PROPOSED RULES
Original Notice.
Preproposal statement of inquiry was filed as WSR 12-03-107.
Title of Rule and Other Identifying Information: Adoption and amendment of the 2012 International Fire Code (IFC), chapter 51-54A WAC; and repeal of chapter 51-54 WAC, 2009 IFC, and all related amendments.
Hearing Location(s): Center Place Event Center, 2426 North Discovery Place, Spokane Valley, WA 99216, on September 14, 2012, at 10 a.m.; and at the DES Presentation Room, 1500 Jefferson S.E., Olympia, WA 98504, on September 21, 2012, at 10 a.m.
Date of Intended Adoption: November 9, 2012.
Submit Written Comments to: Ray Allshouse, Chair, State Building Code Council (SBCC), P.O. Box 41449, Olympia, WA 98504-41449 [98504-1449], e-mail sbcc@ga.wa.gov, fax (360) 586-9088, by September 21, 2012.
Assistance for Persons with Disabilities: Contact Peggy Bryden by September 7, 2012, (360) 407-9280.
Purpose of the Proposal and Its Anticipated Effects, Including Any Changes in Existing Rules: The proposed rules adopt the most recently published edition of the IFC with proposed amendments (chapter 51-54A WAC).
These rules replace the 2009 IFC and existing amendments (chapter 51-54 WAC which will be repealed).
Summary of Changes to Existing Rules:
1. Chapter 51-54 WAC will be repealed entirely, including the repeal of all state amendments.
2. Chapter 51-54A WAC will be adopted to include the adoption of the 2012 IFC.
3. The 2012 IFC was completely reorganized and renumbered by the International Code Council (ICC), from forty-seven to eighty chapter headings, with thirty chapters held in reserve for future use.
4. WAC 51-54A-0202 Definitions - this section will consolidate all definitions for the code into one chapter; definitions were previously scattered throughout the various chapters.
5. WAC 51-54A-0300 will duplicate the amendments previously adopted.
6. WAC 51-54A-0400 will duplicate the amendments previously adopted, except for revisions to remove any references to lockdown procedures involving fire service personnel.
7. WAC 51-54A-0500 will duplicate the amendments previously adopted.
8. WAC 51-54A-0600 will revise amendments to Sections 609 and 609.2 regarding Type 1 hoods, and will duplicate the other amendments previously adopted in Sections 600 and 609.3.
9. WAC 51-54A-0800 will duplicate the amendments previously adopted to Sections 806.1.1 and 806.1.2 and Table 806.1.2.
10. WAC 51-54A-0900 will duplicate seven amendments previously adopted; four previously adopted amendments will be deleted. Issues related to carbon monoxide detection devices are modified in Sections 908.7 and 908.7.1.
11. WAC 51-54A-1000 will duplicate the amendments previously adopted.
12. WAC 51-54A-1100 provides two options to address the issue of photoluminescent stair marking requirements.
13. WAC 51-54A-1200 through 51-54A-8000 are renumbered and will mainly duplicate the amendments previously adopted under their old chapter headings.
14. WAC 51-54A-5306 will adopt new medical gas standards.
The remaining changes are in response to editorial changes or reorganizational moves in the 2012 IFC.
Section | Chapter Title | Notes/Purpose | |
1. | 101 | Scope and general requirements | References the appendices. |
2. | 105 | Permits | Permit requirements. |
3. | 202 | General definitions | Provides definitions. |
4. | 307 | Open burning, recreational fires and portable outdoor fireplaces | Specifies permit and approval process for open burning and recreational fires. |
5. | 308 | Open flames | Regulates the use of candles. |
6. | 401 | General | Emergency planning. |
7. | 402 | Definitions | Referring definitions to Chapter 2. |
8. | 403 | Public assemblages and events | Planning for public events. |
9. | 404 | Fire safety and emergency plans | Fire safety and evacuation planning. |
10. | 405 | Emergency drills | Drill requirements. |
11. | 406 | Employee training and response procedures | Training requirements. |
12. | 407 | Hazard communication | Special provisions for hazardous materials. |
13. | 408 | Use and occupancy related requirements | Special provisions per occupancy group. |
14. | 503 | Fire apparatus access roads | Local adoption provisions. |
15. | 507 | Fire protection water supplies | Specifies fire flow requirements. |
16. | 508 | Fire command center | Separation requirements. |
17. | 605 | Electrical equipment, wiring and hazards | Solar PV power system requirements not adopted. |
18. | 609 | Commercial kitchen hoods | Specifies type one hood requirements/exceptions. |
19. | 806 | Decorative vegetation - new and existing buildings | Specifies natural cut tree requirements for indoor use. |
20. | 903 | Automatic sprinkler systems | Modifies exceptions in Groups E and R, and clarifies requirements for basements. |
21. | 907 | Fire alarm and detection systems | Specifies requirements for licensed boarding homes. |
22. | 908 | Emergency alarm systems | Specifies requirements/exceptions for CO alarms. |
23. | 909 | Elevator hoistway pressurization alternative | Pressurization system requirements. |
24. | 915 | Alerting systems | Sets standard for alerting systems. |
25. | 1007 | Accessible means of egress | Guidelines for egress in accessible parking spaces. |
26. | 1008 | Doors, gates and turnstiles | Requirements for locks and latches in Group I-2. |
