PERMANENT RULES
Date of Adoption: November 9, 2001.
Purpose: To adopt, with state amendments, the 2000 Edition of the Uniform Plumbing Code published by the International Association of Plumbing and Mechanical Officials.
Citation of Existing Rules Affected by this Order: Repealing chapters 51-46 and 51-47 WAC; and new chapters 51-56 and 51-57 WAC.
Statutory Authority for Adoption: RCW 19.27.031, 19.27.074.
Adopted under notice filed as WSR 01-16-122 on July 31, 2001.
Changes Other than Editing from Proposed to Adopted Version: 1. UPC Chapter 15, Firestop Protection for DWV and Stormwater Applications, filed as WAC 51-56-201300 (Appendix M), is not adopted.
2. UPC Chapter 11, Storm Drainage, filed as WAC 51-56-1500 (Chapter 15), is moved and adopted as an appendix chapter, WAC 51-56-201300 (Appendix M).
3. Reference to Underwriters Laboratories standards in Chapter 14 were updated as applicable.
Number of Sections Adopted in Order to Comply with Federal Statute: New 0, Amended 0, Repealed 0; Federal Rules or Standards: New 0, Amended 0, Repealed 0; or Recently Enacted State Statutes: New 2, Amended 0, Repealed 0.
Number of Sections Adopted at Request of a Nongovernmental Entity: New 5, Amended 0, Repealed 0.
Number of Sections Adopted on the Agency's Own Initiative: New 10, Amended 0, Repealed 90.
Number of Sections Adopted in Order to Clarify, Streamline, or Reform Agency Procedures: New 0, Amended 0, Repealed 0.
Number of Sections Adopted Using Negotiated Rule Making:
New 0,
Amended 0,
Repealed 0;
Pilot Rule Making:
New 0,
Amended 0,
Repealed 0;
or Other Alternative Rule Making:
New 24,
Amended 0,
Repealed 90.
Effective Date of Rule:
July 1, 2002.
December 18, 2001
Tim Nogler
for Jim Lewis
Council Chair
OTS-4209.5
STATE BUILDING CODE ADOPTION AND AMENDMENT OF THE 2000 EDITION OF THE UNIFORM PLUMBING CODE
[]
[]
[]
[]
[]
101.4.1.4 Conflict Between Codes. Delete paragraph.
102.4 Appeals. All persons shall have the right to appeal a
decision of the administrative authority. The jurisdiction shall
have a board of appeals to hear and rule on Plumbing Code
appeals. Members of the board shall be appointed by the
jurisdiction. Decisions by the board shall be reported to the
jurisdiction and administered by the administrative authority.
103.1.3 Certification. State rules and regulations concerning
certification shall apply.
[]
205.0 Certified Backflow Assembly Tester - A person certified by
the Washington state department of health under chapter 246-292 WAC to inspect (for correct installation and approval status) and
test (for proper operation) approved backflow assemblies.
208.0 Flammable Vapor or Fumes is the concentration of flammable
constituents in air that exceeds 10 percent of its lower
flammability limit (LFL).
218.0 Plumbing System – Includes all potable water building
supply and distribution pipes, all plumbing fixtures and traps,
all drainage and vent pipe(s), and all building drains including
their respective joints and connection, devices, receptors, and
appurtenances within the property lines of the premises and shall
include potable water piping, potable water treating or using
equipment, medical gas and medical vacuum systems, and water
heaters: Provided, That no certification shall be required for
the installation of a plumbing system within the property lines
and outside a building.
[]
301.1.1 Approvals. Unless otherwise provided for in this code,
all materials, fixtures or devices used or entering into the
construction of plumbing systems, or parts thereof, shall be
submitted to the administrative authority for approval and shall
conform to approved nationally recognized standards, and shall be
free from defects. All pipe, fittings, traps, fixtures, material
and devices used in a plumbing system shall be listed or labeled
by a listing agency or shall be approved by the administrative
authority.
301.1.3 Standards. Standards listed or referred to in this
chapter and Table 14-1 cover materials that conform to the
requirements of this code, when used in accordance with the
limitations imposed in this or other chapters thereof and their
listing. Where a standard covers materials of various grades,
weights, quality, or configurations, there may be only a portion
of the listed standard which is applicable. Design and materials
for special conditions or materials not provided for herein are
allowed to be used only by special permission of the
administrative authority after the administrative authority has
been satisfied as to their adequacy in accordance with Section
301.2.
311.4 Except as hereinafter provided in Sections 908.0, 909.0,
910.0, and Appendix L, Section L 6.0, no vent pipe shall be used
as a soil or waste pipe, nor shall any soil or waste pipe be used
as a vent.
313.6 No water, soil, or waste pipe shall be installed or
permitted outside of a building or in an exterior wall unless,
where necessary, adequate provision is made to protect such pipe
from freezing. All hot and cold water pipes installed outside
the conditioned space shall be insulated to a minimum R-3.
313.7 All pipe penetrating floor/ceiling assemblies and
fire-resistance rated walls or partitions shall be protected in
accordance with the requirements of the building code.
316.1.6 Solvent Cement Plastic Pipe Joints. Plastic pipe and
fittings designed to be joined by solvent cementing shall comply
with this code and the manufacturer's installation instructions.
ABS pipe and fittings shall be cleaned and then joined with
listed solvent cement(s).
CPVC and PVC pipe and fittings shall be cleaned and joined with listed primer(s) and solvent cement(s).
[]
402.0 Water-Conserving Fixtures and Fittings.
402.1 The purpose of this section shall be to implement water
conservation performance standards in accordance with RCW 19.27.170.
402.2 Application. This section shall apply to all new
construction and all remodeling involving replacement of plumbing
fixtures and fittings in all residential, hotel, motel, school,
industrial, commercial use, or other occupancies determined by
the council to use significant quantities of water. Plumbing
fixtures, fittings and appurtenances shall conform to the
standards specified in this section and shall be provided with an
adequate supply of potable water to flush and keep the fixtures
in a clean and sanitary condition without danger of backflow or
cross-connection.
402.3 Water Efficiency Standards.
402.3.1 Standards for Vitreous China Plumbing Fixtures.
402.3.1.1 The following standards shall be adopted as plumbing
materials, performance standards, and labeling standards for
water closets and urinals. Water closets and urinals shall meet
either the ANSI/ASME standards or the CSA standard.
ANSI/ASME A112.19.2M-1998 | Vitreous China Plumbing Fixtures |
ANSI/ASME A112.19.6-1995 | Hydraulic Requirements for Water Closets and Urinals |
CSA B45 | CSA Standards on Plumbing Fixtures |
Tank-type toilets | 1.6 gpf/6.0 lpf |
Flushometer-valve toilets | 1.6 gpf/6.0 lpf |
Flushometer-tank toilets | 1.6 gpf/6.0 lpf |
Electromechanical hydraulic toilets | 1.6 gpf/6.0 lpf |
EXCEPTIONS: | 1. Water closets located in day care centers, intended for use by young children may have a maximum water use of 3.5 gallons per flush or 13.25 liters per flush. |
2. Water closets with bed pan washers may have a maximum water use of 3.5 gallons per flush or 13.25 liters per flush. | |
3. Blow out bowls, as defined in ANSI/ASME A112.19.2M, Section 5.1.2.3 may have a maximum water use of 3.5 gallons per flush or 13.25 liters per flush. |
402.3.1.4 No urinal or water closet that operates on a continuous
flow or continuous flush basis shall be permitted.
402.3.1.5 This section does not apply to fixtures installed
before the effective date of this Section, that are removed and
relocated to another room or area of the same building after the
effective date of this Section.
402.3.2 Standards for Plumbing Fixture Fittings.
402.3.2.1 The following standards are adopted as plumbing
material, performance requirements, and labeling standards for
plumbing fixture fittings. Faucets, aerators, and shower heads
shall meet either the ANSI/ASME standard or the CSA standard.
ANSI/ASME A112.18.1M-1996 | Plumbing Fixture Fittings |
CSA B125 | Plumbing Fittings |
EXCEPTION: | Emergency use showers shall be exempt from the maximum water usage rates. |
Lavatory faucets | 2.5 gpm/9.5 lpm |
Kitchen faucets | 2.5 gpm/9.5 lpm |
Replacement aerators | 2.5 gpm/9.5 lpm |
Public lavatory faucets other than metering | 0.5 gpm/1.9 lpm |
EXCEPTIONS: | 1. Where designed and installed for use by persons with a disability. |
2. Where installed in day care centers, for use primarily by children under 6 years of age. |
402.5.1 The standards for water efficiency and labeling contained
within Section 402.3 shall be in effect as of July 1, 1993, as
provided in RCW 19.27.170 and amended July 1, 1998.
402.5.2 No individual, public or private corporation, firm,
political subdivision, government agency, or other legal entity,
may, for purposes of use in the state of Washington, distribute,
sell, offer for sale, import, install, or approve for
installation any plumbing fixtures or fittings unless the
fixtures or fittings meet the standards as provided for in this
Section.
Sections 402.6 through 402.9 are not adopted.
412.2 Location of Floor Drains. Floor drains shall be installed
in the following areas:
412.2.1 Toilet rooms containing two (2) or more water closets or
a combination of one (1) water closet and one (1) urinal, except
in a dwelling unit. The floor shall slope toward the floor
drains.
412.2.2 Laundry rooms in commercial buildings and common laundry
facilities in multi-family dwelling buildings.
413.0 Minimum Number of Required Fixtures. For minimum number of
plumbing fixtures required, see Building Code Chapter 29 and
Table 29-A.
Sections 413.1 through 413.7 and Table 4-1 are not adopted.
[]
501.0 General. The regulations of this chapter shall govern the
construction, location, and installation of fuel burning and
other water heaters heating potable water. The minimum capacity
for water heaters shall be in accordance with the first hour
rating listed in Table 5-1. See the Mechanical Code for
combustion air and installation of all vents and their
connectors. All design, construction, and workmanship shall be
in conformity with accepted engineering practices, manufacturer's
installation instructions, and applicable standards and shall be
of such character as to secure the results sought to be obtained
by this Code. No water heater shall be hereinafter installed
which does not comply in all respects with the type and model of
each size thereof approved by the administrative authority. A
list of accepted gas equipment standards is included in Table
14-1.
Water heaters used for space heating only are prohibited.
TABLE 5-11,3
Number of Bathrooms | 1 to 1.5 | 2 to 2.5 | 3 to 3.5 | ||||||||
Number of Bedrooms | 1 | 2 | 3 | 2 | 3 | 4 | 5 | 3 | 4 | 5 | 6 |
First Hour Rating2, Gallons | 42 | 54 | 54 | 54 | 67 | 67 | 80 | 67 | 80 | 80 | 80 |
Notes: | 1The first hour rating is found on the "Energy Guide" label. |
2Nonstorage and solar water heaters shall be sized to meet the appropriate first hour rating as shown in the table. | |
3For replacement water heaters, see Section 101.4.1.1.1. |
502.2 Chimney Connector – Delete definition.
502.5 Direct Vent Appliance – Delete definition.
502.7 Unusually Tight Construction – Delete definition.
502.8 Vent – Delete definition.
502.9 Vent Collar – Delete definition
502.10 Vent Connector – Delete definition.
502.11 Venting System – Delete definition.
502.12 Venting Systems-Types – Delete definition.
504.1 Inspection of Chimneys or Vents. Delete paragraph.
505.0 Gas-Fired Water Heater Approval Requirements.
505.1 Gas fired water heaters shall conform to approved
recognized applicable standards or to other standards acceptable
to the administrative authority. Each such water heater shall
bear the label of an approved testing agency, certifying and
attesting that such equipment has been tested and inspected and
meets the requirements of applicable standards.
505.2 Except when reconditioned by the manufacturer or the
manufacturer's approved agent in accordance with its original
approval requirements and reinstalled at its original location,
each reconditioned water heater shall be tested for safety and
conformity to approved standards, and shall bear the label of an
approved testing agency certifying and attesting that such
equipment has been tested and inspected and meets the
requirements of applicable standards. Such label shall also
state clearly that the water heater has been reconditioned, and
shall give the name and address of the reconditioner. Every
person applying for a permit to install a used or reconditioned
water heater shall clearly state on the application for permit
that such equipment is used or reconditioned.
505.3 Gas storage-type water heaters shall be provided with, in
addition to the primary temperature controls, an over-temperature
safety protection device constructed, listed, and installed in
accordance with nationally recognized applicable standards for
such devices and a combination temperature and pressure relief
valve.
506.2 All storage-type water heaters deriving heat from fuels or
types of energy other than gas, shall be provided with, in
addition to the primary temperature controls, an over-temperature
safety protection device constructed, listed, and installed in
accordance with nationally recognized applicable standards for
such devices and a combination temperature and pressure relief
valve.
507.0 Combustion Air. For issues relating to combustion air, see
the Mechanical Code.
Sections 507.1 through 507.5 are not adopted.
509.0 Prohibited Locations. Water heaters which depend on the combustion of fuel for heat shall not be installed in a room used or designed to be used for sleeping purposes, bathroom, clothes closets or in a closet or other confined space opening into a bath or bedroom.
EXCEPTIONS: | 1. Direct vent water heaters. |
2. Water heaters installed in a closet that has a weather-stripped solid door with an approved door closing device, and designed exclusively for the water heater and where all air for combustion and ventilation is supplied from the outdoors. | |
3. Water heaters of the automatic storage type installed as a replacement in a bathroom, when specifically approved, properly vented and supplied with adequate combustion air. |
512.0 Venting of Water Heaters Delete entire section.
513.0 Limitations. Delete entire section.
514.0 Vent Connectors. Delete entire section.
515.0 Location and Support of Venting System. Delete entire
section.
516.0 Length Pitch and Clearance. Delete entire section.
517.0 Vent Termination. Delete entire section.
518.0 Area of Venting System. Delete entire section.
519.0 Multiple Appliance Venting. Delete entire section.
520.0 Existing Venting System. Delete entire section.
521.0 Draft Hoods. Delete entire section.
522.0 Gas Venting into Existing Masonry Chimneys. Delete entire
section.
523.0 Chimney Connectors. Delete entire section.
524.0 Mechanical Draft Systems. Delete entire section.
525.0 Venting Through Ventilating Hoods and Exhaust Systems.
Delete entire section.
[]
603.0 Cross-Connection Control. Cross-connection control shall
be provided in accordance with the provisions of this chapter.
Devices or assemblies for protection of the public water system
must be models approved by the department of health under WAC 246-290-490. The administrative authority shall coordinate with
the local water purveyor where applicable in all matters
concerning cross-connection control within the property lines of
the premises.
No person shall install any water operated equipment or mechanism, or use any water treating chemical or substance, if it is found that such equipment, mechanism, chemical or substance may cause pollution or contamination of the domestic water supply. Such equipment or mechanism may be permitted only when equipped with an approved backflow prevention device or assembly.
603.3.3 For devices and assemblies other than those regulated by
the Washington department of health in conjunction with the local
water purveyor for the protection of public water systems, the
administrative authority shall ensure that the premise owner or
responsible person shall have the backflow prevention assembly
tested by a Washington state department of health certified
backflow assembly tester:
(1) At the time of installation, repair or relocation; and
(2) At least on an annual schedule thereafter, unless more frequent testing is required by the administrative authority.
