PROPOSED RULES
Original Notice.
Preproposal statement of inquiry was filed as WSR 03-08-027.
Title of Rule: Adoption of chapter 51-54 WAC (adoption and amendment of the 2003 Edition of the International Fire Code). Repeal of chapter 51-44 WAC (Adoption and amendment of the 1997 Edition of the Uniform Fire Code) and chapter 51-45 WAC (adoption and amendment of the 1997 Uniform Fire Code Standards).
Purpose: To consider adoption and amendment of the 2003 Edition of the International Fire Code.
Statutory Authority for Adoption: RCW 19.27.031 and 19.27.074.
Statute Being Implemented: Chapters 19.27 and 34.05 RCW.
Summary: The proposed rule includes adoption of the 2003 Edition of the International Fire Code (IFC) published by the International Codes Council (ICC), and repeal of the 1997 Edition of the Uniform Fire Code (UFC) published by the International Council of Building Officials (ICBO). Existing state amendments are being carried forward into the new codes to assure continued provision of safety and flexibility greater than the published versions.
Reasons Supporting Proposal: RCW 19.27.031 and 19.27.074.
Name of Agency Personnel Responsible for Drafting and Implementation: Krista Braaksma, Olympia, Washington 98504-8350, (360) 725-2964; and Enforcement: Local jurisdictions.
Name of Proponent: Washington State Building Code Council, governmental.
Agency Comments or Recommendations, if any, as to Statutory Language, Implementation, Enforcement, and Fiscal Matters: The council is seeking comments on the issues proposed in the rules shown below.
Rule is not necessitated by federal law, federal or state court decision.
Explanation of Rule, its Purpose, and Anticipated Effects: The proposed rule will adopt by reference the 2003 Edition of the IFC and repeal the 1997 Edition of the UFC, which is no longer being updated. The rule will also carry forward existing state amendments into the IFC as applicable to assure continued provision of safety and flexibility greater than the published versions. An additional amendment is proposed based on national studies in response to recent tragedies involving night club fires.
Proposal Changes the Following Existing Rules: The 1997 Edition of the UFC is being updated by adopting the 2003 Edition of the IFC. With the repeal of chapters 51-44 and 51-45 WAC, a new WAC number has been designated, chapter 51-54 WAC.
An additional new amendment is being proposed to Section 903.2.1.2 that would require automatic fire sprinklers in any Group A-2 occupancy with an occupant load greater than 100. This is reduced from the existing threshold of 300.
No small business economic impact statement has been prepared under chapter 19.85 RCW. This rule will update the adoption of model codes to stay current with national standards for the benefit of industry and Washington state interests. No economic impact on small business was identified.
RCW 34.05.328 does not apply to this rule adoption. The State Building Code Council is not listed in this section as one of the agencies required to comply with this regulation.
Hearing Location: Spokane City Council Chambers, West 808 Spokane Falls Boulevard, Spokane, WA, on October 10, 2003, at 10:00 a.m.; and at the Holiday Inn Select/Renton, One Grady Way South, Renton, WA, on October 17, 2003, at 10:00 a.m.
Assistance for Persons with Disabilities: Contact
Sue Mathers by September 26, 2003, TDD (360) 753-7427 or (360) 725-2967.
Submit Written Comments to: Stan Price, Chairman, State Building Code Council, P.O. Box 48350, Olympia, WA 98504-8350, fax (360) 586-9383, e-mail sbcc@cted.wa.gov, by October 17, 2003.
Date of Intended Adoption: November 21, 2003.
August 7, 2003
Tim Nogler
for Stan Price
Council Chair
OTS-6613.2
STATE BUILDING CODE ADOPTION AND AMENDMENT OF THE 2003 EDITION OF THE INTERNATIONAL FIRE CODE
[]
[]
[]
The following referenced codes published by the International Code Council are not adopted as part of the State Building Code: ICC Electrical Code, International Plumbing Code, International Energy Conservation Code, International Private Sewage Disposal Code, International Property Maintenance Code, International Existing Building Code, and International Urban-Wildland Interface Code. When referenced, as appropriate, these references shall mean the National Electrical Code (as adopted and amended by the state of Washington), the Uniform Plumbing Code (as adopted and amended by the state of Washington), the Washington State Energy Code, or other locally adopted code if applicable.