27. | 1009 | Stairways and handrails | Sets requirements/exceptions for certain stairways. |
28. | 1010 | Ramps | Provides exceptions for ramp accessibility. |
29. | 1018 | Corridors | Stipulates how air must move in corridors, and continuity of corridors. |
30. | 1021 | Number of exits and exit configurations | Allows an exception for travel distance where landing platforms for helistops are in place. |
31. | 1103 | Fire safety requirements for existing buildings | Sprinkler requirements for nightclubs and CO alarm requirements for Group I and Group R. |
32. | 1104 | Means of egress for existing buildings | Establishes requirements for photoluminescent stair markings (two options listed). |
33. | 3601 | Marinas -- Scope | Marina requirements; move definitions to Chapter 2. |
34. | 3602 | Definitions | Referring definitions to Chapter 2. |
35. | 3604 | Fire protection equipment | Sets requirements for certain firefighting equipment at marinas. |
36. | 5306 | Medical gas systems | Sets standards for compliance with medical gas maintenance and testing. |
37. | 5601 | General | Regulates explosives. |
38. | 5704 | Storage | Underground tank corrosion protection tied to WAC 173-360-305. |
39. | 5706 | Special operations | Requires coordination with department of ecology spill clean-up protocols. |
40. | 6108 | Fire protection | Requirements/exceptions for barbeques on decks. |
41. | 8000 | Referenced standards | Adopts one additional NFPA standard. |
42. | 8100 | Appendix K -- Wildland-urban-interface code | Specifies certain fire protection methods between the rural and urban boundaries. |
Reasons Supporting Proposal: RCW 19.27.031 and 19.27.074.
Statutory Authority for Adoption: RCW 19.27.031 and 19.27.074.
Statute Being Implemented: Chapters 19.27 and 34.05 RCW.
Rule is not necessitated by federal law, federal or state court decision.
Agency Comments or Recommendations, if any, as to Statutory Language, Implementation, Enforcement, and Fiscal Matters: The council is seeking comments on the issues proposed in the rules shown below.
Name of Proponent: SBCC, governmental.
Name of Agency Personnel Responsible for Drafting and Implementation: Joanne McCaughan, 1500 Jefferson S.E., P.O. Box 41449, Olympia, WA (360) 9279 [407-9279]; and Enforcement: Local jurisdictions.
A small business economic impact statement has been prepared under chapter 19.85 RCW.
Impact on Small Business: The proposed rule adopts the updated 2012 edition of the IFC. Since 1985 the SBCC has been required to update to new editions of the building code, per RCW 19.27.074. The ICC updates the codes, including the IFC, every three years. Their process involves development of interest groups within the design and construction industry and from governmental organizations.
The 2012 IFC contains about sixty significant changes as compared to the 2009 IFC. According to the Proposed Changes to the 2009 Edition of the IFC, published by the ICC, less than seven percent of the approved amendments result in more than a minor increase in cost of construction; most amendments have no impact on construction costs. The primary effect of the amendments is improvement of the code. The objective of the amendments is to create a consistent regulatory system.
The SBCC appointed a technical advisory group (TAG) to review the 2012 IFC, including the significant changes, the applicability of the existing statewide amendments, and several proposed new state amendments (seven new proposals for 2012, plus two tabled proposals from 2011). The TAG included fire service personnel from the state and local regulatory community, local building officials, representatives of the multifamily housing and construction industries, and the fire protection industry. Small business was represented through these appointments. All TAG meetings are open to the public and small businesses are notified; several chose to participate in the review of code amendment proposals.
These proposed rules are anticipated to be job neutral, although there would be some temporary work for installation jobs for certain trades people, for example, if the luminescent path markings requirements are adopted. Where the SBCC found the cost of compliance for small businesses to be disproportionate, the proposed rule mitigates the cost.
Section I: Introduction/Compliance with the Rules: The 2009 IFC with state amendments is currently in effect, codified as chapter 51-54 WAC; for the 2012 code adoption cycle, SBCC staff and the TAG recommend that the newly reorganized IFC be adopted as chapter 51-54A WAC for greater efficiency. For a complete list of all current state amendments to the Fire Code see this link to the WAC language.
The adopted state amendments add flexibility and clarity to the code. Some of the rules may represent a savings for small business building owners and operators, while other rules may incur costs for these entities.
The 2012 edition of the IFC contains about sixty significant revisions from the current 2009 edition. In addition, several proposed state amendments to the code address specific issues, for example:
Carbon monoxide alarm requirements in residential settings; based on legislative requirements that are more protective/prescriptive than the model code. Minimal new impact since the law has been in effect since 2010.