603.4.6.1 Potable water supplies to systems having no pumps or
connections for pumping equipment, and no chemical injection or
provisions for chemical injection, shall be protected from
backflow by one of the following devices:
(1) Atmospheric vacuum breaker.
(2) Pressure vacuum breaker.
(3) Reduced pressure backflow preventer.
(4) A double check valve may be allowed when approved by the water purveyor and the administrative authority.
(5) A spill proof pressure vacuum breaker may be allowed when approved by the water purveyor and the administrative authority.
603.4.13 Potable Water Supply to Carbonators shall be protected
by a listed reduced pressure principle backflow preventer as
approved by the administrative authority for the specific use.
603.4.18.1 Except as provided under Sections 603.4.18.2 and
603.4.18.3, potable water supplies to fire protection systems
that are normally under pressure, including but not limited to
standpipes and automatic sprinkler systems, except in one or two
family residential flow-through or combination sprinkler systems
piped in materials approved for potable water distribution
systems, shall be protected from back-pressure and back-siphonage
by one of the following testable devices:
1. Double check valve assembly.
2. Double check detector assembly.
3. Reduced pressure backflow preventer.
4. Reduced pressure detector assembly.
Potable water supplies to fire protection systems that are not
normally under pressure shall be protected from backflow and
shall meet the requirements of the appropriate standard(s)
referenced in Table 14-1.
604.1 Water distribution pipe, building supply water pipe and
fittings shall be of brass, copper, cast iron, galvanized
malleable iron, galvanized wrought iron, galvanized steel or
other approved materials. Except as provided in Section 604.13,
asbestos-cement, CPVC, PE, PVC, or PEX water pipe materials
manufactured to recognized standards may be used for cold water
distribution systems outside a building. CPVC, PEX water pipe,
tubing, and fittings, manufactured to recognized standards may be
used for hot and cold water distribution systems within a
building. Other products not listed in this section are
acceptable for their intended use, provided that such materials
or distribution systems are listed and approved in accordance
with nationally recognized standards. All materials used in the
water supply system, except valves and similar devices shall be
of like material, except where otherwise approved by the
administrative authority.
604.13 Plastic water service piping may terminate within a
building, provided the connection to the potable water
distribution system shall be made as near as is practical to the
point of entry and shall be accessible. Barbed insert fittings
with hose clamps are prohibited as a transition fitting within
the building.
608.5 Relief valves located inside a building shall be provided
with a drain, not smaller than the relief valve outlet, of
galvanized steel, hard drawn copper piping and fittings, CPVC, or
listed relief valve drain tube with fittings which will not
reduce the internal bore of the pipe or tubing (straight lengths
as opposed to coils) and shall extend from the valve to the
outside of the building with the end of the pipe not more than
two (2) feet (610 mm) nor less than six (6) inches (152 mm) above
the ground or the flood level of the area receiving the discharge
and pointing downward. Such drains may terminate at other
approved locations. No part of such drain pipe shall be trapped
or subject to freezing. The terminal end of the drain pipe shall
not be threaded.
EXCEPTION: | Replacement water heating equipment shall only be required to provide a drain pointing downward from the relief valve to extend between two feet (610 mm) and six inches (152 mm) from the floor. No additional floor drain need be provided. |
Listed parallel water distribution systems shall be installed in accordance with their listing.
[]
701.1.2 ABS and PVC DWV piping installations shall be installed
in accordance with IS 5, IS 9, and Appendix M "Firestop
Protection for DWV and Stormwater Application." Except for
individual single family dwelling units, materials exposed within
ducts or plenums shall have a flame-spread index of not more than
25 and a smoke developed index of not more than 50, when tested
in accordance with the Test for Surface-Burning Characteristics
of the Building Materials (See the Building Code standards based
on ASTM E-84 and ANSI/UL 723).
704.3 Delete entire section.
710.3 The minimum size of any pump or any discharge pipe from a
sump having a water closet connected thereto shall be not less
than two (2) inches (52 mm).
Sections 710.3.1 through 710.3.3 are not adopted.
CHAPTER 7, PART II -- BUILDING SEWERS
Part II Building Sewers. Delete all of Part II (Sections 713
through 723, and Tables 7-7 and 7-8).
[]
810.4 Strainers. Every indirect waste interceptor receiving
discharge containing particles that would clog the receptor drain
shall have a readily removable dome strainer.
[]
903.1.2 ABS and PVC DWV piping installations shall be installed
in accordance with IS 5, IS 9, and Appendix M "Firestop
Protection for DWV and Stormwater Application." Except for
individual single family dwelling units, materials exposed within
ducts or plenums shall have a flame-spread index of not more than
25 and a smoke developed index of not more than 50, when tested
in accordance with the Test for Surface-Burning Characteristics
of the Building Materials (see the Building Code standards based
on ASTM E-84 and ANSI/UL 723).
[]
1302 Medical Gas and Vacuum Piping Systems.
The installation of medical gas and vacuum piping systems shall be in accordance with the requirements of this chapter and/or the appropriate standards adopted by the administrative authority, for additional standards see Table 14-1. The administrative authority shall require evidence of the competency of the installers.
Part II Medical Gas and Vacuum Systems
1309.0 Scope.
1309.1 The provisions herein shall apply to the design,
installation, testing, and verification of medical gas, medical
vacuum systems, and related permanent equipment for safe use in
patient care hospitals, clinics, and other heath care facilities.
1309.2 The purpose of this chapter is to provide minimum
requirements for the design, installation and verification of
medical gas, medical vacuum systems, and related permanent
equipment
1310.0 Definitions.
1310.1 Building Supply – The pipe from the source of supply to a
building or structure.
1310.2 Critical Care Area – An area in a medical facility where
special care is provided, including intensive care units,
coronary care units, recovery rooms, and respiratory care units.
1310.3 Installer Performance Testing – Testing conducted by the
installer or representative prior to system verification using
oil-free, dry nitrogen as stated in Chapter 14.
1310.4 Manifold – A device for connecting outlets of one or more
gas cylinders to the central piping system for that specific gas.
1310.5 Medical Air – Compressed air used in a medical facility.
1310.6 Medical Gas – Gases used in a medical facility, including
oxygen, nitrous oxide, nitrogen, carbon dioxide, helium, medical
air, and mixtures of these gases. Standards of purity apply.
1310.7 Medical Gas System – A system consisting of a central
supply system (manifold, bulk, or compressors), including control
equipment and piping extending to station outlets in the facility
where medical gases may be required.
1310.8 Medical Vacuum System – A system consisting of central
vacuum-producing equipment with vacuum switches and operating
controls, shutoff valves, alarm warning systems, gauges, and a
network of piping extending to and terminating with station
inlets at locations where patient suction may be required.
Includes surgical vacuum systems, waste anesthesia gas disposal
(as scavenging systems), and bedside suction systems.
1310.9 Purge, Flow – The removal of oxygen from a system by
oil-free dry nitrogen during brazing.
1310.10 Purge, System – The removal of nitrogen from a system
with the medical gas required for that system.
1310.11 SCFM – Standard cubic feet per minute, the unit measure
for a volume of gas at standard conditions (68 degrees F (20
degrees C) and 1 atmosphere of pressure).
1310.12 Special Hazard Area – An area, such as a kitchen or
electrical switch gear room.
1310.13 Station Inlet – An inlet in a vacuum piping system at
which the user makes connections and disconnections.
1310.14 Station Outlet – An outlet point in a medical gas piping
system at which the user makes connections and disconnections.
1310.15 System Verification – Testing conducted by a qualified
party other than the installer or material vendor after the
installer performance testing and prior to the medical gas system
being put into service.
1310.16 Use Point – A room or area within a room, where medical
gases are dispensed to a patient for medical purposes.
1310.17 User Outlet – See station outlet.
1310.18 Valve, Isolation – A valve which isolates one piece of
equipment from another.
1310.19 Valve, Riser – A valve at the base of a vertical riser,
which isolates that riser.
1310.20 Valve, Service – A valve serving horizontal piping
extending from a riser to a station outlet or inlet.
1310.21 Valve, Source – A single valve at the source which
controls a number of units that make up the total source.
1310.22 Valve, Zone – A valve which controls the gas or vacuum to
a particular area.
1311.3 The administrative authority shall require evidence of the
competency of the installers.
1311.4 Delete paragraph.
1313.0 System Installation and Installer Performance Testing.
1313.1 Medical gas and medical vacuum systems shall be designed
and installed in accordance with the requirements of this chapter
and the installation requirements of this code, specifically
Chapter 14 of this code.
1313.2 A report of completion of the installer performance
testing which includes the specific items in Chapter 14 shall be
furnished to the administrative authority prior to system
verification.
1314.0 System Verification.
1314.1 Prior to any medical gas system being placed in service,
each and every system shall be verified as described in Chapter
14. This verification shall be accomplished by an independent
third party verification agency which is approved by the
administrative authority.
1314.2 A report which includes at least the specific items in
Chapter 14 shall be furnished to the administrative authority
prior to final acceptance of the system.
Sections 1315 through 1331 are not adopted.
[]
TABLE 14-1
Standards for Materials, Equipment, Joints and Connections
Where more than one standard has been listed for the same material or method, the relevant portions of all such
standards shall apply.
Standard Number | Standard Title | Application | Indicate if Not Approved in the UPC |
AHAM DW-1-92 | Household Electric Dishwashers | Appliances | |
AHAM DW-2PR-86 | Plumbing Requirements for Household Dishwashers | Appliances | |
AHAM FWD-1-83 | Food Waste Disposers | Appliances | |
AHAM HLW-2 PR-86 | Plumbing Requirements for Home Laundry Equipment Appliances | ||
ANSI A13.1-81(R93) | Scheme for the Identification of Piping Systems Piping | ||
ANSI A21.10-93 | Ductile-Iron and Gray-Iron Fittings, 3 in. Through 48 in. (75 mm Through 1200 mm), for Water and Other Liquids (same as AWWA C110) | Piping, Ferrous | |
ANSI A21.11-90 | Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings (same as AWWA C111) | Piping, Ferrous | |
ANSI A21.51-91 | Ductile-Iron Pipe, Centrifugally Cast, for Water (same as AWWA C151) | Piping, Ferrous | |
ANSI A21.53-88 | Ductile-Iron Compact Fittings, 3 in. Through 24 in. (76 mm Through 610 mm) and 54 in. Through 64 in. (1,400 mm Through 1,600 mm), for Water Service (same as AWWA C153) | Piping, Ferrous | |
ANSI A40.3-93 | Stainless steel | Piping, Ferrous | |
ANSI A106.6-70 | Vitrified Clay Pipe (now CSA A60.1M1976(C1992)) | Piping, Nonmetallic | |
ANSI A106.6-77 | Silver brazing joints for wrought and cast bronze solder joint fittings | Joints | |
ANSI A112.14.1-75 (R90) | Backwater Valves | Valves | |
ANSI A112.19.5-79 | Trim for Water-Closet Bowls, Tanks and Urinals | Fixtures | |
ANSI A112.21.2M-83 | Roof Drains | DWV Components | |
ANSI A118.10-93 | Load Bearing, Bonded, Waterproof Membranes for Thin-Set Ceramic Tile and Dimension Stone Installations | Fixtures | |
ANSI B2.1-90 | Pipe Threads (Except Dryseal) (replaced by ASME B1.20.1-98) | Joints | |
ANSI B125.1-84 | Steel pipe (galvanized) | Piping, Ferrous | |
ANSI B125.2-72 | Steel pipe (galvanized) | Piping, Ferrous | |
ANSI Z21.10.1a-94 | Gas Water Heaters - Volume I –Storage Water Heaters with Input Ratings of 75,000 BTU per Hour or Less (22 kW) | Appliances | |
ANSI Z21.10.1b-92 | Gas Water Heaters - Volume I –Storage Water Heaters with Input Ratings of 75,000 BTU per Hour or Less (22 kW) | Appliances | |
ANSI Z21.10.3-90 | Gas Water Heaters - Volume III – Storage, with Input Ratings Above 75,000 Btu per Hour, Circulating and Instantaneous Water Heaters | Appliances | |
ANSI Z21.10.3a-94 | " | Appliances | |