The provisions of this code do not apply to temporary growing structures used solely for the commercial production of horticultural plants including ornamental plants, flowers, vegetables, and fruits. "Temporary growing structure" means a structure that has the sides and roof covered with polyethylene, polyvinyl, or similar flexible synthetic material and is used to provide plants with either frost protection or increased heat retention. A temporary growing structure is not considered a building for purposes of this code.
The provisions of this code do not apply to the construction, alteration, or repair of temporary worker housing except as provided by rule adopted under chapter 70.114A RCW or chapter 37, Laws of 1998 (SB 6168). "Temporary worker housing" means a place, area, or piece of land where sleeping places or housing sites are provided by an employer for his or her employees or by another person, including a temporary worker housing operator, who is providing such accommodations for employees, for temporary, seasonal occupancy, and includes "labor camps" under RCW 70.54.110.
The provisions of this code do not apply to explosives or explosive materials. Explosives and explosive materials shall be governed by chapter 296-52 WAC.
The provisions of this code do not apply to fireworks. Fireworks shall be governed by chapter 212-17 WAC.
[]
[]
105.6.17 Flammable or combustible liquids. An operational
permit is required:
1. To use or operate a pipeline for the transportation within facilities of flammable or combustible liquids. This requirement shall not apply to the off-site transportation in pipelines regulated by the department of transportation (DOT) nor does it apply to piping systems.
2. To store, handle or use Class I liquids in excess of 5 gallons (19 L) in a building or in excess of 10 gallons (37.9 L) outside of a building, except that a permit is not required for the following:
2.1 The storage or use of Class I liquids in the fuel tank of a motor vehicle, aircraft, motorboat, mobile power plant or mobile heating plant, unless such storage, in the opinion of the code official, would cause an unsafe condition.
2.2 The storage or use of paints, oils, varnishes or similar flammable mixtures when such liquids are stored for maintenance, painting or similar purposes for a period of not more than 30 days.
3. To store, handle or use Class II or Class III-A liquids in excess of 25 gallons (95 L) in a building or in excess of 60 gallons (227 L) outside a building, except for fuel oil used in connection with oil-burning equipment.
4. To remove Class I or Class II liquids from an underground storage tank used for fueling motor vehicles by any means other than the approved, stationary on-site pumps normally used for dispensing purposes.
5. To operate tank vehicles, equipment, tanks, plants, terminals, wells, fuel-dispensing stations, refineries, distilleries and similar facilities where flammable and combustible liquids are produced, processed, transported, stored, dispensed or used.
6. To place temporarily out-of-service (for more than 90 days) an underground, protected above-ground or above-ground flammable or combustible liquid tank.
7. To change the type of contents stored in a flammable or combustible liquid tank to a material which poses a greater hazard than that for which the tank was designed and constructed.
8. To manufacture, process, blend or refine flammable or combustible liquids.
9. To engage in the dispensing of liquid fuels into the fuel tanks of motor vehicles at commercial, industrial, governmental or manufacturing establishments.
10. To utilize a site for the dispensing of liquid fuels from tank vehicles into the fuel tanks of motor vehicles at commercial, industrial, governmental or manufacturing establishments.
11. To utilize a site for the dispensing of liquid fuels from tank vehicles into the fuel tanks of marine craft and special equipment at commercial, industrial, governmental or manufacturing establishments.
[]
SECTION 202 GENERAL DEFINITIONS.
ADULT FAMILY HOME means a dwelling in which a person or persons
provide personal care, special care, room and board to more
than one but not more than six adults who are not related by
blood or marriage to the person or persons providing the
services.
CHILD DAY CARE, shall, for the purposes of these regulations,
mean the care of children during any period of a 24-hour day.
ELECTRICAL CODE is the National Electrical Code, promulgated by
the National Fire Protection Association, as adopted in
chapter 296-46 WAC, or the locally adopted Electrical Code.
