composite fenestration structure that has been designed to resist heavy use. Storefront systems include, but are not limited to, exterior fenestration systems that span from the floor level or above to the ceiling of the same story on commercial buildings, with or without mulled windows and doors.
SUBSYSTEM METER. A meter placed downstream of the energy supply meter that measures the energy delivered to a load or a group of loads.
((SUNROOM. A one-story structure attached to a dwelling with a glazing area in excess of 40 percent of the gross area of the structure's exterior walls and roof.))
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-20220 Section C202.20—T.
((THERMAL ISOLATION. Physical and space conditioning separation from conditioned space(s). The conditioned space(s) shall be controlled as separate zones for heating and cooling or conditioned by separate equipment.)) TEMPORARY GROWING STRUCTURE. A temporary growing structure has sides and roof covered with polyethylene, polyvinyl or similar flexible synthetic material and is used to provide plants with either frost protection or increased heat retention. Temporary structures are those that are erected for a period of less than 180 days.
THERMOSTAT. An automatic control device used to maintain temperature at a fixed or adjustable set point.
TIME SWITCH CONTROL. An automatic control device or system that controls lighting or other loads, including switching off, based on time schedules.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-20221 Section C202.21—U.
-FACTOR (THERMAL TRANSMITTANCE).U The coefficient of heat transmission (air to air) through a building component or assembly, equal to the time rate of heat flow per unit area and unit temperature difference between the warm side and cold side air films (Btu/h • ft2 • °F) [W/(m2 • K)].
UNHEATED SLAB-ON-GRADE FLOOR. A slab-on-grade floor that is not a heated slab-on-grade floor.
UNIFORM ILLUMINATION. A quality of illumination delivered by a lighting system typically comprised of similar fixtures mounted at a regular spacing interval. This lighting system provides a uniform contrast ratio of no greater than 5:1 maximum-to-minimum ratio throughout the entire area served, including task areas.
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency. Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040. AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-20222 Section C202.22—V.
VARIABLE REFRIGERANT FLOW SYSTEM. An engineered direct-expansion (DX) refrigerant system that incorporates a common condensing unit, at least one variable capacity compressor, a distributed refrigerant piping network to multiple indoor fan heating and cooling units each capable of individual zone temperature control, through integral zone temperature control devices and a common communications network. Variable refrigerant flow utilizes three or more steps of control on common interconnecting piping.
VENTILATION. The natural or mechanical process of supplying conditioned or unconditioned air to, or removing such air from, any space.
VENTILATION AIR. That portion of supply air that comes from outside (outdoors) plus any recirculated air that has been treated to maintain the desired quality of air within a designated space.
VERTICAL FENESTRATION. All fenestration other than skylights.
VISIBLE TRANSMITTANCE [VT]. The ratio of visible light entering the space through the fenestration product assembly to the incident visible light, visible transmittance, includes the effects of glazing material and frame and is expressed as a number between 0 and 1.
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency. Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040. AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-20223 Section C202.23—W.
WALK-IN COOLER. An enclosed storage space capable of being refrigerated to temperatures above 32°F ((that can be walked into and has a total chilled storage area of less than 3,000 ft2)) (0°C) and less than 55°F (12.8°C) that can be walked into, has a ceiling height of not less than 7 feet (2134 mm) and has a total chilled storage area of less than 3,000 square feet (279 m2).
WALK-IN FREEZER. An enclosed storage space capable of being refrigerated to temperatures at or below 32°F ((that can be walked into and has a total chilled storage area of less than 3,000 ft2)) (0°C) that can be walked into, has a ceiling height of not less than 7 feet (2134 mm) and has a total chilled storage area of less than 3,000 square feet (279 m2).
WALL. That portion of the building envelope, including opaque area and fenestration, that is vertical or tilted at an angle of 60 degrees from horizontal or greater. This includes above-grade walls and below-grade walls, between floor spandrels, peripheral edges of floors, and foundation walls.
WATER HEATER. Any heating appliance or equipment that heats potable water and supplies such water to the potable hot water distribution system.
WOOD-FRAMED AND OTHER WALLS. All other wall types, including wood stud walls.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-30310 Section 303.1—Identification.
C303.1 Identification. Materials, systems and equipment shall be identified in a manner that will allow a determination of compliance with the applicable provisions of this code.
C303.1.1 Building thermal envelope insulation. An R-value identification mark shall be applied by the manufacturer to each piece of building thermal envelope insulation 12 inches (305 mm) or greater in width. Alternately, the insulation installers shall provide a certification listing the type, manufacturer and R-value of insulation installed in each element of the building thermal envelope. For blown or sprayed insulation (fiberglass and cellulose), the initial installed thickness, settled thickness, settled R-value, installed density, coverage area and number of bags installed shall be listed on the certification. For sprayed polyurethane foam (SPF) insulation, the installed thickness of the areas covered and R-value of installed thickness shall be listed on the certification. For insulated siding, the R-value shall be labeled on the product's package and shall be listed on the certification. The insulation installer shall sign, date and post the certification in a conspicuous location on the job site.
C303.1.1.1 Blown or sprayed roof/ceiling insulation. The thickness of blown-in or sprayed roof/ceiling insulation (fiberglass or cellulose) shall be written in inches (mm) on markers that are installed at least one for every 300 square feet (28 m2) throughout the attic space. The markers shall be affixed to the trusses or joists and marked with the minimum initial installed thickness with numbers ((a minimum)) of not less than 1 inch (25 mm) in height. Each marker shall face the attic access opening. Spray polyurethane foam thickness and installed R-value shall be listed on certification provided by the insulation installer.
C303.1.2 Insulation mark installation. Insulating materials shall be installed such that the manufacturer's R-value mark is readily observable upon inspection.
C303.1.3 Fenestration product rating. U-factors of fenestration products (windows, doors and skylights) shall be determined in accordance with NFRC 100 by an accredited, independent laboratory, and labeled and certified by the manufacturer.
U-factors shall be determined by an accredited, independent laboratory, and labeled and certified by the manufacturer.
Products lacking such a labeled U-factor shall be assigned a default U-factor from Table C303.1.3(1), C303.1.3(2) or C303.1.3(4). The solar heat gain coefficient (SHGC) and visible transmittance (VT) of glazed fenestration products (windows, glazed doors and skylights) shall be determined in accordance with NFRC 200 by an accredited, independent laboratory, and labeled and certified by the manufacturer. Products lacking such a labeled SHGC or VT shall be assigned a default SHGC or VT from Table C303.1.3(3).
C303.1.4 Insulation product rating. The thermal resistance (R-value) of insulation shall be determined in accordance with the U.S. Federal Trade Commission R-value rule (C.F.R. Title 16, Part 460) in units of h x ft2 x °F/Btu at a mean temperature of 75°F (24°C).
C303.1.4.1 Insulated siding. The thermal resistance (R-Value) shall be determined in accordance with ASTM C1363. Installation for testing shall be in accordance with the manufacturer's installation instructions.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-303131 Table C303.1.3(1)—Default glazed fenestration U-factors.
Table C303.1.3(1)
Default Glazed Fenestration U-Factors
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-30320 Section C303.2—Installation.
C303.2 Installation. ((All)) Materials, systems and equipment shall be installed in accordance with the manufacturer's ((installation)) instructions and the International Building Code.
C303.2.1 Protection of exposed foundation insulation. Insulation applied to the exterior of basement walls, crawlspace walls and the perimeter of slab-on-grade floors shall have a rigid, opaque and weather-resistant protective covering to prevent the degradation of the insulation's thermal performance. The protective covering shall cover the exposed exterior insulation and extend ((a minimum of)) not less than 6 inches (153 mm) below grade.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40100 Section C401—General.
C401.1 Scope. The ((requirements contained)) provisions in this chapter are applicable to commercial buildings((, or portions of commercial buildings)) and their building sites.
C401.2 Application. Commercial buildings shall comply with one of the following:
1. The requirements of Sections C402, C403, C404, C405, C406, C408 ((and)), C409 and C410.
2. The requirements of Section C407, C408, C409, C410, C402.4, C403.2, C404, C405.2, C405.3, C405.4, C405.6 and C405.7. The building energy consumption shall be equal to or less than ((93)) 87 percent of the standard reference design building.
((C401.2.1 Application to existing buildings. Additions, alterations and repairs to existing buildings shall comply with Sections C402, C403, C404, C405, C408 and C409.))
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40210 Section C402.1—General (Prescriptive).
C402.1 General (Prescriptive). ((The)) Building thermal envelope ((shall)) assemblies for buildings that are intended to comply with ((Section C402.1.1. Section C402.1.2 or Section C402.1.3 shall be permitted as an alternative to the R-values specified in Section C402.1.1. Walk-in coolers and walk-in freezers shall comply with C402.5. Refrigerated warehouse coolers and refrigerated warehouse freezers shall comply with C402.6.
the code on a prescriptive basis, in accordance with the compliance path described in Item 1 of Section C401.2, shall comply with the following:
1. The opaque portions of the building thermal envelope shall comply with the specific insulation requirements of Section C402.2 and the thermal requirements of either the R-value based method of Section C402.1.3, the U-, C- and F-factor based method of Section C402.1.4, or the component performance alternative of Section C402.1.5.
2. Fenestration in building envelope assemblies shall comply with Section C402.5.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40211 Section C402.1.1—((Insulation and fenestration criteria)) Low energy buildings.
C402.1.1 ((Insulation and fenestration criteria. The building thermal envelope shall meet the requirements of Tables C402.2 and C402.3 based on the climate zone specified in Chapter 3. Commercial buildings or portions of commercial buildings enclosing Group R occupancies shall use the R-values from the "Group R" column of Table C402.2. Commercial buildings or portions of commercial buildings enclosing occupancies other than Group R shall use the R-values from the "All other" column of Table C402.2.)) Low energy buildings. The following buildings, or portions thereof, separated from the remainder of the building by building thermal envelope assemblies complying with this code shall be exempt from all thermal envelope provision of this code:
1. Those that are heated and/or cooled with a peak design rate of energy usage less than 3.4 Btu/hx ft2(10.7 W/m2) or 1.0 watt/ft2(10.7 W/m2) of floor area for space conditioning purposes.
2. Those that do not contain conditioned space.
3. Greenhouses where cooling does not include a condensing unit and that are isolated from any other conditioned space.
4. Unstaffed equipment shelters or cabinets used solely for personal wireless service facilities.
C402.1.1.1 Semi-heated buildings and spaces. The building envelope of semi-heated buildings, or portions thereof, shall comply with the same requirements as that for conditioned spaces in Section C402. Building envelope assemblies separating conditioned space from semi-heated space shall comply with exterior envelope insulation requirements. Semi-heated spaces heated by mechanical systems that do not include electric resistance heating equipment are not required to comply with the opaque wall insulation provisions of Section C402.2.3 for walls that separate semi-heated spaces from the exterior or low energy spaces. Semi-heated spaces shall be calculated separately from other conditioned spaces for compliance purposes. Opaque walls in semi-heated spaces shall be calculated as fully code compliant opaque walls for both the target and proposed for the Target UA calculations for Component Performance compliance per Section C402.1.5, and for the Standard Reference Design for Total Building Performance compliance per Section C407.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40212 Section C402.1.2—((U-factor alternative)) Equipment buildings.
C402.1.2 ((U-factor alternative. An assembly with a U-factor, C-factor, or F-factor equal or less than that specified in Table C402.1.2 shall be permitted as an alternative to the R-value in Table C402.2. Commercial buildings or portions of commercial buildings enclosing Group R occupancies shall use the U-factor, C-factor, or F-factor from the "Group R" column of Table C402.1.2. Commercial buildings or portions of commercial buildings enclosing occupancies other than Group R shall use the U-factor, C-factor or F-factor from the "All other" column of Table C402.1.2. The U-factors for typical construction assemblies are included in Appendix A. These values shall be used for all calculations. Where proposed construction assemblies are not represented in Appendix A, values shall be calculated in accordance with the ASHRAE Handbook—Fundamentals using the framing factors listed in Appendix A where applicable and shall include the thermal bridging effects of framing materials.)) Equipment buildings. Buildings that comply with all of the following shall be exempt from the building thermal envelope provisions of this code:
1. Are separate buildings with floor area no more than 500 square feet (50 m2).
2. Are intended to house electronic equipment with installed equipment power totaling at least 7 watts per square foot (75 W/m2) and not intended for human occupancy.
3. Have a heating system capacity not greater than (17,000 Btu/hr) (5 kW) and a heating thermostat set point that is restricted to not more than 50°F (10°C).
4. Have an average wall and roof U-factor less than 0.200.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-402121 Table ((C402.1.2)) C402.1.3—Opaque thermal envelope assembly R-value requirements.
((Table C402.1.2
Opaque Thermal Envelope Assembly Requirementsa
OPTION 1:
Table C402.1.3
Opaque Thermal Envelope Insulation Component
Minimum Requirements, R-value Methoda,g
This alternate nominal R-value compliance option is allowed for projects complying with all of the following:
For other cases where the proposed assembly is not continuous insulation, see Section C402.1.2 for determination of U-factors for assemblies that include metal other than screws and nails.
OPTION 2:
Table C402.1.3
Opaque Thermal Envelope Insulation Component
Minimum Requirements, R-value Methoda,g
This alternate nominal R-value compliance option is allowed for projects complying with all of the following:
For other cases where the proposed assembly is not continuous insulation, see Section C402.1.2 for determination of U-factors for assemblies that include metal other than screws and nails.
AMENDATORY SECTION (Amending WSR 14-24-122, filed 12/3/14, effective 1/3/15)
WAC 51-11C-40213 Section C402.1.3—((Component performance option)) Insulation component R-value method.
((C402.1.3 Component performance building envelope option.
C402.1.3.1 General. Buildings or structures whose design heat loss rate (UAp) and solar heat gain coefficient rate (SHGC * Ap) are less than or equal to the target heat loss rate (UAt) and solar heat gain coefficient rate (SHGC * At) shall be considered in compliance with this section. The stated U-factor, F-factor or allowable area of any component assembly, listed in Table C402.1.2 and Table C402.3, such as roof/ceiling, opaque wall, opaque door, fenestration, floor over conditioned space, slab-on-grade floor, radiant floor or opaque floor may be increased and the U-factor or F-factor for other components decreased, provided that the total heat gain or loss for the entire building envelope does not exceed the total resulting from compliance to the U-factors, F-factors or allowable areas specified in this section. Compliance shall be calculated in total for the building envelope for other than Group R spaces and for Group R spaces.
C402.1.3.2 Component U-factors. The U-factors for typical construction assemblies are included in Chapter 3 and Appendix A. These values shall be used for all calculations. Where proposed construction assemblies are not represented in Chapter 3 or Appendix A, values shall be calculated in accordance with the ASHRAE Handbook—Fundamentals, using the framing factors listed in Appendix A.
For envelope assemblies containing metal framing, the U-factor shall be determined by one of the following methods:
1. Results of laboratory measurements according to acceptable methods of test.
2. ASHRAE Handbook—Fundamentals where the metal framing is bonded on one or both sides to a metal skin or covering.
3. The zone method as provided in ASHRAE Handbook—Fundamentals.
4. Effective framing/cavity R-values as provided in Appendix A.
When return air ceiling plenums are employed, the roof/ceiling assembly shall:
a. For thermal transmittance purposes, not include the ceiling proper nor the plenum space as part of the assembly; and
b. For gross area purposes, be based upon the interior face of the upper plenum surface.
5. Tables in ASHRAE 90.1-2010 Normative Appendix A.
C402.1.3.3 UA calculations. The target UAt and the proposed UAp shall be calculated using Equations C402-1 and C402-2 and the corresponding areas and U-factors from Table C402.1.2 and Table C402.3. For the target UAt calculation, the skylights shall be located in roof/ceiling area up to the maximum skylight area per Section C402.3.1 and the remainder of the fenestration allowed per Section C402.3.1 shall be located in the wall area.
C402.1.3.4 SHGC rate calculations. Solar heat gain coefficient shall comply with Table C402.3. The target SHGCAt and the proposed SHGCAp shall be calculated using Equations C402-3 and C402-4 and the corresponding areas and SHGCs from Table C402.3.)) C402.1.3 Insulation component R-value-based method. Building thermal envelope opaque assemblies shall meet the requirements of Section C402.2 and C402.4 based on the climate zone specified in Chapter 3. For opaque portions of the building thermal envelope intended to comply on an insulation component R-value basis, the R-values for insulation in framing areas, where required, and for continuous insulation, where required, shall not be less than that specified in Table C402.1.3. Commercial buildings or portions of commercial buildings enclosing Group R occupancies shall use the R-values from the "Group R" column of Table C402.1.3. Commercial buildings or portions of commercial buildings enclosing occupancies other than Group R shall use the R-values from the "All other" column of Table C402.1.3. The thermal resistance or R-value of the insulating material installed in, or continuously on, below grade exterior walls of the building envelope required in accordance with Table C402.1.3 shall extend to the lowest floor of the conditioned space enclosed by the below grade wall. Doors having less than 50 percent opaque glass area shall be considered opaque doors. Opaque swinging doors shall comply with the Table C402.1.4 and opaque nonswinging doors shall comply with Table C402.1.3 or C402.1.4.
AMENDATORY SECTION (Amending WSR 14-24-122, filed 12/3/14, effective 1/3/15)
WAC 51-11C-402131 ((Equation C402-1—Target UAt.)) Reserved.
((Equation C402-1
Target UAt
AMENDATORY SECTION (Amending WSR 13-23-096, filed 11/20/13, effective 4/1/14)
WAC 51-11C-402132 ((Equation C402-2—Proposed UAp.)) Reserved.
((Equation C402-2
Proposed UAp
AMENDATORY SECTION (Amending WSR 13-23-096, filed 11/20/13, effective 4/1/14)
WAC 51-11C-402133 ((Equation C402-3—Target SHGCAt.)) Reserved.
((Equation C402-3
Target SHGCAt
AMENDATORY SECTION (Amending WSR 13-23-096, filed 11/20/13, effective 4/1/14)
WAC 51-11C-402134 ((Equation C402-4—Proposed SHGCAp.)) Reserved.
((Equation C402-4
Proposed SHGCAp
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40214 Section C402.1.4—((Semi-heated spaces)) Assembly U-factor, C-factor, or F-factor-based method.
C402.1.4 ((Semi-heated spaces. All spaces shall comply with the requirements in Section C402 unless they meet the definition for semi-heated spaces. For semi-heated spaces, the building envelope shall comply with the same requirements as that for conditioned spaces in Section C402; however, for semi-heated spaces heated by other than electric resistance heating equipment, wall insulation is not required for those walls that separate semi-heated spaces from the exterior provided that the space meets all the requirements of semi-heated space. Semi-heated spaces shall be calculated separately from other conditioned spaces for compliance purposes. Building envelope assemblies separating conditioned space from semi-heated space shall comply with exterior envelope insulation requirements. When choosing the uninsulated wall option, the wall shall not be included in Component Performance Building Envelope Option calculation.)) Assembly U-factor, C-factor, or F-factor-based method. Building thermal envelope opaque assemblies intended to comply on an assembly U-, C-, or F-factor basis shall have a U-, C-, or F-factor not greater than that specified in Table C402.1.4. Commercial buildings or portions of commercial buildings enclosing Group R occupancies shall use the U-, C-, or F-factor from the "Group R" column of Table C402.1.4. Commercial buildings or portions of commercial buildings enclosing occupancies other than Group R shall use the U-, C-, or F-factor from the "All other" column of Table C402.1.4. The C-factor for the below-grade exterior walls of the building envelope, as required in accordance with Table C402.1.4, shall extend to the level of the lowest conditioned floor. Opaque swinging doors shall comply with Table C402.1.4 and opaque nonswinging doors shall comply with Table C402.1.3 or C402.1.4. The U-factors for typical construction assemblies are included in Appendix A. These values shall be used for all calculations. Where proposed construction assemblies are not represented in Appendix A, values shall be calculated in accordance with the ASHRAE Handbook—Fundamentals using the framing factors listed in Appendix A where applicable and shall include the thermal bridging effects of framing materials.
C402.1.4.1 Thermal resistance of cold-formed steel walls. U-factors of walls with cold-formed steel studs shall be permitted to be determined in accordance with Equation 4-1:
Equation 4-1:
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040. NEW SECTION
WAC 51-11C-402141 Table C402.1.4—Opaque thermal envelope requirements, U-factor method.
OPTION 1:
Table C402.1.4
Opaque Thermal Envelope Requirementsa,f
OPTION 2:
Table C402.1.4
Opaque Thermal Envelope Requirementsa,f
NEW SECTION
WAC 51-11C-402142 Table C402.1.4.1—Effective R-values for steel stud wall assemblies.
Table C402.1.4.1
Effective R-values For Steel Stud Wall Assemblies
NEW SECTION
WAC 51-11C-40215 Section C402.1.5—Component performance alternative.
C402.1.5 Component performance alternative. Building envelope values and fenestration areas determined in accordance with Equation 4-2 shall be permitted in lieu of compliance with the U-factors and F-factors in Table C402.1.4 and C402.4 and the maximum allowable fenestration areas in Section C402.4.1.
Equation 4-2
C402.1.5.1 Component U-factors. The U-factors for typical construction assemblies are included in Chapter 3 and Appendix A. These values shall be used for all calculations. Where proposed construction assemblies are not represented in Chapter 3 or Appendix A, values shall be calculated in accordance with the ASHRAE Handbook—Fundamentals, using the framing factors listed in Appendix A.
For envelope assemblies containing metal framing, the U-factor shall be determined by one of the following methods:
1. Results of laboratory measurements according to acceptable methods of test.
2. ASHRAE Handbook—Fundamentals where the metal framing is bonded on one or both sides to a metal skin or covering.
3. The zone method as provided in ASHRAE Handbook—Fundamentals.
4. Effective framing/cavity R-values as provided in Appendix A.
When return air ceiling plenums are employed, the roof/ceiling assembly shall:
a. For thermal transmittance purposes, not include the ceiling proper nor the plenum space as part of the assembly; and
b. For gross area purposes, be based upon the interior face of the upper plenum surface.
5. Tables in ASHRAE 90.1-2010 Normative Appendix A.
C402.1.5.2 SHGC rate calculations. Solar heat gain coefficient shall comply with Table C402.4. The target SHGCAt and the proposed SHGCAp shall be calculated using Equations 4-3 and 4-4 and the corresponding areas and SHGCs from Table C402.4.
Equation 4-3—Target SHGCAt
Equation C402-3
Target SHGCAt
Equation 4-4
Proposed SHGCAp
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40220 Section C402.2—Specific insulation requirements.
C402.2 Specific building thermal envelope insulation requirements (Prescriptive). ((Opaque assemblies shall comply with Table C402.2. Where two or more layers of continuous insulation board are used in a construction assembly, the continuous insulation boards shall be installed in accordance with Section C303.2. If the continuous insulation board manufacturer's installation instructions do not address installation of two or more layers, the edge joints between each layer of continuous insulation boards shall be staggered.)) Insulation in building thermal envelope opaque assemblies shall comply with Sections C402.2.1 through C402.2.6 and Table C402.1.3.
AMENDATORY SECTION (Amending WSR 13-23-096, filed 11/20/13, effective 4/1/14)
WAC 51-11C-402200 ((Table C402.2—Opaque thermal envelope requirements.)) Reserved.
((Table C402.2
Opaque Thermal Envelope Requirementsa, f
This alternate nominal R-value compliance option is allowed for projects complying with all of the following:
For other cases where the proposed assembly is not continuous insulation, see Section C402.1.2 for determination of U-factors for assemblies that include metal other than screws and nails.))
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40221 Section C402.2.1—((Roof assembly)) Multiple layers of continuous insulation.
((C402.2.1 Roof assembly. The minimum thermal resistance (R-value) of the insulating material installed either between the roof framing or continuously on the roof assembly shall be as specified in Table C402.2, based on construction materials used in the roof assembly. Skylight curbs shall be insulated to the level of roofs with insulation entirely above deck or R-5, whichever is less.
Insulation installed on a suspended ceiling with removable ceiling tiles shall not be considered part of the minimum thermal resistance of the roof insulation.
C402.2.1.1 Roof solar reflectance and thermal emittance. Low-sloped roofs, with a slope less than 2 units vertical in 12 horizontal, directly above cooled conditioned spaces in Climate Zones 1, 2, and 3 shall comply with one or more of the options in Table C402.2.1.1.
C402.2.1 Multiple layers of continuous insulation. Where two or more layers of continuous insulation board are used in a construction assembly, the continuous insulation boards shall be installed in accordance with Section C303.2. If the continuous insulation board manufacturer's installation instructions do not address installation of two or more layers, the edge joints between each layer of continuous insulation boards shall be staggered.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-402211 ((Table C402.2.1.1—Reflectance and emittance options.)) Reserved.
((Table C402.2.1.1
Reflectance and Emittance Optionsa
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40222 Section C402.2.2—((Classification of walls)) Roof assembly.
C402.2.2 ((Classification of walls. Walls associated with the building envelope shall be classified in accordance with Section C202.)) Roof assembly. The minimum thermal resistance (R-value) of the insulating material installed either between the roof framing or continuously on the roof assembly shall be as specified in Table C402.1.3, based on construction materials used in the roof assembly. Skylight curbs shall be insulated to the level of roofs with insulation entirely above deck or R-5, whichever is less.
Insulation installed on a suspended ceiling with removable ceiling tiles shall not be considered part of the minimum thermal resistance of the roof insulation.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40223 Section C402.2.3—Above-grade walls.
C402.2.3 Thermal resistance of above-grade walls. The minimum thermal resistance (R-value) of ((the insulating)) materials installed in the wall cavity between the framing members and continuously on the walls shall be as specified in Table ((C402.2)) C402.1.3, based on framing type and construction materials used in the wall assembly. The R-value of integral insulation installed in concrete masonry units (CMU) shall not be used in determining compliance with Table ((C402.2)) C402.1.3.
"Mass walls" shall include walls ((weighing not less than)):
1. Weighing not less than 35 psf (170 kg/m2) of wall surface area((; or)).
2. Weighing not less than 25 psf (120 kg/m2) of wall surface area ((if)) where the material weight is not more than 120 pounds per cubic foot (pcf) (1,900 kg/m3).
3. Having a heat capacity exceeding 7 Btu/ft2 x °F (144 kJ/m2 x K).
4. Having a heat capacity exceeding 5 Btu/ft2 x °F (103 kJ/m2 x K) where the material weight is not more than 120 pcf (1900 kg/m3).
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40224 Section C402.2.4—Below-grade walls.
C402.2.4 Thermal resistance of below-grade walls. The minimum thermal resistance (R-value) of the insulating material installed in, or continuously on, the below-grade walls shall be as specified in Table ((C402.2)) C402.1.3.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40225 Section C402.2.5—Floors ((over unconditioned space)).
((C402.2.5 Floors over outdoor air or unconditioned space. The minimum thermal resistance (R-value) of the insulating material installed either between the floor framing or continuously on the floor assembly shall be as specified in Table C402.2, based on construction materials used in the floor assembly.
"Mass floors" shall include floors weighing not less than:
1. 35 psf (170 kg/m2) of floor surface area; or
2. 25 psf (120 kg/m2) of floor surface area if the material weight is not more than 120 pcf (1,900 kg/m3).)) C402.2.5 Floors. The thermal properties (component R-values or assembly U- or F-factors) of floor assemblies over outdoor air or unconditioned space shall be as specified in Table C402.1.3 or C402.1.4 based on the construction materials used in the floor assembly. Floor framing cavity insulation or structural slab insulation shall be installed to maintain permanent contact with the underside of the subfloor decking or structural slabs.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40226 Section C402.2.6—Slab-on-grade perimeter insulation.
C402.2.6 Slabs-on-grade perimeter insulation. Where the slab-on-grade is in contact with the ground, the minimum thermal resistance (R-value) of the insulation around the perimeter of unheated or heated slab-on-grade floors designed in accordance with the R-value method of Section C402.1.3 shall be as specified in Table ((C402.2)) C402.1.3. The insulation shall be placed on the outside of the foundation or on the inside of the foundation wall. The insulation shall extend downward from the top of the slab for a minimum distance as shown in the table or to the top of the footing, whichever is less, or downward to at least the bottom of the slab and then horizontally to the interior or exterior for the total distance shown in the table. Insulation extending away from the building shall be protected by pavement or by a minimum of 10 inches (254 mm) of soil. Insulation complying with Table C402.1.3 shall be provided under the entire area of heated slabs on grade.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40227 ((Section C402.2.7—Opaque doors.)) Reserved.
((C402.2.7 Opaque doors. Opaque doors (doors having less than 50 percent glass area) shall meet the applicable requirements for doors as specified in Table C402.2 and be considered as part of the gross area of above-grade walls that are part of the building envelope.))
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40228 Section C402.2.8—Insulation of radiant heating systems.
C402.2.8 Insulation of radiant heating systems. Radiant heating system panels, and their associated ((U-bends and headers, designed for sensible heating of an indoor space through heat transfer from the thermally effective panel surfaces to the occupants or indoor space by thermal radiation and natural convection and the bottom surfaces of floor structures incorporating radiant heating shall be insulated with a minimum of R-3.5 (0.62 m2/K × W))) components that are installed in interior or exterior assemblies shall be insulated with a minimum of R-3.5 (0.62 m2/K × W) on all surfaces not facing the space being heated. Radiant heating systems panels that are installed in the building thermal envelope shall be separated from the exterior of the building or unconditioned or exempt spaces by not less than the R-value of insulation installed in the opaque assembly in which they are installed or the assembly shall comply with Section C402.1.4.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40230 Section ((C402.3)) C402.4—Fenestration (Prescriptive).
C402.3 Reserved.