Luminous egress path markings for existing high rise buildings; following the model code to require the markings would incur costs on existing building owners according to testimony provided to the council in November 2011 and to the fire code TAG. Alternatively, permanent adoption of the current emergency rule, in lieu of adopting the model code language, would exempt existing buildings from the requirement to install luminous markings and thus eliminate cost concerns.
Elevator pressurization; the current state amendment to the IFC is deleted and the language from Section 909.21 of the 2012 International Building Code (IBC) is adopted as a state amendment to the IFC.
Construction costs may increase for some building projects (for anticipated impacts see the small business economic impact statement for the IBC).
New code requirements in the 2012 IFC regarding photo voltaic solar installation were not adopted due in part to anticipated economic impact on the solar industry. The fire code TAG recommended that a special TAG be formed to address the issues and develop proposed language for adoption in 2013; the special TAG will be formed in the fall of 2012.
Section II: Compliance Costs for Washington Businesses: The adoption of the updated IFC and state amendments may result in some cost outlay for small businesses in construction industries for specific building projects, for a transition period.
The 2012 edition of the IFC costs $88 on CD and $98.75 for a loose leaf binder. The codes are also available to view on-line at no cost. There is also an on-line subscription service available, at a per user cost.
Some small businesses could see an increase in revenue.
The overall impact would be positive, because the 2012 IFC has been completely reorganized to correspond with certain elements and chapters in the IBC. With the reorganization, the new edition will be easier for businesses and local officials to find the information they need to ensure code compliance and building safety. This change will result in greater efficiency in project planning and development, and an anticipated reduction in review and approval times. The degree of impact diminishes during the code cycle as rules become familiar and construction practices adjust and are accepted.
Costs of Equipment, Supplies, Labor, Professional Services, and Increased Administrative Costs: The costs for compliance with the 2012 IFC are specific to the project and the plan.
2012 IFC Chapter 4 Emergency Planning and Preparedness: In 2009 the SBCC adopted a complete revision of the IFC Chapter 4; that chapter included requirements for Group E lockdown drills and other related responsibilities for fire personnel. The proposed state amendment for 2012 would remove those lockdown-related requirements, which are considered to be the purview and responsibility of the law enforcement community rather than the fire service. This amendment would have no impact on, and would be cost neutral to, small business.
2012 IFC Section [M] 609.2 Commercial Kitchen Hoods: The amendment was referred by the mechanical TAG. It is a clarification of the requirements for hood types and provides a table to identify the type of hood required for domestic cooking, based on the use of the space and the type of cooking. It provides for an additional exception to eliminate the need for a hood where certain electric cooking appliances are being used, but do not produce heavy grease laden vapors as documented by an approved testing agency. There would be some savings to certain businesses that would no longer need to install a Type 1 hood.
Assumptions:
• | EQUIPMENT: TYPE TWO HOODS ARE LESS EXPENSIVE. |
• | SUPPLIES: N/A. |
• | MATERIAL: LABOR: N/A. |
• | PROFESSIONAL SERVICES: FEWER INSPECTIONS WOULD BE REQUIRED. |
• | ADMINISTRATIVE COSTS: LESS RECORDKEEPING WOULD BE REQUIRED. |
2012 IFC Section 903.2.11.1.3 Basements: The 2012 IFC modified language requiring fire sprinklers in basements where certain obstructions are present that restrict the application of water from hose streams; the state amendment modifies the language to situations where the exit access travel distance is increased beyond seventy-five feet. This proposed modification is cost neutral.
2012 IFC Section 1104.24 Egress Path Markings: The 2012
IFC requires installation of photoluminescent marking systems
in the stairways of existing high-rise buildings except for
certain historic buildings. The SBCC has previously adopted
an emergency rule to eliminate this requirement due to cost
concerns expressed by some building owners. In response,
photoluminescent industry representatives provided information
to the TAG on May 4, 2012, indicating that there is a broad
range of products available, and that the products can be
installed at a reasonable price. While cost estimates range
from $1,400 to $5,000 per stairwell per floor, actual
installation experience has shown costs to be lower. For
example, a hospital recently installed the materials at a cost
of $954 per stairwell. According to the PLA, costs for nine
recent projects averaged $1,277 per stairwell. Given this
information, the TAG recommended that the luminescent markings
should be required in high rise buildings with the adoption of
the 2012 Fire Code.
Assumptions:
• | EQUIPMENT: MECHANICAL APPLICATION OF PRODUCTS AND MATERIALS. |
• | SUPPLIES: VARIABLE ACCORDING TO THE NEEDS OF THE CUSTOMER. |
• | MATERIAL: VARIABLE ACCORDING TO THE SPECIFIC LOCATION. |
• | LABOR: FIRE PROTECTION SPECIALISTS TO ENSURE INSTALLATION IS ACCORDING TO PUBLISHED SPECIFICATIONS AND STANDARDS. |
• | PROFESSIONAL SERVICES: BIDDING BY FIRE STOP CONTRACTOR TO IDENTIFY OPTIONS AND ENSURE APPROPRIATE SYSTEMS/PRODUCTS ARE USED. |
• | ADMINISTRATIVE COSTS: ONGOING MAINTENANCE TO ENSURE RELIABILITY. |
Section III: Analysis of Proportionate Impact on Small Businesses.