[B] FAMILY CHILD DAY CARE HOME is a child day care facility,
licensed by the state, located in the dwelling of the person
or persons under whose direct care and supervision the child
is placed, for the care of twelve or fewer children, including
children who reside at the home.
[B] EDUCATIONAL GROUP E. Educational Group E Occupancy includes, among others, the use of a building or structure, or a portion thereof, by six or more persons at any one time for educational purposes through the 12th grade. Religious educational rooms and religious auditoriums, which are accessory to churches in accordance with Section 302.2 of the IBC and have occupant loads of less than 100, shall be classified as Group A-3 Occupancies.
Day Care. The use of a building or structure, or portion thereof, for educational, supervision or personal care services for more than five children older than 2 1/2 years of age, shall be classified as a Group E Occupancy.
EXCEPTION: | Family child day care homes licensed by the Washington state department of social and health services for the care of twelve or fewer children shall be classified as Group R3. |
Group I-1. This occupancy shall include buildings, structures or parts thereof housing more than 16 persons, on a 24-hour basis, who because of age, mental disability or other reasons, live in a supervised residential environment that provides personal care services. The occupants are capable of responding to an emergency situation without physical assistance from staff. This group shall include, but not be limited to, the following:
Residential board and care facilities
Assisted living facilities
Halfway houses
Group homes
Congregate care facilities
Social rehabilitation facilities
Alcohol and drug centers
Convalescent facilities
A facility such as the above with five or fewer persons and adult family homes licensed by the Washington state department of social and health services shall be classified as a Group R-3 or shall comply with the International Residential Code in accordance with Section 101.2. A facility such as above, housing at least six and not more than 16 persons, shall be classified as Group R-4.
A facility such as the above providing licensed care to clients in one of the categories listed in Section 313.1 regulated by either the Washington department of health or the department of social and health services shall be classified as Licensed Care Group LC.
Group I-2. This occupancy shall include buildings and structures used for medical, surgical, psychiatric, nursing or custodial care on a 24-hour basis of more than five persons who are not capable of self-preservation. This group shall include, but not be limited to, the following:
Hospitals
Nursing homes (both intermediate-care facilities and skilled nursing facilities)
Mental hospitals
Detoxification facilities
A facility such as the above with five or fewer persons shall be classified as Group R-3 or shall comply with the International Residential Code in accordance with Section 101.2.
A facility such as the above providing licensed care to clients in one of the categories listed in Section 313.1 regulated by either the Washington department of health or the department of social and health services shall be classified as Licensed Care Group LC.
Group I-3. (Remains as printed in the IFC.)
Group I-4. Day care facilities. This group shall include buildings and structures occupied by persons of any age who receive custodial care for less than 24 hours by individuals other than parents or guardians, relatives by blood marriage, or adoption, and in a place other than the home of the person cared for. A facility such as the above with five or fewer persons shall be classified as Group R-3 or shall comply with the International Residential Code. Places of worship during religious functions are not included.
Adult care facility. A facility that provides accommodations for less than 24 hours for more than five unrelated adults and provides supervision and personal care services shall be classified as Group I-4.
EXCEPTION: | Where the occupants are capable of responding to an emergency situation without physical assistance from the staff, the facility shall be classified as Group A-3. |
EXCEPTIONS: | 1. A child day care facility that provides care for more than five but no more than 100 children 2 1/2 years or less of age, when the rooms where such children are cared for are located on the level of exit discharge and each of these child care rooms has an exit door directly to the exterior, shall be classified as Group E. |
2. Family child day care homes licensed by the Washington state department of social and health services for the care of 12 or fewer children shall be classified as Group R3. |
R-1 Residential occupancies where the occupants are primarily transient in nature, including:
Boarding houses (transient)
Hotels (transient)
Motels (transient)
R-2 Residential occupancies containing sleeping units or more than two dwelling units where the occupants are primarily permanent in nature, including:
Apartment houses
Boarding houses (not transient)
Convents
Dormitories
Fraternities and sororities
Monasteries
Vacation timeshare properties
Hotels (nontransient)
Motels (nontransient)
R-3 Residential occupancies where the occupants are primarily permanent in nature and not classified as R-1, R-2, R-4 or I and where buildings do not contain more than two dwelling units as applicable in Section 101.2, including adult family homes and family child day care homes for the care of 12 or fewer children, licensed by the Washington state department of social and health services, or adult and child care facilities that provide accommodations for five or fewer persons of any age for less than 24 hours. Adult family homes and family child day care homes, or adult and child care facilities that are within a single-family home are permitted to comply with the International Residential Code in accordance with Section 101.2.