ANSI Z21.10.3b-92 | " | Appliances | |
ANSI Z21.12-90 | Draft Hoods | Appliances | |
ANSI Z21.13-91 | Gas-Fired Low-Pressure Steam and Hot Water Boilers and Addenda | Appliances | |
ANSI Z21.15-92 | Manually Operated Gas Valves for Appliances, Appliance Connector Valves and Hose End Valves | Valves | |
ANSI Z21.22a-90 | Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems | Valves | |
ANSI Z21.24-93 | Metal Connectors for Gas Appliances | Appliances | |
ANSI Z21.41-89 | Quick-Disconnect Devices for Use with Gas Fuel | Joints | |
ANSI Z21.56-98 | Gas Fired Pool Heaters | Swimming Pools and Spas | |
ANSI Z21.69-1997•CSA 6.16-M97 | Connectors for Moveable Gas Appliances | Appliances | |
ANSI Z21.70-81 | Earthquake Actuated Automatic Gas Shutoff Systems (withdrawn from ANSI June, 1992) | Valves | |
ANSI Z21.80-1997•CSA 6.22-M97 | Line Pressure Regulators | Fuel Gas | |
ANSI Z21.81-1997•CSA 6.25-M97 | Cylinder Connection Devices | Fuel Gas | |
ANSI Z21.86•CSA 2.32-M98 | Vented Gas-Fired Space Heating Appliances | Appliances | |
ANSI Z34.1-93 | Certification - Third Party Certification Programs for Products, Processes, and Services | Certification | |
ANSI Z124.1-95 | Plastic Bathtub Units | Fixtures | |
ANSI Z124.2-95 | Plastic Shower Receptors and Shower Stalls | Fixtures | |
ANSI Z124.3-95 | Plastic Lavatories | Fixtures | |
ANSI Z124.4-96 | Plastic Water Closet Bowls and Tanks | Fixtures | |
ANSI Z124.5-97 | Plastic Toilet (Water Closet) Seats | Fixtures | |
ANSI Z124.6-97 | Plastic Sinks | Fixtures | |
ANSI Z124.7-97 | Prefabricated Plastic Spa Shells | Fixtures | |
ANSI Z124.8-90 | Plastic Bathtub Liners | Fixtures | |
ANSI Z124.9-94 | Plastic Urinal Fixtures (Note 1) | Fixtures | |
ANSI Z223.1-99 | National Fuel Gas Code | Fuel Gas | |
ARI 1010-84 | Drinking-Fountains and Self-Contained, Mechanically-Refrigerated Drinking Water Coolers | Appliances | |
ASHRAE 90.1-89 | Energy Efficient Design of New Buildings Except Low-Rise Residential Buildings | Miscellaneous | |
ASME A112.1.2-96 | Air Gaps in Plumbing Systems | Piping | |
ASME A112.3.1-93 | Stainless Steel Drainage Systems for Sanitary Storm and Chemical Application, Above and Below Ground (Note 1) | Piping, Ferrous | X |
ASME A112.4.1-93 | Water Heater Relief Valve Drain Tubes | Appliances | |
ASME A112.6.1M-97 | Floor-Affixed Supports for Off-the-Floor Plumbing Fixtures for Public Use | Fixtures | |
ASME A112.18.1M-96 | Plumbing Fixture Fittings | Valves | |
ASME A112.18.6-99 | Flexible Water Connectors | Piping | |
ASME A112.18.3-96 | Performance Requirements for Backflow Protection Devices and Systems in Plumbing Fixture Fittings (Note 8) | Valves | |
ASME A112.19.1M-94 | Enameled Cast Iron Plumbing Fixtures (Supplement 1-1998) | Fixtures | |
ASME A112.19.2M-98 | Vitreous China Plumbing Fixtures | Fixtures | |
ASME A112.19.3M-87 | Stainless Steel Plumbing Fixtures (Designed for Residential Use) | Fixtures | |
ASME A112.19.4M-94 | Porcelain Enameled Formed Steel Plumbing Fixtures (Supplement 1-1998) | Fixtures | |
ASME A112.19.6-95 | Hydraulic Performance Requirements for Water Closets and Urinals | Fixtures | |
ASME A112.19.7M-95 | Whirlpool Bathtub Appliances | Fixtures | |
ASME A112.19.8M-87 | Suction Fittings for Use in Swimming Pools, Wading Pools, Spas, Hot Tubs, and Whirlpool Bathtub Appliances | Swimming Pools and Spas | |
ASME A112.19.9M-91 | Nonvitreous Ceramic Plumbing Fixtures | Fixtures | |
ASME A112.21.1M-91 | Floor Drains (Note 1) | DWV Components | |
ASME A112.21.3M-85 | Hydrants for Utility and Maintenance Use (Note 1) | Valves | |
ASME A112.26.1M-84 | Water Hammer Arresters | Piping | |
ASME A112.36.2M-91 | Cleanouts (Note 1) | DWV Components | |
ASME B1.20.1-83 (R1992) | Pipe Threads, General Purpose (Inch) | Joints | |
ASME B1.20.3-76 (R82/91/98) | Dryseal Pipe Threads, Inch | Joints | |
ASME B16.1-89 | Cast Iron Pipe Flanges and Flanged Fittings, Class 25, 125, 250, and 800 | Piping, Ferrous | |
ASME B16.3-92 | Malleable-Iron Threaded Fittings | Piping, Ferrous | |
ASME B16.4-92 | Gray Iron Threaded Fittings (includes Revision Services) | Piping, Ferrous | |
ASME B16.5-88 | Pipe Flanges and Flanged Fittings | Joints | |
ASME B16.12-91 | Iron Threaded Drainage Fittings (Note 1) | Piping, Ferrous | |
ASME B16.15-85 (R1994) | Cast Bronze Threaded Fittings, Classes 125 and 250 | Piping, Copper Alloy | |
ASME B16.18-84 | Cast Copper Alloy Solder Joint Pressure Fittings (Note 1) | Piping, Copper Alloy | |
ASME B16.21-92 | Nonmetallic Flat Gaskets for Pipe Flanges | Joints | |
ASME B16.22-95 | Wrought Copper and Copper Alloy Solder-Joint Pressure Fittings Alloy | Piping, Copper | |
ASME B16.23-92 | Cast Copper Alloy Solder Joint Drainage Fittings - DWV Alloy | Piping, Copper | |
ASME B16.24-91 | Cast Copper Alloy Pipe Flanges and Flanged Fittings Alloy | Piping, Copper | |
ASME B16.26-88 | Cast copper alloy fittings for flared copper tubes Alloy | Piping, Copper | |
ASME B16.29-86 | Wrought Copper and Wrought Copper Alloy Solder Joint Drainage Fittings-DWV Alloy (Note 1) | Piping, Copper | |
ASME B16.32-92 | Cast Copper Alloy Solder Joint Fittings for Solvent Drainage Systems Alloy | Piping, Copper | |
ASME B16.33-90 | Manually Operated Metallic Gas Valves for Use in Gas Piping Systems up to 125 psig. | Valves | |
ASME B16.34-88 | Valves – Flanged, Threaded and Welding End | Valves | |
ASME B16.38-85 | Large Metallic Valves for Gas Distribution (Manually Operated, NPS 2-1/2 to 12, 125 psig Maximum) | Valves | |
ASME B16.39-86 | Pipe Unions, Malleable Iron Threaded (Includes Revision (R1994) Services) | Piping, Ferrous | |
ASME B16.47-90 | Large Diameter Steel Flanges | Piping, Ferrous | |
ASME B36.10M-85 | Welded and Seamless Wrought Steel Pipe | Piping, Ferrous | |
ASME Section IX | Welding and Brazing Procedures, Welders, Brazers, and Welding and Brazing Operators | Certification | |
ASSE 1001-90 | Pipe Applied Atmospheric-Type Vacuum Breakers | Backflow Protection | |
ASSE 1002-86 | Water Closet Flush Tank Ballcocks | Backflow Protection | |
ASSE 1003-95 | Water Pressure Reducing Valves for Domestic Water Supply Systems | Valves | |
ASSE 1004-90 | Backflow Prevention Requirements for Commercial Dishwashing Machines | Backflow Protection | |
ASSE 1006-89 | Residential Use Dishwashers | Appliances | |
ASSE 1007-92 | Home Laundry Equipment | Appliances | |
ASSE 1008-89 | Household Food Waste Disposer Units | Appliances | |
ASSE 1009-90 | Commercial Food Waste Grinder Units | Appliances | |
ASSE 1010-98 | Performance Requirements for Water Hammer Arrestors | Piping | |
ASSE 1011-95 | Hose-Connection Vacuum Breakers | Backflow Protection | |
ASSE 1013-93 | Reduced Pressure Principle Backflow Preventers | Backflow Protection | |
ASSE 1014-90 | Hand-Held Showers | Fixtures | |
ASSE 1015-93 | Double Check Backflow Prevention Assembly | Backflow Protection | |
ASSE 1016-96 | Individual, Thermostatic Pressure Balancing and Thermostatic Control Valves for Individual Fixtures | Valves | |
ASSE 1017-86 | Thermostatic Mixing Valves, Self Actuated for Primary Domestic Use | Valves | |
ASSE 1018-86 | Trap Seal Primer Valves (water supply fed) | Valves | |
ASSE 1019-95 | Performance Requirements for Vacuum Breaker Wall Hydrant, Freeze Resistant Automatic Draining Type | Backflow Protection | |
ASSE 1020-90 | Pressure Vacuum Breaker Assembly | Backflow Protection | |
ASSE 1021-77 | Dishwasher Air Gaps for Domestic Dishwasher Applications | Backflow Protection | |
ASSE 1023-79 | Hot Water Dispensers Household Storage Type Electrical | Appliances | |
ASSE 1025-78 | Diverters for Plumbing Faucets with Hose Spray, Anti-Siphon Type, Residential Applications | Valves | |
ASSE 1028-81 | Automatic Flow Controllers | Valves | |
ASSE 1032-80 | Dual Check Valve Type Backflow Preventers for Carbonated Beverage Dispensers - Post Mix Types | Backflow Protection | X |
ASSE 1034-81 | Fixed Flow Restrictors | Piping | |
ASSE 1035-95 | Laboratory Faucet Backflow Preventer | Backflow Protection | |
ASSE 1037-90 | Pressurized Flushing Devices (Flushometers) for Plumbing Fixtures | Backflow Protection | |
ASSE 1052-94 | Hose Connection Backflow Preventers | Backflow Protection | |
ASSE 1055-97 | Chemical Dispensing Systems | Backflow Protection | |
ASSE 1056-95 | Back Siphonage Backflow Vacuum Breakers | Backflow Protection | |
ASSE 1062-97 | Temperature Actuated, Flow Reduction Valves for Individual Fixture Fittings | Valves | |
ASSE 1066-97 | Individual Pressure Balancing In-Line Valves for Individual Fixture Fittings (Note 9) | Valves | |
ASSE 6000-98 | Medical Gas Systems Installers, Inspectors and Verifiers | Certification | |
ASTM A 47-90 (R95) | Ferritic Malleable Iron Castings | Piping, Ferrous | |
ASTM A 53-96 (97) | Pipe, Steel, Black and Hot-Dipped, Zinc-Coated Welded, and Seamless | Piping, Ferrous | |
ASTM A 74-98 | Cast Iron Soil Pipe and Fittings (Note 1) | Piping, Ferrous | |
ASTM A 120-84 [D] | Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, (Galvanized) Welded, and Seamless for Ordinary Uses (replaced by A 53) | Piping, Ferrous | |
ASTM A 126-95 | Gray Iron Castings for Valves, Flanges, and Pipe Fittings | Piping, Ferrous | |
ASTM A 197-87 (R-92) | Cupola Malleable Iron [Metric] | Piping, Ferrous | |
ASTM A 312-93 | Seamless and Welded Austenitic Stainless Steel Pipes | Piping, Ferrous | |
ASTM A 377-95 | Ductile-Iron Pressure Pipe | Piping, Ferrous | |
ASTM A 518-92e1 | Corrosion-Resistant High-Silicon Iron Castings [Metric] | Piping, Ferrous | |
ASTM A 536-84(R-93) | Ductile Iron Castings | Piping, Ferrous | |
ASTM A 653-96 | Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process | Piping, Ferrous | |
ASTM A 733-93 | Welded and Seamless Carbon Steel and Austenitic Stainless Steel Pipe Nipples | Piping, Ferrous | |
ASTM A 861-94e1 | High-Silicon Iron Pipe and Fittings (Note 1) | Piping, Ferrous | |
ASTM B 29-92 | Pig Lead | Joints | |
ASTM B 32-96 | Solder Metal (Note 4) | Joints | |
ASTM B 42-96 | Seamless Copper Pipe, Standards Sizes | Piping, Copper Alloy | |
ASTM B 43-96 | Seamless Red Brass Pipe, Standards Sizes | Piping, Copper Alloy | |
ASTM B 75-95a | Seamless Copper Tube | Piping, Copper Alloy | |
ASTM B 88-96 | Seamless Copper Water Tube | Piping, Copper Alloy | |
ASTM B 135-96 | Seamless Brass Tube | Piping, Copper Alloy | |
ASTM B 152-97 | Copper Sheet, Strip, Plate, and Rolled Bar | Miscellaneous | |
ASTM B 251-97 | General Requirements for Wrought Seamless Copper Copper-Alloy Tube | Piping, Copper Alloy | |
ASTM B 280-95a | Seamless Copper Tube for Air Conditioning and Refrigeration Field Service | Piping, Copper Alloy | |
ASTM B 302-97 | Threadless Copper Pipe | Piping, Copper Alloy | |
ASTM B 306-96 | Copper Drainage Tube (DWV) | Piping, Copper Alloy | |
ASTM B 370-92e1 | Copper Sheet and Strip for Building Construction | Miscellaneous | |
ASTM B 447-97 | Welded Copper Tube | Piping, Copper Alloy | |
ASTM B 584-96 | Copper Alloy Sand Casting for General Applications (Note 5) | Piping, Copper Alloy | |
ASTM B 587-96 | Welded Brass Tube | Piping, Copper Alloy | |
ASTM B 641-93 | Seamless and Welded Copper Distribution Tube (Type D) | Piping, Copper Alloy | |
ASTM B 642-88 [D] | Welded Copper Alloy UNS C21000 Water Tube (discontinued 1994) | Piping, Copper Alloy | |
ASTM B 687-96 | Brass, Copper, and Chromium-Plated Pipe Nipples | Piping, Copper Alloy | |
ASTM B 716-93 [D] | Welded Copper Water Tube (discontinued 1994) | Piping, Copper Alloy | |
ASTM B 813-93 | Liquid and Paste Fluxes for Soldering Applications of Copper and Copper Alloy Tube | Joints | |
ASTM B 819-95 | Seamless Copper Tube for Medical Gas Systems | Piping, Copper Alloy | |
ASTM B 828-92e1 | Making Capillary Joints by Soldering of Copper and Copper Alloy Tube and Fittings | Joints | |
ASTM C 14-95 | Concrete Sewer, Storm Drain and Culvert Pipe | Piping, Nonmetallic | |
ASTM C 296-93 | Asbestos-Cement Pressure Pipe | Piping, Nonmetallic | |
ASTM C 412-94 | Concrete Drain Tile | Piping, Nonmetallic | |
ASTM C 425-96 | Compression Joints for Vitrified Clay Pipe and Fittings | Joints | |
ASTM C 428-92 | Asbestos-Cement Nonpressure Sewer Pipe (Notes 6 & 7) | Piping, Nonmetallic | |
ASTM C 443-94 | Joints for Circular Concrete Sewer and Culvert Pipe, Using Rubber Gaskets | Joints | |
ASTM C 478-96 | Precast Reinforced Concrete Manholes Sections | Miscellaneous | |
ASTM C 564-95a | Rubber Gaskets for Cast Iron Soil Pipe and Fittings (Note 1) | Joints | |
ASTM C 700-96 | Vitrified Clay Pipe, Extra Strength, Standard Strength, and Perforated | Piping, Nonmetallic | |
ASTM C 1053-90 (R95) | Borosilicate Glass Pipe and Fittings for Drain, Waste and Vent (DWV) Applications (Note 1) | Piping, Nonmetallic | |
ASTM C 1173-95 | Flexible Transition Couplings for Underground Piping Systems | Joints | |
ASTM C 1277-94 | Shielded Couplings Joining Hubless Cast Iron Soil Pipe and Fittings | Piping, Ferrous | |
ASTM D 396-97 | Specification for Fuel Oil | Miscellaneous | |
ASTM D 1527-96a | Acrylonitrile-Butadiene-Styrene (ABS) Plastic Pipe Sch. 40 and 80 | Piping, Plastic | |
ASTM D 1785-96ae1 | Poly (Vinyl Chloride) (PVC) Plastic Pipe Sch. 40, 80 and 120 | Piping, Plastic | |
ASTM D 1869-95 | Rubber O-rings for Asbestos-Cement Pipe | Joints | |