C402.4 Fenestration (Prescriptive). Fenestration shall comply with ((Table C402.3. Automatic daylighting controls specified by this section shall comply with Section C405.2.2.3.2)) Sections C402.4 through C402.4.4 and Table C402.4, Daylight responsive controls shall comply with this section and Section C405.2.4.1.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-402300 Table ((C402.3)) C402.4—Building envelope requirements—Fenestration.
Table ((C402.3)) C402.4
Building Envelope ((Requirements—))Fenestration Maximum U-factor and SHGC Requirements
AMENDATORY SECTION (Amending WSR 13-23-096, filed 11/20/13, effective 4/1/14)
WAC 51-11C-40231 Section ((C402.3.1)) C402.4.1—Maximum area.
((C402.3.1)) C402.4.1 Maximum area. The vertical fenestration area (not including opaque doors and opaque spandrel panels) shall not exceed 30 percent of the gross above-grade wall area. The skylight area shall not exceed ((3)) 5 percent of the gross roof area.
((C402.3.1.1)) C402.4.1.1 Increased vertical fenestration area with ((daylighting)) daylight responsive controls. ((In Climate Zones 1 through 6,)) A maximum of 40 percent of the gross above-grade wall area shall be permitted to be vertical fenestration for the purpose of prescriptive compliance with Section C402.1.4 or for the component performance alternative in Section C402.1.5, provided all of the following requirements are met:
1. In buildings not greater than two stories above grade, no less than 50 percent of the conditioned floor area is within a daylight zone((;)).
2. ((Automatic daylighting)) In buildings three or more stories above grade, not less than 25 percent of the net floor area is within a daylight zone.
3. Daylight responsive controls complying with Section C402.2.3.1 are installed in daylight zones((; and
3)).
4. Visible transmittance (VT) of vertical fenestration is greater than or equal to 1.1 times solar heat gain coefficient (SHGC).
((C402.3.1.2 Increased skylight area with daylighting controls. The skylight area shall be permitted to be a maximum of 5 percent of the roof area provided automatic daylighting controls are installed in daylight zones under skylights.
C402.3.1.3)) C402.4.1.2 Reserved.
C402.4.1.3 Increased vertical fenestration area with high-performance fenestration. The vertical fenestration area (not including opaque doors and opaque spandrel panels) is permitted to exceed 30 percent but shall not exceed 40 percent of the gross above grade wall area, for the purpose of prescriptive compliance with Section ((C402.1.2 or for the target UA calculation in Equation C402-1,)) C402.1.3 provided that each of the following conditions are met:
1. The vertical fenestration shall have the following U-factors:
a. Nonmetal framing (all) = 0.28
b. Metal framing (fixed) = 0.34
c. Metal framing (operable) = 0.36
d. Metal framing (entrance doors) = 0.60
2. The SHGC of the vertical fenestration shall be less than or equal to 0.35, adjusted for projection factor in compliance with ((C402.3.3.1)) C402.4.3.1.
An area-weighted average shall be permitted to satisfy the U-factor requirement for each fenestration product category listed in Item 1 of this section. Individual fenestration products from different fenestration product categories shall not be combined in calculating the area-weighted average U-factor.
The compliance path described in this section is not permitted to be used for the total building performance compliance path in Section C407. The compliance path described in this section is permitted to be used for the component performance alternative in Section C402.1.5, provided that the requirements of Section C402.1.5 are met.
C402.4.1.4 Increased vertical fenestration area with high-performance mechanical systems. The vertical fenestration area (not including opaque doors and opaque spandrel panels) is permitted to exceed 30 percent but shall not exceed 40 percent of the gross above-grade wall area, for the purpose of prescriptive compliance with Section C402.1.4 or for the component performance alternative in Section C402.1.5, provided that the mechanical system complies with all requirements of Section C403.2.6.1 Dedicated outdoor air systems (DOAS). This increased glazing fraction is not permitted to be used to establish the reference case for the Total Building Performance compliance path in Section C407.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40232 Section ((C402.3.2)) C402.4.2—Minimum skylight fenestration area.
((C402.3.2)) C402.4.2 Minimum skylight fenestration area. For single story buildings only, in an enclosed space greater than ((10,000)) 2,500 square feet (((929)) 232 m2) in floor area, directly under a roof with not less than 75 percent of the ceiling area with a ceiling height((s)) greater than 15 feet (4572 mm), and used as an office, lobby, atrium, concourse, corridor, gymnasium/exercise center, convention center, automotive service, manufacturing, nonrefrigerated warehouse, retail store, distribution/sorting area, transportation, or workshop, the total daylight zone under skylights shall be not less than half the floor area and shall provide ((a minimum skylight area to daylight zone under skylights of either)) one of the following:
1. A minimum skylight area to daylight zone under skylights of not less than 3 percent ((with a)) where all skylights have a VT of at least 0.40((; or)) as determined in accordance with Section C303.1.3.
2. ((Provide)) A minimum skylight effective aperture of at least 1 percent determined in accordance with Equation ((C4-1)) 4-5.
(Equation ((C4-1)) 4-5)
((C402.3.2.1)) C402.4.2.1 Lighting controls in daylight zones under skylights. ((All lighting in the daylight zone shall be controlled by automatic daylighting controls that comply with Section C405.2.2.3.2.
C402.3.2.2)) Daylight responsive controls complying with Section C405.2.4.1 shall be provided to control all electric lights within daylight zones.
C402.4.2.2 Haze factor. Skylights in office, storage, automotive service, manufacturing, nonrefrigerated warehouse, retail store, and distribution/sorting area spaces shall have a glazing material or diffuser with a ((measured)) haze factor greater than 90 percent when tested in accordance with ASTM D 1003.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40233 Section ((C402.3.3)) C402.4.3—Maximum U-factor and SHGC.
((C402.3.3)) C402.4.3 Maximum U-factor and SHGC. ((For vertical fenestration,)) The maximum U-factor and solar heat gain coefficient (SHGC) for fenestration shall be as specified in Table ((C402.3, based on the window projection factor. For skylights, the maximum U-factor and solar heat gain coefficient (SHGC) shall be as specified in Table C402.3)) C402.4.
The window projection factor shall be determined in accordance with Equation ((C4-2)) 4-6.
PF = A/B
(Equation ((C4-2)) 4-6)
Where different windows or glass doors have different PF values, they shall each be evaluated separately.
((C402.3.3.1 SHGC adjustment. Where the fenestration projection factor for a specific vertical fenestration product is greater than or equal to 0.2, the required maximum SHGC from Table C402.3 shall be adjusted by multiplying the required maximum SHGC by the multiplier specified in Table C402.3.3.1 corresponding with the orientation of the fenestration product and the projection factor.
Table C402.3.3.1
SHGC Adjustment Multipliers
C402.3.3.2 Increased vertical fenestration SHGC. In Climate Zones 1, 2 and 3, vertical fenestration entirely located not less than 6 feet (1729 mm) above the finished floor shall be permitted a maximum SHGC of 0.40.
C402.3.3.3 Reserved.
C402.3.3.4 Reserved.
C402.3.3.5 Dynamic glazing. For compliance with Section C402.3.3, the SHGC for dynamic glazing shall be determined using the manufacturer's lowest-rated SHGC, and the VT/SHGC ratio shall be determined using the maximum VT and maximum SHGC. Dynamic glazing shall be considered separately from other fenestration, and area-weighted averaging with other fenestration that is not dynamic glazing shall not be permitted.)) C402.4.3.1 Reserved.
C402.4.3.2 Reserved.
C402.4.3.3 Dynamic glazing. Where dynamic glazing is intended to satisfy the SHGC and VT requirements of Table C402.4, the ratio of the higher to lower labeled SHGC shall be greater than or equal to 2.4, and the dynamic glazing shall be automatically controlled to modulate the amount of solar gain into the space in multiple steps. Dynamic glazing shall be considered separately from other fenestration, and area-weighted averaging with other fenestration that is not dynamic glazing shall not be permitted.
C402.4.3.4 Area-weighted U-factor. An area-weighted average shall be permitted to satisfy the U-factor requirements for each fenestration product category listed in Table C402.4. Individual fenestration products from different fenestration product categories listed in Table C402.4 shall not be combined in calculating area-weighted average U-factor.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40234 Section ((C402.3.4—Area-weighted U-factor)) C402.4.4—Doors.
((C402.3.4 Area-weighted U-factor. An area-weighted average shall be permitted to satisfy the U-factor requirements for each fenestration product category listed in Table C402.3. Individual fenestration products from different fenestration product categories listed in Table C402.3 shall not be combined in calculating area-weighted average U-factor.)) C402.4.4 Doors. Opaque doors shall comply with the applicable requirements for doors as specified in Tables C402.1.3 and C402.1.4 and be considered part of the gross area of above grade walls that are part of the building thermal envelope. Other doors shall comply with the provisions of Section C402.4.3 for vertical fenestration.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40240 Section ((C402.4)) C402.5—Air leakage-thermal envelope.
((C402.4)) C402.5 Air leakage-thermal envelope (Mandatory). The thermal envelope of buildings shall comply with Sections ((C402.4.1 through C402.4.8)) C402.5.1 through C402.5.8.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40241 Section ((C402.4.1)) C402.5.1—Air barriers.
((C402.4.1)) C402.5.1 Air barriers. A continuous air barrier shall be provided throughout the building thermal envelope. The air barriers shall be permitted to be located on the inside or outside of the building envelope, located within the assemblies composing the envelope, or any combination thereof. The air barrier shall comply with Sections ((C402.4.1.1 and C402.4.1.2)) C402.5.1.1 and C402.5.1.2.
C402.4.1.1)) C402.5.1.1 Air barrier construction. The continuous air barrier shall be constructed to comply with the following:
1. The air barrier shall be continuous for all assemblies that are the thermal envelope of the building and across the joints and assemblies.
2. Air barrier joints and seams shall be sealed, including sealing transitions in places and changes in materials. ((Air barrier penetrations shall be sealed in accordance with Section C402.4.2.)) The joints and seals shall be securely installed in or on the joint for its entire length so as not to dislodge, loosen or otherwise impair its ability to resist positive and negative pressure from wind, stack effect and mechanical ventilation.
3. Penetrations of the air barrier shall be caulked, gasketed or otherwise sealed in a manner compatible with the construction materials and location. Joints and seals associated with penetrations shall be sealed in the same manner or taped or covered with moisture vapor-permeable wrapping material. Sealing materials shall be appropriate to the construction materials being sealed and shall be securely installed around the penetration so as not to dislodge, loosen or otherwise impair the penetrations' ability to resist positive and negative pressure from wind, stack effect, and mechanical ventilation. Sealing of concealed fire sprinklers, where required, shall be in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids between fire sprinkler cover plates and walls or ceilings.
4. Recessed lighting fixtures shall comply with Section ((C404.2.8)) C402.5.8. Where similar objects are installed which penetrate the air barrier, provisions shall be made to maintain the integrity of the air barrier.
C402.4.1.2 Air barrier compliance options. A continuous air barrier for the opaque building envelope shall comply with Section C402.4.1.2.3.
C402.4.1.2.1 Materials. Materials with an air permeability no greater than 0.004 cfm/ft2 (0.02 L/s • m2) under a pressure differential of 0.3 inches water gauge (w.g.) (75 Pa) when tested in accordance with ASTM E 2178 shall comply with this section. Materials in Items 1 through 15 shall be deemed to comply with this section provided joints are sealed and materials are installed as air barriers in accordance with the manufacturer's instructions.
1. Plywood with a thickness of not less than 3/8 inch (10 mm).
2. Oriented strand board having a thickness of not less than 3/8 inch (10 mm).
3. Extruded polystyrene insulation board having a thickness of not less than 1/2 inch (12 mm).
4. Foil-back polyisocyanurate insulation board having a thickness of not less than 1/2 inch (12 mm).
5. Closed cell spray foam a minimum density of 1.5 pcf (2.4 kg/m3) having a thickness of not less than 1 1/2 inches (36 mm).
6. Open cell spray foam with a density between 0.4 and 1.5 pcf (0.6 and 2.4 kg/m3) and having a thickness of not less than 4.5 inches (113 mm).
7. Exterior or interior gypsum board having a thickness of not less than 1/2 inch (12 mm).
8. Cement board having a thickness of not less than 1/2 inch (12 mm).
9. Built up roofing membrane.
10. Modified bituminous roof membrane.
11. Fully adhered single-ply roof membrane.
12. A Portland cement/sand parge, or gypsum plaster having a thickness of not less than 5/8 inch (16 mm).
13. Cast-in-place and precast concrete.
14. Fully grouted concrete block masonry.
15. Sheet steel or aluminum.
C402.4.1.2.2 Assemblies. Assemblies of materials and components with an average air leakage not to exceed 0.04 cfm/ft2 (0.2 L/s • m2) under a pressure differential of 0.3 inches of water gauge (w.g.)(75 Pa) when tested in accordance with ASTM E 2357, ASTM E 1677 or ASTM E 283 shall comply with this section. Assemblies listed in Items 1 and 2 shall be deemed to comply provided joints are sealed and requirements of Section C402.4.1.1 are met.
1. Concrete masonry walls coated with one application either of block filler and two applications of a paint or sealer coating;
2. A Portland cement/sand parge, stucco or plaster minimum 1/2 inch (12 mm) in thickness.
C402.4.1.2.3)) 5. Construction documents shall contain a diagram showing the building's pressure boundary in plan(s) and section(s) and a calculation of the area of the pressure boundary to be considered in the test.
C402.5.1.2 Building test. The completed building shall be tested and the air leakage rate of the building envelope shall not exceed 0.40 cfm/ft2 at a pressure differential of 0.3 inches water gauge (2.0 L/s • m2 at 75 Pa) at the upper 95 percent confidence interval in accordance with ASTM E 779 or an equivalent method approved by the code official. A report that includes the tested surface area, floor area, air by volume, stories above grade, and leakage rates shall be submitted to the building owner and the Code Official. If the tested rate exceeds that defined here, a visual inspection of the air barrier shall be conducted and any leaks noted shall be sealed to the extent practicable. An additional report identifying the corrective actions taken to seal air leaks shall be submitted to the building owner and the Code Official and any further requirement to meet the leakage air rate will be waived.
1. Test shall be accomplished using either (1) both pressurization and depressurization or (2) pressurization alone, but not depressurization alone. If both pressurization and depressurization are not tested, the air leakage shall be plotted against the corrected P for pressurization in accordance with Section 9.4.
2. The test pressure range shall be from 25 Pa to 80 Pa per Section 8.10, but the upper limit shall not be less than 50 Pa, and the difference between the upper and lower limit shall not be less than 25 Pa.
3. If the pressure exponent n is less than 0.45 or greater than 0.85 per Section 9.6.4, the test shall be rerun with additional readings over a longer time interval.
C402.5.1.2.1 Building test for mixed-use buildings. Where a building is three or fewer stories above grade plane and contains both commercial and residential uses, the air barrier of the R-2 and R-3 occupancy areas of the building is permitted to be separately tested according to Section R402.X. Alternatively, it is permissible to test the air barrier of the entire building according to Section C402.5.1.2, provided that the tested air leakage rate does not exceed the rate specified in Section C402.5.1.2.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40242 ((Section C402.4.2—Air barrier penetrations.)) Reserved.
((C402.4.2 Air barrier penetrations. Penetrations of the air barrier and paths of air leakage shall be caulked, gasketed or otherwise sealed in a manner compatible with the construction materials and location. Joints and seals shall be sealed in the same manner or taped or covered with a moisture vapor-permeable wrapping material. Sealing materials shall be appropriate to the construction materials being sealed. The joints and seals shall be securely installed in or on the joint for its entire length so as not to dislodge, loosen or otherwise impair its ability to resist positive and negative pressure from wind, stack effect and mechanical ventilation.))
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40243 Section ((C402.4.3—Air leakage of fenestration)) C402.5.3—Rooms containing fuel-burning appliances.
((C402.4.3 Air leakage of fenestration. The air leakage of fenestration assemblies shall meet the provisions of Table C402.4.3. Testing shall be in accordance with the applicable reference test standard in Table C402.4.3 by an accredited, independent testing laboratory and labeled by the manufacturer.
Table C402.4.3
Maximum Air Infiltration Rate
for Fenestration Assemblies
C402.5.3 Rooms containing fuel-burning appliances. Where open combustion air ducts provide combustion air to open combustion space conditioning fuel-burning appliances, the appliances and combustion air openings shall be located outside of the building thermal envelope or enclosed in a room isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table C402.1.3 or C402.1.4, where the walls, floors and ceilings shall meet the minimum of the below-grade wall R-value requirement. The door into the room shall be fully gasketed, and any water lines and ducts in the room insulated in accordance with Section C403. The combustion air duct shall be insulated, where it passes through conditioned space, to a minimum of R-8.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40244 Section ((C402.4.4)) C402.5.4—Doors and access openings.
((C402.4.4)) C402.5.4 Doors and access openings to shafts, chutes, stairways, and elevator lobbies. Doors and access openings from conditioned space to shafts, chutes, stairways and elevator lobbies ((shall either meet the requirements of)) not within the scope of the fenestration assemblies covered by Section ((C402.4.3 or)) C402.5.2 shall be gasketed, weatherstripped or sealed.
AMENDATORY SECTION (Amending WSR 14-24-054, filed 11/25/14, effective 5/1/15)
WAC 51-11C-40245 Section ((C402.4.5)) C402.5.5—Air intakes, exhaust openings, stairways and shafts.
((C402.4.5)) C402.5.5 Air intakes, exhaust openings, stairways and shafts. Stairway enclosures ((and)), elevator shaft vents and other outdoor air intakes and exhaust openings integral to the building envelope shall be provided with dampers in accordance with Section((s C402.4.5.1 and C402.4.5.2.
C402.4.5.1 Stairway and shaft vents. Stairway and shaft vents shall be provided with Class I motorized dampers with a maximum leakage rate of 4 cfm/ft2 (20.3 L/s • m2) at 1.0 inch water gauge (w.g.) (249 Pa) when tested in accordance with AMCA 500D.
Stairway and shaft vent dampers shall be installed with controls so that they are capable of automatically opening upon:
1. The activation of any fire alarm initiating device of the building's fire alarm system; or
2. The interruption of power to the damper.
C402.4.5.2 Outdoor air intakes, exhaust outlets, relief outlets, and return openings. Outdoor air supply, exhaust openings and relief outlets shall be provided with Class I motorized dampers which close automatically when the system is off. Dampers shall have a maximum leakage rate of 4 cfm/ft2 (20.3 L/s • m2) at 1.0 inch water gauge (w.g.) (249 Pa) when tested in accordance with AMCA 500D.
Return air openings used for airside economizer operation shall be equipped with Class I motorized dampers. Dampers shall have a maximum leakage rate of 4 cfm/ft2 (20.3 L/s • m2) at 1.0 inch water gauge (w.g.) (249 Pa) when tested in accordance with AMCA 500D.
See also section C403.2.4.4 for additional requirements from damper shut-off controls.
C403.2.4.3.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40246 Section ((C402.4.6)) C402.5.6—Loading dock weatherseals.
((C402.4.6)) C402.5.6 Loading dock weatherseals. Cargo doors and loading dock doors shall be equipped with weatherseals to restrict infiltration when vehicles are parked in the doorway.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40247 Section ((C402.4.7)) C402.5.7—Vestibules.
((C402.4.7)) C402.5.7 Vestibules. All building entrances shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices. Vestibules shall be designed so that in passing through the vestibule it is not necessary for the interior and exterior doors to open at the same time. The installation of one or more revolving doors in the building entrance shall not eliminate the requirement that a vestibule be provided on any doors adjacent to revolving doors. For the purposes of this section, "building entrances" shall include exit-only doors in buildings where separate doors for entering and exiting are provided.
Interior and exterior doors shall have a minimum distance between them of not less than 7 feet. The exterior envelope of conditioned vestibules shall comply with the requirements for a conditioned space. Either the interior or exterior envelope of unconditioned vestibules shall comply with the requirements for a conditioned space. The building lobby is not considered a vestibule.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40248 Section ((C402.4.8)) C402.5.8—Recessed lighting.
((C402.4.8)) C402.5.8 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be ((sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC-rated and)) all of the following:
1. IC rated.
2. Labeled as having an air leakage rate of not more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E 283 at a 1.57 psf (75 Pa) pressure differential.
((All recessed luminaires shall be)) 3. Sealed with a gasket or caulk between the housing and interior wall or ceiling covering.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40250 ((Section C402.5—Walk-in coolers and walk-in freezers.)) Reserved.
((C402.5 Walk-in coolers and walk-in freezers. Walk-in coolers and walk-in freezers shall comply with all of the following:
1. Shall be equipped with automatic door closers that firmly close walk-in doors that have been closed to within 1 inch of full closure.
2. Doorways shall have strip doors (curtains), spring-hinged doors, or other method of minimizing infiltration when doors are open.
3. Walk-in coolers shall contain wall, ceiling, and door insulation of at least R-25 and walk-in freezers at least R-32.
4. Walk-in freezers shall contain floor insulation of at least R-28.
5. Transparent reach-in doors for walk-in freezers and windows in walk-in freezer doors shall be of triple-pane glass, either filled with inert gas or with heat-reflective treated glass.
6. Transparent reach-in doors for walk-in coolers and windows in walk-in cooler doors shall be double-pane glass with heat-reflective treated glass and gas filled; or triple-pane glass, either filled with inert gas or with heat-reflective treated glass.))
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40260 ((Section C402.6—Refrigerated warehouse coolers and freezers.)) Reserved.
((C402.6 Refrigerated warehouse coolers and refrigerated warehouse freezers. Refrigerated warehouse coolers and refrigerated warehouse freezers shall comply with all of the following:
1. Shall be equipped with automatic door closers that firmly close walk-in doors that have been closed to within 1 inch of full closure.
2. Doorways shall have strip doors (curtains), spring-hinged doors, or other method of minimizing infiltration when doors are open.
3. Refrigerated warehouse coolers shall contain wall, ceiling, and door insulation of at least R-25 and refrigerated warehouse freezers at least R-32.
4. Refrigerated warehouse freezers shall contain floor insulation of at least R-28.
5. Transparent reach-in doors for refrigerated warehouse freezers and windows in refrigerated warehouse freezer doors shall be of triple-pane glass, either filled with inert gas or with heat-reflective treated glass.
6. Transparent reach-in doors for refrigerated warehouse coolers and windows in refrigerated warehouse cooler doors shall be double-pane glass with heat-reflective treated glass and gas filled; or triple-pane glass, either filled with inert gas or with heat-reflective treated glass.))
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40310 Section C403.1—General.
C403.1 General. Mechanical systems and equipment serving heating, cooling, ventilating, and other needs shall comply with Section C403.2 (((referred to as the mandatory provisions) and either:
1. Section C403.3 (Simple systems); or
2. Section C403.4 (Complex systems).)) and shall comply with Sections C403.3 and C403.4 based on the equipment and systems provided.
((Walk-in coolers and walk-in freezers shall comply with Section C403.5. Refrigerated warehouse coolers and refrigerated warehouse freezers shall comply with Section C403.6.))
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40320 Section C403.2—Provisions applicable to all mechanical systems.
C403.2 Provisions applicable to all mechanical systems (Mandatory). Mechanical systems and equipment serving the building heating, cooling or ventilating needs shall comply with Sections C403.2.1 through ((C403.2.11)) C403.2.13.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40321 Section C403.2.1—Calculation of heating and cooling loads.
C403.2.1 Calculation of heating and cooling loads. Design loads associated with heating, ventilating and air conditioning of the building shall be determined in accordance with the procedures described in ANSI/ASHRAE/ACCA Standard 183((. The design loads shall account for the building envelope, lighting, ventilation and occupancy loads based on the project design)) or by an approved equivalent computational procedure, using the design parameters specified in Chapter 3. Heating and cooling loads shall be adjusted to account for load reductions that are achieved where energy recovery systems are utilized in the HVAC system in accordance with the ASHRAE HVAC Systems and Equipment Handbook((. Alternatively, design loads shall be determined by an approved equivalent computation procedure, using the design parameters specified in Chapter 3)) by an approved equivalent computational procedure.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40322 Section C403.2.2—Equipment and systems sizing.
C403.2.2 Equipment and system sizing. The output capacity of heating and cooling equipment ((and systems shall not)) shall be no greater than that of the smallest available equipment size that exceeds the loads calculated in accordance with Section C403.2.1. A single piece of equipment providing both heating and cooling shall satisfy this provision for one function with the capacity for the other function as small as possible, within available equipment options.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40323 Section C403.2.3—HVAC equipment performance requirements.
C403.2.3 HVAC equipment performance requirements. Equipment shall meet the minimum efficiency requirements of Tables C403.2.3(1), C403.2.3(2), C403.2.3(3), C403.2.3(4), C403.2.3(5), C403.2.3(6), C403.2.3(7) ((and)), C403.2.3(8) and C403.2.3(9) when tested and rated in accordance with the applicable test procedure. Plate-type liquid-to-liquid heat exchangers shall meet the minimum requirements of Table C403.2.3(((9))) (10). The efficiency shall be verified through certification and listed under an approved certification program or, if no certification program exists, the equipment efficiency ratings shall be supported by data furnished by the manufacturer. Where multiple rating conditions or performance requirements are provided, the equipment shall satisfy all stated requirements. Where components, such as indoor or outdoor coils, from different manufacturers are used, calculations and supporting data shall be furnished by the designer that demonstrates that the combined efficiency of the specified components meets the requirements herein.
Gas-fired and oil-fired forced air furnaces with input ratings ≥ 225,000 Btu/h (65 kW) and all unit heaters shall also have an intermittent ignition or interrupted device (IID), and have either mechanical draft (including power venting) or a flue damper. A vent damper is an acceptable alternative to a flue damper for furnaces where combustion air is drawn from the conditioned space. All furnaces with input ratings ≥ 225,000 Btu/h (65 kW), including electric furnaces, that are not located within the conditioned space shall have jacket losses not exceeding 0.75 percent of the input rating.
Chilled water plants and buildings with more than 500 tons total capacity shall not have more than 100 tons provided by air-cooled chillers.
C403.2.3.1 Water-cooled centrifugal chilling packages. Equipment not designed for operation at AHRI Standard 550/590 test conditions of 44°F (7°C) leaving chilled-water temperature and 2.4 gmp/ton evaporator fluid flow and 85°F (29°C) entering condenser water temperature with 3 gpm/ton (0.054 I/s • kW) condenser water flow shall have maximum full-load kW/ton (FL) and ((NPLV)) part-load ratings adjusted using Equations ((C4-3 and C4-4)) 4-7 and 4-8.
(Equation C4-3)
(Equation C4-4)))
(Equation 4-7)
(Equation 4-8)
The ((adjusted full-load and NPLV values shall only be)) FLadj and PLVadj values are only applicable for centrifugal chillers meeting all of the following full-load design ranges:
1. ((The leaving evaporator fluid temperature is not less than 36°F (2.2°C).
2. The leaving condenser fluid temperature is not greater than 115°F (46.1°C).)) Minimum evaporator leaving temperature: 36°F.
2. Maximum condenser leaving temperature: 115°F.
3. LIFT is not less than 20°F (11.1°C) and not greater than 80°F (44.4°C).
C403.2.3.2 Positive displacement (air- and water-cooled) chilling packages. Equipment with a leaving fluid temperature higher than 32°F (0°C)((,)) and water-cooled positive displacement chilling packages with a condenser leaving fluid temperature below 115°F (46°C) shall meet the requirements of Table C403.2.3(7) when tested or certified with water at standard rating conditions, in accordance with the referenced test procedure.
C403.2.3.3 Packaged electric heating and cooling equipment. Packaged electric equipment providing both heating and cooling with a total cooling capacity greater than ((20,000)) 6,000 Btu/h shall be a heat pump.
C403.2.3.4 Humidification. If an air economizer is required on a cooling system for which humidification equipment is to be provided to maintain minimum indoor humidity levels, then the humidifier shall be of the adiabatic type (direct evaporative media or fog atomization type).
Reviser's note: The typographical error in the above section occurred in the copy filed by the agency and appears in the Register pursuant to the requirements of RCW 34.08.040. AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403231 Table C403.2.3(1)—Minimum efficiency requirements—Electrically operated unitary air conditioners and condensing units.
Table C403.2.3(1)A
Minimum Efficiency Requirements—Electrically Operated Unitary Air Conditioners and Condensing Units
Table C403.2.3(1)B
((Minimum Efficiency Requirements—Air Conditioners and Condensing Units Serving Computer Rooms
Table C403.2.3(1)C))
Minimum Efficiency Requirements—Electrically Operated Variable Refrigerant Flow Air Conditioners
Table ((C403.2.3(1)D)) C403.2.3(1)C
Minimum Efficiency Requirements—Electrically Operated Variable Refrigerant Flow Air-to-Air and Applied Heat Pumps
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403232 Table C403.2.3(2)—Minimum efficiency requirements—Electrically operated unitary and applied heat pumps.
Table C403.2.3(2)
Minimum Efficiency Requirements—Electrically Operated Unitary and Applied Heat Pumps
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency. Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040. AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403233 Table C403.2.3(3)—Minimum efficiency requirements—Electrically operated PTAC, PTHP, SPVAC, SPVHP, room air conditioners.
Table C403.2.3(3)
Minimum Efficiency Requirements—Electrically Operated Packaged Terminal Air Conditioners, Packaged Terminal Heat Pumps, Single-Package Vertical Air Conditioners, Single-Package Vertical Heat Pumps, Room Air Conditioners and Room Air-Conditioner Heat Pumps
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency. Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040. AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403235 Table C403.2.3(5)—Minimum efficiency requirements—Gas- and oil-fired boilers.
Table C403.2.3(5)
Minimum Efficiency Requirements—Gas- and Oil-Fired Boilers
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403237 Table C403.2.3(7)—Minimum efficiency requirements—Water chilling packages.