Foster family care homes licensed by the Washington state department of social and health services shall be permitted, as an accessory use to a dwelling, for six or fewer children including those of the resident family.
R-4 Residential occupancies shall include buildings arranged for occupancy as residential care/assisted living facilities including more than five but not more than 16 occupants, excluding staff.
EXCEPTION: | Adult family homes, family child day care homes and foster family care homes shall be classified as Group R-3. |
[B] LICENSED CARE GROUP LC. Licensed Care Group LC includes the
use of a building, structure, or portion thereof, for the
business of providing licensed care to clients in one of the
following categories regulated by either the Washington
department of health or the department of social and health
services:
1. Adult residential rehabilitation facility.
2. Alcoholism intensive inpatient treatment service.
3. Alcoholism detoxification service.
4. Alcoholism long-term treatment service.
5. Alcoholism recovery house service.
6. Boarding home.
7. Group care facility.
8. Group care facility for severely and multiple handicapped children.
9. Residential treatment facility for psychiatrically impaired children and youth.
EXCEPTION: | Where the care provided at an alcoholism detoxification service is acute care similar to that provided in a hospital, the facility shall be classified as a Group I-2 Occupancy. |
[]
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040.
NEW SECTION
WAC 51-54-0300
Chapter 3 -- General precautions against
fire.
307.2.1 Authorization. Where required by state or local law
or regulations, open burning shall only be permitted with
prior approval from the state or local air and water quality
management authority, provided that all conditions specified
in the authorization are followed. See also chapter 173-425 WAC.
307.3.2 Recreational fires. Recreational fires shall not be
conducted within 25 feet of a structure or combustible
material. Conditions which could cause a fire to spread
within 25 feet of a structure shall be eliminated prior to
ignition. See also chapter 173-425 WAC.
308.3.4 Aisles and exits. Candles shall be prohibited in
areas where occupants stand, or in an aisle or exit.
EXCEPTION: | Candles used in religious ceremonies. See RCW 19.27.031(3). |
308.3.7 Group A Occupancies. Open-flame devices shall not be
used in a Group A Occupancy.
EXCEPTIONS: | 1. Open-flame devices are allowed to be used in the following situations: |
1.1 Where necessary for ceremonial or religious purposes in accordance with Section 308.5. | |
1.2 On stages and platforms as a necessary part of a performance in accordance with Section 308.6, provided approved precautions are taken to prevent ignition of a combustible material or injury to occupants. | |
1.3 Where candles on tables are securely supported on substantial noncombustible bases and the candle flames are protected provided approved precautions are taken to prevent ignition of a combustible material or injury to occupants. | |
2. Heat-producing equipment complying with Chapter 6 and the International Mechanical Code. | |
3. Gas lights are allowed to be used provided adequate precautions satisfactory to the fire code official are taken to prevent ignition of combustible materials. |
[]
SECTION 503 FIRE APPARATUS ACCESS ROADS.
503.1 Where required. Fire apparatus access roads shall be
provided and maintained in accordance with locally adopted
street, road, and access standards.
503.1.1 Buildings and facilities, is not adopted.
503.1.2 Additional access, is not adopted.
503.1.3 High-piled storage, is not adopted.
503.2 Specifications. This section is not adopted.
503.3 Marking. This section is not adopted.
503.4 Obstruction of fire apparatus access roads. This
section is not adopted.