ASTM D 2104-95 | Polyethylene (PE) Plastic Pipe, Sch. 40 | Piping, Plastic | |
ASTM D 2146-82 [D] | Polypropylene Plastic Molding and Extrusion Materials (replaced by ASTM D 4101) | Piping, Plastic | |
ASTM D 2235-96a | Solvent cement for Acrylonitrile-Butadiene-Styrene (ABS) plastic pipe and fittings | Joints | |
ASTM D 2239-96a | Polyethylene (PE) Plastic Pipe, (SDR-PR) Based on Controlled Inside Diameter | Piping, Plastic | |
ASTM D 2241-96a | Poly(Vinyl Chloride) (PVC) Pressure-Rated pipe (SDR Series) | Piping, Plastic | |
ASTM D 2282-96a | Acrylonitrile-Butadiene-Styrene (ABS) Plastic Pipe (SDR-PR) | Piping, Plastic | |
ASTM D 2321-89 (R95) | Underground Installation of Thermoplastic Pipe for Sewers and Other Gravity-Flow Applications | Piping, Plastic | |
ASTM D 2447-95 | Polyethylene (PE) Plastic Pipe, Sch. 40 and 80 Based on Controlled Outside Diameter | Piping, Plastic | |
ASTM D 2464-96a | Threaded Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings, Sch. 80 (Note 1) | Piping, Plastic | |
ASTM D 2465-73[D] | Threaded Acrylonitrile-Butadiene-Styrene (ABS) Plastic Pipe Fittings, Schedule 80 (discontinued 1986) | Piping, Plastic | |
ASTM D 2466-96a | Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings, Sch. 40 (Note 1) | Piping, Plastic | |
ASTM D 2467-96a | Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings, Sch, 80 (Note 1) | Piping, Plastic | |
ASTM D 2468-96a | Acrylonitrile-Butadiene-Stryene (ABS) Plastic Pipe Fittings (Sch. 40) | Piping, Plastic | |
ASTM D 2469-76[D] | Socket-Type Acrylonitrile-Butadiene-Styrene (ABS) Plastic Pipe Fittings, Schedule 80 (discontinued 1986) | Piping, Plastic | |
ASTM D 2513-96a | Thermoplastic Gas Pressure Pipe Tubing, and Fittings (Note 1) | Piping, Plastic | |
ASTM D 2564-96a | Solvent Cements for Poly(Vinyl Chloride) (PVC) Plastic Piping Systems | Joints | |
ASTM D 2609-96a | Plastic Insert Fittings for Polyethylene (PE) Plastic Pipe (Note 1) | Piping, Plastic | |
ASTM D 2657-96 | Practice for Heating Fusion Joining of Polyolefin Pipe and Fittings | Joints | |
ASTM D 2661-96 | Acrylonitrile-Butadiene-Styrene (ABS) Sch. 40 Plastic Drain, Waste and Vent Pipe and Fittings (Note 1) | Piping, Plastic | |
ASTM D 2665-97a | Poly (Vinyl Chloride) (PVC) Plastic Drain, Waste and Vent Pipe and Fittings | Piping, Plastic | |
ASTM D 2672-96a | Joints for IPS PVC Pipe Using Solvent Cement | Joints | |
ASTM D 2680-95a | Acrylonitrile-Butadiene-Styrene (ABS) and Poly(Vinyl Chloride) (PVC) Composite Sewer Piping | Piping, Plastic | |
ASTM D 2729-96 | Poly (Vinyl Chloride) (PVC) Sewer Pipe and Fittings (Note 1) | Piping, Plastic | |
ASTM D 2737-96a | Polyethylene (PE) Plastic Tubing | Piping, Plastic | |
ASTM D 2740-89 e1 [D] | Poly (Vinyl Chloride) (PVC) Plastic Tubing (discontinued 1991) | Piping, Plastic | |
ASTM D 2751-96 | Acrylonitrile-Butadiene-Styrene (ABS) Sewer Pipe and Fittings (Note 1) | Piping, Plastic | |
ASTM D 2846-96a | Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Hot- and Cold-Water Distribution Systems | Piping, Plastic | |
ASTM D 2855-96 | Making Solvent-Cemented Joints with Poly(Vinyl Chloride) (PVC) Pipe and Fittings | Joints | |
ASTM D 2996-95 | Filament-Wound Fiberglass (Glass-Fiber-Reinforced Thermosetting Resin) pipe | Piping, Plastic | |
ASTM D 3033-85 [D] | Type PSP Poly (Vinyl Chloride) (PVC) Sewer Pipe and Fittings (discontinued 1989) | Piping, Plastic | |
ASTM D 3034-96 | Type PSM Poly(Vinyl Chloride) (PVC) Sewer Pipe and Fittings | Piping, Plastic | |
ASTM D 3036-73[D] | Poly (Vinyl Chloride) (PVC) Plastic Line Couplings (discontinued 1986) | Piping, Plastic | |
ASTM D 3065-94 | Rigid Acrylonitrile-Butadiene-Styrene (ABS) Materials for Pipe and Fittings | Piping, Plastic | |
ASTM D 3122-95 | Solvent Cements for Styrene-Rubber (SR) Plastic Pipe and Fittings | Joints | |
ASTM D 3139-96a | Joints for Plastic Pressure Pipes Using Flexible Elastomeric Seals | Joints | |
ASTM D 3140-90 | Flaring Polyolefin Pipe and Tubing | Joints | |
ASTM D 3212-96a | Joints for Drain and Sewer Plastic Pipes Using Flexible Elastomeric Seals | Joints | |
ASTM D 3298-81 [D] | Perforated Styrene-Rubber (SR) Plastic Drain Pipe (discontinued 1989) | Piping, Plastic | |
ASTM D 3311-94 | Drain, Waste, and Vent (DWV) Plastic Fittings Patterns (Note 1) | Piping, Plastic | |
ASTM D 3965-94 | Rigid Acrylonitrile-Butadiene-Styrene (ABS) Compounds for Pipe and Fittings | Piping, Plastic | |
ASTM D 4068-96 e1 | Chlorinated Polyethylene (CPE) Sheeting for Concealed Water-Containment Membrane | Fixtures | |
ASTM D 4101-96a | Propylene Plastic Injection and Extrusion Materials | Miscellaneous | |
ASTM D 4551-96 | Poly(Vinyl Chloride) (PVC) Plastic Flexible Concealed Water-Containment Membrane | Fixtures | |
ASTM E 84-97a | Standard Test Method for Surface Burning Characteristics of Building Materials | Miscellaneous | |
ASTM E 119-97 | Standard Test Method for Fire Tests of Building Construction and Materials | Miscellaneous | |
ASTM E 814-94b | Standard Test Method for Fire Tests of Through-Penetration Fire Stops | Miscellaneous | |
ASTM F 402-93 | Safe Handling of Solvent Cements, Primers, and Cleaners Used for Joining Thermoplastic Pipe and Fittings | Joints | |
ASTM F 405-96 | Corrugated polyethylene (PE) Tubing and Fittings | Piping, Plastic | |
ASTM F 409-96a | Thermoplastic Accessible and Replaceable Plastic Tube and Tubular Fittings (Note 1) | Piping, Plastic | |
ASTM F 437-96a | Threaded Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Pipe Fittings, Sch. 80 | Piping, Plastic | |
ASTM F 438-96a | Socket-Type Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Pipe Fittings, Sch. 40 | Piping, Plastic | |
ASTM F 439-96b | Socket-Type Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Pipe Fittings, Sch. 80 | Piping, Plastic | |
ASTM F 441-96b | Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Pipe, Sch. 40 and 80 | Piping, Plastic | |
ASTM F 442-96b | Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Pipe (SDR-PR) | Piping, Plastic | |
ASTM F 443-77 e1 [D] | Bell-End Chlorinated Poly (Vinyl Chloride) (CPVC) Pipe, Schedule 40 (discontinued 1987) | Piping, Plastic | |
ASTM F 480-95 | Thermoplastic Well Casing Pipe and Couplings Made in Standard Dimension Ratios (SDR) Schedule 40 and Schedule 80 | Piping, Plastic | |
ASTM F 493-97 | Solvent Cements for Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Pipe and Fittings | Joints | |
ASTM F 628-96 | Acrylonitrile-Butadiene-Styrene (ABS) Sch. 40 Plastic Drain, Waste and Vent Pipe with a Foam Core (Notes 1 & 3) | Piping, Plastic | |
ASTM F 656-96a | Primers for Use in Solvent Cement Joints of Poly(Vinyl Chloride) (PVC) Plastic Pipe and Fittings | Joints | |
ASTM F 667-95 | Large Diameter Corrugated Polyethylene Tubing and Fittings | Piping, Plastic | |
ASTM F 789-95a | Type PS-46 and type PS-115 Poly(Vinyl Chloride) (PVC) Plastic Gravity Flow Sewer Pipe and Fittings (Note 1) | Piping, Plastic | |
ASTM F 794-95a | Poly(Vinyl Chloride) (PVC) Profile Gravity Sewer Pipe and Fittings Based on Controlled Inside Diameter | Piping, Plastic | |
ASTM F 810-93 | Smoothwall Polyethylene (PE) Pipe for Use in Drainage and Waste Disposal Absorption Fields | Piping, Plastic | |
ASTM F 845-95 | Plastic Insert Fittings For Polybutylene (PB) Tubing | Piping, Plastic | X |
ASTM F 876-97 | Crosslinked Polyethylene (PEX) Tubing | Piping, Plastic | |
ASTM F 877-96a | Crosslinked Polyethylene (PEX) Plastic Hot- and Cold-Water Distribution Systems | Piping, Plastic | |
ASTM F 891-96 | Coextruded Poly(Vinyl Chloride) (PVC) Plastic Pipe with a Cellular Core | Piping, Plastic | |
ASTM F 949-96a | Poly(Vinyl Chloride) (PVC) Corrugated Sewer Pipe with a Smooth Interior and Fittings | Piping, Plastic | |
ASTM F 1216-93 | Rehabilitation of Existing Pipelines and Conduits by the Inversion and Curing of a Resin-Impregnated Tube | Piping, Plastic | |
ASTM F 1281-98 | Crosslinked Polyethylene/ Aluminum/ Crosslinked Polyethylene (PEX-Al-PEX) Pressure Pipe | Piping, Plastic | X |
ASTM F 1282-98 | Polyethylene/ Aluminum/ Polyethylene (PE-Al-PE) Composite Pressure Pipe | Piping, Plastic | X |
ASTM F 1412-96 | Polyolefin Pipe and Fittings for Corrosive Waste Drainage Systems | Piping, Plastic | |
ASTM F 1673-95 | Polyvinylidene Fluoride (PVDF) Corrosive Waste Drainage Systems | Piping, Plastic | |
ASTM F 1743-96 | Rehabilitation of Existing Pipelines and Conduits by Pulled-In-Place Installation of Cured-In-Place Thermosetting Resin Pipe (CIPP) | Piping, Plastic | |
ASTM F 1807-97 | Metal Insert Fittings w/ Copper Crimp Ring for SDR 9 Crosslinked Polyethylene (PEX) tubing | Piping, Plastic | |
ASTM F 1866-98 | Poly (Vinyl Chloride) PVC Schedule 40 Drainage and DWV Fabricated Fittings | Piping, Plastic | |
ASTM F 1960-99 | Cold Expansion Fittings with PEX Reinforcing Rings for Use with Cross-linked Polyethylene (PEX) Tubing | Piping, Plastic | |
ASTM F 1961-99 | Metal Cold Flare Compression Fittings with Disk Springs for Cross Linked Polyethylene (PEX) Tubing | Piping, Plastic | |
ASTM F 1974-99 | Metal Insert Fittings for Polyethylene/Aluminum/Polyethylene and Crosslinked Polyethylene/Aluminum/Crosslinked Polyethylene Composite Pressure Pipe | Piping, Plastic | |
AWS A5.8-92 | Filler Metals for Brazing and Braze Welding Joints AWS B2.2-91 Brazing Procedure and Performance Qualification | Certification | |
AWS B2.2-91 | Brazing Procedure and Performance Qualification | Certification | |
AWWA C110 | Ductile-Iron and Gray-Iron Fittings, 3 in. Through 48 in. (75 mm Through 1200 mm), for Water and Other Liquids (same as ANSI A21.10-93) | Piping, Ferrous | |
AWWA C111 | Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings (same as ANSI A21.11-90) | Piping, Ferrous | |
AWWA C151 | Ductile-Iron Pipe, Centrifugally Cast, for Water (same as ANSI A21.51-91) | Piping, Ferrous | |
AWWA C153 | Ductile-Iron Compact Fittings, 3 in. Through 24 in. (76 mm Through 610 mm) and 54 in. Through 64 in. (1,400 mm Through 1,600 mm), for Water Service (same as ANSI A21.53-88) | Piping, Ferrous | |
AWWA C203-91 | Coal-Tar Protective Coatings and Linings for Steel Water Pipelines - Enameled and Tape - Hot Applied Piping AWWA C213-96 Fusion-Bonded Epoxy Coating for the Interior and Exterior of Steel Water Pipelines | Piping, Ferrous | |
AWWA C213-96 | Fusion-Bonded Epoxy Coating for the Interior and Exterior of Steel Water Pipelines | Piping, Ferrous | |
AWWA C215-94 | Extruded Polyolefin Coatings for the Exterior of Steel Water Pipelines | Piping, Ferrous | |
AWWA C400-93 | Asbestos-Cement Distribution Pipe, 4 in. Through 16 in. (100 mm Through 400 mm) for Water Distribution Systems | Piping, Nonmetallic | |
AWWA C500-93 | Metal-Seated Gate Valves for Water Supply Service | Valves | |
AWWA C504-88 | Rubber-Seated Butterfly Valves | Valves | |
AWWA C507-91 | Ball Valves, 6 in. Through 48 in. (152 mm Through 1200 mm) | Valves | |
AWWA C510-92 | Double Check Valve Backflow-Prevention Assembly | Backflow Protection | |
AWWA C511-92 | Reduced-Pressure Principle Backflow-Prevention Assemblies | Backflow Protection | |
AWWA C606-87 | Grooved and Shouldered Joints | Joints | |
AWWA C900-89 | Polyvinyl Chloride (PVC) Pressure Pipe, 4 in. Through 12 in., for Water Distribution | Piping, Plastic | |
AWWA C901-88 | Polyethylene (PE) Pressure Pipe and Tubing, 1/2 in. (13 mm) Through 3 in. (76 mm), for Water | Piping, Plastic | |
AWWA C902-88 | Polybutylene (PB) Pipe, Tubing, and Fittings, 1/2 in. Through 3 in., for Water | Piping, Plastic | X |
CABO A117.1-92 | Specifications to Make Buildings and Facilities Accessible and Usable | Miscellaneous | |
CISPI 301-97 | Hubless Cast Iron Soil Pipe and Fittings for Sanitary and Storm Drain, Waste, and Vent Piping Applications (Note 1) | Piping, Ferrous | |
CISPI HSN-85 | Neoprene Rubber Gaskets for Hub and Spigot Cast Iron Soil Pipe and Fittings | Joints | |
CISPI 310-97 | Couplings for Use in Connection with Hubless Cast Iron Soil Pipe and Fittings for Sanitary and Storm Drain, Waste, and Vent Piping Applications | Joints | |
FS A-A-51145C | Flux, Soldering, Nonelectronic, Paste and Liquid | Joints | |
FS K65.59-71 | Acrylonitrile-Butadiene-Styrene (ABS) sewer pipe and fittings | Piping, Plastic | |
FS M265-811 | Acrylonitrile-Butadiene-Styrene (ABS) Sch. 40 plastic drain, waste and vent pipe and fittings | Piping, Plastic | |
FS O-F-499D-85 | Flux brazing | Joints | |
FS O-F-506C-72 (D) | Flux, soldering | Joints | |
FS OO-L-201 f-70 | Shower pans-sheet lead, grade B, 4 lb. min. | Miscellaneous | |
FS QQ-R-571C-69 [D] | Copper and nickel alloys (rods) | Miscellaneous | |
FS TT-S-1732-71 | Seal compound pipe joint and thread | Joints | |
FS WW-P 325B-76 | Lead pipe and bends | Piping | |
FS WW-P-521F-77 | Copper alloy (bronze) unions | Piping, Copper Alloy | |
FS WW-P-541-E-Gen.1980 | Plumbing fixtures, general specification | Fixtures | |
FS WW-U-516A-74(b) | Copper alloy (bronze) unions | Piping, Copper Alloy | |
FS WW-V-54d | Valve, Gate, Bronze (125, 150 and 200 Pound, Screwed Flange, Solder-End, for Land Use) | Valves | |
FS WW-V 58b | Valves, Gate, Cast Iron; 125 and 250-Pound, Screwed and Flanged (for Land Use) | Valves | |
IAPMO IS 1-91 e1 | Nonmetallic Building Sewers | Piping, Nonmetallic | |