The Impact on Small Businesses Compared to the Largest Businesses in the State Will Not Be Disproportionate: The cost of compliance is a proportionate incremental cost, in relation to hours of labor, or costs per employee. The incremental cost of meeting the 2012 IFC, will have a proportionate impact on building and construction businesses. Building projects tend to be unique to type of construction, building type, building site, as well as size of the project. Costs for design and construction will be distributed among the general contractors and subcontractors. Further, construction industry businesses fit primarily into the category of small business. Where an industry has a significant number of large businesses, the costs of compliance for large businesses are proportional to the number of employees in any size business. The majority of Washington state firms in the design and construction fields qualify as small businesses. The incremental costs of meeting the 2012 Fire Code are generally proportionate between large and small businesses.
Section IV: Small Business Involvement and Impact Reduction Efforts: A representative of the construction industry served on the IFC TAG. Members of the luminescent marking industry provided information to the TAG regarding the code requirements for existing buildings in the IFC. Representatives of the housing industry also served on the TAG and discussed impacts.
Section V: Number of Affected Businesses in Washington:
Businesses Impacted by Updated Fire Code | |||
Type of Business | NAICS CODE # |
# IN STATE (UP TO 49 Employees) |
# IN STATE (50 OR MORE Employees) |
Multifamily Housing Construction | 236116 |
77 |
0 |
Industrial Building Construction | 236210 |
89 |
6 |
Commercial and Institutional Building Construction | 236220 |
1305 |
40 |
Roofing Contractors | 238160 |
973 |
7 |
Architects | 541310 | 602 | 16 |
Engineers | 541330 | 1665 | 96 |
Testing Labs | 541380 | 191 | 14 |
Fire Protection | 922160 | 258 | 6 |
According to the Firestop Contractors International Association, in some cases it may be possible for building maintenance personnel to install the materials according to the manufacturers' instructions. However, according to most manufacturers a certified installer who has been trained in the application specifications is preferred. This is to ensure surface preparation and other requirements are addressed, as well as specific location for the materials and devices. This ensures that products will perform well throughout the life of the product without undue maintenance costs.
A copy of the statement may be obtained by contacting Joanne T. McCaughan, P.O. Box 41449, Olympia, WA 98504-1449, phone (360) 407-9279, fax (360) 586-9088, e-mail joanne.mccaughan@des.wa.gov. See the small business economic impact statement by following this link: 2012 Fire Code SBEIS.
The SBCC is not one of the agencies identified as required to prepare a school district impact statement.
A cost-benefit analysis is not required under RCW 34.05.328. The SBCC is not one of the agencies identified as required to prepare an analysis.
July 31, 2012
C. Ray Allshouse
Council Chair
OTS-4861.2
STATE BUILDING CODE ADOPTION AND AMENDMENT OF THE 2012 EDITION OF THE INTERNATIONAL FIRE CODE
[]
[]
[]
Codes referenced which are not adopted through RCW 19.27.031 or chapter 19.27A RCW shall not apply unless specifically adopted by the authority having jurisdiction. The 2012 International Wildland Urban Interface Code is included in this code as Section 8100 with amendments found in Appendix Chapter K.
The provisions of this code do not apply to temporary growing structures used solely for the commercial production of horticultural plants including ornamental plants, flowers, vegetables, and fruits. "Temporary growing structure" means a structure that has the sides and roof covered with polyethylene, polyvinyl, or similar flexible synthetic material and is used to provide plants with either frost protection or increased heat retention. A temporary growing structure is not considered a building for purposes of this code.
The provisions of this code do not apply to the construction, alteration, or repair of temporary worker housing except as provided by rule adopted under chapter 70.114A RCW or chapter 37, Laws of 1998 (2SSB 6168). "Temporary worker housing" means a place, area, or piece of land where sleeping places or housing sites are provided by an employer for his or her employees or by another person, including a temporary worker housing operator, who is providing such accommodations for employees, for temporary, seasonal occupancy, and includes "labor camps" under RCW 70.54.110.
The manufacture, storage, handling, sale and use of fireworks shall be governed by chapter 70.77 RCW and by chapter 212-17 WAC and local ordinances consistent with chapter 212-17 WAC.
[]
[]
101.2.1 Appendices. Provisions in the appendices shall not
apply unless specifically adopted. The State Building Code
Council has determined that a local ordinance adopting
Appendix K Wildland Urban Interface Code may be adopted by any
local government upon notification of the council.
[]
SECTION 105 SCOPE AND GENERAL REQUIREMENTS
105.1.1 Permits required. Any property owner or authorized
agent who intends to conduct an operation or business, or
install or modify systems and equipment, which is regulated by
this code, or to cause any such work to be done shall first
make application to the fire code official and obtain the
required permit.
[]
SECTION 202 GENERAL DEFINITIONS
ADULT FAMILY HOME means a dwelling in which a person or persons
provide personal care, special care, room and board to more
than one but not more than six adults who are not related by
blood or marriage to the person or persons providing the
services.