[]
903.2.1.2 Group A-2. An automatic sprinkler system shall be
provided for Group A-2 Occupancies where one of the following
conditions exists:
1. The fire area exceeds 5,000 square feet (464.5 m2).
2. The fire area has an occupant load of 100 or more.
3. The fire area is located on a floor other than the level of exit discharge.
903.2.2 Group E. An automatic sprinkler system shall be
provided for Group E Occupancies as follows:
1. Throughout all Group E fire areas greater than 20,000 square feet (1858 m2) in area.
2. Throughout every portion of educational buildings below the level of exit discharge.
EXCEPTION: | An automatic sprinkler system is not required in any fire area or area below the level of exit discharge where every classroom throughout the building has at least one exterior exit door at ground level. |
For the purpose of this section, additions exceeding 60 percent of the value of such building or structure, or alterations and repairs to any portion of a building or structure within a twelve-month period that exceeds 100 percent of the value of such building or structure shall be considered new construction. In the case of additions, fire walls shall define separate buildings.
EXCEPTIONS: | 1. Portable school classrooms, provided aggregate area of clusters of portable school classrooms does not exceed 5,000 square feet (1465 m2); and clusters of portable school classrooms shall be separated as required in Chapter 5 of the building code. |
2. Group E Day Care. |
[B] 903.2.10.3 Buildings over 75 feet in height. An automatic
sprinkler system shall be installed throughout buildings with
a floor level having an occupant load of 30 or more that is
located 75 feet (22 860 mm) or more above the lowest level of
fire department vehicle access.
EXCEPTIONS: | 1. Airport control towers. |
2. Open parking structures. | |
3. Occupancies in Group F-2. |
[B] 909.6.3 Elevator shaft pressurization. Where elevator
shaft pressurization is required to comply with Exception 5 of
Section 707.14.1, the pressurization system shall comply with
the following.
909.6.3.1 Elevator shafts shall be pressurized to not less
than 0.10 inch water column relative to atmospheric pressure.
Elevator pressurization shall be measured with the elevator
cars at the designated primary recall level with the doors in
the open position. The test shall be conducted at the
location of the calculated maximum positive stack effect in
the elevator shaft. The measured pressure shall be sufficient
to provide 0.10 inch of water column as well as accounting for
the stack and wind effect expected on the mean low temperature
January day.
909.6.3.2 The elevator shaft pressurization system shall be
activated by a fire alarm system which shall include smoke
detectors or other approved detectors located near the
elevator shaft on each floor as approved by the building
official and fire chief. If the building has a fire alarm
panel, detectors shall be connected to, with power supplied
by, the fire alarm panel.
909.6.3.3 Elevator shaft pressurization equipment and its
ductwork located within the building shall be separated from
other portions of the building by construction equal to that
required for the elevator shaft.
909.6.3.4 Elevator shaft pressurization air intakes shall be
located in accordance with Section 909.10.3. Such intakes
shall be provided with smoke detectors which upon detection of
smoke, shall deactivate the pressurization fan supplied by
that air intake.
909.6.3.5 The power source for the fire alarm system and the
elevator shaft pressurization system shall be in accordance
with Section 909.11.
909.6.3.6 Hoistway venting required by IBC Section 3004 need
not be provided for pressurized elevator shafts.
909.6.3.7 Elevator machine rooms required to be pressurized by
IBC Section 3006.3 need not be pressurized where separated
from the hoistway shaft by construction in accordance with IBC
Section 707.
909.6.3.8 Special inspection shall be required in accordance
with Section 909.18.8.3 and IBC Section 1704.
[]
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040.
NEW SECTION
WAC 51-54-1000
Chapter 10 -- Means of egress.
[B] 1009.3 Stair treads and risers. Stair riser heights shall
be 7 1/2 inches (190 mm) maximum and 4 inches (102 mm)
minimum. Stair tread depths shall be 10 inches (254 mm)
minimum. The riser height shall be measured vertically
between the leading edges of adjacent treads. The greatest
riser height within any flight of stairs shall not exceed the
smallest by more than 0.375 inch (9.5 mm). Winder treads
shall have a minimum tread depth of 11 inches (279 mm)
measured at a right angle to the tread's leading edge at a
point 12 inches (305 mm) from the side where the treads are
narrower and a minimum tread depth of 10 inches (254 mm). The
greatest winder tread depth at the 12-inch (305 mm) walk line
within any flight of stairs shall not exceed the smallest by
more than 0.375 inch (9.5 mm).