Table C403.2.3(7)
Minimum Efficiency Requirements—Water Chilling Packagesa
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency. Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040. AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403238 Table C403.2.3(8)—Minimum efficiency requirements—Heat rejection equipment.
Table C403.2.3(8)
Minimum Efficiency Requirements—Heat Rejection Equipment
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency. Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040. AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403239 Table C403.2.3(9) and Table C403.2.3(10)—Minimum efficiency requirements((—Heat transfer equipment)).
Table C403.2.3(9)
Minimum Efficiency Requirements—Air Conditioners and Condensing Units Serving Computer Rooms
Table C403.2.3(((9))) (10)
Minimum Efficiency Requirements—Heat Transfer Equipment
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40324 Section C403.2.4—HVAC system controls.
C403.2.4 HVAC system controls. Each heating and cooling system shall be provided with thermostatic controls as specified in Section C403.2.4.1, C403.2.4.1.3, C403.2.4.2, C403.2.4.3, ((C403.2.4.4)) C403.2.4.5, C403.3.1, C403.4, C403.4.1, C403.4.2, C403.4.3, or C403.4.4((, C403.4.5, C403.4.6, C403.4.7, C403.4.8, C403.4.9, or C403.4.10)).
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403241 Section C403.2.4.1—Thermostatic controls.
C403.2.4.1 Thermostatic controls. The supply of heating and cooling energy to each zone shall be controlled by individual thermostatic controls capable of responding to temperature within the zone. Controls in the same zone or in neighboring zones connected by openings larger than 10 percent of the floor area of either zone shall not allow for simultaneous heating and cooling. At a minimum, each floor of a building shall be considered as a separate zone. Controls on systems required to have economizers and serving single zones shall have multiple cooling stage capability and activate the economizer when appropriate as the first stage of cooling. See Section C403.3.1 ((or C403.4.1)) for further economizer requirements. Where humidification or dehumidification or both is provided, at least one humidity control device shall be provided for each humidity control system.
C403.2.4.1.1 Heat pump supplementary heat. Unitary air cooled heat pumps shall include microprocessor controls that minimize supplemental heat usage during start-up, set-up, and defrost conditions. These controls shall anticipate need for heat and use compression heating as the first stage of heat. Controls shall indicate when supplemental heating is being used through visual means (e.g., LED indicators). Heat pumps equipped with supplementary heaters shall be installed with controls that prevent supplemental heater operation above 40°F.
C403.2.4.1.2 Deadband. Where used to control both heating and cooling, zone thermostatic controls shall be configured to provide a temperature range or deadband of at least 5°F (2.8°C) within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum.
C403.2.4.1.3 Setpoint overlap restriction. Where a zone has a separate heating and a separate cooling thermostatic control located within the zone, a limit switch, mechanical stop or direct digital control system with software programming shall be configured to prevent the heating set point from exceeding the cooling setpoint and to maintain a deadband in accordance with Section C403.2.4.1.2.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403242 Section C403.2.4.2—((Setpoint overlap restriction)) Off-hour controls.
((C403.2.4.2 Setpoint overlap restriction. Where used to control both heating and cooling, zone thermostatic controls shall provide a temperature range or deadband of at least 5°F (2.8°C) within which the supply of heating and cooling energy to the zone is capable of being shut off or reduced to a minimum.
C403.2.4.2 Off-hour controls. For all occupancies other than Group R, each zone shall be provided with thermostatic setback controls that are controlled by either an automatic time clock or programmable control system.
C403.2.4.2.1 Thermostatic setback. Thermostatic setback controls shall be configured to set back or temporarily operate the system to maintain zone temperatures down to 55°F (13°C) or up to 85°F (29°C).
C403.2.4.2.2 Automatic setback and shutdown. Automatic time clock or programmable controls shall be capable of starting and stopping the system for seven different daily schedules per week and retaining their programming and time setting during a loss of power for at least 10 hours. Additionally, the controls shall have a manual override that allows temporary operation of the system for up to 2 hours; a manually operated timer configured to operate the system for up to 2 hours; or an occupancy sensor.
C403.2.4.2.3 Automatic start capabilities. Automatic start controls shall be provided for each HVAC system. The controls shall be capable of automatically adjusting the daily start time of the HVAC system in order to bring each space to the desired occupied temperature immediately prior to scheduled occupancy.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403243 Section C403.2.4.3—((Off-hour controls)) Shutoff dampers.
((C403.2.4.3 Off-hour controls. For all occupancies other than Group R, each zone shall be provided with thermostatic setback controls that are controlled by either an automatic time clock or programmable control system.
C403.2.4.3.1 Thermostatic setback capabilities. Thermostatic setback controls shall have the capability to set back or temporarily operate the system to maintain zone temperatures down to 55°F (13°C) or up to 85°F (29°C).
C403.2.4.3.2 Automatic setback and shutdown capabilities. Automatic time clock or programmable controls shall be capable of starting and stopping the system for seven different daily schedules per week and retaining their programming and time setting during a loss of power for at least 10 hours. Additionally, the controls shall have a manual override that allows temporary operation of the system for up to 2 hours; a manually operated timer capable of being adjusted to operate the system for up to 2 hours; or an occupancy sensor.
C403.2.4.3.3 Automatic start capabilities. Automatic start controls shall be provided for each HVAC system. The controls shall be capable of automatically adjusting the daily start time of the HVAC system in order to bring each space to the desired occupied temperature immediately prior to scheduled occupancy.)) C403.2.4.3 Shutoff dampers. Outdoor air supply, exhaust openings and relief outlets and stairway and shaft vents shall be provided with Class I motorized dampers.
Return air openings used for airside economizer operation shall be equipped with Class I motorized dampers.
Class 1 dampers shall have a maximum leakage rate of 4 cfm/ft2(20.3 L/s x m2) at 1.0 inch water gauge (w.g.) (249 Pa) when tested in accordance with AMCA 500D and shall be labeled by an approved agency such purpose.
Outdoor air intake and exhaust dampers shall be installed with automatic controls configured to close when the systems or spaces served are not in use or during unoccupied period warm-up and setback operation, unless the systems served require outdoor or exhaust air in accordance with the International Mechanical Code or the dampers are opened to provide intentional economizer cooling.
Stairway and shaft vent dampers shall be installed with automatic controls configured to open upon the activation of any fire alarm initiating device of the building's fire alarm system or the interruption of power to the damper.
Gravity (nonmotorized) dampers shall have an air leakage rate not greater than 20 cfm/ft2 (101.6 L/s x m2) where not less than 24 inches (610 mm) in either dimension and 40 cfm/ft2 (203.2 L/s x m2) where less than 24 inches (610 mm) in either dimension. The rate of air leakage shall be determined at 1.0 inch water gauge (249 Pa) when tested in accordance with AMCA 500D for such purpose. The dampers shall be labeled by an approved agency. Gravity dampers for ventilation air intakes shall be protected from direct exposure to wind.
AMENDATORY SECTION (Amending WSR 14-24-054, filed 11/25/14, effective 5/1/15)
WAC 51-11C-403244 Section C403.2.4.4—((Shutoff damper controls)) Zone isolation.
((C403.2.4.4 Shutoff damper controls. Both outdoor air supply and exhaust ducts shall be equipped with motorized dampers that will automatically shut when the systems or spaces served are not in use or during building warm-up, cooldown, and setback.
See also section C402.4.5 for additional damper requirements and maximum leakage rates.
C403.2.4.4 Zone isolation. HVAC systems serving zones that are over 25,000 square feet (2323 m2) in floor area or that span more than one floor and are designed to operate or be occupied nonsimultaneously shall be divided into isolation areas. Each isolation area shall be equipped with isolation devices and controls configured to automatically shut off the supply of conditioned air and outdoor air to and exhaust air from the isolation area. Each isolation area shall be controlled independently by a device meeting the requirements of Section C403.2.4.2.2. Central systems and plants shall be provided with controls and devices that will allow system and equipment operation for any length of time while serving only the smallest isolation area served by the system or plant.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403245 Section C403.2.4.5—Snowmelt ((system)) and freeze protection controls.
C403.2.4.5 Snow- and ice-melt system controls. Snow- and ice-melting systems, supplied through energy service to the building, shall include automatic controls ((capable of shutting)) configured to shut off the system when the pavement temperature is above 50°F (10°C) and no precipitation is falling and an automatic or manual control that ((will allow)) is configured to shutoff when the outdoor temperature is above 40°F (4°C) so that the potential for snow or ice accumulation is negligible.
C403.2.4.6 Freeze protection system controls. Freeze protection systems, such as heat tracing of outdoor piping and heat exchangers, including self-regulating heat tracing, shall include automatic controls configured to shut off the systems when outdoor air temperatures are above 40°F (4°C) or when the conditions of the protected fluid will prevent freezing.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403246 Section ((C403.2.4.6)) C403.2.4.7—Economizer fault detection and Section C403.2.4.8—Combustion heating equipment controls.
((C403.2.4.6)) C403.2.4.7 Economizer fault detection and diagnostics (FDD). Air-cooled unitary direct-expansion units with a cooling capacity of 54,000 Btu/h or greater listed in Tables C403.2.3(1) through C403.2.3(3) that are equipped with an economizer in accordance with Section C403.3 shall include a fault detection and diagnostics (FDD) system complying with the following:
1. The following temperature sensors shall be permanently installed to monitor system operation:
1.1. Outside air.
1.2. Supply air.
1.3. Return air.
2. Temperature sensors shall have an accuracy of ±2°F (1.1°C) over the range of 40°F to 80°F (4°C to 26.7°C).
3. Refrigerant pressure sensors, where used, shall have an accuracy of ±3 percent of full scale.
4. The unit controller shall be configured to provide system status by indicating the following:
4.1. Free cooling available.
4.2. Economizer enabled.
4.3. Compressor enabled.
4.4. Heating enabled.
4.5. Mixed air low limit cycle active.
4.6. The current value of each sensor.
5. The unit controller shall be capable of manually initiating each operating mode so that the operation of compressors, economizers, fans and the heating system can be independently tested and verified.
6. The unit shall be configured to report faults to a fault management application accessible by day-to-day operating or service personnel or annunciated locally on zone thermostats.
7. The FDD system shall be configured to detect the following faults:
7.1. Air temperature sensor failure/fault.
7.2. Not economizing when the unit should be economizing.
7.3. Economizing when the unit should not be economizing.
7.4. Damper not modulating.
7.5. Excess outdoor air.
C403.2.4.8 Combustion heating equipment controls. Combustion heating equipment with a capacity over 225,000 Btu/h shall have modulating or staged combustion control.
AMENDATORY SECTION (Amending WSR 13-20-120, filed 10/1/13, effective 11/1/13)
WAC 51-11C-403247 Sections ((C403.2.4.7—Hotel/motel)) C403.2.4.9 through C403.2.4.11—Group R controls.
((C403.2.4.7)) C403.2.4.9 Group R-1 hotel/motel guest rooms. For hotel and motel guest rooms, a minimum of one of the following control technologies shall be required in hotels/motels with over 50 guest rooms such that the space temperature would automatically setback (winter) or set up (summer) by no less than 5°F (3°C) when the occupant is not in the room:
1. Controls that are activated by the room occupant via the primary room access method - Key, card, deadbolt, etc.
2. Occupancy sensor controls that are activated by the occupant's presence in the room.
C403.2.4.10 Group R-2 and R-3 dwelling units. The primary space conditioning system within each dwelling unit shall be provided with at least one programmable thermostat for the regulation of space temperature. The thermostat shall allow for, at a minimum, a 5-2 programmable schedule (weekdays/weekends) and be capable of providing at least two programmable setback periods per day.
Each additional system provided within the dwelling unit shall be provided with at least one adjustable thermostat for the regulation of temperature.
Each thermostat shall be capable of being set by adjustment or selection of sensors and configured as follows: When used to control heating only: 55°F to 75°F; when used to control cooling only: 70°F to 85°F; all other: 55°F to 85°F with an adjustable deadband of not less than 10°F.
C403.2.4.11 Group R-2 sleeping units. The primary space conditioning system within each sleeping unit shall be provided with at least one programmable thermostat for the regulation of space temperature. The thermostat shall allow for, at a minimum, a 5-2 programmable schedule (weekdays/weekends) and be capable of providing at least two programmable setback periods per day.
Each additional system provided within the sleeping unit shall be provided with at least one adjustable thermostat for the regulation of temperature.
Each thermostat shall be capable of being set by adjustment or selection of sensors and configured as follows: When used to control heating only: 55°F to 75°F; when used to control cooling only: 70°F to 85°F; all other: 55°F to 85°F with an adjustable deadband of not less than 10°F.
AMENDATORY SECTION (Amending WSR 13-20-120, filed 10/1/13, effective 11/1/13)
WAC 51-11C-403248 Section ((C403.2.4.8—Residential occupancy)) C403.2.4.12—Direct digital control((s)) systems.
((C403.2.4.8 Group R-2 and R-3 dwelling units. The primary space conditioning system within each dwelling unit shall be provided with at least one programmable thermostat for the regulation of space temperature. The thermostat shall allow for, at a minimum, a 5-2 programmable schedule (weekdays/weekends) and be capable of providing at least two programmable setback periods per day.
Each additional system provided within the dwelling unit shall be provided with at least one adjustable thermostat for the regulation of temperature.
Each thermostat shall be capable of being set by adjustment or selection of sensors as follows: When used to control heating only: 55°F to 75°F; when used to control cooling only: 70°F to 85°F; all other: 55°F to 85°F with an adjustable deadband of not less than 10°F.
C403.2.4.9 Group R-2 sleeping units. The primary space conditioning system within each sleeping unit shall be provided with at least one programmable thermostat for the regulation of space temperature. The thermostat shall allow for, at a minimum, a 5-2 programmable schedule (weekdays/weekends) and be capable of providing at least two programmable setback periods per day.
Each additional system provided within the sleeping unit shall be provided with at least one adjustable thermostat for the regulation of temperature.
Each thermostat shall be capable of being set by adjustment or selection of sensors as follows: When used to control heating only: 55°F to 75°F; when used to control cooling only: 70°F to 85°F; all other: 55°F to 85°F with an adjustable deadband of not less than 10°F.)) C403.2.4.12 Direct digital control systems. Direct digital control (DDC) shall be required as specified in Sections C403.2.4.12.1 through C403.2.4.12.3.
C403.2.4.12.1 DDC applications. DDC shall be provided in the applications and qualifications listed in Table C403.2.4.12.1.
C403.2.4.12.2 DDC controls. Where DDC is required by Section C403.2.4.12.1, the DDC system shall be capable of all of the following, as required to provide the system and zone control logic required in Sections C403.2, C403.3, and C403.4:
1. Monitoring zone and system demand for fan pressure, pump pressure, heating and cooling.
2. Transferring zone and system demand information from zones to air distribution system controllers and from air distribution systems to heating and cooling plant controllers.
C403.2.4.12.3 DDC display. Where DDC is required by Section C403.2.12.1 for new buildings, the DDC system shall be capable of trending and graphically displaying input and output points.
Table C403.2.4.12.1
DDC Applications and Qualifications
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403249 Section ((C403.2.4.9—Direct digital control system capabilities)) C403.2.5—Hot water boiler controls.
((C403.2.4.10 Direct digital control system capabilities. All complex systems equipped with direct digital control (DDC) systems and all buildings with total cooling capacity exceeding 780,000 Btu/h (2,662 kW) shall have the following capability:
1. Trending: All control system input and output points shall be accessible and programmed for trending, and a graphic trending package shall be provided with the control system.
2. Demand Response Setpoint Adjustment: Control logic shall increase the cooling zone set points by at least 2°F (1°C) and reduce the heating zone set points by at least 2°F (1°C) when activated by a demand response signal. The demand response signal shall be a binary input to the control system or other interface approved by the serving electric utility.)) C403.2.5 Hot water boiler outdoor temperature setback control. Hot water boilers that supply heat to the building through one- or two-pipe heating systems shall have an outdoor setback control that lowers the boiler water temperature based on the outdoor temperature.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40325 Section ((C403.2.5)) C403.2.6—Ventilation.
((C403.2.5)) C403.2.6 Ventilation. Ventilation, either natural or mechanical, shall be provided in accordance with Chapter 4 of the International Mechanical Code. Where mechanical ventilation is provided, the system shall ((provide the capability to reduce the outdoor air supply to)) be configured to provide no greater than 150 percent of the minimum outdoor air required by Chapter 4 of the International Mechanical Code or other applicable code or standard, whichever is greater.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403251 Section ((C403.2.5.1—Demand control ventilation)) C403.2.6.1—Dedicated outdoor air systems (DOAS).
((C403.2.5.1 Demand controlled ventilation. Demand control ventilation (DCV) shall be provided for spaces larger than 500 square feet (50 m2) and with an occupant load greater than 25 people per 1000 square feet (93 m2) of floor area (as established in Table 403.3 of the International Mechanical Code) and served by systems with one or more of the following:
1. An air-side economizer;
2. Automatic modulating control of the outdoor air damper; or
3. A design outdoor airflow greater than 3,000 cfm (1400 L/s).
C403.2.6.1 Dedicated outdoor air systems (DOAS). For office, retail, education, libraries and fire stations, outdoor air shall be provided to each zone by a dedicated outdoor air system (DOAS) which delivers 100 percent outside air without requiring operation of the heating and cooling system fans for ventilation air delivery. The DOAS shall include either energy recovery ventilation and/or demand control ventilation. If the DOAS includes heating or cooling coils, the system shall be configured to deliver supply air within 5°F (3°C) of the space conditioning setpoint, except that DOAS greater than 500 cfm shall not use heating or heat recovery to warm supply air above 60ºF (16ºC) when representative building loads or outdoor air temperature indicate the majority of zones require cooling.
C403.2.6.1.1 Impracticality. In cases where full compliance with all the requirements of Section C403.2.6.1 is impractical, the applicant is permitted to arrange a predesign conference with the design team and the code official to seek modifications. The applicant shall identify specific requirements that are impractical, and shall identify design solutions and modifications that achieve a comparable level of energy efficiency. The code official is authorized to waive specific requirements in this code to the extent that the code official determines those requirements to be impractical.
C403.2.6.1.2 Heating/cooling system fan controls. For systems meeting the requirements of Section C403.2.6.1 dedicated outdoor air systems, equipment and controls shall be configured to cycle off zone heating and cooling equipment fans and/or pumps, primary cooling air, heating and cooling coils, and parallel heating fans when there is no call for heating or cooling in the zone.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403252 Section ((C403.2.5.2—Occupancy sensors)) C403.2.6.2—Demand control ventilation.
((C403.2.5.2 Occupancy sensors. Classrooms, gyms, auditoriums and conference rooms larger than 500 square feet of floor area shall have occupancy sensor control that will either close outside air dampers or turn off serving equipment when the space is unoccupied except where equipped with another means to automatically reduce outside air intake below design rates when spaces are partially occupied.)) C403.2.6.2 Demand controlled ventilation. Demand control ventilation (DCV) shall be provided for spaces larger than 500 square feet (50 m2) and with an occupant load greater than or equal to 25 people per 1000 square feet (93 m2) of floor area (as established in Table 403.3 of the International Mechanical Code) and served by systems with one or more of the following:
1. An air-side economizer;
2. Automatic modulating control of the outdoor air damper; or
3. A design outdoor airflow greater than 3,000 cfm (1400 L/s).
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403253 Section ((C403.2.5.3—Loading dock and parking garage ventilation system controls)) C403.2.6.3—Occupancy sensors.
((C403.2.5.3 Enclosed loading dock and parking garage exhaust ventilation system control. Mechanical ventilation systems for enclosed loading docks and parking garages shall be designed to exhaust the airflow rates (maximum and minimum) determined in accordance with the International Mechanical Code.
Ventilation systems shall be equipped with a control device that operates the system automatically upon detection of vehicle operation or the presence of occupants by approved automatic detection devices. Each of the following types of controllers shall be capable of shutting off fans or modulating fan speed. Control devices shall not reduce airflow rates below the minimum requirement in accordance with the International Mechanical Code during scheduled periods of occupied operation.
1. Gas sensor controllers used to activate the exhaust ventilation system shall stage or modulate fan speed upon detection of specified gas levels. All equipment used in sensor controlled systems shall be designed for the specific use and installed in accordance with the manufacturer's recommendations. The system shall be arranged to operate automatically by means of carbon monoxide detectors applied in conjunction with nitrogen dioxide detectors. Garages and loading docks shall be equipped with a controller and a full array of carbon monoxide (CO) sensors set to maintain levels of carbon monoxide below 35 parts per million (ppm). Additionally, a full array of nitrogen dioxide detectors shall be connected to the controller set to maintain the nitrogen dioxide level below the OSHA standard for eight hour exposure. Spacing and location of the sensors shall be installed in accordance with manufacturer recommendations.
2. Occupant detection sensors used to activate the system shall detect entry into the parking garage along both the vehicle and pedestrian pathways.
C403.2.5.3.1 System activation devices for enclosed loading docks. Ventilation systems for enclosed loading docks shall be activated by one of the following:
1. Gas sensors installed in accordance with the International Mechanical Code; or
2. Occupant detection sensors used to activate the system that detects entry into the loading area along both the vehicle and pedestrian pathways.
C403.2.5.3.2 System activation devices for enclosed parking garages. Ventilation systems for enclosed parking garages shall be activated by gas sensors.
C403.2.6.3 Occupancy sensors. Classrooms, gyms, auditoriums and conference rooms larger than 500 square feet of floor area shall have occupancy sensor control that will either close outside air dampers or turn off serving equipment when the space is unoccupied except where equipped with another means to automatically reduce outside air intake below design rates when spaces are partially occupied.
AMENDATORY SECTION (Amending WSR 13-20-120, filed 10/1/13, effective 11/1/13)
WAC 51-11C-403254 Section ((C403.2.5.4—Exhaust systems)) C403.2.6.4—Loading dock and parking garage ventilation system controls.
((C403.2.5.4 Exhaust systems.
C403.2.5.4.1 Kitchen hoods. Each kitchen area with total exhaust capacity larger than 2,000 cfm shall be provided with make-up air sized so that at least 50% of exhaust air volume be (a) unheated or heated to no more than 60°F and (b) uncooled or cooled without the use of mechanical cooling.
C403.2.5.4.2 Laboratory exhaust systems. Buildings with laboratory exhaust systems having a total exhaust rate greater than 5,000 cfm (2,360 L/s) shall include heat recovery systems to precondition makeup air from laboratory exhaust. The heat recovery system shall be capable of increasing the outside air supply temperature at design heating conditions by 25°F (13.9°C) in Climate Zones 4C/5B and 35°F (19.4°C) in Climate Zone 6B. A provision shall be made to bypass or control the heat recovery system to permit air economizer operation as required by Section C403.4.
C403.2.6.4 Enclosed loading dock and parking garage exhaust ventilation system control. Mechanical ventilation systems for enclosed loading docks and parking garages shall be designed to exhaust the airflow rates (maximum and minimum) determined in accordance with the International Mechanical Code.
Ventilation systems shall be equipped with a control device that operates the system automatically by means of carbon monoxide detectors applied in conjunction with nitrogen dioxide detectors. Controllers shall be configured to shut off fans or modulate fan speed to 50 percent or less of design capacity, or intermittently operate fans less than 20 percent of the occupied time or as required to maintain acceptable contaminant levels in accordance with the International Mechanical Code provisions.
Gas sensor controllers used to activate the exhaust ventilation system shall stage or modulate fan speed upon detection of specified gas levels. All equipment used in sensor controlled systems shall be designed for the specific use and installed in accordance with the manufacturer's recommendations. The system shall be arranged to operate automatically by means of carbon monoxide detectors applied in conjunction with nitrogen dioxide detectors. Garages and loading docks shall be equipped with a controller and a full array of carbon monoxide (CO) sensors set to maintain levels of carbon monoxide below 35 parts per million (ppm). Additionally, a full array of nitrogen dioxide detectors shall be connected to the controller set to maintain the nitrogen dioxide level below the OSHA standard for eight hour exposure. Spacing and location of the sensors shall be installed in accordance with manufacturer recommendations.
C403.2.6.4.1 System activation devices for enclosed loading docks. Ventilation systems for enclosed loading docks shall be activated by one of the following:
1. Gas sensors installed in accordance with the International Mechanical Code; or
2. Occupant detection sensors used to activate the system that detects entry into the loading area along both the vehicle and pedestrian pathways.
C403.2.6.4.2 System activation devices for enclosed parking garages. Ventilation systems for enclosed parking garages shall be activated by gas sensors.
AMENDATORY SECTION (Amending WSR 14-24-122, filed 12/3/14, effective 1/3/15)
WAC 51-11C-40326 Section ((C403.2.6—Energy recovery)) C403.2.7—Exhaust systems.
((C403.2.6 Energy recovery.
C403.2.6.1 Energy recovery ventilation systems. Any system with minimum outside air requirements at design conditions greater than 5,000 CFM or any system required by Table C403.2.6 shall include an energy recovery system. The energy recovery system shall have the capability to provide a change in the enthalpy of the outdoor air supply of not less than 50 percent of the difference between the outdoor air and return air enthalpies, at design conditions. Where an air economizer is required, the energy recovery system shall include a bypass or controls which permit operation of the economizer as required by Section C403.4. Where a single room or space is supplied by multiple units, the aggregate ventilation (cfm) of those units shall be used in applying this requirement.
C403.2.6.2 Condensate systems. On-site steam heating systems shall have condensate water heat recovery. On-site includes a system that is located within or adjacent to one or more buildings within the boundary of a contiguous area or campus under one ownership and which serves one or more of those buildings.
Buildings using steam generated off-site with steam heating systems which do not have condensate water recovery shall have condensate water heat recovery.
C403.2.6.3 Condenser heat recovery. Facilities having food service, meat or deli departments and having 500,000 Btu/h or greater of remote refrigeration condensers shall have condenser waste heat recovery from freezers and coolers and shall use the waste heat for service water heating, space heating or for dehumidification reheat. Facilities having a gross conditioned floor area of 40,000 ft2 or greater and 1,000,000 Btu/h or greater of remote refrigeration shall have condenser waste heat recovery from freezers and coolers and shall use the waste heat for service water heating, and either for space heating or for dehumidification reheat for maintaining low space humidity.)) C403.2.7 Exhaust systems.
C403.2.7.1 Kitchen exhaust systems. Replacement air introduced directly into the exhaust hood cavity shall not be greater than 10 percent of the hood exhaust airflow rate. Conditioned supply air delivered to any space shall not exceed the greater of the following:
1. The ventilation rate required to meet the space heating or cooling load.
2. The hood exhaust flow minus the available transfer air from adjacent space where available transfer air is considered that portion of outdoor ventilation air not required to satisfy other exhaust needs, such as restrooms, and not required to maintain pressurization of adjacent spaces.
Where total kitchen hood exhaust airflow rate is greater than 2,000 cfm each hood shall be a factory built commercial exhaust hood listed by a nationally recognized testing laboratory in compliance with UL 710. Each hood shall have a maximum exhaust rate as specified in Table C403.2.7.1 and shall comply with one of the following:
1. Not less than 50 percent of all replacement air shall be transfer air that would otherwise be exhausted.
2. Demand ventilation systems on not less than 75 percent of the exhaust air that are configured to provide not less than a 50-percent reduction in exhaust and replacement air system airflow rates, including controls necessary to modulate airflow in response to appliance operation and to maintain full capture and containment of smoke, effluent and combustion products during cooking and idle.
3. Listed energy recovery devices with a sensible heat recovery effectiveness of not less than 40 percent on not less than 50 percent of the total exhaust airflow.
Where a single hood, or hood section, is installed over appliances with different duty ratings, the maximum allowable flow rate for the hood or hood section shall be based on the requirements for the highest appliance duty rating under the hood or hood section.
Table C403.2.7.1
Maximum Net Exhaust Flow Rate,
CFM Per Linear Foot of Hood Length
C403.2.7.2 Laboratory exhaust systems. Buildings with laboratory exhaust systems having a total exhaust rate greater than 5,000 cfm (2360 L/s) shall include heat recovery systems to precondition makeup air from laboratory exhaust. The heat recovery system shall be capable of increasing the outside air supply temperature at design heating conditions by 25°F (13.9°C). A provision shall be made to bypass or control the heat recovery system to permit air economizer operation as required by Section C403.3.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403261 ((Table C403.2.6—Energy recovery requirement.)) Reserved.
((Table C403.2.6
Energy Recovery Requirement
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40327 Section ((C403.2.7)) C403.2.8—Duct and plenum insulation and sealing.
((C403.2.7)) C403.2.8 Duct and plenum insulation and sealing.
((C403.2.7.1)) C403.2.8.1 Ducts, shafts and plenums conveying ((outside)) outdoor air from the exterior of the building to the mechanical system shall meet all air leakage and building envelope insulation requirements of Section C402, plus building envelope vapor control requirements from the International Building Code, extending continuously from the building exterior to an automatic shutoff damper or heating or cooling equipment. For the purposes of building envelope insulation requirements, duct surfaces shall meet the requirements for metal framed walls per Table ((C402.1.2)) C402.1.4. Duct surfaces included as part of the building envelope shall not be used in the calculation of maximum glazing area as described in Section ((402.3.1)) C402.4.1.
((C403.2.7.2)) C403.2.8.2 All other supply and return air ducts and plenums shall be insulated with a minimum of R-6 insulation where located in unconditioned spaces and where located outside the building with a minimum of R-8 insulation ((where located outside the building)) in Climate Zone 4 and R-12 insulation in Climate Zone 5. Where located within a building envelope assembly, the duct or plenum shall be separated from the building exterior or unconditioned or exempt spaces by minimum insulation value as required for exterior walls by Section ((C402.2.3)) C402.1.3.
