NOMINAL STUD DEPTH (inches) | SPACING OF FRAMING (inches) | CAVITYR-VALUE (insulation) | CORRECTION FACTOR (Fc) | EFFECTIVE R-VALUE (ER) (Cavity R-Value x Fc) |
| 3 1/2 | 16 | 13 | 0.46 | 5.98 |
| 15 | 0.43 | 6.45 |
| 3 1/2 | 24 | 13 | 0.55 | 7.15 |
| 15 | 0.52 | 7.80 |
| 6 | 16 | 19 | 0.37 | 7.03 |
| 21 | 0.35 | 7.35 |
| 6 | 24 | 19 | 0.45 | 8.55 |
| 21 | 0.43 | 9.03 |
| 8 | 16 | 25 | 0.31 | 7.75 |
| 24 | 25 | 0.38 | 9.50 |
(Effective October 29, 2023)
Table C402.1.4.2—Effective R-values for steel stud wall assemblies.
Table C402.1.4.2
Effective R-values For Steel Stud Wall Assemblies
NOMINAL STUD DEPTH (inches) | SPACING OF FRAMING (inches) | CAVITYR-VALUE (insulation) | CORRECTION FACTOR (Fc) | EFFECTIVE R-VALUE (ER) (Cavity R-Value × Fc) |
| 3 1/2 | 16 | 13 | 0.46 | 5.98 |
| 15 | 0.43 | 6.45 |
| 3 1/2 | 24 | 13 | 0.55 | 7.15 |
| 15 | 0.52 | 7.80 |
| 6 | 16 | 19 | 0.37 | 7.03 |
| 21 | 0.35 | 7.35 |
| 6 | 24 | 19 | 0.45 | 8.55 |
| 21 | 0.43 | 9.03 |
| 8 | 16 | 25 | 0.31 | 7.75 |
| 24 | 25 | 0.38 | 9.50 |