EXCEPTIONS: | 1. Circular stairways in accordance with Section 1009.7. |
2. Winders in accordance with Section 1009.8. | |
3. Spiral stairways in accordance with Section 1009.9. | |
4. Aisle stairs in assembly seating areas where the stair pitch or slope is set, for sightline reasons, by the slope of the adjacent seating area in accordance with Section 1024.11.2. | |
5. In occupancies in Group R-3, as applicable in Section 1001.1, within dwelling units in occupancies in Group R-2, as applicable in Section 1001.1, and in occupancies in Group U, which are accessory to an occupancy in Group R-3 as applicable in Section 1001.1, the maximum riser height shall be 7.75 inches (197 mm) and the minimum tread depth shall be 10 inches (254 mm), the minimum winder tread depth at the walk line shall be 10 inches (254 mm), and the minimum winder tread depth shall be 6 inches (152 mm). A nosing not less than 0.75 inch (19.1 mm) but not more than 1.25 inches (32 mm) shall be provided on stairways with solid risers where the tread depth is less than 11 inches (279 mm). | |
6. See the International Existing Building Code for the replacement of existing stairways. |
[B] 1010.8 Handrails. Ramps with a rise greater than 6 inches
(152 mm) shall have handrails on both sides complying with
Section 1009.11. At least one handrail shall extend in the
direction of ramp run not less than 12 inches (305 mm)
horizontally beyond the top and bottom of the ramp runs.
[B] 1024.11 Assembly aisle walking surfaces. Aisles with a
slope not exceeding one unit vertical in eight units
horizontal (12.5-percent slope) shall consist of a ramp having
a slip-resistant walking surface. Aisles with a slope
exceeding one unit vertical in eight units horizontal
(12.5-percent slope) shall consist of a series of risers and
treads that extends across the full width of aisles and
complies with Sections 1024.11.1 through 1024.11.3.
EXCEPTION: | When provided with fixed seating, aisles in Group A-1 Occupancies shall be permitted to have a slope not steeper than one unit vertical in five units horizontal (20-percent slope). |
EXCEPTIONS: | 1. Handrails are not required for ramped aisles having a gradient no greater than one unit vertical in five units horizontal (20-percent slope) and seating on both sides. |
2. Handrails are not required if, at the side of the aisle, there is a guard that complies with the graspability requirements of handrails. |
[]
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040.
NEW SECTION
WAC 51-54-3000
Chapter 30 -- Compressed gasses.
3006.1 General. Compressed gases at hospitals and similar
facilities intended for inhalation or sedation including, but
not limited to, analgesia systems for dentistry, podiatry,
veterinary and similar uses shall comply with this section in
addition to other requirements of this chapter.
EXCEPTION: | All distribution piping, supply manifolds, connections, regulators, valves, alarms, sensors and associated equipment stall be in accordance with the Plumbing Code. |
[]
3301.1 Scope. The possession, manufacture, storage, handling,
sale and use of explosives and explosive materials shall be
governed by chapter 296-52 WAC and local ordinances consistent
with chapter 296-52 WAC. The manufacture, storage, handling,
sale and use of fireworks shall be governed by chapter 212-17 WAC and local ordinances consistent with chapter 212-17 WAC.
[]
3402.1 Definitions.
MOTOR VEHICLE. For the purposes of this chapter, the term motor
vehicle includes, but is not limited to, a vehicle, machine,
tractor, trailer, or semi-trailer, or any combination thereof,
propelled or drawn by mechanical power and used upon the
highways in the transportation of passengers or property. The
term "motor vehicle" also includes freight containers or cargo
tanks used, or intended for use, in connection with motor
vehicles. For reference, see 49 CFR Pt. 171.8 (October 1994).