Where located within conditioned space, supply ducts which convey supply air at temperatures less than 55°F or greater than 105°F shall be insulated with a minimum of R-3.3 insulation ((where located within conditioned space)).
All ducts, air handlers, and filter boxes shall be sealed. Joints and seams shall comply with Section 603.9 of the International Mechanical Code.
((C403.2.7.3)) C403.2.8.3 Duct construction. Ductwork shall be constructed and erected in accordance with the International Mechanical Code.
((C403.2.7.3.1)) C403.2.8.3.1 Low-pressure duct systems. All longitudinal and transverse joints, seams and connections of supply and return ducts operating at a static pressure less than or equal to 2 inches water gauge (w.g.) (500 Pa) shall be securely fastened and sealed with welds, gaskets, mastics (adhesives), mastic-plus embedded-fabric systems or tapes installed in accordance with the manufacturer's installation instructions. Pressure classifications specific to the duct system shall be clearly indicated on the construction documents in accordance with the International Mechanical Code.
((C403.2.7.3.2)) C403.2.8.3.2 Medium-pressure duct systems. All ducts and plenums designed to operate at a static pressure greater than 2 inches water gauge (w.g.) (500 Pa) but less than 3 inches w.g. (750 Pa) shall be insulated and sealed in accordance with Section C403.2.7. Pressure classifications specific to the duct system shall be clearly indicated on the construction documents in accordance with the International Mechanical Code.
((C403.2.7.3.3)) C403.2.8.3.3 High-pressure duct systems. Ducts designed to operate at static pressures in excess of 3 inches water gauge (w.g.) (750 Pa) shall be insulated and sealed in accordance with Section ((C403.2.7)) C403.2.8. In addition, ducts and plenums shall be leak-tested in accordance with the SMACNA HVAC Air Duct Leakage Test Manual ((with the)) and shown to have a rate of air leakage (CL) less than or equal to ((6.0)) 4.0 as determined in accordance with Equation ((C4-5)) 4-9.
(Equation ((C4-5)) 4-9)
Documentation shall be furnished by the designer demonstrating that representative sections totaling at least 25 percent of the duct area have been tested and that all tested sections meet the requirements of this section.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40328 Section ((C403.2.8)) C403.2.9—Piping insulation.
((C403.2.8)) C403.2.9 Piping insulation. All piping serving as part of a heating or cooling system shall be thermally insulated in accordance with Table ((C403.2.8)) C403.2.9.
((C403.2.8.1)) C403.2.9.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that due to sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesives tape shall not be permitted.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403281 Table ((C403.2.8)) C403.2.9—Minimum pipe insulation thickness.
Table ((C403.2.8)) C403.2.9
Minimum Pipe Insulation Thickness (thickness in inches)a
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40329 Section ((C403.2.9)) C403.2.10—Mechanical system commissioning and completion requirements.
((C403.2.9)) C403.2.10 Mechanical systems commissioning and completion requirements. Mechanical systems shall be commissioned and completed in accordance with Section ((C408.2)) C408.
AMENDATORY SECTION (Amending WSR 13-20-120, filed 10/1/13, effective 11/1/13)
WAC 51-11C-403291 Section ((C403.2.10)) C403.2.11—Air system design and control.
((C403.2.10)) C403.2.11 Air system design and control. Each HVAC system having a total fan system motor nameplate horsepower (hp) exceeding 5 horsepower (hp) (3.7 kW) shall ((meet)) comply with the provisions of Sections ((C403.2.10.1 through C403.2.10.3)) C403.2.11.1 through C403.2.11.3.
The air flow requirements of Section C403.2.11.5 shall apply to all fan motors. Group R occupancy exhaust fans shall also comply with Section C403.2.11.4.
((C403.2.10.1)) C403.2.11.1 Allowable fan ((floor)) motor horsepower. Each HVAC system at fan system design conditions shall not exceed the allowable fan system motor nameplate hp (Option 1) or fan system bhp (Option 2) as shown in Table ((C403.2.10.1(1))) C403.2.11.1(1). This includes supply fans, exhaust fans, return/relief fans, and fan-powered terminal units associated with systems providing heating or cooling capability. Single zone variable-air-volume systems shall comply with the constant volume fan power limitation.
((C403.2.10.2)) C403.2.11.2 Motor nameplate horsepower. For each fan, the selected fan motor shall be no larger than the first available motor size greater than the brake horsepower (bhp). The fan brake horsepower (bhp) shall be indicated on the design documents to allow for compliance verification by the code official.
((C403.2.10.3 Fractional hp fan motors. Motors for fans that are 1/12 hp or greater and less than 1 hp shall be electronically commutated motors or shall have a minimum motor efficiency of 70 percent when rated in accordance with DOE 10 C.F.R. 431. These motors shall also have the means to adjust motor speed for either balancing or remote control. Belt-driven fans may use sheave adjustments for airflow balancing in lieu of a varying motor speed.
C403.2.11.3 Fan efficiency. Fans shall have a fan efficiency grade (FEG) of not less than 67 when determined in accordance with AMCA 205 by an approved, independent testing laboratory and labeled by the manufacturer. The total efficiency of the fan at the design point of operation shall be within 15 percentage points of the maximum total efficiency of the fan.
C403.2.11.4 Group R occupancy exhaust fan efficacy. The Group R occupancies of the building shall be provided with ventilation that meets the requirements of the International Mechanical Code, as applicable, or with other approved means of ventilation. Mechanical ventilation system fans with 400 cfm or less in capacity shall meet the efficacy requirements of Table C403.2.11.4.
C403.2.11.5 Fan airflow control. Each cooling system listed in Table C403.2.11.5 shall be designed to vary the indoor fan airflow as a function of load and shall comply with the following requirements:
1. Direct expansion (DX) and chilled water cooling units that control the capacity of the mechanical cooling directly based on space temperature shall have not fewer than two stages of fan control. Low or minimum speed shall not be greater than 66 percent of full speed. At low or minimum speed, the fan system shall draw not more than 40 percent of the fan power at full fan speed. Low or minimum speed shall be used during periods of low cooling load and ventilation-only operation.
2. Other units including DX cooling units and chilled water units that control the space temperature by modulating the airflow to the space shall have modulating fan control. Minimum speed shall be not greater than 50 percent of full speed. At minimum speed, the fan system shall draw more than 30 percent of the power at full fan speed. Low or minimum speed shall be used during periods of low cooling load and ventilation-only operation.
3. Units that include an airside economizer in accordance with Section C403.3 shall have not fewer than two speeds of fan control during economizer operation.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403292 ((Table C403.2.10.1—Fan power limitation.)) Tables for Section C403.2.11
Table ((C403.2.10.1(1))) C403.2.11.1(1)
Fan Power Limitation
Table ((C403.2.10.1(2))) C403.2.11.1(2)
Fan Power Limitation Pressure Drop Adjustment
Table C403.2.11.4
Mechanical Ventilation System Fan Efficacy
Table C403.2.11.5
Fan Control
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency. Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040. AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403293 Section ((C403.2.11)) C403.2.12—Heating outside a building.
((C403.2.11)) C403.2.12 Heating outside a building. Systems installed to provide heat outside a building shall be radiant systems.
Such heating systems shall be controlled by an occupancy sensing device or a timer switch, so that the system is automatically deenergized when no occupants are present.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403294 Section ((C403.2.12)) C403.2.13—System criteria.
((C403.2.12 System criteria.)) C403.2.13 Variable flow capability. For fan and pump motors 7.5 hp and greater including motors in or serving custom and packaged air handlers serving variable air volume fan systems, constant volume fans, heating and cooling hydronic pumping systems, pool and service water pumping systems, domestic water pressure boosting systems, cooling tower fan, and other pump or fan motors where variable flows are required, there shall be:
1. Variable speed drives; or
2. Other controls and devices that will result in fan and pump motor demand of no more than 30 percent of design wattage at 50 percent of design air volume for fans when static pressure set point equals 1/3 the total design static pressure, and 50 percent of design water flow for pumps, based on manufacturer's certified test data. Variable inlet vanes, throttling valves (dampers), scroll dampers or bypass circuits shall not be allowed.
((C403.2.12.1)) C403.2.13.1 Heat rejection equipment. The requirements of this section apply to heat rejection equipment used in comfort cooling systems such as air-cooled condensers, open cooling towers, closed-circuit cooling towers, and evaporative condensers.
Heat rejection equipment shall have a minimum efficiency performance not less than values specified in Table C403.2.3(8). These requirements apply to all propeller, axial fan and centrifugal fan cooling towers. Table C403.2.3(8) specifies requirements for air-cooled condensers that are within rating conditions specified within the table.
((C403.2.12.1.1)) C403.2.13.1.1 Variable flow controls. Cooling tower fans 7.5 hp and greater shall have control devices that vary flow by controlling the leaving fluid temperature or condenser temperature/pressure of the heat rejection device.
((C403.2.12.1.2)) C403.2.13.1.2 Limitation on centrifugal fan cooling towers. Open cooling towers with a combined rated capacity of 1,100 gpm and greater at 95°F condenser water return, 85°F condenser water supply and 75°F outdoor wet-bulb temperature shall meet the energy efficiency requirement for axial fan open circuit cooling towers.
((C403.2.12.2 Large volume fan systems. Single or multiple fan systems serving a zone or adjacent zones without separating walls with total air flow over 10,000 cfm (3,540 L/s) are required to reduce airflow based on space thermostat heating and cooling demand. A variable speed drive shall reduce airflow to a maximum 75 percent of peak airflow or minimum ventilation air requirement as required by Section 403 of the International Mechanical Code, whichever is greater.
All air-conditioning equipment and air-handling units with direct expansion cooling and a cooling capacity at AHRI conditions greater than or equal to 110,000 Btu/h that serve single zones shall have their supply fans controlled by two-speed motors or variable speed drives. At cooling demands less than or equal to 50 percent, the supply fan controls shall be able to reduce the airflow to no greater than the larger of the following:
1. Two-thirds of the full fan speed; or
2. The volume of outdoor air required to meet the ventilation requirements of Section 403 of the International Mechanical Code.))
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403295 Section ((C403.2.13)) C403.2.14—Electric motor efficiency.
((C403.2.13)) C403.2.14 Electric motor efficiency. ((Design A and B squirrel-cage, T-frame induction permanently wired polyphase motors of 1 hp or more having synchronous speeds of 3,600, 1,800 and 1,200 rpm shall have a nominal full-load motor efficiency no less than the corresponding values for energy efficient motors provided in NEMA Standard MG-1.
Fan motors less than 1 hp in series terminal units shall be electronically commutated motors, or shall have a minimum motor efficiency of 65 percent when rated in accordance with NEMA Standard MG-1 at full load rating conditions.)) Electric motors, including fractional hp motors, shall comply with the provisions of Section C405.8.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40330 Section C403.3—((Simple HVAC systems and equipment)) Economizers.
C403.3 ((Simple HVAC systems and equipment (Prescriptive). This section applies to unitary or packaged HVAC systems listed in Tables C403.2.3(1) through C403.2.3(8), each serving one zone and controlled by a single thermostat in the zone served. It also applies to two-pipe heating systems serving one or more zones, where no cooling system is installed.
To qualify as a simple system, systems shall have no active humidification or simultaneous heating and cooling and shall be one of the following:
1. Air cooled, constant volume packaged equipment, which provide heating, cooling or both, and require only external connection to duct work and energy services with cooling capacity of 135,000 Btu/h or less.
2. Air cooled, constant volume split systems, which provide heating, cooling or both, with cooling capacity of 84,000 Btu/h or less.
3. Heating only systems which have a capacity of less than 1,000 cfm or which have a minimum outside air supply of less than 30 percent of the total air circulation.
The combined airflow rate of all simple systems serving single rooms must be less than 10,000 cfm or they do not qualify as simple systems.)) Economizers. Air economizers shall be provided on all new systems including those serving computer server rooms, electronic equipment, radio equipment, and telephone switchgear. Economizers shall comply with Sections C403.3.1.1 through C403.3.1.4.
AMENDATORY SECTION (Amending WSR 14-24-122, filed 12/3/14, effective 1/3/15)
WAC 51-11C-40331 Section C403.3.1—((Economizers)) Integrated economizer control.
((C403.3.1 Economizers. Each cooling system that has a fan shall include an air economizer meeting the requirements of Sections C403.3.1.1 through C403.3.1.1.4.
Table C403.3.1(2)
Equipment Efficiency Performance
Exception for Economizers
C403.3.1.1 Air economizers. Air economizers shall comply with Sections C403.3.1.1.1 through C403.3.1.1.4.
C403.3.1.1.1 Design capacity. Air economizer systems shall be capable of modulating outdoor air and return air dampers to provide up to 100 percent of the design supply air quantity as outdoor air for cooling.
C403.3.1.1.2 Control signal. Economizer dampers shall be capable of being sequenced with the mechanical cooling equipment and shall not be controlled by only mixed air temperature. Air economizers on systems with cooling capacity greater than 65,000 Btu/h shall be capable of providing partial cooling even when additional mechanical cooling is required to meet the remainder of the cooling load.
C403.3.1.1.3 High-limit shutoff. Air economizers shall be capable of automatically reducing outdoor air intake to the design minimum outdoor air quantity when outdoor air intake will no longer reduce cooling energy usage. High-limit shutoff control types for specific climates shall be chosen from Table C403.3.1.1.3(1). High-limit shutoff control settings for these control types shall be those specified in Table C403.3.1.1.3(2).
C403.3.1.1.4 Relief of excess outdoor air. Systems shall be capable of relieving excess outdoor air during air economizer operation to prevent over-pressurizing the building. The relief air outlet shall be located to avoid recirculation into the building.)) C403.3.1 Integrated economizer control. Economizer systems shall be integrated with the mechanical cooling system and be configured to provide partial cooling even where additional mechanical cooling is required to provide the remainder of the cooling load. Controls shall not be capable of creating a false load in the mechanical cooling system by limiting or disabling the economizer or any other means, such as hot gas bypass, except at the lowest stage of mechanical cooling.
Units that include an air economizer shall comply with the following:
1. Unit controls shall have the mechanical cooling capacity control interlocked with the air economizer controls such that the outdoor air damper is at the 100 percent open position when mechanical cooling is on and the outdoor air damper does not begin to close to prevent coil freezing due to minimum compressor run time until the leaving air temperature is less than 45°F (7°C).
2. Direct expansion (DX) units with cooling capacity 65,000 Btu/h (19 kW) or greater of rated capacity shall comply with the following:
2.1. DX units that control the capacity of the mechanical cooling directly based on occupied space temperature shall have not fewer than two stages of mechanical cooling capacity.
2.2. Other DX units, including those that control space temperature by modulating the airflow to the space, shall be in accordance with Table C403.3.1.
Table C403.3.1
DX Cooling Stage Requirements for Modulating Airflow Units
AMENDATORY SECTION (Amending WSR 13-20-120, filed 10/1/13, effective 11/1/13)
WAC 51-11C-40332 Section C403.3.2—((Hydronic system controls)) Economizer heating system impact.
((C403.3.2 Hydronic system controls. Hydronic systems of at least 300,000 Btu/h (87,930 W) design output capacity supplying heated to comfort conditioning systems shall include controls that meet the requirements of Section C403.4.3.)) C403.3.2 Economizer heating system impact. HVAC system design and economizer controls shall be such that economizer operation does not increase building heating energy use during normal operation.
NEW SECTION
WAC 51-11C-40333 Section C403.3.3—Air economizers.
C403.3.3 Air economizers. Air economizers shall comply with Sections C403.3.3.1 through C403.3.3.5.
C403.3.3.1 Design capacity. Air economizer systems shall be configured to modulate outdoor air and return air dampers to provide up to 100 percent of the design supply air quantity as outdoor air for cooling.
C403.3.3.2 Control signal. Economizer controls and dampers shall be configured to sequence the dampers with the mechanical cooling equipment and shall not be controlled by only mixed air temperature. Air economizers on systems with cooling capacity greater than 65,000 Btu/h shall be configured to provide partial cooling even when additional mechanical cooling is required to meet the remainder of the cooling load.
C403.3.3.3 High-limit shutoff. Air economizers shall be configured to automatically reduce outdoor air intake to the design minimum outdoor air quantity when outdoor air intake will no longer reduce cooling energy usage. High-limit shutoff control types for specific climates shall be chosen from Table C403.3.3.3. High-limit shutoff control settings for these control types shall be those specified in Table C403.3.3.3.
Table C403.3.3.3
High-limit Shutoff Control Setting for Air Economizersb
C403.3.3.4 Relief of excess outdoor air. Systems shall be capable of relieving excess outdoor air during air economizer operation to prevent over-pressurizing the building. The relief air outlet shall be located to avoid recirculation into the building.
C403.3.3.5 Economizer dampers. Return, exhaust/relief and outdoor air dampers used in economizers shall comply with Section C403.2.4.3.
NEW SECTION
WAC 51-11C-40334 Section C403.3.4—Water-side economizers.
C403.3.4 Water-side economizers. Water-side economizers shall comply with Sections C403.3.4.1 and C403.3.4.2.
C403.3.4.1 Design capacity. Water economizer systems shall be capable of cooling supply air by indirect evaporation and providing up to 100 percent of the expected system cooling load at outdoor air temperatures of 50°F dry-bulb (10°C dry-bulb)/45°F wet-bulb (7.2°C wet-bulb) and below.
C403.3.4.2 Maximum pressure drop. Precooling coils and water-to-water heat exchangers used as part of a water economizer system shall either have a waterside pressure drop of less than 15 feet (4572 mm) of water or a secondary loop shall be created so that the coil or heat exchanger pressure drop is not seen by the circulating pumps when the system is in the normal cooling (noneconomizer) mode.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40340 Section C403.4—((Complex HVAC systems and equipment)) Hydronic and multiple-zone HVAC systems.
C403.4 ((Complex HVAC systems and equipment (prescriptive). This section applies to HVAC equipment and systems not covered in Section C403.3)) Hydronic and multiple-zone HVAC system controls and equipment (prescriptive). Hydronic and multiple zone HVAC system controls and equipment shall comply with this section.
For buildings with a total equipment cooling capacity of 300 tons and above, the equipment shall comply with one of the following:
1. No one unit shall have a cooling capacity of more than 2/3 of the total installed cooling equipment capacity;
2. The equipment shall have a variable speed drive; or
3. The equipment shall have multiple compressors.
AMENDATORY SECTION (Amending WSR 14-24-122, filed 12/3/14, effective 1/3/15)
WAC 51-11C-40341 ((Section C403.4.1—Economizers.)) Reserved.
((C403.4.1 Economizers. Air economizers shall be provided on all new systems including those serving computer server rooms, electronic equipment, radio equipment, and telephone switchgear. Economizers shall comply with Sections C403.4.1.1 through C403.4.1.4.
C403.4.1.1 Design capacity. Water economizer systems shall be capable of cooling supply air by indirect evaporation and providing up to 100 percent of the expected system cooling load at outdoor air temperatures of 50°F dry-bulb (10°C dry-bulb)/45°F wet-bulb (7.2°C wet-bulb) and below.
C403.4.1.2 Maximum pressure drop. Precooling coils and water-to-water heat exchangers used as part of a water economizer system shall either have a waterside pressure drop of less than 15 feet (4572 mm) of water or a secondary loop shall be created so that the coil or heat exchanger pressure drop is not seen by the circulating pumps when the system is in the normal cooling (noneconomizer) mode.
C403.4.1.3 Integrated economizer control. Economizer systems shall be integrated with the mechanical cooling system and be capable of providing partial cooling even where additional mechanical cooling is required to meet the remainder of the cooling load.
C403.4.1.4 Economizer heating system impact. HVAC system design and economizer controls shall be such that economizer operation does not increase the building heating energy use during normal operation.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40342 Section ((C403.4.2—VAV)) C403.4.1—Fan control.
((C403.4.2 Variable air volume (VAV) fan control. Individual VAV fans with motors of 7.5 horsepower (5.6 kW) or greater shall be:
1. Driven by a mechanical or electrical variable speed drive;
2. Driven by a vane-axial fan with variable-pitch blades; or
3. The fan shall have controls or devices that will result in fan motor demand of no more than 30 percent of their design wattage at 50 percent of design airflow when static pressure set point equals one-third of the total design static pressure, based on manufacturer's certified fan data.
C403.4.2.1)) C403.4.1 Multi-zone system fan control. Controls shall be provided for fans in accordance with Section C403.4.1.1 through C403.4.1.2.
C403.4.1.1 Static pressure sensor location. Static pressure sensors used to control VAV fans shall be ((placed in a position)) located such that the controller setpoint is no greater than ((one-third the total design fan static pressure, except for systems with zone reset control complying with Section C403.4.2.2. For sensors installed)) 1.2 inches w.c. (2099 Pa). Where this results in one or more sensors being located downstream of major duct splits, ((at least)) not less than one sensor shall be located on each major branch to ensure that static pressure can be maintained in each branch.
((C403.4.2.2))
C403.4.1.2 Set points for direct digital control. For systems with direct digital control of individual zones ((boxes)) reporting to the central control panel, the static pressure setpoint shall be reset based on the zone requiring the most pressure((, i.e., the setpoint is reset lower until one zone damper is nearly wide open)). In such cases, the set point is reset lower until one zone damper is nearly wide open. The direct digital controls shall be capable of monitoring zone damper positions or shall have an alternative method of indicating the need for static pressure that is configured to provide all of the following:
1. Automatically detecting any zone that excessively drives the reset logic.
2. Generating an alarm to the system operational location.
3. Allowing an operator to readily remove one or more zones from the reset algorithm.
AMENDATORY SECTION (Amending WSR 13-20-120, filed 10/1/13, effective 11/1/13)
WAC 51-11C-40343 Section ((C403.4.3)) C403.4.2—Hydronic systems controls.
((C403.4.3)) C403.4.2 Hydronic systems controls. The heating of fluids that have been previously mechanically cooled and the cooling of fluids that have been previously mechanically heated shall be limited in accordance with Sections ((C403.4.3.1 through C403.4.3.3)) C403.4.2.1 through C403.4.2.3. Hydronic heating systems comprised of multiple-packaged boilers and designed to deliver conditioned water or steam into a common distribution system shall include automatic controls ((capable of sequencing)) configured to sequence operation of the boilers. Hydronic heating systems comprised of a single boiler and greater than 500,000 Btu/h (146,550 W) input design capacity shall include either a multi-staged or modulating burner.
((C403.4.3.1)) C403.4.2.1 Three-pipe system. Hydronic systems that use a common return system for both hot water and chilled water are prohibited.
((C403.4.3.2)) C403.4.2.2 Two-pipe changeover system. Systems that use a common distribution system to supply both heated and chilled water shall be designed to allow a dead band between changeover from one mode to the other of at least 15°F (8.3°C) outside air temperatures; be designed to and provided with controls that will allow operation in one mode for at least 4 hours before changing over to the other mode; and be provided with controls that allow heating and cooling supply temperatures at the changeover point to be no more than 30°F (16.7°C) apart.
((C403.4.3.3)) C403.4.2.3 Hydronic (water loop) heat pump systems. Hydronic heat pump systems shall comply with Sections ((C403.4.3.3.1 through C403.4.3.3.3)) C403.4.2.3.1 through C403.4.2.3.3.
((C403.4.3.3.1)) C403.4.2.3.1 Temperature dead band. Hydronic heat pumps connected to a common heat pump water loop with central devices for heat rejection and heat addition shall have controls that are ((capable of providing)) configured to provide a heat pump water supply temperature dead band of at least 20°F (11.1°C) between initiation of heat rejection and heat addition by the central devices.
((C403.4.3.3.2)) C403.4.2.3.2 Heat rejection. Heat rejection equipment shall comply with Sections ((C403.4.3.3.2.1 and C403.4.3.3.2.2)) C403.4.2.3.2.1 and C403.4.2.3.2.2.
((C403.4.3.3.2.1)) C403.4.2.3.2.1 Climate Zones 3 and 4. For Climate Zones 3 and 4:
1. If a closed-circuit cooling tower is used directly in the heat pump loop, either an automatic valve shall be installed to bypass all but a minimal flow of water around the tower, or lower leakage positive closure dampers shall be provided.
2. If an open-circuit tower is used directly in the heat pump loop, an automatic valve shall be installed to bypass all heat pump water flow around the tower.
3. If an open- or closed-circuit cooling tower is used in conjunction with a separate heat exchanger to isolate the cooling tower from the heat pump loop, then heat loss shall be controlled by shutting down the circulation pump on the cooling tower loop.
((C403.4.3.3.2.2)) C403.4.2.3.2.2 Climate Zones 5 through 8. For Climate Zones 5 through 8, if an open- or closed-circuit cooling tower is used, then a separate heat exchanger shall be provided to isolate the cooling tower from the heat pump loop, and heat loss shall be controlled by shutting down the circulation pump on the cooling tower loop and providing an automatic valve to stop the flow of fluid.
((C403.4.3.3.3)) C403.4.2.3.3 Isolation valve. Each hydronic heat pump on the hydronic system having a total pump system power exceeding 10 horsepower (hp) (7.5 kW) shall have a two-way (but not three-way) valve. For the purposes of this section, pump system power is the sum of the nominal power demand (i.e., nameplate horsepower at nominal motor efficiency) of motors of all pumps that are required to operate at design conditions to supply fluid from the heating or cooling source to all heat transfer devices (e.g., coils, heat exchanger) and return it to the source. This converts the system into a variable flow system and, as such, the primary circulation pumps shall comply with the variable flow requirements in Section ((C403.4.3.6)) C403.4.2.6.
((C403.4.3.4)) C403.4.2.4 Part load controls. Hydronic systems greater than or equal to 300,000 Btu/h (((87,930 W))) (88 kW) in design output capacity supplying heated or chilled water to comfort conditioning systems shall include controls that ((have the capability)) are configured to:
1. Automatically reset the supply-water temperatures ((using zone-return water temperature, building-return water temperature, or outside air temperature as an indicator of building heating or cooling demand)) in response to varying building heating and cooling demand using coil valve position, zone-return water temperature or outdoor air temperature. The temperature shall be ((capable of being)) reset by ((at least)) not less than 25 percent of the design supply-to-return water temperature difference((; and
2. Reduce system pump flow by at least 50 percent of design flow rate utilizing adjustable speed drive(s) on pump(s), or multiple-staged pumps where at least one-half of the total pump horsepower is capable of being automatically turned off or control valves designed to modulate or step down, and close, as a function of load, or other approved means.
Hydronic systems serving hydronic heat pumps are exempt from item 1, and only those hydronic systems with a total pump system power greater than 3 hp (2.2 kw) shall have controls meeting the requirements of item 2, above.
C403.4.3.5)).
2. Automatically vary fluid flow for hydronic systems with a combined motor capacity of 3 hp or larger with three or more control valves or other devices by reducing the system design flow rate by not less than 50 percent by designed valves that modulate or step open and close, or pumps that modulate or turn on and off as a function of load.
3. Automatically vary pump flow or chilled-water systems and heat rejection loops serving water-cooled unitary air conditioners with a combined motor capacity of 3 hp or larger by reducing pump design flow by not less than 50 percent utilizing adjustable speed drives or pumps, or multiple-staged pumps where not less than one-half of the total pump horsepower is capable of being automatically turned off. Pump flow shall be controlled to maintain one control valve nearly wide open or to satisfy the minimum differential pressure.
C403.4.2.5 Boiler turndown. Boiler systems with design input of greater than 1,000,000 Btu/h (293 kW) shall comply with the turndown ratio specified in Table C403.4.2.5.
The system turndown requirement shall be met through the use of multiple single input boilers, one or more modulating boilers or a combination of single input and modulating boilers.
Table C403.4.2.5
Boiler Turndown
C403.4.2.6 Pump isolation. Chilled water plants including more than one chiller shall ((have the capability)) be capable of and configured to reduce flow automatically through the chiller plant when a chiller is shut down and automatically shut off flow to chillers that are shut down. Chillers piped in series for the purpose of increased temperature differential shall be considered as one chiller.
Boiler plants including more than one boiler shall ((have the capability)) be capable of and configured to reduce flow automatically through the boiler plant when a boiler is shut down ((and automatically shut off flow to boilers that are shut down)).
((C403.4.3.6)) C403.4.2.7 Variable flow controls. Individual pumps ((requiring variable speed control per Section C403.4.9)) required by this code to have variable speed control shall be controlled in one of the following manners:
1. For systems having a combined pump motor horsepower less than or equal to 20 hp (15 kW) and without direct digital control of individual coils, pump speed shall be a function of either:
1.1. Required differential pressure; or
1.2. Reset directly based on zone hydronic demand, or other zone load indicators; or
1.3. Reset directly based on pump power and pump differential pressure.
2. For systems having a combined pump motor horsepower that exceeds 20 hp (15 kW) or smaller systems with direct digital control, pump speed shall be a function of either:
2.1. The static pressure set point as reset based on the valve requiring the most pressure; or
2.2. Directly controlled based on zone hydronic demand.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-403431 ((Table C403.4.3.1.1.3—High limit shutoff controls.)) Reserved.
((Table C403.3.1.1.3(1)
High-limit Shutoff Control Options for Air Economizers
Table C403.3.1.1.3(2)
High-limit Shutoff Control Setting for Air Economizers
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40344 Section ((C403.4.4)) C403.4.3—Heat rejection equipment ((fan speed control)).
((C403.4.4)) C403.4.3 Heat rejection equipment ((fan speed control. Each fan powered by a motor of 7.5 hp (5.6 kW) or larger shall have controls that automatically change the fan speed to control the leaving fluid temperature or condensing temperature/pressure of the heat rejection device)). Heat rejection equipment such as air-cooled condensers, dry coolers, open-circuit cooling towers, closed-circuit cooling towers and evaporative condensers used for comfort cooling applications shall comply with this section.