IAPMO IS 2-90 | Tile-Lined Roman Bathtubs | Fixtures | |
IAPMO IS 3-93 e1 | Copper Plumbing Tube, Pipe and Fittings | Piping, Copper Alloy | |
IAPMO IS 4-96 | Tile-Lined Shower Receptors (and Replacements) | Fixtures | |
IAPMO IS 5-92 e1 | ABS Building Drain, Waste, and Vent Pipe and Fittings | Piping, Plastic | |
IAPMO IS 6-95 | Hubless Cast Iron Sanitary and Rainwater Systems | Piping, Ferrous | |
IAPMO IS 7-90 e1 | Polyethlene (PE) cold Water Building Supply | Piping, Plastic | |
IAPMO IS 8-95 e1 | PVC Cold Water Building Supply and Yard Piping | Piping, Plastic | |
IAPMO IS 9-95 e1 | PVC Building Drain, Waste and Vent Pipe Fittings | Piping, Plastic | |
IAPMO IS 11-87 e1 | ABS Sewer Pipe and Fittings | Piping, Plastic | |
IAPMO IS 12-93 e1 | Polyethylene (PE) for Gas Yard Piping | Piping, Plastic | |
IAPMO IS 13-91 e1 | Protectively Coated | Pipe Piping | |
IAPMO IS 15-82 | Asbestos Cement Pressure Pipe for Water Service and Yard Piping | Piping, Nonmetallic | |
IAPMO IS 16-84 | Low Pressure Air Test for Building Sewers | Piping | |
IAPMO IS 18-85 e1 | Extra Strength Vitrified Clay Pipe in Building Drains | Piping, Nonmetallic | |
IAPMO IS 20-98 | CPVC Solvent Cemented Hot and Cold Water Distribution Systems | Piping, Plastic | |
IAPMO IS 21-89 e1 | Welded Copper and Copper Alloy Water Tube | Piping, Copper Alloy | |
IAPMO IS 26-99 | Trenchless Polyethylene (PE) Pipe for Sewer Laterals | Piping, Plastic | |
IAPMO PS 1-99 | Prefabricated Septic Tanks | DWV Components | |
IAPMO PS 2-89 | Cast Brass and Tubing P-Traps | Piping, Copper Alloy | |
IAPMO PS 4-99 | Drains for Prefabricated and Precast Showers | Fixtures | |
IAPMO PS 7-84 | Tubing Trap Wall Adapters | DWV Components | |
IAPMO PS 9-84 | Diversion Tees and Twin Waste Elbows | DWV Components | |
IAPMO PS 13-89 | Testing and Rating Procedure for Grease Traps (Note 2) | DWV Components | |
IAPMO PS 14-99 | Flexible Metallic Water Connectors | Piping | |
IAPMO PS 16-97 | Subdrains for Built-Up Shower Pans | Fixtures | |
IAPMO PS 23-89 | Dishwasher Drain Airgaps | Backflow Protection | |
IAPMO PS 25-84 | Fittings for Joining Polyethylene Pipe for Water Service and Yard Piping | Joints | |
IAPMO PS 31-95 | Backflow Prevention Assemblies | Backflow Protection | |
IAPMO PS 34-96 | Polyethylene Encasement Sleeve for Potable Water Pipe and Tubing | Piping | |
IAPMO PS 36-90 | Lead-Free Sealing Compounds for Threaded Joints | Joints | |
IAPMO PS 37-90 | Black Plastic PVC or PE Pressure-Sensitive Corrosion Preventive Tape | Piping | |
IAPMO PS 38-99 | ABS and PVC Backwater Valves | DWV Components | |
IAPMO PS 39-91 | Testing Mechanical Fittings Composed of Multiple Components For Various Fitting Configuration For Use With Thermoplastic Gas Pressure Pipe | Fuel Gas | |
IAPMO PS 40-91 | Anodeless Transition Riser for Use with Polyethylene and PVC Gas Yard Piping | Fuel Gas | |
IAPMO PS 41-99 | Copper and Other Metallic Roof/Deck/Balcony Drains | DWV Components | |
IAPMO PS 42-96 | Pipe Alignment and Secondary Support Systems | Piping | |
IAPMO PS 43-91 | Cushioned Bathtubs And Whirlpool Bathtub Appliances | Fixtures | |
IAPMO PS 44-92 | Shielded Transition Couplings for Use with Dissimilar DWV Pipe and Fittings Above Ground | Joints | |
IAPMO PS 45-91 | Bathtub Three-Way Diverter Valves with Backflow Protection | Valves | |
IAPMO PS 47-99 | Plastic Roof Drains | DWV Components | |
IAPMO PS 48-92 | Material Safety Data Verification For Plumbing Products | Miscellaneous | |
IAPMO PS 49-92 | Backflow Prevention Requirements for Fixture Fittings with Hose Connected Singular Moveable Outlets | Backflow Protection | |
IAPMO PS 50-92 | Dual Flush Devices For Water Closets | Fixtures | |
IAPMO PS 51-98 | Plastic and Metallic Expansion Joints | Joints | |
IAPMO PS 52-99 | Sumps and Sewage Ejector Tanks | DWV Components | |
IAPMO PS 53-92 | Grooved Mechanical Pipe Couplings and Grooved End Fittings | Joints | |
IAPMO PS 54-99 | Metallic and Plastic Utility Boxes | Miscellaneous | |
IAPMO PS 55-92 | Bathwaste Strainer Drains | Fixtures | |
IAPMO PS 57-92 | PVC Hydraulically Actuated Diaphragm Type Water Control Valves | Valves | |
IAPMO PS 58-92 | Supports for Off-the-Floor Plumbing Fixtures With or Without Concealed Tanks | Fixtures | |
IAPMO PS 59-92 | Septic Effluent and Waste Water Diverter Valves | DWV Components | |
IAPMO PS 60-96 | Sewage Holding Tank Containing Sewage Ejector Pump for Direct Mounted Water Closet | DWV Components | |
IAPMO PS 61-92 | Fabricated Stainless Steel Security Water Closets | Fixtures | |
IAPMO PS 62-93 | Enameled Cast Iron Sanitary Floor Sinks | Fixtures | |
IAPMO PS 63-99 | Plastic Leaching Chambers | DWV Components | |
IAPMO PS 64-98 | Pipe Flashings | Piping | |
IAPMO PS 65-93 | Airgap Units for Water Conditioning Equipment Installation | Backflow Protection | |
IAPMO PS 66-93 | Dielectric Waterway Fittings | Piping | |
IAPMO PS 67-93 | Early-Closure Replacement Flappers or Early-Closure Replacement Flapper With Mechanical Assemblies | Fixtures | |
IAPMO PS 69-98 | Plastic Bathwaste and Overflow Assemblies | Piping, Plastic | |
IAPMO PS 70-93 | Bathtub/Whirlpool Bathtubs with Pressure Sealed Doors | Fixtures | |
IAPMO PS 71-93 | Electronic Controlled Showers | Fixtures | |
IAPMO PS 72-93 | Valves with Atmospheric Vacuum Breakers | Valves | |
IAPMO PS 73-93 | Dental Vacuum Pumps | Miscellaneous | |
IAPMO PS 74-99 | Reinforced Flexible Water Connectors | Piping | |
IAPMO PS 76-95 | Ballcock or Flushometer Valve Tailpiece Trap Primers and Trap Primer Receptors/Adapters | DWV Components | |
IAPMO PS 77-99 | Electrohydraulic Water Closets | Fixtures | |
IAPMO PS 78-95 | Dual Flush for Electrohydraulic and Gravity 6 Liter (1.6 Gallons) Water Closet | Fixtures | |
IAPMO PS 79-95 | Multiport Electronic Trap Primer | DWV Components | |
IAPMO PS 80-95 | Grease Interceptors and Clarifiers | DWV Components | |
IAPMO PS 81-95 | Precast Concrete Seepage Pit Liners and Covers | DWV Components | |
IAPMO PS 82-95 | Fiberglass (Glass Fiber Reinforced Thermosetting Resin) Fittings | Piping, Plastic | |
IAPMO PS 83-95 | Epoxy Coated Cast Iron Sanitary Floor Sinks | Fixtures | |
IAPMO PS 84-95 | PVC Plastic Sanitary Floor Sinks | Fixtures | |
IAPMO PS 85-95 | Tools for Mechanically Formed Tee Connections in Copper Tubing | Piping | |
IAPMO PS 86-95 | Rainwater Diverter Valve for Nonroofed Area Slabs | DWV Components | |
IAPMO PS 87-95 | Diverter and Shut-Off Valves for Pool/Spas | Valves | |
IAPMO PS 88-95 | Pre-Pressurized Potable Water Tanks | Miscellaneous | |
IAPMO PS 89-95 | Soaking and Hydrotherapy (Whirlpool) Bathtubs with Hydraulic Seatlift | Fixtures | |
IAPMO PS 90-95 | Elastomeric Test Caps/Cleanout Caps | DWV Components | |
IAPMO PS 91-95 | Plastic Stabilizers for Use with Plastic Closet Bends | Piping, Plastic | |
IAPMO PS 92-95 | Heat Exchangers | Miscellaneous | |
IAPMO PS 93-99 | Water Closet Seats with Spray | Fixtures | |
IAPMO PS 94-96 | P-Trap, Supply Stop and Riser Insulated Protector | Miscellaneous | |
IAPMO PS 95-98 | Drain, Waste, and Vent Hangers and Plastic Pipe Support Hooks | Piping | |
IAPMO PS 96-96 | Passive Direct Solar Water Heaters | Miscellaneous | |
IAPMO PS 97-97 | Mechanical Cast Iron Closet Flanges | Piping, Ferrous | |
IAPMO PS 98-96 | Prefabricated Fiberglass Church Baptistries | Fixtures | |
IAPMO PS 99-96 | Terrazzo Plumbing Fixtures | Fixtures | |
IAPMO PS 100-96 | Porous Filter Protector for Sub-Drain Weep Holes | DWV Components | |
IAPMO PS 101-97 | Suction Relief Valves | Valves | |
IAPMO PS 102-97 | Short Pattern Fixture Trap | DWV Components | |
IAPMO PS 103-97 | Water Heater Stands With or Without Pans | Appliances | |
IAPMO PS 104-97 | Pressure Relief Connection for Dispensing Equipment | Valves | |
IAPMO PS 105-97 | Polyethylene Distribution Boxes | DWV Components | |
IAPMO PS 106-98 | Pre-Fabricated, Tileable Shower Receptors | Fixtures | |
IAPMO PS 107-98 | Aramid Reinforced Rubber Hose for Use in Nonpotable Water Radiant Heating and Snowmelting | Piping, Plastic | X |
IAPMO PS 108-98 | Grease Fire Suppression Systems | Appliances | |
IAPMO PS 109-96 | Rigid Unshielded Mechanical Couplings for Use with Plain End Drain, Waste, and Vent (DWV) Pipe and Plain End Sewer Pipe | Joints | |
IAPMO PS 110-99 | PVC Cold Water Compression Fittings | Fittings | |
IAPMO PS 111-99 | PVC Cold Water Gripper Fittings | Fittings | |
IAPMO PS 112-99 | PVC Plastic Valves for Cold Water Distribution Systems Outside a Building and CPVC Plastic Valves for Hot and Cold Water Distribution Systems | Valves | |
IAPMO PS 113-99 | Hydraulically Powered Household Food Waster Grinders | Appliances | |
IAPMO PS 114-99 | Remote, Floor Box Industrial Water Supply, Air Supply, Drainage | Miscellaneous | |
IAPMO PS 115-99 | Hot Water Demand or Automatic Activated Hot Water Pumping Systems | Miscellaneous | |
IAPMO PS 116-99 | Hot Water Circulating Devices Which Do Not Use a Pump | Miscellaneous | |
IAPMO SPS 3-93 | Skimmers (Spas, Hot Tubs and Swimming Pools) | Swimming Pools and Spas | |
IAPMO SPS 4-89 | Special Use Suction Fittings for Swimming Pools, Spas and Hot Tubs (For Suction Side Automatic Swimming Pool Cleaners) | Swimming Pools and Spas | |
IAS LC 1-97 | Fuel Gas Piping Systems Using Corrugated Stainless Steel Tubing (CSST) (same as CSA 6.26-M97) | Fuel Gas | X |
MIL-F-1183 H-83 [D] | Fittings, Pipe, Cast Bronze, Silver-Brazing | Piping, Copper Alloy | |
MIL-F-18180C1 | Flanges and Flanged Fittings, Pipe, Steel (150, 300, 400, 600, 900, 1500, and 2500 pounds) | Piping, Ferrous | |
MIL-P-17552 | Pumps, Centrifugal, Water, Horizontal, General Service; and Pumps, Centrifugal Water, Horizontal, Boiler-Feed; Electric Motor or Steam Driven | Pumps | |
MIL-P-21214B-92 | Vertical sump pumps | Pumps | |
SSPMA-85 | |||
MIL-P-21251C | Plumping Units, Sewage, Duplex, Automatic, Wet-Pit-Type | Pumps | |
MIL-P-22561-82(D) | Glass (standard cancelled per Department of Defense) | Miscellaneous | |
MIL-V-29193-80(D) | Pressurized flushing devices | Fixtures | |
MIL-P-52407 | Pump, Centrifugal: Electric-Motor-Driven, Shallow (A)-1976 (D) Well (for Water) | Pumps | |
MIL-P-62156 | Submersible, axial flow, electric motor driven | Pumps | |
MIL-P-B-81 (D) | (1)-1983 (D) | ||
SSPMA-85 | Sewage pumps | Pumps | |
MSS SP-25-93 | Standard Marking System for Valves, Fittings, Flanges and Unions | Piping | |
MSS SP-42-90 (R95) | Class 150 Corrosion Resistant Gate, Globe, Angle and Check Valves with Flanged and Butt Weld Ends | Piping, Ferrous | |
MSS SP-44-91 | Steel Pipeline Flanges | Piping, Ferrous | |
MSS SP-58-93 | Pipe Hangers And Supports – Materials, Design and Manufacture | Piping | |
MSS SP-67-90 | Butterfly Valves | Valves | |
MSS SP-70-90 | Cast Iron Gate Valves, Flanged and Threaded Ends | Valves | |
MSS SP-71-90 | Cast Iron Swing Check Valves, Flanged and Threaded Ends | Valves | |
MSS SP-72-92 | Ball Valves with Flanged or Butt-Welding Ends for General Service | Valves | |
MSS SP-73-91 | Brazing Joints for Wrought and Cast Copper Alloy Solder Joint Pressure Fittings | Joints | |
MSS SP-78-87 (R92) | Cast Iron Plug Valves, Flanged and Threaded Ends | Valves | |
MSS SP-80-87 | Bronze Gate, Globe, Angle and Check Valves | Valves | |
MSS SP-83-87 | Steel Pipe Unions Socket-Welding and Threaded | Piping, Ferrous | |
MSS SP-84 [D] | Steel Valves – Socket-Welding Ends and Threaded Ends (discontinued) | Valves | |
NFPA 13R-1996 | Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height | Miscellaneous | |
NFPA 13D-1996 | Installation of Sprinkler Systems in One-and Two-Family Dwellings and Manufactured Homes | Miscellaneous | |
NFPA 31-97 | Installation of Oil-Burning Equipment | Miscellaneous | |
NFPA 54-96 | National Fuel Gas Code | Fuel Gas | |
NFPA 58-98 | Storage and Handling of Liquified Petroleum Gases | Fuel Gas | |
NFPA 99-99 (Ch. 2 &4) | Medical Gas Systems | Piping | |
NFPA 99-99 (Ch. 2 &4) | Gas and Vacuum Systems | Piping | |
NFPA 211-96 | Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances | Miscellaneous | |
NFPA 8501-97 | Single Burner Boiler Operation | Appliances | |
NSF 3-96 | Commercial Spray-Type Dishwashing and Glasswashing Machines | Appliances | |
NSF 12-93 | Automatic Ice Making Equipment | Appliances | |
NSF 14-98 | Plastic Piping Components and Related Materials | Piping, Plastic | |
NSF 18-96 | Manual Food and Beverage Dispensing Equipment | Appliances | |
NSF 24-96 | Plumbing System Components for Manufactured Homes and Recreational Vehicles | Miscellaneous | |
NSF 29-93 | Chemical Feeders for Commercial Dishwashers | Appliances | |
NSF 40-99 | Residential Wastewater Treatment Systems | DWV Components | |
NSF 41-98 | Nonliquid Saturated Treatment Systems | DWV Components | |
NSF 42-98 | Drinking Water Treatment Units -Aesthetic Effects | Appliances | |
NSF 44-98 | Cation Exchange Water Softeners | Appliances | |
NSF 46-97 | Evaluation of Components and Devices Used in Wastewater Treatment Systems | DWV Components | |
NSF 53-98 | Drinking Water Treatment Units - Health Effects | Appliances | |
NSF 58-98 | Reverse Osmosis Drinking Water Treatment Systems | Appliances | |
NSF 61-98 | Drinking Water System Components -Health Effects | Miscellaneous | |