ALERT SIGNAL. A distinctive signal indicating the need for
trained personnel and occupants to initiate a specific action,
such as shelter-in-place.
ALERT SYSTEM. Approved devices, equipment and systems or
combinations of systems used to transmit or broadcast an alert
signal.
CHILD DAY CARE, shall, for the purposes of these regulations,
mean the care of children during any period of a 24-hour day.
COVERED BOAT MOORAGE is a pier or system of floating or fixed
access ways to which vessels on water may be secured and any
portion of which are covered by a roof.
ELECTRICAL CODE is the National Electrical Code, promulgated by
the National Fire Protection Association, as adopted by rule
or local ordinance under the authority of chapter 19.28 RCW.
EMERGENCY DRILL. An exercise performed to train staff and
occupants and to evaluate their efficiency and effectiveness
in carrying out emergency procedures.
EXISTING. Buildings, facilities or conditions that are already
in existence, constructed or officially authorized prior to
the adoption of this code.
FAMILY CHILD DAY CARE HOME is a child day care facility, licensed
by the state, located in the dwelling of the person or persons
under whose direct care and supervision the child is placed,
for the care of twelve or fewer children, including children
who reside at the home.
GRAVITY-OPERATED DROP OUT VENTS are automatic smoke and heat vents
containing heat-sensitive glazing designed to shrink and drop
out of the vent openings when exposed to fire.
HOSPICE CARE CENTERS. A building or portion thereof used on a
24-hour basis for the provision of hospice services to
terminally ill inpatients.
MOTOR VEHICLE. Includes, but not limited to, a vehicle, machine,
tractor, trailer or semitrailer, or any combination thereof,
propelled or drawn by mechanical power and designed for use
upon the highways in the transportation of passengers or
property. It does not include a vehicle, locomotive or car
operated exclusively on a rail or rails, or a trolley bus
operated by electric power derived from a fixed overhead wire,
furnishing local passenger transportation similar to
street-railway service. The term "motor vehicle" also
includes freight containers or cargo tanks used, or intended
for use, in connection with motor vehicles.
NIGHTCLUB. An A-2 Occupancy use under the 2006 International
Building Code in which the aggregate area of concentrated use
of unfixed chairs and standing space that is specifically
designated and primarily used for dancing or viewing
performers exceeds three hundred fifty square feet, excluding
adjacent lobby areas. "Nightclub" does not include theaters
with fixed seating, banquet halls, or lodge halls.
OCCUPANCY CLASSIFICATION. For the purposes of this code, certain
occupancies are defined as follows:
Educational Group E. Educational Group E Occupancy includes,
among others, the use of a building or structure, or a portion
thereof, by six or more persons at any one time for
educational purposes through the 12th grade. Religious
educational rooms and religious auditoriums, which are
accessory to places of religious worship in accordance with
Section 508.3.1 of the International Building Code and have
occupant loads of less than 100, shall be classified as Group
A-3 occupancies.
DAY CARE. The use of a building or structure, or portion
thereof, for educational, supervision or personal care
services for more than five children older than 2 1/2 years of
age, shall be classified as an E Occupancy.
EXCEPTION: | Family child day care homes licensed by the state of Washington for the care of twelve or fewer children shall be classified as Group R-3. |
Group I-1. This occupancy shall include buildings, structures or parts thereof housing more than 16 persons, on a 24-hour basis, who because of age, mental disability or other reasons, live in a supervised residential environment that provides personal care services. The occupants are capable of responding to an emergency situation without physical assistance from staff. This group shall include, but not be limited to, the following:
Alcohol and drug centers
Assisted living facilities
Congregate care facilities
Convalescent facilities
Group homes
Halfway houses
Residential board and care facilities
Social rehabilitation facilities
A facility such as the above with five or fewer persons and adult family homes licensed by Washington state shall be classified as a Group R-3 or shall comply with the International Residential Code in accordance with Section 101.2 of the International Building Code.
A facility such as the above, providing licensed care to clients in one of the categories listed in IBC Section 310.1 licensed by Washington state shall be classified as Group R-2.
Group I-2. This occupancy shall include buildings and structures used for medical, surgical, psychiatric, nursing or custodial care for persons who are not capable of self-preservation. This group shall include, but not be limited to, the following:
Child care facilities
Detoxification facilities
Hospice care centers
Hospitals
Mental hospitals
Nursing homes
A facility such as the above providing licensed care to clients in one of the categories listed in IBC Section 310.1 licensed by Washington state shall be classified as Group R-2.
Group I-3. (Remains as printed in the IFC.)
Group I-4. Day care facilities. This group shall include buildings and structures occupied by persons of any age who receive custodial care for less than 24 hours by individuals other than parents or guardians, relatives by blood, marriage, or adoption, and in a place other than the home of the person cared for. A facility such as the above with five or fewer persons shall be classified as Group R-3 or shall comply with the International Residential Code in accordance with Section 101.2 of the International Building Code. Places of worship during religious functions are not included.