C403.4.3.1 Fan speed control.The fan speed shall be controlled as provided in Sections C403.4.3.2.1 and C403.4.3.2.2.
C403.4.3.1.1 Fan motors not less than 7.5 hp. Each fan powered by a motor of 7.5 hp (5.6 kW) or larger shall have controls that automatically change the fan speed to control the leaving fluid temperature or condensing temperature/pressure of the heat rejection device.
C403.4.3.1.2 Multiple-cell heat rejection equipment. Multiple-cell heat rejection equipment with variable speed fan drives shall be controlled in both of the following manners:
1. To operate the maximum number of fans allowed that comply with the manufacturer's requirements for all system components.
2. So all fans can operate at the same fan speed required for the instantaneous cooling duty, as opposed to staged (on/off) operation. Minimum fan speed shall be the minimum allowable speed of the fan drive system in accordance with the manufacturer's recommendations.
C403.4.3.2 Limitation on centrifugal fan open-circuit cooling towers. Centrifugal fan open-circuit cooling towers with a combined rated capacity of 1,100 gpm (4164 L/m) or greater at 95°F (35°C) condenser water return, 85°F (29°C) condenser water supply, and 75°F (24°C) outdoor air wet-bulb temperature shall meet the energy efficiency requirement for axial fan open-circuit cooling towers listed in Table C403.2.3(8).
C403.4.3.3 Tower flow turndown. Open-circuit cooling towers used on water-cooled chiller systems that are configured with multiple- or variable-speed condenser water pumps shall be designed so that all open circuit cooling tower cells can be run in parallel with the larger of the flow that is produced by the smallest pump at its minimum expected flow rate or at 50 percent of the design flow for the cell.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40345 Section ((C403.4.5)) C403.4.4—Requirements for ((complex)) mechanical systems serving multiple zones.
((C403.4.5)) C403.4.4 Requirements for ((complex)) mechanical systems serving multiple zones. Sections ((C403.4.5.1 through C403.4.5.4)) C403.4.4.1 through C403.4.4.4 shall apply to complex mechanical systems serving multiple zones. Supply air systems serving multiple zones shall be VAV systems which, during periods of occupancy, are designed and ((capable of being controlled)) configured to reduce primary air supply to each zone to one of the following before reheating, recooling or mixing takes place:
1. Thirty percent of the maximum supply air to each zone.
2. Three hundred cfm (142 L/s) or less where the maximum flow rate is less than 10 percent of the total fan system supply airflow rate.
3. The minimum ventilation requirements of Chapter 4 of the International Mechanical Code.
4. ((Minimum flow rates required by applicable codes or standards for occupant health and safety.)) Any higher rate that can be demonstrated to reduce overall system annual energy use by offsetting reheat/recool energy losses through a reduction in outdoor air intake for the system, as approved by the code official.
5. The airflow rates to comply with applicable codes or accreditation standards such as pressure relationships or minimum air change rates.
((C403.4.5.1)) C403.4.4.1 Single duct variable air volume (VAV) systems, terminal devices. Single duct VAV systems shall use terminal devices capable of ((reducing)) and configured to reduce the supply of primary supply air before reheating or recooling takes place.
((C403.4.5.2)) C403.4.4.2 Dual duct and mixing VAV systems, terminal devices. Systems that have one warm air duct and one cool air duct shall use terminal devices which are capable of ((reducing)) and configured to reduce the flow from one duct to a minimum before mixing of air from the other duct takes place.
((C403.4.5.3 Reserved.
C403.4.5.4)) C403.4.4.3 Multiple-zone VAV system ventilation optimization control. Multiple-zone VAV systems with direct digital control of individual zone boxed reporting to a central control panel shall have automatic controls configured to reduce outdoor air intake flow below design rates in response to changes in system ventilation efficiency (Ev) as defined by the International Mechanical Code.
C403.4.4.4 Supply-air temperature reset controls. Multiple zone HVAC systems shall include controls that automatically reset the supply-air temperature in response to representative building loads, or to outdoor air temperature. The controls shall be capable of resetting the supply air temperature at least 25 percent of the difference between the design supply-air temperature and the design room air temperature.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40346 ((Section C403.4.6—Heat recovery for service water heating.)) Reserved.
((C403.4.6 Heat recovery for service water heating. Condenser heat recovery shall be installed for heating or reheating of service hot water provided the facility operates 24 hours a day, the total installed heat capacity of water cooled systems exceeds 1,500,000 Btu/hr of heat rejection, and the design service water heating load exceeds 250,000 Btu/hr.
The required heat recovery system shall have the capacity to provide the smaller of:
1. Sixty percent of the peak heat rejection load at design conditions; or
2. The preheating required to raise the peak service hot water draw to 85°F (29°C).
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40350 Section C403.5—((Walk-in coolers and freezers)) Energy recovery.
((C403.5 Walk-in coolers and walk-in freezers. Walk-in coolers and walk-in freezers shall comply with all of the following:
1. Anti-sweat heaters without anti-sweat heater controls shall have a total door rail, glass, and frame heater power draw of less than or equal to 7.1 watts per square foot of door opening for walk-in freezers, and 3.0 watts per square foot of door opening for walk-in coolers.
2. Anti-sweat heater controls shall reduce the energy use of the anti-sweat heater as a function of the relative humidity in the air outside the door or to the condensation on the inner glass pane.
3. Evaporator fan motors that are less than 1 horsepower and less than 460 volts shall use electronically commutated motors (brushless direct current motors) or 3-phase motors.
4. Condenser fan motors that are less than 1 horsepower shall use electronically commutated motors, permanent split capacitor-type motors or 3-phase motors.)) C403.5 Energy recovery.
C403.5.1 Energy recovery ventilation systems. Any system with minimum outside air requirements at design conditions greater than 5,000 cfm or any system where the system's supply airflow rate exceeds the value listed in Tables C403.5.1(1) and C403.5.1(2), based on the climate zone and percentage of outdoor airflow rate at design conditions, shall include an energy recovery system. Table C403.5.1(1) shall be used for all ventilation systems that operate less than 8,000 hours per year, and Table C403.5.1(2) shall be used for all ventilation systems that operate 8,000 hours or more per year. The energy recovery system shall have the capability to provide a change in the enthalpy of the outdoor air supply of not less than 50 percent of the difference between the outdoor air and return air enthalpies, at design conditions. Where an air economizer is required, the energy recovery system shall include a bypass or controls which permit operation of the economizer as required by Section C403.3. Where a single room or space is supplied by multiple units, the aggregate ventilation (cfm) of those units shall be used in applying this requirement. The return/exhaust air stream temperature for heat recovery device selection shall be 70°F (21°C) at 30 percent relative humidity, or as calculated by the registered design professional.
Table C403.5.1(1)
Energy Recovery Requirement
(Ventilation systems operating less than 8,000 hours per year)
Table C403.5.1(2)
Energy Recovery Requirement
(Ventilation systems operating not less than 8,000 hours per year)
C403.5.2 Condensate systems. On-site steam heating systems shall have condensate water heat recovery. On-site includes a system that is located within or adjacent to one or more buildings within the boundary of a contiguous area or campus under one ownership and which serves one or more of those buildings.
Buildings using steam generated off-site with steam heating systems which do not have condensate water recovery shall have condensate water heat recovery.
C403.5.3 Condenser heat recovery. Facilities having food service, meat or deli departments and having 500,000 Btu/h or greater of remote refrigeration condensers shall have condenser waste heat recovery from freezers and coolers and shall use the waste heat for service water heating, space heating or for dehumidification reheat. Facilities having a gross conditioned floor area of 40,000 ft2 or greater and 1,000,000 Btu/h or greater of remote refrigeration shall have condenser waste heat recovery from freezers and coolers and shall use the waste heat for service water heating, and either for space heating or for dehumidification reheat for maintaining low space humidity.
C403.5.4 Heat recovery for service water heating. Condenser heat recovery shall be installed for heating or reheating of service hot water provided the facility operates 24 hours a day, the total installed heat capacity of water cooled systems exceeds 1,500,000 Btu/hr of heat rejection, and the design service water heating load exceeds 250,000 Btu/hr.
The required heat recovery system shall have the capacity to provide the smaller of:
1. Sixty percent of the peak heat rejection load at design conditions; or
2. The preheating required to raise the peak service hot water draw to 85°F (29°C).
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40360 ((Section C403.6—Refrigerated warehouse coolers and freezers.)) Reserved.
((C403.6 Refrigerated warehouse coolers and refrigerated warehouse freezers. Refrigerated warehouse coolers and refrigerated warehouse freezers shall comply with all of the following:
1. Evaporator fan motors that are less than 1 horsepower and less than 460 volts shall use electronically commutated motors (brushless direct current motors) or 3-phase motors.
2. Condenser fan motors that are less than 1 horsepower shall use electronically commutated motors, permanent split capacitor-type motors or 3-phase motors.))
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40402 Section C404.2—Service water-heating equipment performance efficiency.
C404.2 Service water-heating equipment performance efficiency. Water-heating equipment and hot water storage tanks shall meet the requirements of Table C404.2. The efficiency shall be verified through certification and listed under an approved certification program, or if no certification program exists, the equipment efficiency ratings shall be supported by data furnished by the manufacturer. Water-heating equipment also intended to be used to provide space heating shall meet the applicable provisions of Table C404.2.
C404.2.1 High input-rated service water heating systems. Gas-fired water-heating equipment installed in new buildings shall be in compliance with this section. Where a singular piece of water-heating equipment serves the entire building and the input rating of the equipment is 1,000,000 Btu/h (293 kW) or greater, such equipment shall have a thermal efficiency, Et, of not less than 90 percent. Where multiple pieces of water-heating equipment serve the building and the combined input rating of the water-heating equipment is 1,000,000 Btu/h (293 kW) or greater, the combined input-capacity-weighted-average thermal efficiency, Et, shall not be less than 90 percent.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-404021 Table C404.2—Minimum performance of water-heating equipment.
Table C404.2
Minimum Performance of Water-Heating Equipment
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency. Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040. AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40403 Section C404.3—((Temperature controls)) Efficient heated water supply piping.
((C404.3 Temperature controls. Service water-heating equipment shall be provided with controls to allow a setpoint of 110°F (43°C) for equipment serving dwelling units and 90°F (32°C) for equipment serving other occupancies. The outlet temperature of lavatories in public facility rest rooms shall be limited to 110°F (43°C).)) C404.3 Efficient heated water supply piping. Heated water supply piping shall be in accordance with Section C404.3.1 or C404.3.2. The flow rate through 1/4-inch (6.4 mm) piping shall be not greater than 0.5 gpm (1.9 L/m). The flow rate through 5/16-inch (7.9 mm) piping shall be not greater than 1 gpm (3.8 L/m). The flow rate through 3/8-inch (9.5 mm) piping shall be not greater than 1.5 gpm (5.7 L/m). Water heaters, circulating water systems and heat trace temperature maintenance systems shall be considered sources of heated water.
C404.3.1 Maximum allowable pipe length method. The maximum allowable piping length from the nearest source of heater water to the termination of the fixture supply pipe shall be in accordance with the following. Where the piping contains more than one size of pipe, the largest size of pipe within the piping shall be used for determining the maximum allowable length of the piping in Table C404.3.1.
1. For a public lavatory faucet, use the "Public lavatory faucets" column in Table C404.3.1.
2. For all other plumbing fixtures and plumbing appliances, use the "Other fixtures and appliances" column in Table C404.6.1.
Table C404.6.1
Piping Volume and Maximum Piping Lengths
C404.3.2 Maximum allowable pipe volume method. The water volume in the piping shall be calculated in accordance with Section C404.3.2.1.
The volume from the nearest source of heated water to the termination of the fixture supply pipe shall be as follows:
1. For a public lavatory faucet: Not more than 2 ounces (0.06 L).
2. For other plumbing fixtures or plumbing appliances; not more than 0.5 gallon (1.89 L).
C404.3.2.1 Water volume determination. The volume shall be the sum of the internal volumes of pipe, fittings, valves, meters and manifolds between the nearest source of heated water and the termination of the fixture supply pipe. The volume in the piping shall be determined from the "Volume" column in Table C404.3.1. The volume contained within fixture shutoff valves, within flexible water supply connectors to a fixture fitting and within a fixture fitting shall not be included in the water volume determination. Where heated water is supplied by a recirculating system or heat-traced piping, the volume shall include the portion of the fitting on the branch pipe that supplies water to the fixture.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40406 Section C404.6—Pipe insulation.
((C404.6 Pipe insulation. For automatic-circulating hot water and heat-traced systems, piping shall be insulated with not less than 1 inch (25 mm) of insulation having a conductivity not exceeding 0.27 Btu per inch/h × ft2 × °F (1.53 W per 25 mm/m2 × K). The first 8 feet (2438 mm) of piping in nonhot-water-supply temperature maintenance systems served by equipment without integral heat traps shall be insulated with 0.5 inch (12.7 mm) of material having a conductivity not exceeding 0.27 Btu per inch/h × ft2 × °F (1.53 W per 25 mm/m2 × K).
C404.6 Insulation of piping. Piping from a water heater to the termination of the heated water fixture supply pipe shall be insulated in accordance with Table C403.2.9. On both the inlet and outlet piping of a storage water heater or heated water storage tank, the piping to a heat trap or the first 8 feet (2438 mm) of piping, whichever is less, shall be insulated. Piping that is heat traced shall be insulated in accordance with Table C403.2.9 or the heat trace manufacturer's instructions. Tubular pipe insulation shall be installed in accordance with the insulation manufacturer's instructions. Pipe insulation shall be continuous except where the piping passes through a framing member. The minimum insulation thickness requirements of this section shall not supersede any greater insulation thickness requirements necessary for the protection of piping from freezing temperatures or the protection of personnel against external surface temperatures on the insulation.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40407 Section C404.7—((Hot water system controls)) Heated-water circulating and temperature maintenance systems.
((C404.7 Hot water system controls. Circulating hot water system pumps or heat trace shall be arranged to be turned off either automatically or manually when there is limited hot water demand. Ready access shall be provided to the operating controls.)) C404.7 Heated-water circulating and temperature maintenance systems. Heated-water circulation systems shall be in accordance with Section C404.7.1. Heat trace temperature maintenance systems shall be in accordance with Section C404.7.2. Controls for hot water storage shall be in accordance with Section C404.7.3. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
C404.7.1 Circulation systems. Heated-water circulation systems shall be provided with a circulation pump. The system return pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermo-syphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water.
C404.7.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1. Controls for such systems shall be able to automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. Heat trace shall be arranged to be turned off automatically when there is no hot water demand.
C404.7.3 Controls for hot water storage. The controls on pumps that circulate water between a water heater and a heated-water storage tank shall limit operation of the pump from heating cycle startup to not greater than 5 minutes after the end of the cycle.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40408 Section C404.8—((Shut-off controls)) Demand recirculation controls.
((C404.8 Shut-off controls. Systems designed to maintain usage temperatures in hot water pipes, such as circulating hot water systems or heat traced pipes, shall be equipped with automatic time switches or other controls to turn off the system during periods of nonuse.)) C404.8 Demand recirculation controls. A water distribution system having one or more recirculation pumps that pump water from a heated-water supply pipe back to the heated-water source through a cold-water supply pipe shall be a demand recirculation water system. Pumps shall have controls that comply with both of the following:
1. The control shall start the pump upon receiving a signal from the action of a user of a fixture or appliance, sensing the presence of a user of a fixture or sensing the flow of hot or tempered water to a fixture fitting or appliance.
2. The control shall limit the temperature of the water entering the cold-water piping to 104°F (40°C).
NEW SECTION
WAC 51-11C-404091 Section C404.10—Drain water heat recovery units.
C404.10 Drain water heat recovery units. Drain water heat recovery units shall comply with CSA B55.2. Potable waterside pressure loss shall be less than 10 psi (69 kPa) at maximum design flow. For Group R occupancies, the efficiency of drain water heat recovery unit efficiency shall be in accordance with CSA B55.1.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40410 Section ((C404.10)) C404.11—Pools and ((in-ground)) spas.
((C404.10 Pools and in-ground permanently installed spas)) C404.11 Energy consumption of pools and permanent spas (mandatory). ((Pools and in-ground permanently installed spas shall comply with Sections C404.10.1 through C404.10.4)) The energy consumption of pools and permanent spas shall be controlled by the requirements in Sections C404.11.1 through C404.11.4.
((C404.10.1)) C404.11.1 Heaters. Heat pump pool heaters shall have a minimum COP of 4.0 determined in accordance with ASHRAE Standard 146. Other pool heating equipment shall comply with the applicable efficiencies in Section ((C404.2.3)) C404.2.
((All heaters shall be equipped with a readily accessible on-off switch that is mounted outside of the heater to allow shutting off the heater without adjusting the thermostat setting.)) The electric power to all heaters shall be controlled by a readily accessible on-off switch that is an integral part of the heater, mounted on the exterior of the heater, or external to and within 3 feet of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas-fired heaters shall not be equipped with constant burning pilot lights.
((C404.10.2)) C404.11.2 Time switches. Time switches or other control method that can automatically turn off and on heaters and pump((s)) motors according to a preset schedule shall be installed ((on all)) for heaters and pump((s)) motors. Heaters((, pumps)) and pump motors that have built-in ((timers)) time switches shall be ((deemed)) in compliance with this ((requirement)) section.
((C404.10.3)) C404.11.3 Covers. Heated pools and ((in-ground permanently installed)) permanent spas shall be provided with a vapor-retardant cover on or at the water surface. Pools heated to more than 90°F shall have a pool cover with a minimum insulation value of R-12, and the sides and bottom of the pool shall also have a minimum insulation value of R-12.
((C404.10.4)) C404.11.4 Heat recovery. Heated indoor swimming pools, spas or hot tubs with water surface area greater than 200 square feet shall provide for energy conservation by an exhaust air heat recovery system that heats ventilation air, pool water or domestic hot water. The heat recovery system shall be ((capable of decreasing)) configured to decrease the exhaust air temperature at design heating conditions (80°F indoor) by 36°F (10°C) ((in Climate Zones 4C and 5B and 48°F (26.7°C) in Climate Zone 6B)).
C404.12 Energy consumption of portable spas (mandatory). The energy consumption of electric-powered portable spas shall be controlled by the requirements of APSP 14.
NEW SECTION
WAC 51-11C-40413 Section C404.13—Service water-heating system commissioning and completion requirements.
C404.13 Service water-heating system commissioning and completion requirements. Service water-heating systems, swimming pool water-heating systems, spa water-heating systems and the controls for those systems shall be commissioned and completed in accordance with Section C408.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40501 Section C405.1—General.
C405.1 General (mandatory). This section covers lighting system controls, ((the connection of ballasts,)) the maximum lighting power for interior applications, electrical energy consumption, ((minimum acceptable lighting equipment for exterior applications)) vertical and horizontal transportation systems, and minimum efficiencies for motors and transformers.
((Walk-in coolers and walk-in freezers shall comply with C405.10. Refrigerated warehouse coolers and refrigerated warehouse freezers shall comply with C405.11.))
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40502 Section C405.2—Electrical power and lighting systems.
C405.2 Lighting controls (mandatory). Lighting systems shall be provided with controls as specified in Sections C405.2.1((, C405.2.2, C405.2.3, C405.2.4 and C405.2.5)) through C405.2.8.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-405021 Section C405.2.1—((Manual lighting)) Occupant sensor controls.
((C405.2.1 Manual lighting controls. All buildings shall include manual lighting controls that meet the requirements of Sections C405.2.1.1 and C405.2.1.2.
C405.2.1.1 Interior lighting controls. Each area enclosed by walls or floor-to-ceiling partitions shall have at least one manual control for the lighting serving that area. The required controls shall be located within the area served by the controls or be a remote switch that identifies the lights served and indicates their status.
C405.2.1.2 Light reduction controls. Each area that is required to have a manual control shall also allow the occupant to reduce the connected lighting load in a reasonably uniform illumination pattern by at least 50 percent. Lighting reduction shall be achieved by one of the following or other approved method:
1. Controlling all lamps or luminaires;
2. Dual switching of alternate rows of luminaires, alternate luminaires or alternate lamps;
3. Switching the middle lamp luminaires independently of the outer lamps; or
4. Switching each luminaire or each lamp.
C405.2.1 Occupant sensor controls. Occupant sensor controls shall be installed to control lights in the following space types:
1. Classrooms/lecture/training rooms.
2. Conference/meeting/multipurpose rooms.
3. Copy/print rooms.
4. Lounges.
5. Employee lunch and break rooms.
6. Private offices.
7. Restrooms.
8. Storage rooms.
9. Janitorial closets.
10. Locker rooms.
11. Other spaces 300 square feet (28 m2) or less that are enclosed by floor-to-ceiling height partitions.
12. Warehouses.
C405.2.1.1 Occupant sensor control function. Occupant sensor controls shall comply with the following:
1. Automatically turn off lights within 30 minutes of all occupants leaving the space.
2. Be manual on or controlled to automatically turn the lighting on to not more than 50 percent power.
3. Shall incorporate a manual control to allow occupants to turn lights off.
C405.2.1.2 Occupant sensor control function in warehouses. In warehouses, the lighting in aisleways and open areas shall be controlled with occupancy sensors that automatically reduce lighting power by not less than 50 percent when the areas are unoccupied. The occupancy sensor shall control lighting in each aisleway independently, and shall not control lighting beyond the aisleway being controlled by the sensor.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-405022 Section C405.2.2—((Additional lighting)) Time switch controls.
C405.2.2 ((Additional lighting)) Time switch controls. Each area of the building that is ((required to have a manual control shall also have controls that meet the requirements of Sections C405.2.2.1, C405.2.2.2 and C405.2.2.3)) not provided with occupant sensor controls complying with Section C405.2.1.1 shall be provided with time switch controls complying with Section C405.2.2.1.
C405.2.2.1 ((Automatic)) Time switch control ((devices)) function. ((Automatic time switch controls shall be installed to control lighting in all areas of the building. Automatic time switches shall have a minimum 7 day clock and be capable of being set for 7 different day types per week and incorporate an automatic holiday "shut-off" feature, which turns off all loads for at least 24 hours and then resumes normally scheduled operations. Automatic time switches shall also have program back-up capabilities, which prevent the loss of program and time settings for at least 10 hours, if power is interrupted.
The automatic time switch control device shall include an override switching device that complies with the following:
1. The override switch shall be in a readily accessible location;
2. The override switch shall be located where the lights controlled by the switch are visible; or the switch shall provide a mechanism which announces the area controlled by the switch;
3. The override switch shall permit manual operation;
4. The override switch, when initiated, shall permit the controlled lighting to remain on for a maximum of 2 hours; and
5. Any individual override switch shall control the lighting for a maximum area of 5,000 square feet (465 m2).
C405.2.2.2 Occupancy sensors. Occupancy sensors shall be installed in all classrooms, conference/meeting rooms, employee lunch and break rooms, private offices, restrooms, warehouse spaces, storage rooms and janitorial closets, and other spaces 300 square feet (28 m2) or less enclosed by floor-to-ceiling height partitions. These automatic control devices shall be installed to automatically turn off lights within 30 minutes of all occupants leaving the space, and shall either be manual on or shall be controlled to automatically turn the lighting on to not more than 50 percent power.
C405.2.2.3 Daylight zone control. Daylight zones shall be designed such that lights in the daylight zone are controlled independently of general area lighting and are controlled in accordance with Section C405.2.2.3.2. Each daylight control zone shall not exceed 2,500 square feet (232 m2). Contiguous daylight zones adjacent to vertical fenestration are allowed to be controlled by a single controlling device provided that they do not include zones facing more than two adjacent cardinal orientations (i.e., north, east, south, west). The primary daylight zone shall be controlled separately from the secondary daylight zone. Daylight zones under skylights more than 15 feet (4572 mm) from the perimeter shall be controlled separately from daylight zones adjacent to vertical fenestration. Controls shall:
1. Control only luminaires within the daylit area.
2. Incorporate time-delay circuits to prevent cycling of light level changes of less than three minutes.
C405.2.2.3.1 Reserved.
C405.2.2.3.2 Automatic daylighting controls. Setpoint and other controls for calibrating the lighting control device shall be readily accessible.
Daylighting controls device shall be capable of automatically reducing the lighting power in response to available daylight by either one of the following methods:
1. Continuous dimming using dimming ballasts and daylight-sensing automatic controls that are capable of reducing the power of general lighting in the daylit zone continuously to less than 20 percent of rated power at maximum light output.
2. Stepped dimming using multi-level switching and daylight-sensing controls that are capable of reducing lighting power automatically. The system shall provide a minimum of two control channels per zone and be installed in a manner such that at least one control step is between 50 percent and 70 percent of design lighting power and another control step is no greater than 35 percent of design power, and the system is capable of automatically turning the system off.
C405.2.2.3.3 Reserved.)) Each space provided with time switch controls shall also be provided with a manual control for light reduction in accordance with Section C405.2.2.2. Time switch controls shall comply with the following:
1. Have a minimum 7 day clock.
2. Be capable of being set for 7 different day types per week.
3. Incorporate an automatic holiday "shut-off" feature, which turns off all controlled lighting loads for at least 24 hours and then resumes normally scheduled operations.
4. Have program back-up capabilities, which prevent the loss of program and time settings for at least 10 hours, if power is interrupted.
5. Include an override switching device that complies with the following:
5.1. A manual control.
5.2. The override switch, when initiated, shall permit the controlled lighting to remain on for not more than 2 hours.
5.3. Any individual override switch shall control the lighting for an area not larger than 5,000 square feet (465 m2).
C405.2.2.2 Light reduction controls. Spaces required to have light-reduction controls shall have a manual control that allows the occupant to reduce the connected lighting load in a reasonably uniform illumination pattern by at least 50 percent. Lighting reductions shall be achieved by one of the following approved methods:
1. Controlling all lamps or luminaires.
2. Dual switching of alternate rows of luminaires, alternate luminaires or alternate lamps.
3. Switching the middle lamp luminaires independently of the outer lamps.
4. Switching each luminaire or each lamp.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-405023 Section C405.2.3—((Specific application)) Manual controls.
C405.2.3 ((Specific application)) Manual controls. ((Specific application controls shall be provided for the following:
1. Display and accent light shall be controlled by a dedicated control which is independent of the controls for other lighting within the room or space.
2. Lighting in cases used for display case purposes shall be controlled by a dedicated control which is independent of the controls for other lighting within the room or space.
3. Hotel and motel sleeping units and guest suites shall have a master control device at the main room entry that controls all permanently installed luminaires and switched receptacles. Where a hotel/motel includes more than 50 rooms, controls shall be automatic to ensure all power to the lights and switched outlets are turned off when the occupant is not in the room.
4. Supplemental task lighting, including permanently installed under-shelf or under-cabinet lighting, shall be automatically shut off whenever that space is unoccupied and shall have a control device integral to the luminaires or be controlled by a wall-mounted control device provided the control device is readily accessible.
5. Lighting for nonvisual applications, such as plant growth and food warming, shall be controlled by a dedicated control which is independent of the controls for other lighting within the room or space.
6. Lighting equipment that is for sale or for demonstrations in lighting education shall be controlled by a dedicated control which is independent of the controls for other lighting within the room or space.
7. Luminaires serving the exit access and providing means of egress illumination required by Section 1006.1 of the International Building Code, including luminaires that function as both normal and emergency means of egress illumination shall be controlled by a combination of listed emergency relay and occupancy sensors, or signal from another building control system, that automatically shuts off the lighting when the areas served by that illumination are unoccupied.
Manual controls for lights shall comply with the following:
1. Shall be readily accessible to occupants.
2. Shall be located where the controlled lights are visible, or shall identify the area served by the lights and indicate their status.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-405024 Section C405.2.4—((Exterior lighting)) Daylight responsive controls.
C405.2.4 ((Exterior lighting)) Daylight responsive controls. ((Lighting not designated for dusk-to-dawn operation shall be controlled by either a combination of a photosensor and a time switch, or an astronomical time switch. Lighting designated for dusk-to-dawn operation shall be controlled by an astronomical time switch or photosensor. All time switches shall be capable of retaining programming and the time setting during loss of power for a period of at least 10 hours.)) Daylight responsive controls complying with Section C405.2.3.1 shall be provided to control the lighting within daylight zones in the following spaces:
1. Sidelight daylight zones as defined in Section C405.2.4.2 with more than two general lighting fixtures within the primary and secondary sidelight daylight zones.
2. Toplight daylight zones as defined in Section C405.2.4.3 with more than two general lighting fixtures within the daylight zone.
C405.2.4.1 Daylight responsive controls function. Where required, daylight responsive controls shall be provided within each space for control of lights in that space and shall comply with all of the following:
1. Lights in primary sidelight daylight zones shall be controlled independently of lights in secondary sidelight daylight zones in accordance with Section C405.2.4.2.
2. Lights in toplight daylight zones in accordance with Section C405.2.4.3 shall be controlled independently of lights in sidelight daylight zones in accordance with Section C405.2.4.2.
3. Daylight responsive controls within each space shall be configured so that they can be calibrated from within that space by authorized personnel.
4. Calibration mechanisms shall be readily accessible.
5. Daylight responsive controls shall be configured to completely shut off all controlled lights in that zone.
6. Lights in sidelight daylight zones in accordance with Section C405.2.4.2 facing different cardinal orientations (i.e., within 45 degrees of due north, east, south, west) shall be controlled independently of each other.
7. Incorporate time-delay circuits to prevent cycling of light level changes of less than three minutes.
8. The maximum area a single daylight responsive control device serves shall not exceed 2,500 square feet (232 m2).
C405.2.4.1.1 Dimming. Daylight responsive controls shall be capable of automatically reducing the power of general lighting in the daylight zone in response to available daylight, while maintaining uniform illumination in the space through one of the following methods:
1. Continuous dimming using dimming ballasts/dimming drivers and daylight-sensing controls. The system shall reduce lighting power continuously to less than 15 percent of rated power at maximum light output.