NSF 62-97 | Water Distillation Systems | Appliances | |
NSPI 1-1991 | Public Swimming Pools | Swimming Pools and Spas | |
PDI G-101-85 | Testing and Rating Procedure for Grease Interceptors with Appendix of Sizing and Installation Data | DWV Components | |
PDI-WH 201-92 | Water Hammer Arresters | Piping | |
SAE J1670-93 | Type "F" Clamps for Plumbing Applications | Joints | |
SAMA LF6a | Medical Care Facility Brassware | Miscellaneous | |
UL 80-96 | Steel Inside Tanks for Oil-Burner Fuel | Miscellaneous | |
UL 103-95 | Factory-Built Chimneys for Residential Type and Building Heating Appliances | Miscellaneous | |
UL 125-97 | Valves for Anhydrous Ammonia and LP-Gas (Other than Safety Relief) | Valves | |
UL 132-97 | Safety Relief Valves for Anhydrous Ammonia and LP-Gas | Valves | |
UL 144-99 | LP Gas Regulators | Valves | |
UL 174-96 | Household Electric Storage Tank Water Heaters | Appliances | |
UL 343-97 | Pumps for Oil-Burning Appliances | Pumps | |
UL 352-97 | Constant-Level Oil Valves | Valves | |
UL 378-93 | Draft Equipment | Miscellaneous | |
UL 399-93 | Drinking-Water Coolers | Appliances | |
UL 430-94 | Waste Disposers | Appliances | |
UL 441-96 | Gas Vents | Miscellaneous | |
UL 443-95 | Steel Auxiliary Tanks for Oil-Burner Fuel | Miscellaneous | |
UL 499-97 | Electrical Heating Appliances | Appliances | |
UL 563-95 | Ice Makers | Appliances | |
UL 569-95 | Pigtails and Flexible Hose Connectors for LP-Gas | Fuel Gas | |
UL 723-96 | Test for Surface Burning Characteristics of Building Materials | Miscellaneous | |
UL 726-95 | Oil-Fired Boiler Assemblies | Appliances | |
UL 732-95 | Oil-Fired Storage Tank Water Heaters | Appliances | |
UL 749-97 | Household Dishwashers | Appliances | |
UL 778-96 | Motor-Operated Water Pumps | Pumps | |
UL 834-95 | Heating, Water Supply, and Power Boilers -Electric | Appliances | |
UL 921-96 | Commercial Electric Dishwashers | Appliances | |
UL 1453-95 | Electric Booster and Commercial Storage Tank Water Heaters | Appliances | |
WAC 246-290-490 | Washington State Department of Health Cross Connection Control Requirements | Backflow Protection | |
WQA S-100-95 | Household, Commercial and Portable Exchange Water Softeners (replaced by NSF 44-98) | Appliances | |
WQA S-200-93 | Household and Commercial Water Filters | Appliances | |
WQA S-300-91 | Point-of-Use Low Pressure Reverse Osmosis Drinking Water Systems | Appliances | |
3-GP-28 | Fuel Oil, Canadian Government Specification Board | Miscellaneous |
Footnotes: | 1. Although this standard is referenced in Table 14-1, some of the pipe, tubing, fittings, valves, or fixtures included in the standard are not acceptable for use under the provisions of the Uniform Plumbing Code. |
2. PDI Standard G101 by reference. | |
3. Additional Requirements for Inner and Outer Layers. | |
4. See Section 316.1.3 for restriction. | |
5. Alloy C85200 for cleanout plugs. | |
6. Limited to domestic sewage. | |
7. Type II only. | |
8. Fixture fittings with hose connected singular moveable outlets shall have two check valves and an atmospheric vacuum breaker. | |
9. ASSE 1066 is not intended to limit the maximum outlet temperature at point of use. | |
10. See section 315.0 for Trenching, Excavation, and Backfilling requirements when installing building drains and sewers. Engineers may wish to consult ASTM D2321 when preparing plans and specifications for sewer mains or specific projects. |
[]
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040.
NEW SECTION
WAC 51-56-201300
Appendix M -- Storm drainage.
M 1.0 General.
M 1.1 Where Required. All roofs, paved areas, yards, courts, and
courtyards shall be drained into a separate storm sewer system,
or into a combined sewer system where a separate storm sewer
system is not available, or to some other place of disposal
satisfactory to the administrative authority. In the case of
one- and two-family dwellings, storm water may be discharged on
flat areas such as streets or lawns so long as the storm water
shall flow away from the building and away from adjoining
property, and shall not create a nuisance.
M 1.2 Storm Water Drainage to Sanitary Sewer Prohibited. Storm
water shall not be drained into sewers intended for sanitary
drainage only.
M 1.3 Material Uses. Rainwater piping placed within the interior
of a building or run within a vent or shaft shall be of cast
iron, galvanized steel, wrought iron, brass, copper, lead,
Schedule 40 ABS DWV, Schedule 40 PVC DWV, or other approved
materials, and changes in direction shall conform to the
requirements of Section 706.0.
M 1.4 Expansion Joints Required. Expansion joints or sleeves
shall be provided where warranted by temperature variations or
physical conditions.
M 1.5 Subsoil Drains.
M 1.5.1 Subsoil drains shall be provided around the perimeter of
buildings having basements, cellars, or crawl spaces or floors
below grade. Such subsoil drains may be positioned inside or
outside of the footing, shall be of perforated, or open-jointed
approved drain tile or pipe not less than three (3) inches (76
mm) in diameter, and shall be laid in gravel, slag, crushed rock,
approved three-quarter (3/4) inch (19.1 mm) crushed recycled
glass aggregate, or other approved porous material with a minimum
of four (4) inches (102 mm) surrounding the pipe on all sides.
Filter media shall be provided for exterior subsoil piping.
M 1.5.2 Subsoil drains shall be piped to a storm drain, to an
approved water course, to the front street curb or gutter, or to
an alley; or the discharge from the subsoil drains shall be
conveyed to the alley by a concrete gutter. Where a continuously
flowing spring or groundwater is encountered, subsoil drains
shall be piped to a storm drain or an approved water course.
M 1.5.3 Where it is not possible to convey the drainage by
gravity, subsoil drains shall discharge to an accessible sump pit
provided with an approved automatic electric pump. A sump pit
shall be at least fifteen (15) inches (381 mm) in diameter,
eighteen (18) inches (457 mm) in depth, and provided with a
fitted cover. The sump pump shall have an adequate capacity to
discharge all water coming into the sump as it accumulates to the
required discharge point, and the capacity of the pump shall not
be less than fifteen (15) gpm (1.0 L/s). The discharge piping
from the sump pump shall be a minimum of one and one-half (1-1/2)
inches (38 mm) in diameter and have a union to make the pump
accessible for servicing.
M 1.5.4 For separate dwellings not serving continuously flowing
springs or ground water, the sump discharge pipe may discharge
onto a concrete splash block with a minimum length of twenty-four
(24) inches (610 mm). This pipe shall be within four (4) inches
(102 mm) of the splash block and positioned to direct the flow
parallel to the recessed line of the splash block.
M 1.5.5 Subsoil drains subject to backflow when discharging into
a storm drain shall be provided with a backwater valve in the
drain line so located as to be accessible for inspection and
maintenance.
M 1.5.6 Nothing in Section 1501.5 shall prevent drains that serve
either subsoil drains or areaways of a detached building from
discharging to a properly graded open area, provided that:
(1) They do not serve continuously flowing springs or ground water;
(2) The point of discharge is at least ten (10) feet (3048 mm) from any property line; and
(3) It is impracticable to discharge such drains to a storm drain, to an approved water course, to the front street curb or gutter, or to an alley.
M 1.6 Building Subdrains. Building subdrains located below the
public sewer level shall discharge into a sump or receiving tank,
the contents of which shall be automatically lifted and
discharged into the drainage system as required for building
sumps.
M 1.7 Areaway Drains. All open subsurface space adjacent to a
building, serving as an entrance to the basement or cellar of a
building, shall be provided with a drain or drains. Such areaway
drains shall be two (2) inches (51 mm) minimum diameter for
areaways not exceeding one hundred (100) square feet (9.3 m2) in
area, and shall be discharged in the manner provided for subsoil
drains not serving continuously flowing springs or ground water
(see Section 1501.5.2). Areaways in excess of one hundred (100)
square feet (9.3 m2) shall not drain into subsoil. Areaway
drains for areaways exceeding one hundred (100) square feet (9.3
m2) shall be sized according to Table M-2.
M 1.8 Window Areaway Drains. Window areaways not exceeding ten
(10) square feet (0.9 m2) in area may discharge to the subsoil
drains through a two (2) inch (51 mm) pipe. However, window
areaways exceeding ten (10) square feet (0.9 m2) in area shall be
handled in the manner provided for entrance areaways (see Section
1501.7).
M 1.9 Filling Stations and Motor Vehicle Washing Establishments.
Public filling stations and motor vehicle washing establishments
shall have the paved area sloped toward sumps or gratings within
the property lines. Curbs not less than six (6) inches (152 mm)
high shall be placed where required to direct water to gratings
or sumps.
M 1.10 Paved Areas. Where the occupant creates surface water
drainage, the sumps, gratings or floor drains shall be piped to a
storm drain or an approved water course.
M 1.11 Roof Drainage.
M 1.11.1 Primary Roof Drainage. Roof areas of a building shall
be drained by roof drains or gutters. The location and sizing of
drains and gutters shall be coordinated with the structural
design and pitch of the roof. Unless otherwise required by the
administrative authority, roof drains, gutters, vertical
conductors or leaders, and horizontal storm drains for primary
drainage shall be sized based on a storm of sixty (60) minutes
duration and 100-year return period (see Appendix D).
M 1.11.2 Secondary Roof Drainage.
M 1.11.2.1 Where parapet walls or other construction extend above
the roof and create areas where storm water would become trapped
if the primary roof drainage system failed to provide sufficient
drainage, an independent secondary roof drainage system
consisting of scuppers, standpipes, or roof drains shall be
provided. Secondary roof drainage systems shall be sized in
accordance with Section 1501.11.1 of this code. Overflow drains
shall be the same size as the roof drains with the inlet flow
line two (2) inches (51 mm) above the low point of the roof and
shall be installed independent from the roof drains.
M 1.11.2.2 Where secondary roof drainage is provided by means of
roof drains or standpipes, the secondary system shall be separate
from the primary system and shall discharge independently at
grade or other approved point of discharge.
M 1.11.2.3 Where secondary roof drainage is provided, the
overflow level(s) into the secondary system shall be determined
by the structural design of the roof, including roof deflection,
at a level not less than two (2) inches (51 mm) above the level
of the primary drain. An allowance shall be made to account for
the required overflow head of water above the secondary inlets.
The elevation of the secondary inlet plus the required overflow
head shall not exceed the maximum allowable water level on the
roof.
M 1.11.2.4 Scuppers shall be sized as rectangular weirs, using
hydraulic principles to determine the required length and
resulting overflow head (see Appendix D). Secondary roof drains
and standpipes shall be sized according to Table M-1. Where
standpipes are used, the head allowance required under Section
1501.11.2.3 shall be not less than one and one-half (1-1/2)
inches (38 mm).
M 1.11.3 Equivalent Systems. When approved by the administrative
authority, the requirements of Sections 1501.11.1 and 1501.11.2
shall not preclude the installation of an engineered roof
drainage system that has sufficient capacity to prevent water
from ponding on the roof in excess of that allowed in the roof
structural design with a rainfall rate of at least twice that for
a 100-year, 60-minute storm and with a blockage in any single
point in the storm drainage system.
M 1.12 Cleanouts.
M 1.12.1 Cleanouts for building storm drains shall comply with
the requirements of this section. Rain leaders and conductors
connected to a building storm sewer shall have a cleanout
installed at the base of the outside leader or outside conductor
before it connects to the horizontal drain. Cleanouts shall be
placed inside the building near the connection between the
building drain and the building sewer or installed outside the
building at the lower end of the building drain and extended to
grade.
M 1.12.2 Each cleanout shall be installed so that it opens to
allow cleaning in the direction of flow of the soil or waste or
at right angles thereto, and except in the case of wye branch and
end-of-line cleanouts, shall be installed vertically above the
flow line of the pipe.
M 1.12.3 Cleanouts installed under concrete or asphalt paving
shall be made accessible by yard boxes, or extending flush with
paving with approved materials and be adequately protected.
M 1.12.4 Approved manholes may be installed in lieu of cleanouts
when first approved by the administrative authority. The maximum
distance between manholes shall not exceed three hundred (300)
feet (91.4 m).