Adult care facility. A facility that provides accommodations for less than 24 hours for more than five unrelated adults and provides supervision and personal care services shall be classified as Group I-4.
EXCEPTION: | Where the occupants are capable of responding to an emergency situation without physical assistance from the staff, the facility shall be classified as Group R-3. |
EXCEPTIONS: | 1. A child day care facility that provides care for more than five but no more than 100 children 2 1/2 years or less of age, where the rooms in which the children are cared for are located on a level of exit discharge serving such rooms and each of these child care rooms has an exit door directly to the exterior, shall be classified as Group E. |
2. Family child day care homes licensed by Washington state for the care of 12 or fewer children shall be classified as Group R-3. |
R-1 Residential occupancies containing sleeping units where the occupants are primarily transient in nature, including:
Boarding houses (transient)
Hotels (transient)
Motels (transient)
Congregate living facilities (transient) with 10 or fewer occupants are permitted to comply with the construction requirements for Group R-3.
R-2 Residential occupancies containing sleeping units or more than two dwelling units where the occupants are primarily permanent in nature, including:
Apartment houses
Boarding houses (nontransient)
Boarding homes as licensed by Washington state under chapter 388-78A WAC
Convents
Dormitories
Fraternities and sororities
Hotels (nontransient)
Live/work units
Motels (nontransient)
Monasteries
Residential treatment facilities as licensed by Washington state under chapter 246-337 WAC
Vacation timeshare properties
Congregate living facilities with sixteen or fewer occupants are permitted to comply with the construction requirements for Group R-3.
R-3 Residential occupancies where the occupants are primarily permanent in nature and not classified as Group R-1, R-2, R-4 or I, including: Buildings that do not contain more than two dwelling units. Adult care facilities that provide accommodations for five or fewer persons of any age for less than 24 hours. Child care facilities that provide accommodations for five or fewer persons of any age for less than 24 hours. Congregate living facilities with sixteen or fewer persons. Adult care within a single-family home, adult family homes and family child day care homes are permitted to comply with the International Residential Code.
Foster family care homes licensed by Washington state are permitted to comply with the International Residential Code, as an accessory use to a dwelling, for six or fewer children including those of the resident family.
R-4 Classification is not adopted. Any reference in this code to R-4 does not apply.
PORTABLE SCHOOL CLASSROOM. A structure, transportable in one or
more sections, which requires a chassis to be transported, and
is designed to be used as an educational space with or without
a permanent foundation. The structure shall be trailerable
and capable of being demounted and relocated to other
locations as needs arise.
RECALL SIGNAL. An electrically or mechanically operated signal
used to recall occupants after an emergency drill or to
terminate a shelter-in-place event that shall be distinct from
any alarm or alert signal used to initiate an emergency plan,
or other signals.
SHELTER-IN-PLACE. An emergency response used to minimize
exposure of facility occupants to chemical or environmental
hazards by taking refuge in predetermined interior rooms or
areas where actions are taken to isolate the interior
environment from the exterior hazard.
[]
307.2.1 Authorization. Where required by state or local law
or regulations, open burning shall only be permitted with
prior approval from the state or local air and water quality
management authority, provided that all conditions specified
in the authorization are followed. See also chapter 173-425 WAC.
307.4.2 Recreational fires. Recreational fires shall not be
conducted within 25 feet of a structure or combustible
material. Conditions which could cause a fire to spread
within 25 feet of a structure shall be eliminated prior to
ignition. See also chapter 173-425 WAC.
[]
308.1.4 Open-flame cooking devices. This section is not
adopted.
308.1.7 Religious ceremonies. Participants in religious
ceremonies shall not be precluded from carrying hand-held
candles. See RCW 19.27.031(3).
308.1.9 Aisles and exits. Candles shall be prohibited in
areas where occupants stand, or in an aisle or exit.
EXCEPTION: | Candles used in religious ceremonies. |
[]
401.1 Scope. Reporting of emergencies, coordination with
emergency response forces, emergency plans and procedures for
managing or responding to emergencies shall comply with the
provisions of this section.
EXCEPTION: | Firms that have approved on-premises firefighting organizations and that are in compliance with approved procedures for fire reporting. |
401.3 Emergency responder notification. Notification of
emergency responders shall be in accordance with Sections
401.3.1 through 401.3.3.
401.3.1 Fire events. In the event an unwanted fire occurs on
a property, the owner or occupant shall immediately report
such condition to the fire department.
401.3.2 Alarm activations. Upon activation of a fire alarm
signal, employees or staff shall immediately notify the fire
department.
401.3.3 Delayed notification. A person shall not, by verbal
or written directive, require any delay in the reporting of a
fire to the fire department.
401.4 Required plan implementation. In the event an unwanted
fire is detected in a building or a fire alarm activates, the
emergency plan shall be implemented.
401.5 Making false report. A person shall not give, signal or
transmit a false alarm.
401.6 Emergency evacuation drills. The sounding of a fire
alarm signal and the carrying out of an emergency evacuation
drill in accordance with the provisions of Section 405 shall
be allowed.