2. Stepped dimming using multi-level switching and daylight-sensing controls. The system shall provide a minimum of two steps of uniform illumination between 0 percent and 100 percent of rated power at maximum light output. Each step shall be in equal increments of power, plus or minus 10 percent.
General lighting within daylight zones in offices, classrooms, laboratories and library reading rooms shall use the continuous dimming method. Stepped dimming is not allowed as a method of daylight zone control in these spaces.
C405.2.4.2 Sidelight daylight zone. The sidelight daylight zone is the floor area adjacent to vertical fenestration which complies with the following:
1. Where the fenestration is located in a wall, the sidelight daylight zone includes the primary and secondary daylight zones. The primary daylight zone shall extend laterally to the nearest full height wall, or up to 1.0 times the height from the floor to the top of the fenestration, and longitudinally from the edge of the fenestration to the nearest full height wall, or up to 2 feet (610 mm), whichever is less, as indicated in Figure C405.2.4.2(1). The secondary daylight zone begins at the edge of the primary daylight zone and extends laterally to the nearest full height wall, or up to 2.0 times the height from the floor to the top of the fenestration, whichever is less, as indicated in Figure C405.2.4.2(1).
2. Where the fenestration is located in a rooftop monitor, the sidelight daylight zone shall extend laterally to the nearest obstruction that is taller than 0.7 times the ceiling height, or up to 1.0 times the height from the floor to the bottom of the fenestration, whichever is less, and longitudinally from the edge of the fenestration to the nearest obstruction that is taller than 0.7 times the ceiling height, or up to 0.25 times the height from the floor to the bottom of the fenestration, whichever is less, as indicated in Figures C405.2.4.2(2) and C405.2.4.2(3).
3. Where clerestory fenestration is located in a wall, the sidelight daylight zone includes a lateral area twice the depth of the clerestory fenestration height, projected upon the floor at a 45 degree angle from the center of the clerestory fenestration. The longitudinal width of the daylight zone is calculated the same as for fenestration located in a wall. Where the 45 degree angle is interrupted by an obstruction greater than 0.7 times the ceiling height, the daylight zone shall remain the same lateral area but be located between the clerestory and the obstruction, as indicated in Figure C405.2.4.2(4).
4. If the rough opening area of a vertical fenestration assembly is less than 10 percent of the calculated primary daylight zone area for this fenestration, it does not qualify as a daylight zone.
5. Where located in existing buildings, the visible transmittance of the fenestration is no less than 0.20.
6. In parking garages with floor area adjacent to perimeter wall openings, the daylight zone shall include the area within 20 feet of any portion of a perimeter wall that has a net opening to wall ratio of at least 40 percent.
Figure C405.2.4.2(1)
Daylight Zone Adjacent to Fenestration in a Wall
Figure C405.2.4.2(2)
Daylight Zone Under a Rooftop Monitor
Figure C405.2.4.2(3)
Daylight Zone Under a Sloped Rooftop Monitor
Figure C405.2.4.2(4)
Daylight Zone Adjacent to Clerestory Fenestration in a Wall
C405.2.4.3 Toplight daylight zone. The toplight daylight zone is the floor area underneath a roof fenestration assembly which complies with the following:
1. The toplight daylight zone shall extend laterally and longitudinally beyond the edge of the roof fenestration assembly to the nearest obstruction that is taller than 0.7 times the ceiling height, or up to 0.7 times the ceiling height, whichever is less, as indicated in Figure C405.2.4.3(1).
2. Where toplight daylight zones overlap with sidelight daylight zones, lights within the overlapping area shall be assigned to the toplight daylight zone.
3. Where located in existing buildings, the product of the visible transmittance of the roof fenestration assembly and the area of the rough opening of the roof fenestration assembly, divided by the area of the daylight zone is no less than 0.008.
4. Where located under atrium fenestration, the daylight zone shall include the bottom floor area directly beneath the atrium fenestration, and the top floor directly under the atrium fenestration, as indicated in Figure C405.2.4.3(2). The daylight zone area at the top floor is calculated the same as for a toplight daylight zone. Intermediate levels below the top floor that are not directly beneath the atrium are not included.
Figure C405.2.4.3(1)
Daylight Zone Under a Rooftop Fenestration Assembly
Figure C405.2.4.3(2)
Daylight Zone Under Atrium Fenestration
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-405025 Section C405.2.5—((Area)) Additional lighting controls.
C405.2.5 ((Area)) Additional lighting controls. ((The maximum lighting power that may be controlled from a single switch or automatic control shall not exceed that which is provided by a 20 ampere circuit loaded to not more than 80 percent. A master control may be installed provided the individual switches retain their capability to function independently. Circuit breakers may not be used as the sole means of switching.
Specific application lighting controls shall be provided with controls, in addition to controls required by other sections, for the following:
1. Display and accent light shall be controlled by a dedicated control which is independent of the controls for other lighting within the room or space.
2. Lighting in cases used for display case purposes shall be controlled by a dedicated control which is independent of the controls for other lighting within the room or space.
3. Hotel and motel sleeping units and guest suites shall have control device(s) configured to automatically switch off all installed luminaires and switched receptacles within 20 minutes after all occupants leave the room.
4. Supplemental task lighting, including permanently installed under-shelf or under-cabinet lighting, shall be automatically shut off whenever that space is unoccupied and shall have a control device integral to the luminaires or be controlled by a wall-mounted control device provided the control device is readily accessible.
5. Lighting for nonvisual applications, such as plant growth and food warming, shall be controlled by a dedicated control which is independent of the controls for other lighting. Each control zone shall be no greater than the area served by a single luminaire or 4,000 square feet, whichever is larger.
6. Lighting equipment that is for sale or for demonstrations in lighting education shall be controlled by a dedicated control which is independent of the controls for other lighting within the room or space.
7. Luminaires serving the exit access and providing means of egress illumination required by Section 1006.1 of the International Building Code, including luminaires that function as both normal and emergency means of egress illumination shall be controlled by a combination of listed emergency relay and occupancy sensors, or signal from another building control system, that automatically shuts off the lighting when the areas served by that illumination are unoccupied.
NEW SECTION
WAC 51-11C-40526 Section C405.2.6—Digital timer switch.
C405.2.6 Digital timer switch controls. For each of the following space types, when under 300 square feet, digital timer switch controls may be provided in lieu of occupancy sensor controls:
1. Copy/print rooms.
2. Storage rooms.
3. Janitorial closets.
C405.2.6.1 Digital timer switch function. Digital timer switches shall comply with the following:
1. Turn lights on or off with operation of a button, switch or other manual means.
2. Automatically turn lights off within 15 minutes of the lights being turned on. The time delay shall be configurable only by removing the switch faceplate. A switch where the time delay is selected or configurable from the front of the switch faceplate is not permitted.
3. The switch shall provide audible indication of impending shut-off of the lights one minute before shut off.
4. The switch shall provide visible indication of impending shut-off by flashing the lights one minute before shut off.
NEW SECTION
WAC 51-11C-40527 Section C405.2.7—Exterior lighting controls.
C405.2.7 Exterior lighting controls. Lighting for exterior applications other than emergency lighting that is intended to be automatically off during building operation, lighting specifically required to meet health and life safety requirements or decorative gas lighting systems shall:
1. Be provided with a control that automatically turns off the lighting as a function of available daylight.
2. Where lighting the building façade or landscape, the lighting shall have controls that automatically shut off the lighting as a function of dawn/dusk and a set opening and closing time.
3. Where not covered in Item 2, the lighting shall have controls configured to automatically reduce the connected lighting power by at least 30 percent from no later than 12 midnight to 6 a.m. or from one hour after business closing to one hour before business opening or during any period when no activity has been detected for a time of no longer than 15 minutes.
Time switches shall be capable of retaining programming and the time setting for at least 10 hours without power.
NEW SECTION
WAC 51-11C-40528 Section C405.2.8—Area controls.
C405.2.8 Area controls. The maximum lighting power that may be controlled from a single switch or automatic control shall not exceed that which is provided by a 20 ampere circuit loaded to not more than 80 percent. A master control may be installed provided the individual switches retain their capability to function independently. Circuit breakers may not be used as the sole means of switching.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40503 ((Section C405.3—))Reserved.
((C405.3 Reserved.))
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40504 Section ((C405.4)) C405.3—Exit signs.
((C405.4)) C405.3 Exit signs (mandatory). Internally illuminated exit signs shall not exceed 5 watts per side.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40505 Section ((C405.5)) C405.4—Interior lighting power requirements.
((C405.5)) C405.4 Interior lighting power requirements (prescriptive). A building complies with this section if its total connected lighting power calculated under Section ((C405.5.1)) C405.4.1 is no greater than the interior lighting power calculated under Section ((C405.5.2)) C405.4.2.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-405051 Section ((C405.5.1)) C405.4.1—Total connected interior lighting power.
((C405.5.1)) C405.4.1 Total connected interior lighting power. The total connected interior lighting power (((watts))) shall be the ((sum of the watts of all interior lighting equipment as determined in accordance with Sections C405.5.1.1 through C405.5.1.4.)) determined in accordance with Equation 4-10.
TCLP = [SL + LV + LTPB + Other]
(Equation 4-10)
Where:
TCLP = Total connected lighting power (watts).
SL = Labeled wattage of luminaires for screw-in lamps.
LV = Wattage of the transformer supplying low-voltage lighting.
LTPB = Wattage of line-voltage lighting tracks and plug-in busways as the specified wattage of the luminaires but at least 50 W/lin. ft., or the wattage limit of the system's circuit breaker, or the wattage limit of other permanent current limiting devices on the system.
Other = The wattage of all other luminaires and lighting, sources not covered above and associated with interior lighting verified by data supplied by the manufacturer or other approved sources.
((C405.5.1.1 Screw lamp holders. The wattage shall be the maximum labeled wattage of the luminaire.
C405.5.1.2 Low-voltage lighting. The wattage shall be the specified wattage of the transformer supplying the system.
C405.5.1.3 Other luminaires. The wattage of all other lighting equipment shall be the wattage of the lighting equipment verified through data furnished by the manufacturer or other approved sources.
C405.5.1.4 Line-voltage lighting track and plug-in busway. The wattage shall be:
1. The specified wattage of the luminaires included in the system with a minimum of 50 W/lin ft. (162 W/lin. m);
2. The wattage limit of the system's circuit breaker; or
3. The wattage limit of other permanent current limiting device(s) on the system.))
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040. AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-405052 Section ((C405.5.2)) C405.4.2—Interior lighting power requirements.
((C405.5.2)) C405.4.2 Interior lighting power. The total interior lighting power allowance (watts) is determined according to Table ((C405.5.2(1))) C405.4.2(1) using the Building Area Method, or Table ((C405.5.2(2))) C405.4.2(2) using the Space-by-Space Method, for all areas of the building covered in this permit.
C405.4.2.1 Building area method. For the Building Area Method, the interior lighting power allowance is the floor area for each building area type listed in Table ((C405.5.2(1))) C405.4.2(1) times the value from Table ((C405.5.2(1))) C405.4.2(1) for that area. For the purposes of this method, an "area" shall be defined as all contiguous spaces that accommodate or are associated with a single building area type as listed in Table ((C405.5.2(1))) C405.4.2(1). Where this method is used to calculate the total interior lighting power for an entire building, each building area type shall be treated as a separate area.
C405.4.2.2 Space-by-Space Method. For the Space-by-Space Method, the interior lighting power allowance is determined by multiplying the floor area of each space times the value for the space type in Table ((C405.5.2(2))) C405.4.2(2) that most closely represents the proposed use of the space, and then summing the lighting power allowances for all spaces. Tradeoffs among spaces are permitted.
Each area enclosed by partitions that are 80 percent of the ceiling height or taller shall be considered a separate space and assigned the appropriate space type from Table C405.4.2(2). If a space has multiple functions where more than one space type is applicable, that space shall be broken up into smaller subspaces, each using their own space type. Any of these subspaces that are smaller in floor area than 20 percent of the enclosed space and less than 1,000 square feet need not be broken out separately.
C405.4.2.2.1 Additional interior lighting power. Where using the Space-by-Space Method, an increase in the interior lighting power allowance is permitted for specific lighting functions. Additional power shall be permitted only where the specified lighting is installed and automatically controlled separately from the general lighting, to be turned off during nonbusiness hours. This additional power shall be used only for the specified luminaires and shall not be used for any other purpose. An increase in the interior lighting power allowance is permitted for lighting equipment to be installed in sales areas specifically to highlight merchandise, the additional lighting power shall be determined in accordance with Equation 4-11.
(Equation 4-11)
Additional Interior Lighting Power Allowance = 500 watts + (Retail Area 1 × 0.6 W/ft2) + (Retail Area 2 × 0.6 W/ft2) + (Retail Area 3 × 1.4 W/ft2) + (Retail Area 4 × 2.5 W/ft2).
Where:
Retail Area 1 = The floor area for all products not listed in Retail Area 2, 3 or 4.
Retail Area 2 = The floor area used for the sale of vehicles, sporting goods and small electronics.
Retail Area 3 = The floor area used for the sale of furniture, clothing, cosmetics and artwork.
Retail Area 4 = The floor area used for the sale of jewelry, crystal and china.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-405053 Table ((C405.5.2(1))) C405.4.2(1)—Interior lighting power allowances—Building area method.
Table ((C405.5.2(1))) C405.4.2(1)
Interior Lighting Power Allowances—Building Area Method
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-405054 Table ((C405.5.5.2(2))) C405.4.2(2)—Interior lighting power allowances—Space-by-space method.
Table ((C405.5.2(2))) C405.4.2(2)
Interior Lighting Power Allowances—Space-by-Space Method
Calculate the additional lighting power as follows:
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40506 Section ((C405.6)) C405.5—Exterior lighting.
((C405.6)) C405.5 Exterior lighting (mandatory). Where the power for exterior lighting is supplied through the energy service to the building, all exterior lighting shall comply with ((Sections C405.6.1 and C405.6.2)) Section C405.5.1.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-405061 Section ((C405.6.1)) C405.5.1—Exterior building grounds lighting.
((C405.6.1)) C405.5.1 Exterior building grounds lighting. All exterior building grounds luminaires that operate at greater than 100 watts shall ((contain lamps having)) have a minimum efficacy of ((60)) 80 lumens per watt unless the luminaire is controlled by a motion sensor or qualifies for one of the exceptions under Section ((C405.6.2)) C405.5.2.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-405062 Section ((C405.6.2)) C405.5.2—Exterior building lighting power.
((C405.6.2)) C405.5.2 Exterior building lighting power. The total exterior lighting power allowance for all exterior building applications is the sum of the base site allowance plus the individual allowances for areas that are to be illuminated and are permitted in Table ((C405.6.2(2))) C405.5.2(2) for the applicable lighting zone. Tradeoffs are allowed only among exterior lighting applications listed in Table ((C405.6.2(2))) C405.5.2(2), Tradable Surfaces section. The lighting zone for the building exterior is determined from Table ((C405.6.2(1))) C405.5.2(1) unless otherwise specified by the local jurisdiction. ((Exterior lighting for all applications (except those included in the exceptions to Section C405.6.2) shall comply with the requirements of Section C405.6.1)).
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-405063 Table ((C405.6.2(1))) C405.5.2(1)—Exterior lighting zones.
Table ((C405.6.2(1))) C405.5.2(1)
Exterior Lighting Zones
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-405064 Table ((C405.6.2(2))) C405.5.2(2)—Individual lighting power allowances for building exteriors.
Table ((C405.6.2(2))) C405.5.2(2)
Individual Lighting Power Allowances for Building Exteriors
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40507 Section C405.7—Electrical energy consumption.
C405.6 Electrical transformers. Electric transformers shall meet the minimum efficiency requirements of Table C405.6 as tested and rated in accordance with the test procedure listed in DOE 10 C.F.R. 431. The efficiency shall be verified through certification under an approved certification program or, where no certification program exists, the equipment efficiency ratings shall be supported by data furnished by the transformer manufacturer.
Table C405.6
Minimum Nominal Efficiency Levels For 10 C.F.R. 431 Low Voltage Dry-Type Distribution Transformers
C405.7 Electrical energy consumption (mandatory). ((In buildings having individual)) Each dwelling unit((s, provisions shall be made to determine the electrical energy consumed by each tenant by separately metering individual dwelling units)) located in a Group R-2 building shall have a separate electrical meter. A utility tenant meter meets this requirement. See Section C409 for additional requirements for energy metering and energy consumption management.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40508 Section C405.8—Electric motors.
((C405.8 Electric motors. All permanently wired polyphase motors of 1 hp or more, which are not part of an HVAC system, shall comply with Section C403.2.13.
C405.8 Electric motor efficiency (mandatory). All electric motors, fractional or otherwise, shall meet the minimum efficiency requirements of Tables C405.8(1) through C405.8(4) when tested and rated in accordance with DOE 10 C.F.R. The efficiency shall be verified through certification under an approved certification program or, where no certification program exists, the equipment efficiency ratings shall be supported by data furnished by the motor manufacturer.
Fractional hp fan motors that are 1/12 hp or greater and less than 1 hp which are not covered by Tables C405.8(3) and C405.8(4) shall be electronically commutated motors or shall have a minimum motor efficiency of 70 percent when rated in accordance with DOE 10 C.F.R. 431. These motors shall also have the means to adjust motor speed for either balancing or remote control. Belt-driven fans may use sheave adjustments for airflow balancing in lieu of a varying motor speed.
Table C405.8(1)
Minimum Nominal Full-load Efficiency for 60 Hz NEMA General Purpose Electric Motors (Subtype I) Rated 600 Volts or Less (Random Wound)a
Table C405.8(2)
Minimum Nominal Full-load Efficiency of General Purpose Electric Motors (Subtype II) And All Design B Motors Greater Than 200 Horsepowera
Table C405.8(3)
Minimum Average Full Load Efficiency for Polyphase Small Electric Motorsa
Table C405.8(4)
Minimum Average Full Load Efficiency For Capacitor-start Capacitor-run and Capacitor-start Induction-run Small Electric Motorsa
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40509 Section C405.9—((Transformers)) Vertical and horizontal transportation systems.
((C405.9 Transformers. The minimum efficiency of a low voltage dry-type distribution transformer shall be the Class I Efficiency Levels for distribution transformers specified in Table 4-2 of NEMA TP-1.)) C405.9 Vertical and horizontal transportation systems and equipment. Vertical and horizontal transportation systems and equipment shall comply with this section.
C405.9.1 Elevator cabs. For the luminaires in each elevator cab, not including signals and displays, the sum of the lumens divided by the sum of the watts shall be no less than 35 lumens per watt. Ventilation fans in elevators that do not have their own air conditioning system shall not consume more than 0.33 watts/cfm at the maximum rated speed of the fan. Controls shall be provided that will de-energize ventilation fans and lighting systems when the elevator is stopped, unoccupied and with its doors closed for over 15 minutes.
C405.9.2 Escalators and moving walks. Escalators and moving walks shall comply with ASME A17.1/CSA B44 and shall have automatic controls configured to reduce speed to the minimum permitted speed in accordance with ASME A17.1/CSA B44 or applicable local code when not conveying passengers.
C405.9.2.1 Regenerative drive. An escalator designed either for one-way down operation only or for reversible operation shall have a variable frequency regenerative drive that supplies electrical energy to the building electrical system when the escalator is loaded with passengers whose combined weight exceeds 750 pounds.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40510 Section C405.10—((Walk-in coolers and freezers)) Controlled receptacles.
((C405.10 Walk-in coolers and walk-in freezers. Walk-in coolers and walk-in freezers shall comply with all of the following:
1. Lights shall use light sources with an efficacy of 40 lumens per watt or more, including ballast losses (if any). Light sources with an efficacy of less than 40 lumens per watt, including ballast losses (if any), may be used in conjunction with a timer or device that turns off the lights within 15 minutes of when the walk-in cooler or walk-in freezer is not occupied by people.)) C405.10 Controlled receptacles. At least 50 percent of all 125 volt 15- and 20-ampere receptacles installed in private offices, open offices, conference rooms, rooms used primarily for printing and/or copying functions, break rooms, individual workstations and classrooms, including those installed in modular partitions and modular office workstation systems, shall be controlled as required by this section. In rooms larger than 200 square feet (19 m2), a controlled receptacle shall be located within 72 inches (1.8 m) of each uncontrolled receptacle. Controlled receptacles shall be visibly differentiated from standard receptacles and shall be controlled by one of the following automatic control devices:
1. An occupant sensor that turns receptacle power off when no occupants have been detected for a maximum of 20 minutes.
2. A time-of-day operated control device that turns receptacle power off at specific programmed times and can be programmed separately for each day of the week. The control device shall be configured to provide an independent schedule for each portion of the building not to exceed 5,000 square feet (2,323 m2) and not to exceed one full floor. The device shall be capable of being overridden for periods of up to two hours by a timer accessible to occupants. Any individual override switch shall control the controlled receptacles for a maximum area of 5,000 square feet (465 m2). Override switches for controlled receptacles are permitted to control the lighting within the same area.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40511 ((Section C405.11—Refrigerated warehouse coolers and freezers.)) Reserved.
((C405.11 Refrigerated warehouse coolers and refrigerated warehouse freezers. Refrigerated warehouse coolers and refrigerated warehouse freezers shall comply with all of the following:
1. Lights shall use light sources with an efficacy of 40 lumens per watt or more, including ballast losses (if any). Light sources with an efficacy of less than 40 lumens per watt, including ballast losses (if any), may be used in conjunction with a timer or device that turns off the lights within 15 minutes of when the refrigerated warehouse cooler or refrigerated warehouse freezer is not occupied by people.))
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40512 ((Section C405.12—Escalators and moving walks.)) Reserved.
((C405.12 Escalators and moving walks.
C405.12.1 Variable speed escalators. Where variable speed escalators and moving walks are permitted by the administrative authority, all escalators and moving walks shall reduce their operating speed to no more than 15 feet per minute when no passengers have been detected for a period of time not exceeding three times the amount of time required to transfer a passenger between landings. Such escalators and moving walks shall comply with the requirements of ANSI/ASME A17.1 for variable speed escalators and moving walks.
C405.12.2 Regenerative drive. Escalators designed either for one-way down operation only or for reversible operation shall have variable frequency regenerative drives that supply electrical energy to the building electrical system when loaded with more than 5 passengers.))
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40600 Section C406—Additional efficiency package options.
((Sections C406.1 through C406.4 are not adopted.)) C406.1 Requirements. Buildings shall comply with no less than two of the following:
1. More efficient HVAC performance in accordance with Section C406.2.
2. Reduced lighting power in accordance with Section C406.3.
3. Enhanced lighting controls in accordance with Section C406.4.
4. On-site supply of renewable energy in accordance with Section C406.5.
5. Provision of a dedicated outdoor air system for certain HVAC equipment in accordance with Section C406.6.
6. High-efficiency service water heating in accordance with Section C406.7.
7. Enhanced envelope performance in accordance with Section C406.8.
8. Reduced air infiltration in accordance with Section C406.9.
C406.1.1 Tenant spaces. Tenant spaces shall comply with Section C406.2, C406.3, C406.4, or C406.7, where applicable. Where an entire building complies with Section C406.5, C406.8 or C406.9, tenant spaces within the building shall be deemed to comply with this section.
NEW SECTION
WAC 51-11C-40602 Section C406.2—HVAC option.
C406.2 More efficient HVAC equipment and fan performance. Buildings shall comply with Sections C406.2.1 through C406.2.3.
C406.2.1 HVAC system selection. No less than 90 percent of the total HVAC capacity serving the building shall be provided by equipment that is listed in Tables C403.2.3(1) through C403.2.3(9) or a combination thereof.
C406.2.2 Minimum equipment efficiency. Equipment shall exceed the minimum efficiency requirements listed in Tables C403.2.3(1) through C403.2.3(7) by 15 percent, in addition to the requirements of Section C403. Where multiple performance requirements are provided, the equipment shall exceed all requirements by 15 percent.
C406.2.3 Minimum fan efficiency. Stand-alone supply, return and exhaust fans designed for operating with motors over 750 watts (1 hp) shall have an energy efficiency classification of not less than FEG 71 as defined in AMCA 205. The total efficiency of the fan at the design point of operation shall be within 10 percentage points of either the maximum total efficiency of the fan or the static efficiency of the fan.
NEW SECTION
WAC 51-11C-40603 Section C406.3—LPA option.
C406.3 Reduced lighting power. Buildings shall comply with Sections C406.3.1 and, where applicable, C406.3.2.
C406.3.1 Reduced lighting power density. The total interior lighting power (watts) of the building shall be determined by using 75 percent of the lighting power values specified in Table C405.4.2(1) times the floor area for the building types, or by using 75 percent of the interior lighting power allowance calculated by the Space-by-Space Method in Section C405.4.2.
C406.3.2 Lamp fraction. Not less than 95 percent of the interior lighting power (watts) from lamps in permanently installed light fixtures in dwelling units and sleeping units shall be provided by lamps with a minimum efficacy of 60 lumens per watt.
NEW SECTION
WAC 51-11C-40604 Section C406.4—Lighting controls option.
C406.4 Enhanced digital lighting controls. Interior lighting shall be located, scheduled and operated in accordance with Section C405.2.2 and no less than 90 percent of the total installed interior lighting power shall be configured with the following enhanced control functions.
1. Luminaires shall be configured for continuous dimming.
2. Each luminaire shall be individually addressed.
NEW SECTION
WAC 51-11C-40605 Section C406.5—On-site renewable energy option.
C406.5 On-site renewable energy. Buildings shall be provided with on-site renewable energy systems with a total system rating per square foot of conditioned floor area of the building of not less than the value specified in Table C406.5.
NEW SECTION
WAC 51-11C-40606 Section C406.6—DOAS option.
C406.6 Dedicated outdoor air system (DOAS). For buildings not subject to the provisions of Section C403.2.6.1, provide DOAS in accordance with Section C403.2.6.1.
NEW SECTION
WAC 51-11C-40607 Section C406.7—Service water heating option.
C406.7 Reduced energy use in service water heating. Buildings shall comply with Sections C406.7.7 and C406.7.2.
C406.7.1 Building type. Not less than 90 percent of the conditioned floor area shall be of the following types:
1. Group R-1: Boarding houses, hotels or motels.
2. Group I-2: Hospitals, psychiatric hospitals and nursing homes.
3. Group A-2: Restaurants and banquet halls or buildings containing food preparation areas.
4. Group F: Laundries.
5. Group R-2: Buildings with residential occupancies.
6. Group A-3: Health clubs and spas.
7. Buildings with a service hot water load of 10 percent or more of total building energy loads, as shown with an energy analysis as described in Section C407.
C406.7.1 Load fraction. Not less than 60 percent of the annual building service hot water energy use, or not less than 100 percent of the annual building service hot water heating energy use in buildings subject to the requirements of Section C403.6.4, shall be provided by one or more of the following:
1. Service hot water system delivering heating requirements using heat pump technology with a minimum COP of 3.0.
2. Waste heat recovery from service hot water, heat recovery chillers, building equipment, process equipment, a combined heat and power system, or other approved system.
3. Solar water-heating systems.
NEW SECTION
WAC 51-11C-40608 Section C406.8—Envelope option.
C406.8 Enhanced envelope performance. The total UA of the building thermal envelope shall be 15 percent lower than the maximum allowable UA for a building of identical configuration and fenestration area in accordance with Section C402.1.4, where UA equals the sum of the U-values of each distinct envelope assembly multiplied by the area in square feet of that assembly.
NEW SECTION
WAC 51-11C-40609 Section C406.9—Air infiltration option.
C406.9 Reduced air infiltration. Air infiltration shall be verified by whole building pressurization testing conducted in accordance with ASTM E779 or ASTM E1827 by an independent third party. The measured air leakage rate of the building envelope shall not exceed 0.25 cfm/ft2 (2.0 L/s•m2) under a pressure differential of 0.3 in. water (75 Pa), with the calculated surface area being the sum of the above and below grade building envelope. A report that includes the tested surface area, floor area, air by volume, stories above grade, and leakage rates shall be submitted to the code official and the building owner.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40702 Section C407.2—Mandatory requirements.
C407.2 Mandatory requirements. Compliance with this section requires that the criteria of Sections ((C402.4)) C402.5, C403.2, C404 and C405 be met.
The building permit application for projects utilizing this method shall include in one submittal all building and mechanical drawings and all information necessary to verify that the building envelope and mechanical design for the project corresponds with the annual energy analysis. If credit is proposed to be taken for lighting energy savings, then an electrical permit application shall also be submitted and approved prior to the issuance of the building permit. If credit is proposed to be taken for energy savings from other components, then the corresponding permit application (e.g., plumbing, boiler, etc.) shall also be submitted and approved prior to the building permit application. Otherwise, components of the project that would not be approved as part of a building permit application shall be modeled the same in both the proposed building and the standard reference design and shall comply with the requirements of this code.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40703 Section C407.3—Performance-based compliance.
C407.3 Performance-based compliance. Compliance based on total building performance requires that a proposed building (proposed design) be shown to have an annual energy consumption based on site energy expressed in Btu and Btu per square foot of conditioned floor area that is less than or equal to ((the annual energy consumption of)) 87 percent of that of the standard reference design.
AMENDATORY SECTION (Amending WSR 14-24-122, filed 12/3/14, effective 1/3/15)
WAC 51-11C-40705 Section C407.5—Calculation procedure.
C407.5 Calculation procedure. Except as specified by this section, the standard reference design and proposed design shall be configured and analyzed using identical methods and techniques.
