If you have: | Then make sure they: | |
All container connections | Are provided with either of the following: | |
1. | Automatic excess flow valves; or | |
2. | Quick-closing internal valves that remain closed except during delivery operations. | |
Note: If the control mechanism is provided with a secondary control remote from the delivery connection, then a fusible section (melting point 208°F to 220°F) is required to permit the internal valve to close automatically in case of fire. | ||
Exemption: Filling connections, safety relief devices, and liquid level and pressure gauge connections are exempt from automatic excess flow valves and quick-closing internal valves. | ||
Filling connections | Prevent back-flow in the event the filling connection breaks with at least one of the following: | |
1. | Automatic back pressure check valves; | |
2. | Excess flow check valves; | |
3. | Quick closing internal valves. | |
Exemption: An automatic valve is not required if: | ||
1. | The filling and discharge connect to a common opening in the container shell; and | |
2. | The opening is fitted with a quick-closing internal valve. | |
Nonrecessed container fittings and appurtenances | Are protected against physical damage by one of the following methods: | |
1. | A protected location; | |
2. | The vehicle frame or bumper. | |
A protective housing that meets the following: | ||
1. | Is fabricated from material that is compatible with the containers design and construction requirements; | |
2. | Designed to withstand static loadings in any direction equal to twice the weight of the container and attachments when filled using a safety factor of not less than 4, based on the ultimate strength of the material used. | |
Note: Protect nonrecessed container fittings and appurtenances with a weather cover as needed for proper operation of valves and safety relief devices. | ||
Columnar-type gauges | 1. | Are restricted to stationary storage installations. |
2. | Are shielded against the direct rays of the sun. | |
3. | Are equipped with all of the following: | |
a. | Shut off valves having metallic hand-wheels; | |
b. | Excess flow valves; | |
c. | Extra heavy glass that is adequately protected with a metal housing applied by the gauge manufacturer. | |
Hydrostatic relief valves | Are installed between each pair of valves in the liquid ammonia piping or hose. |