3404.2.7.10.1 Leaking tank disposition. Leaking tanks shall
be handled in accordance with WAC 173-360-325.
3404.2.7.11 Tank lining. Steel tanks are allowed to be lined
only for the purpose of protecting the interior from corrosion
or providing compatibility with a material to be stored. Only
those liquids tested for compatibility with the lining
material are allowed to be stored in lined tanks. Lining of
leaking underground storage tanks shall be done in accordance
with the provisions of WAC 173-360-325.
3404.2.8.7 Arrangement. Tanks shall be listed for
above-ground use, and each tank shall be in its own vault.
EXCEPTION: | Below-grade vaults may contain a maximum of three tanks. |
3404.2.11 Underground tanks. Underground storage of flammable
and combustible liquids in tanks shall comply with Section
3404.2 and Sections 3404.2.11.1 through 3404.2.11.5.2.
Corrosion protection shall comply with WAC 173-360-305.
3405.4.1 Unit with a capacity of 60 gallons or less. Solvent
distillation units used to recycle Class I, II or III-A
liquids having a distillation chamber capacity of 60 gallons
or less shall be listed, labeled and installed in accordance
with Section 3405.4 and UL 2208.
EXCEPTIONS: | 1. Solvent distillation units installed in dry-cleaning plants in accordance with Chapter 12. |
2. Solvent distillation units used in continuous through-put industrial processes where the source of heat is remotely supplied using steam, hot water, oil or other heat transfer fluids, the temperature of which is below the autoignition point of the solvent. | |
3. Approved research, testing and experimental processes. |
3406.5.4.1 Marine craft and special equipment. Liquids
intended for use as motor fuels are allowed to be transferred
from tank vehicles into the fuel tanks of marine craft and
special equipment when approved by the fire code official, and
when:
1. The tank vehicle's specific function is that of supplying fuel to fuel tanks.
2. The operation is not performed where the public has access or where there is unusual exposure to life and property.
3. The dispensing line does not exceed 50 feet in length.
4. The dispensing nozzle is approved.
5. Each premises is issued a separate permit in accordance with Section 105.6.17.
3406.5.4.5 Commercial, industrial, governmental or
manufacturing. Dispensing of Class II and III motor vehicle
fuel from tank vehicles into the fuel tanks of motor vehicles
located at commercial, industrial, governmental or
manufacturing establishments is allowed where permitted,
provided such dispensing operations are conducted in
accordance with the following: (Those sections not noted here
remain unchanged.)
6. Mobile fueling shall not take place within 15 feet of streets, alleys, public ways, buildings, property lines, combustible storage or storm drains.
EXCEPTIONS: | 1. The distance to storm drains can be eliminated if an approved storm drain cover or an approved equivalent that will prevent any fuel from reaching the drain is in place prior to fueling or home being placed within 15 feet of the drain. When placement of a storm drain cover will cause the accumulation of excessive water or difficulty in safely conducting the fueling, it shall not be used and the fueling shall not take place within 15 feet of a drain. |
2. The distance to storm drains can be eliminated for drains that direct intake to approved oil-water separators. |
17. Fuel dispensing is prohibited within 25 feet of any source of ignition.
25. Operators shall place a drip pan or absorbent, in good condition, under each fuel fill opening prior to and during all dispensing operations. Drip pans shall be liquid-tight. The pan or absorbent shall have a capacity of at least 3 gallons. Spills retained in the drip pan or absorbent pillow need not be reported. Operators, when fueling, shall have on their persons an absorbent pad capable of capturing diesel foam overfills. Except during fueling, the nozzle shall face upwards and an absorbent pad shall be kept under the nozzle to prevent drips. Contaminated absorbent pads shall be disposed of regularly in accordance with local, state and federal requirements.
26. All persons and parties with an interest in the property (i.e., property owner, lessor, real estate company, property manager as well as operators of the property) must give consent in writing to allow the mobile fueling to occur on the property. Managers, lessees, renters and other persons cannot solely give permission. Each person or party must indicate that they are under the risk of spills.
[]