C407.5.1 Building specifications. The standard reference design and proposed design shall be configured and analyzed as specified by Table C407.5.1(1). Table C407.5.1(1) shall include by reference all notes contained in Table ((C402.2)) C402.1.4.
C407.5.2 Thermal blocks. The standard reference design and proposed design shall be analyzed using identical thermal blocks as specified in Section C407.5.2.1, C407.5.2.2 or C407.5.2.3.
C407.5.2.1 HVAC zones designed. Where HVAC zones are defined on HVAC design drawings, each HVAC zone shall be modeled as a separate thermal block.
C407.5.2.2 HVAC zones not designed. Where HVAC zones have not yet been designed, thermal blocks shall be defined based on similar internal load densities, occupancy, lighting, thermal and temperature schedules, and in combination with the following guidelines:
1. Separate thermal blocks shall be assumed for interior and perimeter spaces. Interior spaces shall be those located more than 15 feet (4572 mm) from an exterior wall. Perimeter spaces shall be those located closer than 15 feet (4572 mm) from an exterior wall.
2. Separate thermal blocks shall be assumed for spaces adjacent to glazed exterior walls: A separate zone shall be provided for each orientation, except orientations that differ by no more than 45 degrees (0.79 rad) shall be permitted to be considered to be the same orientation. Each zone shall include floor area that is 15 feet (4572 mm) or less from a glazed perimeter wall, except that floor area within 15 feet (4572 mm) of glazed perimeter walls having more than one orientation shall be divided proportionately between zones.
3. Separate thermal blocks shall be assumed for spaces having floors that are in contact with the ground or exposed to ambient conditions from zones that do not share these features.
4. Separate thermal blocks shall be assumed for spaces having exterior ceiling or roof assemblies from zones that do not share these features.
C407.5.2.3 Multifamily ((Group R)) residential buildings. ((Group R)) Residential spaces shall be modeled using one thermal block per space except that those facing the same orientations are permitted to be combined into one thermal block. Corner units and units with roof or floor loads shall only be combined with units sharing these features.
C407.5.3 Equipment efficiencies. All HVAC equipment in the standard reference design shall be modeled at the minimum efficiency levels, both part load and full load, in accordance with Section C403.2.3. Chillers shall use Path A efficiencies as shown in Table C403.2.3(7). Where efficiency ratings include supply fan energy, the efficiency rating shall be adjusted to remove the supply fan energy. For Baseline Systems HVAC Systems 3, 4, 6, 8, 9, 10 and 11, calculate the minimum COPnfcooling and COPnfheating using the equation for the applicable performance rating as indicated in Tables C403.2.3(1) through C403.2.3(3). Where a full- and part-load efficiency rating is provided in Tables C403.2.3(1) through C403.2.3(3), use Equation 4-12.
(Equation 4-12)
COPnfcooling = 7.84E-8 x EER x Q + 0.338 x EER
COPnfcooling = -0.0076 x SEER2 + 0.3796 x SEER
COPnfheating = 1.48E-7 x COP47 x Q + 1.062 x COP47(applies to heat-pump heating efficiencies only)
COPnfheating = -0.0296 x HSPF2 + 0.7134 x HSPF
Where:
COPnfcooling = The packaged HVAC equipment cooling energy efficiency.
COPnfheating = The packaged HVAC equipment heating energy efficiency.
Q = The AHRI-rated cooling capacity in Btu/h.
EER, SEER, COP and HSPF shall be at AHRI test conditions. Fan energy shall be modeled separately according to Table C407.5.1(1).
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-407051 Table C407.5.1(1)—Specifications for the standard reference and proposed design.
Table C407.5.1(1)
Specifications for the Standard Reference and Proposed Designs
AMENDATORY SECTION (Amending WSR 14-24-122, filed 12/3/14, effective 1/3/15)
WAC 51-11C-407052 Table C407.5.1(2)/(3)—HVAC systems map.
Table C407.5.1(2)
HVAC Systems Map for Buildings Governed by Section C403.2.6.1d
Table C407.5.1(3)
HVAC Systems Map for All Other Buildings
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-407053 Table ((C407.5.1(3))) C407.5.1(4)—Specifications for the standard reference design HVAC system description.
Table ((C407.5.1(3))) C407.5.1(4)
Specifications for the Standard Reference Design HVAC System Descriptions
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency. Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040. AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-407054 Table ((C407.5.1(4))) C407.5.1(5)—Number of chillers.
Table ((C407.5.1(4))) C407.5.1(5)
Number of Chillers
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-407055 Table ((C407.5.1(5))) C407.5.1(6)—Water chiller types.
Table ((C407.5.1(5))) C407.5.1(6)
Water Chiller Types
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40706 Section C407.6—Calculation software tool.
C407.6 Calculation software tools. Calculation procedures used to comply with this section shall be software tools capable of calculating the annual energy consumption of all building elements that differ between the standard reference design and the proposed design and shall include the following capabilities.
1. Building operation for a full calendar year (8,760 hours).
2. Climate data for a full calendar year (8,760 hours) and shall reflect approved coincident hourly data for temperature, solar radiation, humidity and wind speed for the building location.
3. Ten or more thermal zones.
4. Thermal mass effects.
5. Hourly variations in occupancy, illumination, receptacle loads, thermostat settings, mechanical ventilation, HVAC equipment availability, service hot water usage and any process loads.
6. Part-load performance curves for mechanical equipment.
7. Capacity and efficiency correction curves for mechanical heating and cooling equipment.
8. Printed code official inspection checklist listing each of the proposed design component characteristics from Table C407.5.1(1) determined by the analysis to provide compliance, along with their respective performance ratings (e.g., R-value, U-factor, SHGC, HSPF, AFUE, SEER, EF, etc.).
9. Air-side economizers with integrated control.
10. Standard reference design characteristics specified in Table C407.5.1(1).
C407.6.1 Specific approval. Performance analysis tools meeting the applicable subsections of Section C407 and tested according to ASHRAE Standard 140 shall be permitted to be approved. Tools are permitted to be approved based on meeting a specified threshold for a jurisdiction. The code official shall be permitted to approve tools for a specified application or limited scope.
C407.6.2 Input values. Where calculations require input values not specified by Sections C402, C403, C404 and C405, those input values shall be taken from an approved source.
C407.6.3 Exceptional calculation methods. ((When)) Where the simulation program does not model a design, material, or device of the proposed design, an Exceptional Calculation Method shall be used if approved by the ((building)) code official. If there are multiple designs, materials, or devices that the simulation program does not model, each shall be calculated separately and Exceptional Savings determined for each. ((At no time shall)) The total Exceptional Savings shall not constitute more than half of the difference between the baseline building performance and the proposed building performance. ((All)) Applications for approval of an exceptional method shall include:
1. Step-by-step documentation of the Exceptional Calculation Method performed detailed enough to reproduce the results;
2. Copies of all spreadsheets used to perform the calculations;
3. A sensitivity analysis of energy consumption when each of the input parameters is varied from half to double the value assumed;
4. The calculations shall be performed on a time step basis consistent with the simulation program used; and
5. The Performance Rating calculated with and without the Exceptional Calculation Method.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40801 Section C408.1—General.
C408.1 General. ((This section covers the commissioning of the building)) A building commissioning process led by a certified commissioning professional shall be completed for mechanical systems in Section C403, service water heating systems in Section C404, electrical power and lighting systems in Section C405 and energy metering in Section C409.
C408.1.1 Commissioning in construction documents. Construction document notes shall clearly indicate provisions for commissioning and completion requirements in accordance with this section and are permitted to refer to specifications for further requirements.
C408.1.2 Commissioning plan. A commissioning plan shall be developed by the project's certified commissioning professional and shall outline the organization, schedule, allocation of resources, and documentation requirements of the commissioning process. Items 1 through 4 shall be included with the construction documents, and items 5 through 8 shall be submitted prior to the first mechanical inspection. For projects where no mechanical inspection is required, items 5 through 8 shall be submitted prior to the first electrical inspection.
1. A narrative description of the activities that will be accomplished during each phase of commissioning, including the personnel intended to accomplish each of the activities.
2. Roles and responsibilities of the commissioning team, including statement of qualifications of the commissioning professional in accordance with Section C408.1.1.
3. A schedule of activities including systems testing and balancing, functional performance testing, and verification of the building documentation requirements in Section C103.6.
4. Where the certified commissioning professional is an employee of one of the registered design professionals of record or an employee or subcontractor of the project contractor, an In-House Commissioning Disclosure and Conflict Management Plan shall be submitted with the commissioning plan. This plan shall disclose the certified commissioning professional's contractual relationship with other team members and provide a conflict management plan demonstrating that the certified commissioning professional is free to identify any issues discovered and report directly to the owner.
5. A listing of the specific equipment, appliances or systems to be tested and a description of the tests to be performed.
6. Functions to be tested.
7. Conditions under which the test will be performed.
8. Measurable criteria for performance.
C408.1.3 Final commissioning report. A final commissioning report shall be completed and certified by the certified commissioning professional and delivered to the building owner or owner's authorized agent. The report shall be organized with mechanical, lighting, service water heating and metering findings in separate sections to allow independent review. The report shall record the activities and results of the commissioning process and be developed from the final commissioning plan with all of its attached appendices. The report shall include:
1. Results of functional performance tests.
2. Disposition of deficiencies found during testing, including details of corrective measures used or proposed.
3. Functional performance test procedures used during the commissioning process including measurable criteria for test acceptance, provided herein for repeatability.
C408.1.4. Commissioning process completion requirements. Prior to ((passing)) the final mechanical, plumbing and electrical inspections or obtaining a certificate of occupancy, the ((registered design)) certified commissioning professional or approved agency shall provide evidence of systems commissioning and completion in accordance with the provisions of this section.
Copies of all documentation shall be given to the owner and made available to the code official upon request in accordance with Section((s C408.1.2 and C408.1.3.
C408.1.1 Commissioning plan. A commissioning plan shall be developed by a registered design professional or approved agency and shall include the following items:
1. A narrative description of the activities that will be accomplished during each phase of commissioning, including the personnel intended to accomplish each of the activities.
2. Roles and responsibilities of the commissioning team.
3. A schedule of activities including systems testing and balancing, functional testing, and supporting documentation.
4. A listing of the specific equipment, appliances or systems to be tested and a description of the tests to be performed.
5. Functions to be tested.
6. Conditions under which the test will be performed.
7. Measurable criteria for performance.
C408.1.2 Preliminary commissioning report.)) C408.1.4.3.
C408.1.4.1 Commissioning progress report for code compliance. A preliminary report of commissioning test procedures and results shall be completed and certified by the ((registered design)) certified commissioning professional or approved agency and provided to the building owner or owner's authorized agent. The report shall be organized with mechanical, lighting, service water heating and metering findings in separate sections to allow independent review. The report shall be identified as "Preliminary Commissioning Report" and shall identify:
1. Itemization of deficiencies found during testing required by this ((section)) code that have not been corrected at the time of report preparation.
2. Deferred tests that cannot be performed at the time of report preparation because of climatic conditions, with anticipated date of completion.
3. Climatic conditions required for performance of the deferred tests.
4. ((Record of progress and completion of operator training.
C408.1.2.1)) Status of the project's record documents, manuals and systems operation training with respect to requirements in Section C103.6.
C408.1.4.2 Acceptance of report. Buildings, or portions thereof, shall not ((pass the final mechanical and electrical inspections or obtain a certificate of occupancy, until such time as the)) be considered acceptable for a final inspection pursuant to Section C104.3 until the code official has received a letter of transmittal from the building owner acknowledging that the building owner or owner's authorized agent has received the Preliminary Commissioning Report. Completion of the Commissioning Compliance Checklist (Figure ((C408.1.2.1)) C408.1.4.2) is deemed to satisfy this requirement.
((C408.1.2.2)) C408.1.4.3 Copy of report. The code official shall be permitted to require that a copy of the Preliminary Commissioning Report be made available for review by the code official.
((C408.1.3 Documentation requirements. The construction documents shall specify that the documents described in this section be provided to the building owner within 90 days of the date of receipt of the certificate of occupancy.
C408.1.3.1 Record documents. Construction documents shall be updated to convey a record of the alterations to the original design. Such updates shall include updated mechanical, electrical and control drawings red-lined, or redrawn if specified, that show all changes to size, type and locations of components, equipment and assemblies.
C408.1.3.2 Manuals. An operating and maintenance manual shall be provided and include all of the following:
1. Submittal data stating equipment size and selected options for each piece of equipment requiring maintenance.
2. Manufacturer's operation manuals and maintenance manuals for each piece of equipment requiring maintenance, except equipment not furnished as part of the project. Required routine maintenance actions shall be clearly identified.
3. Name and address of at least one service agency.
4. Controls system maintenance and calibration information, including wiring diagrams, schematics, record documents, and control sequence descriptions. Desired or field-determined setpoints shall be permanently recorded on control drawings at control devices or, for digital control systems, in system programming instructions.
5. A narrative of how each system is intended to operate, including recommended setpoints. Sequence of operation is not acceptable for this requirement.
C408.1.3.3 System balancing report. A written report describing the activities and measurements completed in accordance with Section C408.2.2.
C408.1.3.4 Final commissioning report. A report of test procedures and results identified as "Final Commissioning Report" shall be delivered to the building owner and shall include:
1. Results of functional performance tests.
2. Disposition of deficiencies found during testing, including details of corrective measures used or proposed.
3. Functional performance test procedures used during the commissioning process including measurable criteria for test acceptance, provided herein for repeatability.
C408.1.4 Systems operation training. Training of the maintenance staff for equipment included in the manuals required by Section C408.1.3.2 shall include at a minimum:
1. Review of systems documentation.
2. Hands-on demonstration of all normal maintenance procedures, normal operating modes, and all emergency shutdown and start-up procedures.
3. Training completion report.))
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-408012 Figure ((C408.1.2.1)) C408.1.4.2—Commissioning compliance checklist.
Figure ((C408.1.2.1)) C408.1.4.2
Commissioning Compliance Checklist
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40802 Section C408.2—Mechanical systems commissioning ((and completion requirements)).
C408.2 Mechanical systems commissioning ((and completion requirements)). Mechanical equipment and controls subject to Section C403 shall ((comply with Section C408.2.
Construction document notes shall clearly indicate provisions for commissioning and completion requirements in accordance with this section and are permitted to refer to specifications for further requirements. Exception: Systems which (a) qualify as simple systems using the criteria in Section C403.3, (b) are not required to have an economizer per Section C403.3.1, and (c) where the building total mechanical equipment capacity is less than 480,000 Btu/h (140,690 W) cooling capacity and 600,000 Btu/h (175,860 W) heating capacity.)) be included in the commissioning process required by Section C408.1. The commissioning process shall minimally include all energy code requirements for which the code states that equipment or controls shall "be capable of" or "configured to" perform specific functions.
C408.2.1 Reserved.
C408.2.2 Systems adjusting and balancing. HVAC systems shall be balanced in accordance with generally accepted engineering standards. Air and water flow rates shall be measured and adjusted to deliver final flow rates within the tolerances provided in the ((product)) project specifications. Test and balance activities shall include air system and hydronic system balancing.
C408.2.2.1 Air systems balancing. Each supply air outlet and zone terminal device shall be equipped with means for air balancing in accordance with the requirements of Chapter 6 of the International Mechanical Code. Discharge dampers used for air system balancing are prohibited on constant volume fans and variable volume fans with motors 10 hp (18.6 kW) and larger. Air systems shall be balanced in a manner to first minimize throttling losses then, for fans with system power of greater than 1 hp (0.74 kW), fan speed shall be adjusted to meet design flow conditions.
C408.2.2.2 Hydronic systems balancing. Individual hydronic heating and cooling coils shall be equipped with means for balancing and measuring flow. Hydronic systems shall be proportionately balanced in a manner to first minimize throttling losses, then the pump impeller shall be trimmed or pump speed shall be adjusted to meet design flow conditions. Each hydronic system shall have either the capability to measure pressure across the pump, or test ports at each side of each pump.
C408.2.3 Functional performance testing. Functional performance testing specified in Sections C408.2.3.1 through C408.2.3.3 shall be conducted. Written procedures which clearly describe the individual systematic test procedures, the expected systems' response or acceptance criteria for each procedure, the actual response or findings, and any pertinent discussion shall be followed. ((At a minimum,)) Testing shall affirm operation during actual or simulated winter and summer design conditions and during full outside air conditions.
C408.2.3.1 Equipment. Equipment functional performance testing shall demonstrate the installation and operation of components, systems, and system-to-system interfacing relationships in accordance with approved plans and specifications such that operation, function, and maintenance serviceability for each of the commissioned systems is confirmed. Testing shall include all modes and sequence of operation, including under full-load, part-load and the following emergency conditions:
1. All modes as described in the sequence of operation;
2. Redundant or automatic back-up mode;
3. Performance of alarms; and
4. Mode of operation upon a loss of power and restoration of power.
C408.2.3.2 Controls. HVAC control systems shall be tested to document that control devices, components, equipment, and systems are calibrated((,)) and adjusted and operate in accordance with approved plans and specifications. Sequences of operation shall be functionally tested to document they operate in accordance with approved plans and specifications.
C408.2.3.3 Economizers. Air economizers shall undergo a functional test to determine that they operate in accordance with manufacturer's specifications.
AMENDATORY SECTION (Amending WSR 13-23-096, filed 11/20/13, effective 4/1/14)
WAC 51-11C-40803 Section C408.3—Lighting system ((functional testing)) commissioning.
((C408.3 Lighting system functional testing. Controls for automatic lighting systems shall comply with Section C408.3.1.)) C408.3 Electrical power and lighting systems commissioning. Electrical power and lighting systems subject to Section C405 shall be included in the commissioning process required by Section C408.1. The commissioning process shall minimally include all energy code requirements for which the code requires specific daylight responsive controls, "control functions," and where the code states that equipment shall be "configured to" perform specific functions.
C408.3.1 Functional testing. ((Testing shall ensure that control hardware and software are calibrated, adjusted, programmed and in proper working condition in accordance with the construction documents and manufacturer's installation instructions. Written procedures which clearly describe the individual systematic test procedures, the expected systems' response or acceptance criteria for each procedure, the actual response or findings, and any pertinent discussion shall be followed. At a minimum, testing shall affirm operation during normally occupied daylight conditions. The construction documents shall state the party who will conduct the required functional testing.
Where occupant sensors, time switches, programmable schedule controls, photosensors or daylighting controls are installed, the following procedures shall be performed:
1. Confirm that the placement, sensitivity and time-out adjustments for occupant sensors yield acceptable performance.
2. Confirm that the time switches and programmable schedule controls are programmed to turn the lights off.
3. Confirm that the placement and sensitivity adjustments for photosensor controls reduce electric light based on the amount of usable daylight in the space as specified.)) Prior to passing final inspection, the certified commissioning professional shall provide evidence that the lighting control systems have been tested to ensure that control hardware and software are calibrated, adjusted, programmed and in proper working condition in accordance with the construction documents and manufacturer's instructions. Written procedures which clearly describe the individual systematic test procedures, the expected systems' response or acceptance criteria for each procedure, the actual response or findings, and any pertinent discussion shall be followed. Functional testing shall comply with Section C408.3.1.1 through C408.3.1.3 for the applicable control type.
C408.3.1.1 Occupant sensor controls. Where occupancy sensors are provided, the following procedures shall be performed:
1. Certify that the occupancy sensor has been located and aimed in accordance with manufacturer recommendations.
2. For projects with seven or fewer occupancy sensors, each sensor shall be tested. For projects with more than seven occupancy sensors, testing shall be done for each unique combination of sensor type and space geometry. Where multiples of each unique combination of sensor type and space geometry are provided, no fewer than the greater of one or 10 percent of each combination shall be tested unless the code official or design professional requires a higher percentage to be tested. Where 30 percent or more of the tested controls fail, all remaining identical combinations shall be tested.
3. For each occupancy sensor to be tested, verify the following:
3.1. Where occupancy sensors include status indicators, verify correct operation.
3.2. The controlled lights turn off or down to the permitted level within the required time.
3.3. For auto-on occupancy sensors, the lights turn on to the permitted level within the required time.
3.4. For manual on sensors, the lights turn on only when manually activated.
3.5. The lights are not incorrectly turned on by movement in adjacent areas or by HVAC operation.
C408.3.1.2 Time switch controls. Where automatic time switches are provided, the following procedures shall be performed:
1. Confirm that the automatic time switch control is programmed with accurate weekday, weekend and holiday schedules, and set-up and preference program settings.
2. Provide documentation to the owner of automatic time switch programming, including weekday, weekend, holiday schedules and set-up and preference program settings.
3. Verify the correct time and date in the time switch.
4. Verify that any battery backup is installed and energized.
5. Verify that the override time limit is set to not more than two hours.
6. Simulate occupied conditions. Verify and document the following:
6.1. All lights can be turned on and off by their respective area control switch.
6.2. The switch only operates lighting in the enclosed space in which the switch is located.
7. Simulate unoccupied condition. Verify the following:
7.1. All nonexempt lighting turns off.
7.2. Manual override switch allows only the lights in the enclosed space where the override switch is located to turn on or remain on until the next scheduled shut off occurs.
8. Additional testing as specified by the certified commissioning professional.
C408.3.1.3 Daylight responsive controls. Where daylight responsive controls are provided, the following procedures shall be performed:
1. All control devices have been properly located, field-calibrated and set for accurate setpoints and threshold light levels.
2. Daylight controlled lighting loads adjusted to light level setpoints in response to available daylight.
3. The locations of calibration adjustment equipment are readily accessible only to authorized personnel.
C408.3.2 Documentation requirements. The construction documents shall specify that documents certifying that the installed lighting controls meet documented performance criteria of Section C405 be provided to the building owner within 90 days from the date of receipt of the certificate of occupancy.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40804 Section C408.4—Service water heating systems commissioning ((and completion requirements)).
C408.4 Service water heating systems commissioning and completion requirements. Service water heating equipment and controls ((shall comply with Section C408.4. Construction document notes shall clearly indicate provisions for commissioning and completion requirements in accordance with this section and are permitted to refer to specifications for further requirements.
subject to Section C404 shall be included in the commissioning process required by Section C408.1. The commissioning process shall minimally include all energy code requirements for which the code states that equipment or controls shall "be capable of" or "configured to" perform specific functions.
C408.4.1 Functional performance testing. Functional performance testing specified in Sections C408.4.1.1 through C408.4.1.3 shall be conducted. Written procedures which clearly describe the individual systematic test procedures, the expected systems' response or acceptance criteria for each procedure, the actual response or findings, and any pertinent discussion shall be followed. ((At a minimum,)) Testing shall affirm operation with the system under 50 percent water heating load.
C408.4.1.1 Equipment. Equipment functional performance testing shall demonstrate the installation and operation of components, systems, and system-to-system interfacing relationships in accordance with approved plans and specifications such that operation, function, and maintenance serviceability for each of the commissioned systems is confirmed. Testing shall include all modes and sequence of operation, including under full-load, part-load and the following emergency conditions:
1. Redundant or automatic back-up mode;
2. Performance of alarms; and
3. Mode of operation upon a loss of power and restoration of power.
C408.4.1.2 Controls. Service water heating controls shall be tested to document that control devices, components, equipment, and systems are calibrated, adjusted and operate in accordance with approved plans and specifications. Sequences of operation shall be functionally tested to document they operate in accordance with approved plans and specifications.
C408.4.1.3 Pools and spas. Service water heating equipment, time switches, and heat recovery equipment which serve pools and ((in-ground permanently installed)) permanent spas shall undergo a functional test to determine that they operate in accordance with manufacturer's specifications.
NEW SECTION
WAC 51-11C-408045 Section C408.5—Other systems commissioning.
C408.5 Systems installed to meet Section C406 or C407. Equipment, components, controls or configuration settings for mechanical, service water heating, electrical power or lighting systems which are included in the project to comply with Section C406 or C407 shall be included in the commissioning process required by Section C408.1.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40805 Section ((C408.5)) C408.6—Metering system commissioning.
((C408.5)) C408.6 Metering system commissioning. Energy metering systems required by Section C409 shall comply with Section ((C408.5)) C408.6 and be included in the commissioning process required by Section C408.1. ((Construction documents shall clearly indicate provisions for commissioning in accordance with Section C408 and are permitted to refer to specifications for further requirements)) The commissioning process shall include all energy metering equipment and controls required by Section C409.
((C408.5.1)) C408.6.1 Functional performance testing. Functional performance testing shall be conducted by following written procedures which clearly describe the individual systematic test procedures, the expected systems' response or acceptance criteria for each procedure, the actual response or findings, and any pertinent discussion. Functional testing shall document that energy source meters, energy end-use meters, the energy metering data acquisition system, and required energy consumption display are calibrated, adjusted and operate in accordance with approved plans and specifications. At a minimum, testing shall confirm that:
1. The metering system devices and components work properly under low and high load conditions.
2. The metered data is delivered in a format that is compatible with the data collection system.
3. The energy display is accessible to building operation and management personnel.
4. The energy display meets code requirements regarding views required in Section C409.4.3. The display shows energy data in identical units (e.g., kWh).
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40901 Section C409.1—General.
C409.1 General. New buildings and additions with a gross conditioned floor area over 50,000 square feet shall comply with Section C409. Buildings shall be equipped to measure, monitor, record and display energy consumption data for each energy source and end use category per the provisions of this section, to enable effective energy management.
C409.1.1 Alternate metering methods. Where approved by the building official, energy use metering systems may differ from those required by this section, provided that they are permanently installed and that the source energy measurement, end use category energy measurement, data storage and data display have similar accuracy to and are at least as effective in communicating actionable energy use information to the building management and users, as those required by this section.
C409.1.2 Conversion factor. Any threshold stated in kW shall include the equivalent BTU/h heating and cooling capacity of installed equipment at a conversion factor of 3,412 Btu per kW at 50 percent demand.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40903 Section C409.3—End-use metering.
C409.3 End-use metering. Meters shall be provided to collect energy use data for each end-use category listed in Sections C409.3.1 through C409.3.2. These meters shall collect data for the whole building or for each separately metered portion of the building where not exempted by the exception to Section C409.1. Multiple meters may be used for any end-use category, provided that the data acquisition system totals all of the energy used by that category.
C409.3.1 HVAC system energy use. This category shall include all energy including electrical, gas, liquid fuel, district steam and district chilled water that is used by boilers, chillers, pumps, fans and other equipment used to provide space heating, space cooling, dehumidification and ventilation to the building, but not including energy that serves process loads, water heating or miscellaneous loads as defined in Section C409.3. Multiple HVAC energy sources, such as gas, electric and steam, are not required to be summed together.
C409.3.2 Water heating energy use. This category shall include all energy used for heating of domestic and service hot water, but not energy used for space heating.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-40905 Section C409.5—Metering for existing buildings.
C409.5 Metering for existing buildings.
C409.5.1 Existing buildings that were constructed subject to the requirements of this section. Where new or replacement systems or equipment are installed in an existing building that was constructed subject to the requirements of this section, metering shall be provided for such new or replacement systems or equipment so that their energy use is included in the corresponding end-use category defined in Section C409.2. This includes systems or equipment added in conjunction with additions or alterations to existing buildings.
C409.5.1.1 Small existing buildings. Metering and data acquisition systems shall be provided for additions over 25,000 square feet to buildings that were constructed subject to the requirement of this section, in accordance with the requirements of sections C409.2 and C409.3.
NEW SECTION
WAC 51-11C-41000 Section C410—Refrigeration system requirements.
C410.1 General (prescriptive). Walk-in coolers, walk-in freezers, refrigerated warehouse coolers, refrigerated warehouse freezers, and refrigerated display cases shall comply with this Section.
C410.1.1 Refrigeration equipment performance. Refrigeration equipment shall have an energy use in kWh/day not greater than the values of Tables C410.2(1) and C410.2(2) when tested and rated in accordance with AHRI Standard 1200. The energy use shall be verified through certification under an approved certification program or, where a certification program does not exist, the energy use shall be supported by data furnished by the equipment manufacturer.
Table C410.1.1(1)
Minimum Efficiency Requirements: Commercial Refrigeration
Table C410.1.1(2)
Minimum Efficiency Requirements: Commercial Refrigerators and Freezers
C410.2 Walk-in coolers, walk-in freezers, refrigerated warehouse coolers and refrigerated warehouse freezers. Refrigerated warehouse coolers and refrigerated warehouse freezers shall comply with this section. Walk-in coolers and walk-in freezers that are not either site assembled or site constructed shall comply with the following:
1. Be equipped with automatic door-closers that firmly close walk-in doors that have been closed to within 1 inch (25 mm) of full closure.
2. Doorways shall have strip doors, curtains, spring-hinged doors or other method of minimizing infiltration when doors are open.
3. Walk-in coolers and refrigerated warehouse coolers shall contain wall, ceiling, and door insulation of not less than R-25 or have wall, ceiling and door assembly U-factors no greater than U-0.039. Walk-in freezers and refrigerated warehouse freezers shall contain wall, ceiling and door insulation of not less than R-32 or have wall, ceiling and door assembly U-factors no greater than U-0.030.
4. The floor of walk-in freezers shall contain floor insulation of not less than R-28 or have a floor assembly U-factor no greater than U-0.035.
5. Transparent reach-in doors for walk-in freezers and windows in walk-in freezer doors shall be of triple-pane glass, either filled with inert gas or with heat-reflective treated glass.
6. Windows and transparent reach-in doors for walk-in coolers doors shall be of double-pane or triple-pane, inert gas-filled, heat-reflective treated glass.
7. Evaporator fan motors that are less than 1 hp (0.746 kW) and less than 460 volts shall use electronically commutated motors, brushless direct-current motors, or 3-phase motors.
8. Condenser fan motors that are less than 1 hp (0.746 kW) shall use electronically commutated motors, permanent split capacitor-type motors or 3-phase motors.