The inlet and outlet connections shall be made by the use of a flexible compression joint no closer than twelve (12) inches (305 mm) to, and not farther than three (3) feet (914 mm) from the manhole. No flexible compression joints shall be embedded in the manhole base.
M 1.13 All rainwater sumps serving "public use" occupancy
buildings shall be provided with dual pumps arranged to function
alternately in case of overload of mechanical failure.
M 2.0 Materials.
M 2.1 Conductors.
M 2.1.1 Conductors installed aboveground in buildings shall be
constructed of materials specified in Table 14-1.
M 2.1.2 The inside of conductors installed above ground level
shall be of seamless copper water tube, Type K, L or M; Schedule
40 copper pipe or Schedule 40 copper alloy pipe; Type DWV copper
drainage tube; service weight cast iron soil pipe or hubless cast
iron soil pipe; standard weight galvanized steel pipe; or
Schedule 40 ABS or Schedule 40 PVC plastic pipe.
M 2.2 Leaders.
M 2.2.1 Leaders shall be constructed of materials specified in
Table 14-1.
M 2.2.2 Leaders shall be of seamless copper water tube, Type K, L
or M; Schedule 40 copper pipe; Schedule 40 copper alloy pipe;
type DWV copper drainage tube; service weight cast iron soil pipe
or hubless cast iron soil pipe; galvanized steel sheet metal or
copper sheet metal; standard weight galvanized steel pipe; Class
DL or XL lead pipe; or Schedule 40 ABS or Schedule 40 PVC plastic
pipe.
M 2.3 Underground Building Storm Drains. All underground
building storm drains shall be constructed of materials specified
in Table 14-1.
M 2.4 Building Storm Sewers. Building storm sewers shall be
constructed of materials specified in Table 14-1.
M 2.5 Subsoil Drains.
M 2.5.1 Subsoil drains shall be constructed of materials
specified in Table 14-1.
M 2.5.2 Subsoil drains shall be open-jointed or of perforated
pipe, vitrified clay, plastic, cast iron, or porous concrete.
M 3.0 Traps on Storm Drains and Leaders.
M 3.1 Where Required. Leaders and storm drains, when connected
to a combined sewer, shall be trapped. Floor and area drains
connected to a storm drain shall be trapped.
EXCEPTION: | Traps shall not be required where roof drains, rain leaders and other inlets are at locations allowed under Section 906.0, Vent Terminals. |
M 3.3 Trap Size. Traps, when installed for individual
conductors, shall be the same size as the horizontal drain to
which they are connected.
M 3.4 Method of Installation of Combined Sewer. Individual
storm-water traps shall be installed on the storm-water drain
branch serving each storm-water inlet, or a single trap shall be
installed in the main storm drain just before its connection with
the combined building sewer. Such traps shall be provided with
an accessible cleanout on the outlet side of the trap.
M 4.0 Leaders, Conductors, and Connections.
M 4.1 Improper Use. Leaders or conductors shall not be used as
soil, waste, or vent pipes, nor shall soil, waste, or vent pipes
be used as leaders or conductors.
M 4.2 Protection of Leaders. Leaders installed along alleyways,
driveways, or other locations where they may be exposed to damage
shall be protected by metal guards, recessed into the wall, or
constructed from ferrous pipe.
M 4.3 Combining Storm with Sanitary Drainage. The sanitary and
storm drainage system of a building shall be entirely separate,
except where a combined sewer is used, in which case the building
storm drain shall be connected in the same horizontal plane
through single wye fittings to the combined building sewer at
least ten (10) feet (3048 mm) downstream from any soil stack.
M 5.0 Roof Drains.
M 5.1 Material.
M 5.1.1 Roof drains shall be constructed of materials specified
in Table 14-1.
M 5.1.2 Roof drains shall be of cast iron, copper or copper
alloy, lead or plastic.
M 5.2 Dome or Strainer for General Use. All roof drains and
overflow drains, except those draining to hanging gutters, shall
be equipped with strainers extending not less than four (4)
inches (102 mm) above the surface of the roof immediately
adjacent to the drain. Strainers shall have a minimum inlet area
above the roof level of not less than one and one-half (1-1/2)
times the area of the conductor or leader to which the drain is
connected.
M 5.3 Strainers for Flat Decks. Roof drain strainers for use on
sun decks, parking decks, and similar areas which are normally
serviced and maintained may be of the flat surface-type. Such
roof drain strainers shall be level with the deck and shall have
an available inlet area of no less than two (2) times the area of
the conductor or leader to which the drain is connected.
M 5.4 Roof Drain Flashings. Connection between the roof and roof
drains which pass through the roof and into the interior of the
building shall be made watertight by the use of proper flashing
material.
M 5.4.1 Where lead flashing material is used, it shall be a
minimum of four (4) pounds per square foot (19.5 kg/m2).
M 5.4.2 Where copper flashing material is used, it shall be a
minimum of twelve (12) ounces per square foot (3.7 kg/m2).
M 6.0 Size of Leaders, Conductors, and Storm Drains.
M 6.1 Vertical Conductors and Leaders. Vertical conductors and
leaders shall be sized on the basis of the maximum projected roof
area and Table M-1.
M 6.2 Size of Horizontal Storm Drains and Sewers. The size of
building storm drains or building storm sewers or any of their
horizontal branches shall be based upon the maximum projected
roof or paved area to be handled and Table M-2.
M 6.3 Size of Roof Gutters. The size of semicircular gutters
shall be based on the maximum projected roof area and Table M-3.
M 6.4 Side Walls Draining onto a Roof. Where vertical walls
project above a roof so as to permit storm water to drain to the
roof area below the adjacent roof area may be computed from Table
M-1 as follows:
1. For one (1) wall – add fifty (50) percent of the wall area to the roof area figures.
2. For two (2) adjacent walls – add thirty-five (35) percent of the total wall areas.
3. Two (2) walls opposite of same height – add no additional area.
4. Two (2) walls opposite of differing heights – add fifty (50) percent of wall area above top of lower wall.
5. Walls on three (3) sides – add fifty (50) percent of area of the inner wall below the top of the lowest wall, plus allowance for the area of wall above top of lowest wall, per (2) and (4) above.
6. Walls on four (4) sides – no allowance for wall areas below top of lowest wall – add for areas above the top of the lowest wall per (1), (2), (4) and (5) above.
M 7.0 Values for Continuous Flow.
Where there is a continuous or semi-continuous discharge into the building storm drain or building storm sewer, as from a pump, ejector, air-conditioning plant, or similar device, one (1) gpm (3.8 L/min.) of such discharge shall be computed as being equivalent to twenty-four (24) square feet (2.2 m2) of roof area, based upon a rate of rainfall of four (4) inches (102 mm) per hour.
M 8.0 Testing.
M 8.1 Testing Required. New building storm drainage systems and
parts of existing systems that have been altered, extended or
repaired shall be tested as described in Section 1508.2.1 to
disclose leaks and defects.
M 8.2 Methods of Testing Storm Drainage Systems. Except for
outside leaders and perforated or open jointed drain tile, the
piping of storm drain systems shall be tested upon completion of
the rough piping installation by water or air, and proved tight.
The administrative authority may require the removal of any
cleanout plugs to ascertain if the pressure has reached all parts
of the system. Either of the following test methods shall be
used:
M 8.2.1 Water Test. After piping has been installed, the water
test shall be applied to the drainage system, either in its
entirety or in sections. If applied to the entire system, all
openings in the piping shall be tightly closed except for the
highest opening, and the system shall be filled with water to the
point of overflow. If the system is tested in sections, each
opening shall be tightly plugged except for the highest opening
of the section under test, and each section shall be filled with
water, but no section shall be tested with less than a ten (10)
foot (3048 mm) head of water. In testing successive sections, at
least the upper ten (10) foot (3048 mm) of the next preceding
section shall be tested so that no joint of pipe in the building
(except the uppermost ten (10) foot (3048 mm) of a roof drainage
system, which shall be filled with water to the flood level of
the uppermost roof drain) shall have been submitted to a test of
less than a ten (10) foot (3048 mm) head of water. The water
shall be kept in the system or in the portion under test for at
least fifteen (15) minutes before inspection starts; the system
shall then be tight at all points.
M 8.2.2 Air Test. The air test shall be made by attaching an air
compressor testing apparatus to any suitable opening after
closing all other inlets and outlets to the system, forcing air
into the system until there is a uniform gage pressure of five
(5) psi (34.5 kPa) or sufficient to balance a column of mercury
ten (10) inches (254 mm) in height. This pressure shall be held
without introduction of additional air for a period of at least
fifteen (15) minutes.
M 8.2.3 Exceptions. When circumstances exist that make air and
water tests, described in Sections 1508.2.1 and 1508.2.2 above,
impractical, and for minor maintenance, repairs and
installations, the administrative authority may perform the
inspection as considered advisable by said authority to assure
that the work has been in accordance with provisions of this
code.
TABLE M-1
Sizing Roof Drains, Leaders, and Vertical Rainwater Piping
Size of Drain, Leader or Pipe, Inches | Flow, gpm | Maximum Allowable Horizontal Projected Roof Areas Square feet at Various Rainfall Rates |
|||||
1"/Hr | 2"/Hr | 3"/Hr | 4"/Hr | 5"/Hr | 6"/Hr | ||
2 | 23 | 2176 | 1088 | 725 | 544 | 435 | 363 |
3 | 67 | 6440 | 3220 | 2147 | 1610 | 1288 | 1073 |
4 | 144 | 13,840 | 6920 | 4613 | 3460 | 2768 | 2307 |
5 | 261 | 25,120 | 12,560 | 8373 | 6280 | 5024 | 4187 |
6 | 424 | 40,800 | 20,400 | 13,600 | 10,200 | 8160 | 6800 |
8 | 913 | 88,000 | 44,000 | 29,333 | 22,000 | 17,600 | 14,667 |
TABLE M-1 (Metric)
Sizing Roof Drains, Leaders, and Vertical Rainwater Piping
Size of Drain, Leader or Pipe, mm | Flow, L/s | Maximum Allowable Horizontal Projected Roof Areas Square meters at Various Rainfall Rates |
|||||
25mm/Hr | 50mm/Hr | 75mm/Hr | 100mm/Hr | 125mm/Hr | 150mm/Hr | ||
50 | 1.5 | 202 | 101 | 67 | 51 | 40 | 34 |
75 | 4.2 | 600 | 300 | 200 | 150 | 120 | 100 |
100 | 9.1 | 1286 | 643 | 429 | 321 | 257 | 214 |
125 | 16.5 | 2334 | 1117 | 778 | 583 | 467 | 389 |
150 | 26.8 | 3790 | 1895 | 1263 | 948 | 758 | 632 |
200 | 57.6 | 8175 | 4088 | 2725 | 2044 | 1635 | 1363 |
Notes: | 1.The sizing data for vertical conductors, leaders, and drains is based on the pipes flowing 7/24 full. |
2.For rainfall rates other than those listed, determine the allowable roof area by dividing the area given in the 1 inch/hour (25 mm/hr) column by the desired rainfall rate. | |
3.Vertical piping may be round, square, or rectangular. Square pipe shall be sized to enclose its equivalent round pipe. Rectangular pipe shall have at least the same cross-sectional area as its equivalent round pipe, except that the ratio of its side dimensions shall not exceed 3 to 1. |
TABLE M-2
Sizing of Horizontal Rainwater Piping
Size of Pipe, inches | Flow at 1/8"/ft slope, gpm | Maximum Allowable Horizontal Projected Roof Areas Square Feet at Various Rainfall Rates |
|||||
1"/Hr | 2"/Hr | 3"/Hr | 4"/Hr | 5"/Hr | 6"/Hr | ||
3 | 34 | 3288 | 1644 | 1096 | 822 | 657 | 548 |
4 | 78 | 7520 | 3760 | 2506 | 1880 | 1504 | 1253 |
5 | 139 | 13,360 | 6680 | 4453 | 3340 | 2672 | 2227 |
6 | 222 | 21,400 | 10,700 | 7133 | 5350 | 4280 | 3566 |
8 | 478 | 46,000 | 23,000 | 15,330 | 11,500 | 9200 | 7670 |
10 | 860 | 82,800 | 41,400 | 27,600 | 20,700 | 16,580 | 13,800 |
12 | 1384 | 133,200 | 66,600 | 44,400 | 33,300 | 26,650 | 22,200 |
15 | 2473 | 238,000 | 119,000 | 79,333 | 59,500 | 47,600 | 39,650 |
Size of Pipe, inches | Flow at 1/4"/ft slope, gpm | Maximum Allowable Horizontal Projected Roof Areas Square Feet at Various Rainfall Rates |