401.7 Unplanned evacuation. Evacuations made necessary by the
unplanned activation of a fire alarm system or by any other
emergency shall not be substituted for a required evacuation
drill.
401.8 Interference with fire department operations. It shall
be unlawful to interfere with, attempt to interfere with,
conspire to interfere with, obstruct or restrict the mobility
of or block the path of travel of a fire department emergency
vehicle in any way, or to interfere with, attempt to interfere
with, conspire to interfere with, obstruct or hamper any fire
department operation.
[]
ALARM SIGNAL.
ALERT SIGNAL.
ALERT SYSTEM.
EMERGENCY DRILL.
SHELTER-IN-PLACE.
RECALL SIGNAL.
[]
403.1 Fire watch personnel. When, in the opinion of the fire
code official, it is essential for public safety in a place of
assembly or any other place where people congregate, because
of the number of persons, or the nature of the performance,
exhibition, display, contest or activity, the owner, agent or
lessee shall provide one or more fire watch personnel, as
required and approved, to remain on duty during the times such
places are open to the public, or when such activity is being
conducted.
403.1.1 Duties. Fire watch personnel shall keep diligent
watch for fires, obstructions to means of egress and other
hazards during the time such place is open to the public or
such activity is being conducted and take prompt measures for
remediation of hazards, extinguishment of fires that occur and
assist in the evacuation of the public from the structures.
403.2 Public safety plan. In other than Group A or E
occupancies, where the fire code official determines that an
indoor or outdoor gathering of persons has an adverse impact
on public safety through diminished access to buildings,
structures, fire hydrants and fire apparatus access roads or
where such gatherings adversely affect public safety services
of any kind, the fire code official shall have the authority
to order the development of, or prescribe a plan for, the
provision of an approved level of public safety.
403.2.1 Contents. The public safety plan, where required by
Section 403.2, shall address such items as emergency vehicle
ingress and egress, fire protection, emergency medical
services, public assembly areas and the directing of both
attendees and vehicles (including the parking of vehicles),
vendor and food concession distribution, and the need for the
presence of law enforcement, and fire and emergency medical
services personnel at the event.
403.3 Crowd managers. Trained crowd managers shall be
provided for facilities or events where more than 1,000
persons congregate. The minimum number of crowd managers
shall be established at a ratio of one crowd manager to every
250 persons. Where approved by the fire code official, the
ratio of crowd managers shall be permitted to be reduced where
the facility is equipped throughout with an approved automatic
sprinkler system or based upon the nature of the event.
[]
404.1 General. Fire safety, evacuation, shelter-in-place
plans and associated drills shall comply with the requirements
of Sections 404.2 through 404.5.1.
404.2 Fire safety and evacuation plans. Fire safety and
evacuation plans shall comply with the requirements of
Sections 404.2.1 through 404.2.2.2.
404.2.1 Where required. An approved fire safety and
evacuation plan shall be prepared and maintained for the
following occupancies and buildings.
1. Group A having an occupant load of 100 or more.
2. Group B buildings having an occupant load of 500 or more persons or more than 100 persons above or below the lowest level of exit discharge.
3. Group E.
4. Group F buildings having an occupant load of 500 or more persons or more than 100 persons above or below the lowest level of exit discharge.
5. Group H.
6. Group I.
7. Group R-1.
8. Group R-2 college and university buildings. Boarding homes, group homes, and residential treatment facilities licensed by the state of Washington.
9. High-rise buildings.
10. Group M buildings having an occupant load of 500 or more persons or more than 100 persons above or below the lowest level of exit discharge.
11. Covered malls exceeding 50,000 square feet (4645 m2) in aggregate floor area.
12. Underground buildings.
13. Buildings with an atrium and having an occupancy in Group A, E or M.
404.2.2 Contents. Fire evacuation and safety plan contents
shall be in accordance with Sections 404.2.2.1 and 404.2.2.2.
404.2.2.1 Fire evacuation plans. Fire evacuation plans shall
include the following:
1. Emergency egress or escape routes and whether evacuation of the building is to be complete or, where approved, by selected floors or areas only.
2. Procedures for employees who must remain to operate critical equipment before evacuating.
3. Procedures for assisted rescue for persons unable to use the general means of egress unassisted.
4. Procedures for accounting for employees and occupants after evacuation has been completed.
5. Identification and assignment of personnel responsible for rescue or emergency medical aid.
6. The preferred and any alternative means of notifying occupants of a fire.
7. The preferred and any alternative means of reporting fires and other emergencies to the fire department or designated emergency response organization.
8. Identification and assignment of personnel who can be contacted for further information or explanation of duties under the plan.
9. A description of the emergency voice/alarm communication system alert tone and preprogrammed voice messages, where provided.
404.2.2.2 Fire safety plans. Fire safety plans shall include
the following:
1. The procedure for reporting a fire or other emergency.
2. The life safety strategy and procedures for notifying, relocating or evacuating occupants, including occupants who need assistance.