9. Where antisweat heaters without antisweat heater controls are provided, they shall have a total door rail, glass and frame heater power draw of not more than 7.1 W/ft2 (76 W/m2) of door opening for walk-in freezers and 3.0 W/ft2 (32 W/m2) of door opening for walk-in coolers.
10. Where antisweat heater controls are provided, they shall reduce the energy use of the antisweat heater as a function of the relative humidity in the air outside the door or to the condensation on the inner glass pane.
11. Lights in walk-in coolers, walk-in freezers, refrigerated warehouse coolers and refrigerated warehouse freezers shall either use light sources with an efficacy of not less than 40 lumens per watt, including ballast losses, or shall use light sources with an efficacy of not less than 40 lumens per watt, including ballast losses, in conjunction with a device that turns off the lights within 15 minutes when the space is not occupied.
C410.2.1 Walk-in coolers and walk-in freezers. Site-assembled or site-constructed walk-in coolers and walk-in freezers shall comply with the following:
1. Automatic door closers shall be provided that fully close walk-in doors that have been closed to within 1 inch (25 mm) of full closure.
2. Doorways shall be provided with strip doors, curtains, spring-hinged doors or other method of minimizing infiltration when the doors are open.
3. Walk-in cooler walls, ceilings and doors shall be provided with insulation having a thermal resistance of not less than R-25 or have wall, ceiling and door assembly U-factors no greater than U-0.039. Walk-in freezers walls, ceilings and doors shall be provided with insulation having a thermal resistance of not less than R-32 or have wall, ceiling, door and slab assembly U-factors no greater than U-0.030.
4. The floor of walk-in freezers shall be provided with insulation having a thermal resistance of not less than R-28 or have a floor assembly U-factor no greater than U-0.035.
5. Transparent reach-in doors for and windows in opaque walk-in freezer doors shall be provided with triple-pane glass having the interstitial spaces filled with inert gas or provided with heat-reflective treated glass.
6. Transparent reach-in doors for and windows in opaque walk-in cooler doors shall be double-pane heat-reflective treated glass having the interstitial space gas filled.
7. Evaporator fan motors that are less than 1 hp (0.746 kW) and less than 460 volts shall be electronically commutated motors or 3-phase motors.
8. Condenser fan motors that are less than 1 hp (0.746 kW) in capacity shall be of the electronically commutated or permanent split capacitor-type or shall be 3-phase motors.
9. Antisweat heaters that are not provided with antisweat heater controls shall have a total door rail, glass and frame heater power draw not greater than 7.1 W/ft2 (76 W/m2) of door opening for walk-in freezers, and not greater than 3.0 W/ft2 (32 W/m2) of door opening for walk-in coolers.
10. Antisweat heater controls shall be capable of reducing the energy use of the antisweat heater as a function of the relative humidity in the air outside the door or to the condensation on the inner glass pane.
11. Light sources shall have an efficacy of not less than 40 lumens per watt, including any ballast losses, or shall be provided with a device that automatically turns off the lights within 15 minutes of when the walk-in cooler or walk-in freezer was last occupied.
C410.2.2 Refrigerated display cases. Site-assembled or site-constructed refrigerated display cases shall comply with the following:
1. Lighting and glass doors in refrigerated display cases shall be controlled by one of the following:
1.1. Time switch controls to turn off lights during nonbusiness hours. Timed overrides for display cases shall turn the lights on for up to 1 hour and shall automatically time out to turn the lights off.
1.2. Motion sensor controls on each display case section that reduce lighting power by at least 50 percent within 3 minutes after the area within the sensor range is vacated.
2. Low-temperature display cases shall incorporate temperature-based defrost termination control with a time-limit default. The defrost cycle shall terminate first on an upper temperature limit breach and second upon a time limit breach.
3. Antisweat heater controls shall reduce the energy use of the antisweat heater as a function of the relative humidity in the air outside the door or to the condensation on the inner glass pane.
C410.3 Refrigeration systems. Refrigerated display cases, walk-in coolers or walk-in freezers that are served by remote compressor and remote condensers not located in a condensing unit, shall comply with Sections C410.4.1 and C410.4.2.
C410.3.1 Condensers serving refrigeration systems. Fan-powered condensers shall comply with the following:
1. The design saturated condensing temperatures for air-cooled condensers shall not exceed the design dry-bulb temperature plus 10°F (5.6°C) for low-temperature refrigeration systems, and the design dry-bulb temperature plus 15°F (8°C) for medium temperature refrigeration systems where the saturated condensing temperature for blend refrigerants shall be determined using the average of liquid and vapor temperatures as converted from the condenser drain pressure.
2. Condenser fan motors that are less than 1 hp (0.75 kW) shall use electronically commutated motors, permanent split-capacitor-type motors or 3-phase motors.
3. Condenser fans for air-cooled condensers, evaporatively cooled condensers, air- or water-cooled fluid coolers or cooling towers shall reduce fan motor demand to not more than 30 percent of design wattage at 50 percent of design air volume, and incorporate one of the following continuous variable speed fan control approaches:
3.1. Refrigeration system condenser control for air-cooled condensers shall use variable setpoint control logic to reset the condensing temperature setpoint in response to ambient dry-bulb temperature.
3.2. Refrigeration system condenser control for evaporatively cooled condensers shall use variable setpoint control logic to reset the condensing temperature setpoint in response to ambient wet-bulb temperature.
4. Multiple fan condensers shall be controlled in unison.
5. The minimum condensing temperature setpoint shall be not greater than 70°F (21°C).
C410.3.2 Compressor systems. Refrigeration compressor systems shall comply with the following:
1. Compressors and multiple-compressor system suction groups shall include control systems that use floating suction pressure control logic to reset the target suction pressure temperature based on the temperature requirements of the attached refrigeration display cases or walk-ins.
2. Liquid subcooling shall be provided for all low-temperature compressor systems with a design cooling capacity equal to or greater than 100,000 Btu/hr (29.3 kW) with a design-saturated suction temperature of -10°F (-23°C) or lower. The subcooled liquid temperature shall be controlled at a maximum temperature setpoint of 50°F (10°C) at the exit of the subcooler using either compressor economizer (interstage) ports or a separate compressor suction group operating at a saturated suction temperature of 18°F (-7.8°C) or higher.
2.1. Insulation for liquid lines with a fluid operating temperature less than 60°F (15.6°C) shall comply with Table C403.2.10.
3. Compressors that incorporate internal or external crankcase heaters shall provide a means to cycle the heaters off during compressor operation.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-50000 Chapter 5 [CE]—((Referenced standards)) Existing buildings.
((This chapter lists the standards that are referenced in various sections of this document. The standards are listed herein by the promulgating agency of the standard, the standard identification, the effective date and title, and the section or sections of this document that reference the standard. The application of the referenced standards shall be as specified in Section 106.
C501 General.
C501.1 Scope. The provisions of this chapter shall control the alteration, repair, addition and change of occupancy of existing buildings and structures.
C501.2 Existing buildings. Except as specified in this chapter, this code shall not be used to require the removal, alteration or abandonment of, nor prevent the continued use and maintenance of, an existing building or building system lawfully in existence at the time of adoption of this code.
C501.3 Maintenance. Buildings and structures, and parts thereof, shall be maintained in a safe and sanitary condition. Devices and systems which are required by this code shall be maintained in conformance with the code edition under which installed. The owner or the owner's authorized agent shall be responsible for the maintenance of buildings and structures. The requirements of this chapter shall not provide the basis for removal or abrogation of energy conservation, fire protection and safety systems and devices in existing structures.
C501.4 Compliance. Alterations, repairs, additions and changes of occupancy to, or relocation of, existing buildings and structures shall comply with the provisions for alterations, repairs, additions and changes of occupancy or relocation, respectively, in the International Building Code, International Fire Code, International Fuel Gas Code, International Mechanical Code, Uniform Plumbing Code, and NFPA 70.
C501.5 New and replacement materials. Except as otherwise required or permitted by this code, materials permitted by the applicable code for new construction shall be used. Like materials shall be permitted for repairs, provided no hazard to life, health or property is created. Hazardous materials shall not be used where the code for new construction would not permit their use in buildings of similar occupancy, purpose and location.
C501.6 Historic buildings. The building official may modify the specific requirements of this code for historic buildings and require alternate provisions which will result in a reasonable degree of energy efficiency. This modification may be allowed for those buildings or structures that are listed in the state or national register of historic places; designated as a historic property under local or state designation law or survey; certified as a contributing resource with a national register listed or locally designated historic district; or with an opinion or certification that the property is eligible to be listed on the national or state registers of historic places either individually or as a contributing building to a historic district by the state historic preservation officer or the keeper of the national register of historic places.
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency. Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040. NEW SECTION
WAC 51-11C-50200 Section C502—Additions.
C502.1 General. Additions to an existing building, building system or portion thereof shall conform to the provisions of this code as they relate to new construction without requiring the unaltered portion of the existing building or building system to comply with this code. Additions shall not create an unsafe or hazardous condition or overload existing building systems. An addition shall be deemed to comply with this code if the addition alone complies or if the existing building and addition comply with this code as a single building. Additions shall comply with Section C502.2.
C502.2 Prescriptive compliance. Additions shall comply with Sections C502.2.1 through C502.2.6.2.
C502.2.1 Vertical fenestration. Additions with vertical fenestration that results in a total building vertical fenestration area less than or equal to that specified in Section C402.4.1 shall comply with Section C402.4. Additions with vertical fenestration that results in a total building vertical fenestration area greater than that specified in Section C402.4.1 shall comply with one of the following:
1. Vertical fenestration alternate per Section C402.4.1.1 or C402.4.1.3 for the addition only.
2. Component performance option with target area adjustment per Section C402.1.5 or the total building performance option in Section C407 for the whole building.
C502.2.2 Skylight area. Additions with skylights that result in a total building skylight area less than or equal to that specified in Section C402.4.1 shall comply with Section C402.4. Additions with skylights that result in a total building skylight area greater than that specified in Section C402.4.1 shall comply with the component performance option with the target area adjustment per Section C402.1.5 or the total building performance option in Section C407 for the whole building.
C502.2.3 Building mechanical systems. New mechanical systems and equipment serving the building heating, cooling or ventilation needs, that are part of the addition, shall comply with Section C403.
C502.2.4 Service water heating systems. New service water-heating equipment, controls and service water heating piping shall comply with Section C404.
C502.2.5 Pools and permanent spas. New pools and permanent spas shall comply with Section C404.11.
C502.2.6 Lighting and power systems. New lighting systems that are installed as part of the addition shall comply with Section C405.
C502.2.6.1 Interior lighting power. The total interior lighting power for the addition shall comply with Section C405.4.2 for the addition alone, or the existing building and the addition shall comply as a single building.
C502.2.6.2 Exterior lighting power. The total exterior lighting power for the addition shall comply with Section C405.5.1 for the addition alone, or the existing building and the addition shall comply as a single building.
C502.2.7 Refrigeration systems. New refrigerated spaces and refrigeration equipment shall comply with Section C410.
NEW SECTION
WAC 51-11C-50300 Section C503—Alterations.
C503.1 General. Alterations to any building or structure shall comply with the requirements of the code for new construction. Alterations shall be such that the existing building or structure is no less conforming with the provisions of this code than the existing building or structure was prior to the alteration. Alterations to an existing building, building system or portion thereof shall conform to the provisions of this code as they relate to new construction without requiring the unaltered portions of the existing building or building system to comply with this code. Alterations shall not create an unsafe or hazardous condition or overload existing building systems.
C503.2 Change in space conditioning. Any nonconditioned space that is altered to become conditioned space or semi-heated space shall be required to be brought into full compliance with this code. Any semi-heated space that is altered to become conditioned space shall be required to be brought into full compliance with this code.
C503.3 Building envelope. New building envelope assemblies that are part of the alteration shall comply with Sections C402.1 through C402.5 as applicable.
C503.3.1 Roof replacement. Roof replacements shall comply with Table C402.1.3 or C402.1.4 where the existing roof assembly is part of the building thermal envelope and contains insulation entirely above the roof deck.
C503.3.2 Vertical fenestration. The addition of vertical fenestration that results in a total building vertical fenestration area less than or equal to that specified in Section C402.4.1 shall comply with Section C402.4. Alterations that result in a total building vertical fenestration area greater than specified in Section C402.4.1 shall comply with one of the following:
1. Vertical fenestration alternate per Section C402.1.3 for the new vertical fenestration added.
2. Vertical fenestration alternate per Section C402.4.1.1 for the area adjacent to the new vertical fenestration added.
3. Component performance option with target area adjustment per Section C402.1.5 or the total building performance option in Section C407 for the whole building.
C503.3.2.1 Application to replacement fenestration products. Where some or all of an existing fenestration unit is replaced with a new fenestration product, including sash and glazing, the replacement fenestration unit shall meet the applicable requirements for U-factor and SHGC in Table C402.4.
C503.3.3 Skylight area. The addition of skylights that results in a total building skylight area less than or equal to that specified in Section C402.4.1 shall comply with Section C402.4. Alterations that result in a total building skylight area greater than that specified in Section C402.4.1 shall comply with the component performance option with target area adjustment per Section C402.1.5 or the total building performance option in Section C407 for the whole building.
C503.4 Mechanical systems. Those parts of systems which are altered or replaced shall comply with Section C403. Additions or alterations shall not be made to an existing mechanical system that will cause the existing mechanical system to become out of compliance.
All new systems in existing buildings, including packaged unitary equipment and packaged split systems, shall comply with Section C403.
Where mechanical cooling is added to a space that was not previously cooled, the mechanical system shall comply with either Section C403.2.6.1 or C403.3.
Alterations to existing mechanical cooling systems shall not decrease economizer capacity unless the system complies with either Section C403.2.6 or C403.3. In addition, for existing mechanical cooling systems that do not comply with either Section C403.2.6 or C403.3, including both the individual unit size limits and the total building capacity limits on units without economizer; other alterations shall comply with Table C503.4.
When space cooling equipment is replaced, controls shall comply with all requirements under Section C403.2.6 and related subsections or provide for integrated operation with economizer in accordance with Section C403.3.1.
Existing equipment currently in use may be relocated within the same floor or same tenant space if removed and reinstalled within the same permit.
Table C503.4
Economizer Compliance Options for Mechanical Alterations
C503.5 Service hot water systems. New service hot water systems that are part of the alteration shall comply with Section C404.
C503.6 Lighting and motors. Alterations that replace 50 percent or more of the luminaires in a space enclosed by walls or ceiling-height partitions, replace 50 percent or more of parking garage luminaires, or replace 50 percent or more of the total installed wattage of exterior luminaires shall comply with Sections C405.4 and C405.5. Where less than 50 percent of the fixtures in an interior space enclosed by walls or ceiling-height partitions or parking garage are new, or 50 percent or more of the installed exterior wattage is altered, the installed lighting wattage shall be maintained or reduced.
Where new wiring is being installed to serve added fixtures and/or fixtures are being relocated to a new circuit, controls shall comply with Sections C405.2.2.3, C405.2.4, C405.2.5, C405.3, and as applicable C408.3. In addition, office areas less than 300 ft2 enclosed by walls or ceiling-height partitions, and all meeting and conference rooms, and all school classrooms, shall be equipped with occupancy sensors that comply with Section C405.2.1 and C408.3. Where a new lighting panel (or a moved lighting panel) with all new raceway and conductor wiring from the panel to the fixtures is being installed, controls shall also comply with the other requirements in Sections C405.2 and C408.3.
Where new walls or ceiling-height partitions are added to an existing space and create a new enclosed space, but the lighting fixtures are not being changed, other than being relocated, the new enclosed space shall have controls that comply with Sections C405.2.1, C 405.2.2, C405.2.4 and C408.3.
Those motors which are altered or replaced shall comply with Section C405.8.
C503.7 Refrigeration systems. Those parts of systems which are altered or replaced shall comply with Section C410. Additions or alterations shall not be made to an existing refrigerated space or system that will cause the existing mechanical system to become out of compliance. All new refrigerated spaces or systems in existing buildings, including refrigerated display cases, shall comply with Section C410.
NEW SECTION
WAC 51-11C-50400 Section C504—Repairs.
C504.1 General. Buildings and structures, and parts thereof, shall be repaired in compliance with Section C501.3 and this section. Work on nondamaged components that is necessary for the required repair of damaged components shall be considered part of the repair and shall not be subject to the requirements for alterations in this chapter. Routine maintenance required by Section C501.3, ordinary repairs exempt from permit, and abatement of wear due to normal service conditions shall not be subject to the requirements for repairs in this section.
C504.2 Application. For the purposes of this code, the following shall be considered repairs.
1. Glass only replacements in an existing sash and frame.
2. Roof repairs.
3. Air barriers shall not be required for roof repair where the repairs to the building do not include alterations, renovations or repairs to the remainder of the building envelope.
4. Replacement of existing doors that separate conditioned space from the exterior shall not require the installation of a vestibule or revolving door, provided however that an existing vestibule that separates a conditioned space from the exterior shall not be removed.
5. Repairs where only the bulb and/or ballast within the existing luminaires in a space are replaced provided that the replacement does not increase the installed interior lighting power.
NEW SECTION
WAC 51-11C-50500 Section C505—Change of occupancy or use.
C505.1 General. Spaces undergoing a change in occupancy shall be brought up to full compliance with this code in the following cases:
1. Any space that is converted from an F, S or U occupancy to an occupancy other than F, S or U.
2. Any space that is converted to a Group R dwelling unit or portion thereof, from another use or occupancy.
3. Any Group R dwelling unit or portion thereof permitted prior to July 1, 2002, that is converted to a commercial use or occupancy.
Where the use in a space changes from one use in Table C405.4.2 (1) or (2) to another use in Table C405.4.2 (1) or (2), the installed lighting wattage shall comply with Section C405.4.
NEW SECTION
WAC 51-11C-600000 Chapter 6 [CE]—Referenced standards.
This chapter lists the standards that are referenced in various sections of this document. The standards are listed herein by the promulgating agency of the standard, the standard identification, the effective date and title, and the section or sections of this document that reference the standard. The application of the referenced standards shall be as specified in Section C106.
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040. AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-61011 Section A101.1—Scope.
A101.1 Scope. The following defaults shall apply to Chapter 4 of both the (RE) and (CE) sections of the ((IECC)) WSEC. This chapter includes tables of seasonal average heat loss coefficients for specified nominal insulation.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-61015 Section A101.5—Building materials.
A101.5 Building materials. Default R-values used for building materials shall be as shown in Table A101.5.
Table A101.5
Default R-values for Building Materials
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-61022 Section A102.2—Component description.
A102.2 Component description. The four types of ceilings are characterized as follows:
A102.2.1 Ceilings below a vented attic. Attic insulation is assumed to be blown-in, loose-fill fiberglass with a K-value of 2.6 h • ft2 • °F/Btu per inch. Full bag count for specified R-value is assumed in all cases. Ceiling dimensions for flat ceiling calculations are 45 by 30 feet, with a gabled roof having a 4/12 pitch. The attic is assumed to vent naturally at the rate of 3 air changes per hour through soffit and ridge vents. A void fraction of 0.002 is assumed for all attics with insulation baffles. Standard-framed, unbaffled attics assume a void fraction of 0.008.
Attic framing is either standard or advanced. Standard framing assumes tapering of insulation depth around the perimeter with resultant decrease in thermal resistance. An increased R-value is assumed in the center of the ceiling due to the effect of piling leftover insulation. Advanced framing assumes full and even depth of insulation extending to the outside edge of exterior walls. Advanced framing does not change from the default value.
U-factors for flat ceilings below vented attics with standard framing may be modified with the following table:
Vented scissors truss attics assume a ceiling pitch of 2/12 with a roof pitch of either 4/12 or 5/12. Unbaffled standard framed scissors truss attics are assumed to have a void fraction of 0.016.
A102.2.2 Vaulted ceilings. Insulation is assumed to be fiberglass batts installed in roof joist cavities. In the vented case, at least 1.5 inches between the top of the batts and the underside of the roof sheathing is left open for ventilation in each cavity. A ventilation rate of 3.0 air changes per hour is assumed. In the unvented or dense pack case, the ceiling cavity is assumed to be fully packed with insulation, leaving no space for ventilation.
A102.2.3 Roof decks. Rigid insulation is applied to the top of roof decking with no space left for ventilation. Roofing materials are attached directly on top of the insulation. Framing members are often left exposed on the interior side.
A102.2.4 Metal truss framing. Overall system tested values for the roof/ceiling Uo for metal framed truss assemblies from approved laboratories shall be used, when such data is acceptable to the building official.
Alternatively, the Uo for roof/ceiling assemblies using metal truss framing may be obtained from Tables A102.2.4(1) through A102.2.4(5).
A102.2.5 Metal building roof. Table A102.2.5: The base assembly is a roof where the insulation is compressed when installed beneath metal roof panels attached to the steel structure (purlins). Additional assemblies include continuous insulation, uncompressed and uninterrupted by framing.
U-factors for metal building roofs shall be taken from Table A102.2.5, provided the average purlin spacing is at least 52 inches and the R-value of the thermal spacer block is greater than or equal to the thermal spacer block R-value indicated in Table A107.2.5 for the assembly. It is not acceptable to use the U-factors in Tables A102.2.6(1), A102.2.6(2) and A102.2.6(3) if additional insulated sheathing is not continuous.
A102.2.5.1 Single layer. The rated R-value of insulation is for insulation installed perpendicular to and draped over purlins and then compressed when the metal roof panels are attached. A minimum R-3 (R-0.5) thermal spacer block between the purlins and the metal roof panels is required, unless compliance is shown by the overall assembly U-factor.
A102.2.5.2 Double layer. The first rated R-value of insulation is for insulation installed perpendicular to and draped over purlins. The second rated R-value of insulation is for unfaced insulation installed above the first layer and parallel to the purlins and then compressed when the metal roof panels are attached. A minimum R-3 (R-0.5) thermal spacer block between the purlins and the metal roof panels is required, unless compliance is shown by the overall assembly U-factor.
A102.2.5.3 Continuous insulation. For continuous insulation (e.g., insulation boards or blankets), it is assumed that the insulation is installed below the purlins and is uninterrupted by framing members. Insulation exposed to the conditioned space or semi-heated space shall have a facing, and all insulation seams shall be continuously sealed to provide a continuous air barrier.
A102.2.5.4 Liner system (Ls). A continuous membrane is installed below the purlins and uninterrupted by framing members. Uncompressed, unfaced insulation rests on top of the membrane between the purlins. For multilayer installations, the last rated R-value of insulation is for unfaced insulation draped over purlins and then compressed when the metal roof panels are attached. A minimum R-3 (R-0.5) thermal spacer block between the purlins and the metal roof panels is required, unless compliance is shown by the overall assembly U-factor.
A102.2.5.5 Filled cavity. The first rated R-value of insulation is for faced insulation installed parallel to the purlins. The second rated R-value of insulation is for unfaced insulation installed above the first layer, parallel to and between the purlins and compressed when the metal roof panels are attached. The facer of the first layer of insulation is of sufficient width to be continuously sealed to the top flange of the purlins and to accommodate the full thickness of the second layer of insulation. A supporting structure retains the bottom of the first layer at the prescribed depth required for the full thickness of the second layer of insulation being installed above it. A minimum R-5 (R-0.9) thermal spacer block between the purlins and the metal roof panels is required, unless compliance is shown by the overall assembly U-factor.
A102.2.6 Roofs with insulation entirely above deck (uninterrupted by framing). Tables A102.2.6(1) through A102.2.6(3): The base assembly is continuous insulation over a structural deck. ((Added insulation is continuous and uninterrupted by framing. For the insulation, the first column lists the R-value for continuous insulation with a uniform thickness; the second column lists the comparable area-weighted average R-value for continuous insulation provided that the insulation thickness is never less than R-5 (except at roof drains) and that the slope is)) These tables indicate effective U-factors for tapered roof insulation, sloped from a maximum R-value (Rmax) at the peak of the slope to a minimum R-value (Rmin) at the low point of the slope. The rows of the tables represent the rated R-value of the insulation at the minimum conditions (except at roof drains) and the columns of the table represent the rated R-value of the insulation at the maximum conditions. The slope of the tapered insulation shall be no greater than 1/4 inch per foot.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-610226 Tables A102.2.6—Assembly U-factors for roofs with insulation entirely above deck.
((Table A102.2.6
Assembly U-factors for Roofs with Insulation Entirely above Deck
(Uninterrupted by Framing)
Table A102.2.6(1)
Assembly U-factors for Roofs with Tapered Insulation Entirely Above Deck Single Slope Rectangular to One-sided,e,f,g,h
(Uninterrupted by Framing)
Table A102.2.6(2)
Assembly U-factors for Roofs with Tapered Insulation Entirely Above Deck Sloped Triangle (Roof with Center Drain)e,f,g,h,i
(Uninterrupted by Framing)
Table A102.2.6(3)
Assembly U-factors for Roofs with Tapered Insulation Entirely Above Deck Sloped Triangle (Roof with Perimeter Drains)e,f,g,h,i
(Uninterrupted by Framing)
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040. AMENDATORY SECTION (Amending WSR 13-20-120, filed 10/1/13, effective 11/1/13)
WAC 51-11C-61031 Section A103.1—General.
A103.1 General. The tables in this section list heat loss coefficients for the opaque portion of above-grade wood stud frame walls, metal stud frame walls and concrete masonry walls (Btu/h • ft2 • °F). They are derived from procedures listed in the ASHRAE Fundamentals Handbook. For intermediate floor slabs which penetrate the insulated wall, use the concrete wall U-factors in Table A103.3.7.1(1).
Insulation is assumed to uniformly fill the entire cavity and to be installed as per manufacturer's directions. All walls are assumed to be finished on the inside with 1/2 inch gypsum wallboard, and on the outside with either beveled wood siding over 1/2 inch plywood sheathing or with 5/8 inch T1-11 siding. Insulated sheathing (either interior or exterior) is assumed to cover the entire opaque wall surface, except where modified in accordance with footnote ((h)) g to Table ((C402.1.1)) C402.1.3.
Metal building walls have a different construction and are addressed in Table A103.3.6.3.
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-610337 Section A103.3.7—Concrete and masonry walls.
A103.3.7 Concrete and masonry walls.
A103.3.7.1 Concrete masonry walls. The nominal R-values in Tables A103.3.7.1(1), A103.3.7.1(2) and A103.3.7.1(3) may be used for purposes of calculating concrete masonry wall section U-factors in lieu of the ASHRAE isothermal planes calculation method as provided in Chapter 27 of the ASHRAE Fundamentals Handbook.
Table A103.3.7.1(1)
Default U-factors for Concrete ((and)) Masonry Walls
((8" Concrete Masonry
12" Concrete Masonry
8" Clay Brick))
Table A103.3.7.1(2)
Default U-factors for 80-Inch Clay Brick Masonry Walls
((6" Concrete Poured or Precast))
Table A103.3.7.1(3)
Default U-factors for 6-Inch Concrete Poured
or Precast Masonry Walls
Notes for Tables A103.3.7.1(2) and A103.3.7.1(3):
1. Grouted cores at 40" x 48" on center vertically and horizontally in partial grouted walls.
2. Interior insulation values include 1/2" gypsum board on the inner surface.
3. Furring and stud spacing is 16" on center. Insulation is assumed to fill furring space and is not compressed.
4. Intermediate values may be interpolated using this table. Values not contained in this table may be computed using the procedures listed in the ASHRAE Fundamentals Handbook.
((5. Concrete Masonry Unit (CMU) assembly U-values are based on local test data for Washington state CMU block material using the ASTM C-236-87 steady state thermal conductance test. Tests included an 8"x8"x16" CMU with all cells filled with vermiculite (1995) and 8"x8"x16" CMU with all cells filled with polymaster foam in place insulation (1996). Refer to ASHRAE Standard 90.1 for additional nationally recognized data on the thermal performance of CMU block walls.))
Table A103.3.7.1(2)
Default U-Factors for Concrete and Masonry Wallsa, b, c, d
Note for Default Table A103.3.7.1(2):
A103.3.7.2 Peripheral edges of intermediate concrete floors. See Table A103.3.7.2.
Table A103.3.7.2
Default U-factors for Peripheral Edges of Intermediate Concrete Floorsa, b, c, d
Note for Table A103.3.7.2:
AMENDATORY SECTION (Amending WSR 13-04-056, filed 2/1/13, effective 7/1/13)
WAC 51-11C-61051 Section A105.1—General.
A105.1 General. Tables A105.1(1), A105.1(2) and A105.1(3) list heat loss coefficients for floors over unconditioned spaces in units of Btu/h • ft2 • °F.
They are derived from procedures listed in the ASHRAE Fundamentals Handbook, assuming an average outdoor temperature of 45°F, an average indoor temperature of 65°F and a crawlspace area of 1350 ft2 and 100 feet of perimeter. The crawlspace is assumed to be 2.5 feet high, with 24 inches below grade and 6 inches above grade.
Table A105.1(1)
Default U-factors for Wood-Framed Floors
over Vented Crawlspace or
Unheated Basement
Table A105.1(2)
Default U-factors for Wood-Framed Floors over Heated Plenum Crawlspaces
Table A105.1(3)
Default U-factors for Exposed Floors
NEW SECTION
WAC 51-11C-80500 Appendix D—Renewable energy.
AE101.1 On-site renewable energy systems. Each new commercial building or addition larger than 5,000 square feet of gross conditioned floor area shall include a renewable energy generation system consisting of at least 70 watts rated peak photovoltaic energy production, or 240 kBtu of annual solar water heating energy production, per 1,000 square feet of conditioned floor area or fraction thereof. For buildings over 5 stories in height, the conditioned area for this calculation shall be based on the conditioned area of the largest 5 above-grade stories in the building. If the on-site renewable energy option in C406 is selected, this energy shall be in addition to that required by C406.
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||