|||||
1"/Hr | 2"/Hr | 3"/Hr | 4"/Hr | 5"/Hr | 6"/Hr | ||
3 | 48 | 4640 | 2320 | 1546 | 1160 | 928 | 773 |
4 | 110 | 10,600 | 5300 | 3533 | 2650 | 2120 | 1766 |
5 | 196 | 18,880 | 9440 | 6293 | 4720 | 3776 | 3146 |
6 | 314 | 30,200 | 15,100 | 10,066 | 7550 | 6040 | 5033 |
8 | 677 | 65,200 | 32,600 | 21,733 | 16,300 | 13,040 | 10,866 |
10 | 1214 | 116,800 | 58,400 | 38,950 | 29,200 | 23,350 | 19,450 |
12 | 1953 | 188,000 | 94,000 | 62,600 | 47,000 | 37,600 | 31,350 |
15 | 3491 | 336,000 | 168,000 | 112,000 | 84,000 | 67,250 | 56,000 |
Size of Pipe, inches | Flow at 1/2"/ft slope, gpm | Maximum Allowable Horizontal Projected Roof Areas Square Feet at Various Rainfall Rates |
|||||
1"/Hr | 2"/Hr | 3"/Hr | 4"/Hr | 5"/Hr | 6"/Hr | ||
3 | 68 | 6576 | 3288 | 2192 | 1644 | 1310 | 1096 |
4 | 156 | 15,040 | 7520 | 5010 | 3760 | 3010 | 2500 |
5 | 278 | 26,720 | 13,360 | 8900 | 6680 | 5320 | 4450 |
6 | 445 | 42,800 | 21,400 | 14,267 | 10,700 | 8580 | 7140 |
8 | 956 | 92,000 | 46,000 | 30,650 | 23,000 | 18,400 | 15,320 |
10 | 1721 | 165,600 | 82,800 | 55,200 | 41,400 | 33,150 | 27,600 |
12 | 2768 | 266,400 | 133,200 | 88,800 | 66,600 | 53,200 | 44,400 |
15 | 4946 | 476,000 | 238,000 | 158,700 | 119,000 | 95,200 | 79,300 |
Notes: | 1. The sizing data for horizontal piping is based on the pipes flowing full. |
2. For rainfall rates other than those listed, determine the allowable roof area by dividing the area given in the 1 inch/hr (25mm/hr) column by the desired rainfall rate. |
TABLE M-2 (Metric)
Sizing of Horizontal Rainwater Piping
Size of Pipe, mm | Flow at 10mm/m slope, L/s | Maximum Allowable Horizontal Projected Roof Areas Square Meters at Various Rainfall Rates |
|||||
25mm/Hr | 50mm/Hr | 75mm/Hr | 100mm/Hr | 125mm/Hr | 150mm/Hr | ||
75 | 2.1 | 305 | 153 | 102 | 76 | 61 | 51 |
100 | 4.9 | 700 | 350 | 233 | 175 | 140 | 116 |
125 | 8.8 | 1241 | 621 | 414 | 310 | 248 | 207 |
150 | 14.0 | 1988 | 994 | 663 | 497 | 398 | 331 |
200 | 30.2 | 4273 | 2137 | 1424 | 1068 | 855 | 713 |
250 | 54.3 | 7692 | 3846 | 2564 | 1923 | 1540 | 1282 |
300 | 87.3 | 12,375 | 6187 | 4125 | 3094 | 2476 | 2062 |
375 | 156.0 | 22,110 | 11,055 | 7370 | 5528 | 4422 | 3683 |
Size of Pipe, mm |
Flow at 20mm/m slope, L/s | Maximum Allowable Horizontal Projected Roof Areas Square Meters at Various Rainfall Rates |
|||||
25mm/Hr | 50mm/Hr | 75mm/Hr | 100mm/Hr | 125mm/Hr | 150 mm/Hr | ||
75 | 3.0 | 431 | 216 | 144 | 108 | 86 | 72 |
100 | 6.9 | 985 | 492 | 328 | 246 | 197 | 164 |
125 | 12.4 | 1754 | 877 | 585 | 438 | 351 | 292 |
150 | 19.8 | 2806 | 1403 | 935 | 701 | 561 | 468 |
200 | 42.7 | 6057 | 3029 | 2019 | 1514 | 1211 | 1009 |
250 | 76.6 | 10,851 | 5425 | 3618 | 2713 | 2169 | 1807 |
300 | 123.2 | 17,465 | 8733 | 5816 | 4366 | 3493 | 2912 |
375 | 220.2 | 31,214 | 15,607 | 10,405 | 7804 | 6248 | 5202 |
Size of Pipe, mm | Flow at 40mm/m slope, L/s | Maximum Allowable Horizontal Projected Roof Areas Square Meters at Various Rainfall Rates |
|||||
25mm/Hr | 50mm/Hr | 75mm/Hr | 100mm/Hr | 125mm/Hr | 150mm/Hr | ||
75 | 4.3 | 611 | 305 | 204 | 153 | 122 | 102 |
100 | 9.8 | 1400 | 700 | 465 | 350 | 280 | 232 |
125 | 17.5 | 2482 | 1241 | 827 | 621 | 494 | 413 |
150 | 28.1 | 3976 | 1988 | 1325 | 994 | 797 | 663 |
200 | 60.3 | 8547 | 4273 | 2847 | 2137 | 1709 | 1423 |
250 | 108.6 | 15,390 | 7695 | 5128 | 3846 | 3080 | 2564 |
300 | 174.6 | 24,749 | 12,374 | 8250 | 6187 | 4942 | 4125 |
375 | 312.0 | 44,220 | 22,110 | 14,753 | 11,055 | 8853 | 7367 |
Notes: | 1. The sizing data for horizontal piping is based on the pipes flowing full. |
2. For rainfall rates other than those listed, determine the allowable roof area by dividing the area given in the 1 inch/hr (25mm/hr) column by the desired rainfall rate. |
TABLE M-3
Size of Gutters
Diameter of Gutter in Inches | Maximum Rainfall in Inches per Hour | ||||
1/16" per ft slope | 2 | 3 | 4 | 5 | 6 |
3 | 340 | 226 | 170 | 136 | 113 |
4 | 720 | 480 | 360 | 288 | 240 |
5 | 1250 | 834 | 625 | 500 | 416 |
6 | 1920 | 1280 | 960 | 768 | 640 |
7 | 2760 | 1840 | 1380 | 1100 | 918 |
8 | 3980 | 2655 | 1990 | 1590 | 1325 |
10 | 7200 | 4800 | 3600 | 2880 | 2400 |
Diameter of Gutter in Inches | Maximum Rainfall in Inches per Hour | ||||
1/8" per ft slope | 2 | 3 | 4 | 5 | 6 |
3 | 480 | 320 | 240 | 192 | 160 |
4 | 1020 | 681 | 510 | 408 | 340 |
5 | 1760 | 1172 | 880 | 704 | 587 |
6 | 2720 | 1815 | 1360 | 1085 | 905 |
7 | 3900 | 2600 | 1950 | 1560 | 1300 |
8 | 5600 | 3740 | 2800 | 2240 | 1870 |
10 | 10200 | 6800 | 5100 | 4080 | 3400 |
Diameter of Gutter in Inches | Maximum Rainfall in Inches per Hour | ||||
1/4" per ft slope | 2 | 3 | 4 | 5 | 6 |
3 | 680 | 454 | 340 | 272 | 226 |
4 | 1440 | 960 | 720 | 576 | 480 |
5 | 2500 | 1668 | 1250 | 1000 | 834 |
6 | 3840 | 2560 | 1920 | 1536 | 1280 |
7 | 5520 | 3680 | 2760 | 2205 | 1840 |
8 | 7960 | 5310 | 3980 | 3180 | 2655 |
10 | 14,400 | 9600 | 7200 | 5750 | 4800 |
Diameter of Gutter in Inches | Maximum Rainfall in Inches per Hour | ||||
1/2" per ft slope | 2 | 3 | 4 | 5 | 6 |
3 | 960 | 640 | 480 | 384 | 320 |
4 | 2040 | 1360 | 1020 | 816 | 680 |
5 | 3540 | 2360 | 1770 | 1415 | 1180 |
6 | 5540 | 3695 | 2770 | 2220 | 1850 |
7 | 7800 | 5200 | 3900 | 3120 | 2600 |
8 | 11,200 | 7460 | 5600 | 4480 | 3730 |
10 | 20,000 | 13,300 | 10,000 | 8000 | 6660 |
TABLE M-3 (Metric)
Size of Gutters
Diameter of Gutter in mm | Maximum Rainfall in Millimeters per Hour | ||||
5.2mm/m slope | 50.8 | 76.2 | 101.6 | 127.0 | 152.4 |
76.2 | 31.6 | 21.0 | 15.8 | 12.6 | 10.5 |
101.6 | 66.9 | 44.6 | 33.4 | 26.8 | 22.3 |
127.0 | 116.1 | 77.5 | 58.1 | 46.5 | 38.7 |
152.4 | 178.4 | 119.1 | 89.2 | 71.4 | 59.5 |
177.8 | 256.4 | 170.9 | 128.2 | 102.2 | 85.3 |
203.2 | 369.7 | 246.7 | 184.9 | 147.7 | 123.1 |
254.0 | 668.9 | 445.9 | 334.4 | 267.6 | 223.0 |
Diameter of Gutter in mm | Maximum Rainfall in Millimeters per Hour | ||||
10.4mm/m slope | 50.8 | 76.2 | 101.6 | 127.0 | 152.4 |
76.2 | 44.6 | 29.7 | 22.3 | 17.8 | 14.9 |
101.6 | 94.8 | 63.3 | 47.4 | 37.9 | 31.6 |
127.0 | 163.5 | 108.9 | 81.8 | 65.4 | 54.5 |
152.4 | 252.7 | 168.6 | 126.3 | 100.8 | 84.1 |
177.8 | 362.3 | 241.5 | 181.2 | 144.9 | 120.8 |
203.2 | 520.2 | 347.5 | 260.1 | 208.1 | 173.7 |
254.0 | 947.6 | 631.7 | 473.8 | 379.0 | 315.9 |
Diameter of Gutter in mm | Maximum Rainfall in Millimeters per Hour | ||||
20.9mm/m slope | 50.8 | 76.2 | 101.6 | 127.0 | 152.4 |
76.2 | 63.2 | 42.2 | 31.6 | 25.3 | 21.0 |
101.6 | 133.8 | 89.2 | 66.9 | 53.5 | 44.6 |
127.0 | 232.3 | 155.0 | 116.1 | 92.9 | 77.5 |
152.4 | 356.7 | 237.8 | 178.4 | 142.7 | 118.9 |
177.8 | 512.8 | 341.9 | 256.4 | 204.9 | 170.9 |
203.2 | 739.5 | 493.3 | 369.7 | 295.4 | 246.7 |
254.0 | 1338.0 | 891.8 | 668.9 | 534.2 | 445.9 |
Diameter of Gutter in mm | Maximum Rainfall in Millimeters per Hour | ||||
41.7mm/m slope | 50.8 | 76.2 | 101.6 | 127.0 | 152.4 |
76.2 | 89.2 | 59.5 | 44.6 | 35.7 | 29.7 |
101.6 | 189.5 | 126.3 | 94.8 | 75.8 | 63.2 |
127.0 | 328.9 | 219.2 | 164.4 | 131.5 | 109.6 |
152.4 | 514.7 | 343.3 | 257.3 | 206.2 | 171.9 |
177.8 | 724.6 | 483.1 | 362.3 | 289.9 | 241.4 |
203.2 | 1040.5 | 693.0 | 520.2 | 416.2 | 346.5 |
254.0 | 1858.0 | 1238.4 | 929.0 | 743.2 | 618.7 |
[]
OTS-4211.3
STATE BUILDING CODE ADOPTION AND AMENDMENT OF APPENDIX A AND APPENDIX I OF THE 2000 EDITION OF THE UNIFORM PLUMBING CODE
[]
[]
[]
[]
[]
604.1 Location. Polyethylene piping may terminate within a
building or structure. The connection to the potable water
distribution system shall be accessible, except that it may be
buried underground outside of the building or structure in an
accessible location. Barbed insert fittings with hose clamps are
prohibited within a building.
[]
604.1 Location. PVC piping may terminate within a building or
structure. The connection to the potable water distribution
system shall be accessible, except that it may be buried
underground outside of the building or structure in an accessible
location.
[]
OTS-4191.1
REPEALER
The following chapter of the Washington Administrative Code is repealed:
WAC 51-46-001 | Authority. |
WAC 51-46-002 | Purpose. |
WAC 51-46-003 | Uniform Plumbing Code. |
WAC 51-46-007 | Exceptions. |
WAC 51-46-008 | Implementation. |
WAC 51-46-0100 | Chapter 1 -- Administration. |
WAC 51-46-0101 | Section 101 Title, scope and general. |
WAC 51-46-0102 | Organization and enforcement. |
WAC 51-46-0103 | Section 103 Permits and inspections. |
WAC 51-46-0200 | Chapter 2 -- Definitions. |
WAC 51-46-0205 | Section 205.0 - C. |
WAC 51-46-0215 | Section 215.0 - M. |
WAC 51-46-0218 | Section 218.0 - P. |
WAC 51-46-0300 | Chapter 3 -- General regulations. |
WAC 51-46-0301 | Materials -- Standards and alterations. |
WAC 51-46-0310 | Workmanship. |
WAC 51-46-0311 | Prohibited fittings and practices. |
WAC 51-46-0313 | Protection of piping, materials, and structures. |
WAC 51-46-0314 | Hangers and supports. |
WAC 51-46-0316 | Joints and connections. |
WAC 51-46-0392 | Table 3-2 Hangers and supports. |
WAC 51-46-0400 | Chapter 4 -- Plumbing fixtures and fixture fittings. |
WAC 51-46-0402 | Water-conserving fixtures and fittings. |
WAC 51-46-0412 | Floor drains and shower stalls. |
WAC 51-46-0413 | Minimum number of required fixtures. |
WAC 51-46-0500 | Chapter 5 -- Water heaters. |
WAC 51-46-0501 | General. |
WAC 51-46-0502 | Definitions. |
WAC 51-46-0505 | Gas-fired water heater approval requirements. |
WAC 51-46-0507 | Combustion air. |
WAC 51-46-0509 | Prohibited locations. |
WAC 51-46-0512 | Venting of water heaters. |
WAC 51-46-0513 | Limitations. |
WAC 51-46-0514 | Vent connectors. |
WAC 51-46-0515 | Location and support of venting system. |
WAC 51-46-0516 | Length pitch and clearance. |
WAC 51-46-0517 | Vent termination. |
WAC 51-46-0518 | Area of venting system. |
WAC 51-46-0519 | Multiple appliance venting. |
WAC 51-46-0520 | Existing venting system. |
WAC 51-46-0521 | Draft hoods. |
WAC 51-46-0522 | Gas venting into existing masonry chimneys. |
WAC 51-46-0523 | Installation. |
WAC 51-46-0524 | Mechanical draft systems. |
WAC 51-46-0525 | Venting through ventilating hoods and exhaust systems. |
WAC 51-46-0600 | Water supply and distribution. |
WAC 51-46-0603 | Cross-connection control. |
WAC 51-46-0604 | Materials. |
WAC 51-46-0608 | Water pressure, pressure regulators, pressure relief valves, and vacuum relief valves. |
WAC 51-46-0609 | Installation, testing, unions, and location. |
WAC 51-46-0610 | Size of potable water piping. |
WAC 51-46-0700 | Sanitary drainage. |
WAC 51-46-0701 | Materials. |
WAC 51-46-0704 | Fixture connections (drainage). |
WAC 51-46-0710 | Drainage of fixtures located below the next upstream manhole or below the main sewer level. |
WAC 51-46-0713 | Building sewers. |
WAC 51-46-0793 | Table 7-3 Drainage fixture unit values. |
WAC 51-46-0800 | Indirect wastes. |
WAC 51-46-0810 | Steam and hot water drainage condensers and sumps. |
WAC 51-46-0814 | Refrigeration wastes. |
WAC 51-46-0815 | Air-conditioning equipment. |
WAC 51-46-0900 | Vents. |
WAC 51-46-0903 | Materials. |
WAC 51-46-1000 | Traps and interceptors. |
WAC 51-46-1003 | Traps -- Described. |
WAC 51-46-1012 | Laundries. |
WAC 51-46-1300 | Medical gas systems. |
WAC 51-46-1301 | Scope. |
WAC 51-46-1302 | Definitions. |
WAC 51-46-1303 | Plan review. |
WAC 51-46-1304 | System installation and performance testing. |
WAC 51-46-1305 | System verification. |
WAC 51-46-1400 | Referenced standards. |
WAC 51-46-1401 | Referenced standards. |
WAC 51-46-1491 | Table 14-1 Standards for materials, equipment, joints and connections. |
WAC 51-46-97120 | Appendix M -- Storm drainage. |
WAC 51-46-97121 | General. |
WAC 51-46-97122 | Materials. |
WAC 51-46-97123 | Traps on storm drains and leaders. |
WAC 51-46-97124 | Leaders, conductors, and connections. |
WAC 51-46-97125 | Roof drains. |
WAC 51-46-97126 | Size of leaders, conductors, and storm drains. |
WAC 51-46-97127 | Values for continuous flow. |
WAC 51-46-97128 | Testing. |
WAC 51-46-97129 | Tables M-1 through M-3. |
OTS-4192.1
REPEALER
The following chapter of the Washington Administrative Code is repealed:
WAC 51-47-001 | Authority. |
WAC 51-47-002 | Purpose. |
WAC 51-47-003 | Uniform Plumbing Code Standards. |
WAC 51-47-007 | Exceptions. |
WAC 51-47-008 | Implementation. |