3. Site plans indicating the following:
3.1. The occupancy assembly point.
3.2. The locations of fire hydrants.
3.3. The normal routes of fire department vehicle access.
4. Floor plans identifying the locations of the following:
4.1. Exits.
4.2. Primary evacuation routes.
4.3. Secondary evacuation routes.
4.4. Accessible egress routes.
4.5. Areas of refuge.
4.6. Exterior areas for assisted rescue.
4.7. Manual fire alarm boxes.
4.8. Portable fire extinguishers.
4.9. Occupant-use hose stations.
4.10. Fire alarm annunciators and controls.
5. A list of major fire hazards associated with the normal use and occupancy of the premises, including maintenance and housekeeping procedures.
6. Identification and assignment of personnel responsible for maintenance of systems and equipment installed to prevent or control fires.
7. Identification and assignment of personnel responsible for maintenance, housekeeping and controlling fuel hazard sources.
404.3 Shelter-in-place plans. Shelter-in-place plans shall
comply with the requirements of Sections 404.3.1 through
404.3.2.
404.3.1 Where required. A shelter-in-place plan shall be
prepared and maintained for all Group E occupancies.
EXCEPTION: | Day cares not colocated on a Group E campus. |
1. Identification of the procedures of initiating the shelter-in-place plan throughout the facility or campus.
2. Identification of prearranged alert and recall signals to notify all occupants.
3. Identification of procedures for reporting the facility is sheltering-in-place to the local emergency dispatch center.
4. A means of two-way communication between a central location and each secure area, and consideration for maintaining means of communication in absence of primary power.
5. Identification of protective security measures.
6. Location of emergency supplies.
7. Accountability procedures for staff to report the presence or absence of occupants.
8. Identification of crisis response team members in accordance with the National Incident Management System.
9. Actions to be taken in the event of a fire or medical emergency while sheltering-in-place.
404.4 Maintenance. Emergency plans shall be reviewed or
updated annually or as necessitated by changes in staff
assignments, occupancy or the physical arrangement of the
building.
404.5 Availability. Emergency plans shall be available in the
workplace for reference and review by employees, and copies
shall be furnished to the fire code official for review upon
request.
404.5.1 Distribution. The fire safety and evacuation plans
shall be distributed to the tenants and building service
employees by the owner or owner's agent. Tenants shall
distribute to their employees applicable parts of the fire
safety plan affecting the employees' actions in the event of a
fire or other emergency.
[]
405.1 General. Emergency drills complying with the provisions
of this section shall be conducted at least annually in the
occupancies listed in Section 404.2.1 or when required by the
fire code official. Drills shall be designed in cooperation
with the local authorities.
405.2 Frequency. Required emergency drills shall be held at
the intervals specified in Table 405.2 or more frequently
where necessary to familiarize all occupants with the drill
procedure.
405.2.1 Group E occupancies. The occupancy shall conduct at a
minimum the following drills during the year:
1. One drill using the school mapping information system.
EXCEPTION: | Day cares not colocated on a school campus. |
3. One shelter-in-place drill.
Emergency Drill Frequency and Participation
Group or Occupancy | Frequency | Participation |
Group A | Quarterly | Employees |
Group Bc | Annually | Employees |
Group E | Monthlya,e | All Occupants |
Group F | Annually | Employees |
Group I | Quarterly on each shift | Employeesb |
Group R-1 | Quarterly on each shift | Employees |
Group R-2f | Quarterly on each shift | Employees |
Group R-2d | Four Annually | All Occupants |
High-rise buildings | Annually | Employees |
aThe frequency shall be allowed to be modified in accordance with Section 408.3.2. | |
bFire and evacuation drills in residential care assisted living facilities shall include complete evacuation of the premises in accordance with Section 408.10.5. Where occupants receive habilitation or rehabilitation training, fire prevention and fire safety practices shall be included as part of the training program. | |
cGroup B buildings having an occupant load of 500 or more persons or more than 100 persons above or below the lowest level of exit discharge. | |
dApplicable to Group R-2 college and university buildings in accordance with Section 408.3. | |
eDay cares colocated on a Group E campus shall participate in emergency drills occurring on the campus. | |
fApplicable to boarding homes, group homes, and residential treatment facilities licensed by the state of Washington. |
405.4 Time. Drills shall be held at unexpected times and
under varying conditions to simulate the unusual conditions
that occur in case of an emergency.
405.5 Recordkeeping. Records shall be maintained of required
emergency evacuation drills and include the following
information:
1. Identity of the person conducting the drill.
2. Date and time of the drill.
3. Notification method used.
4. Staff members on duty and participating.
5. Number of occupants participating.
6. Special conditions simulated.
7. Problems encountered and corrective actions taken.
8. Weather conditions when occupants were evacuated.
9. Time required to accomplish complete evacuation, or shelter-in-place.
405.6 Notification. Where required by the fire code official,
prior notification of emergency drills shall be given to the
fire code official.
405.7 Initiation. Emergency drills shall be initiated in
accordance with Sections 405.7.1 through 405.7.2.
405.7.1 Fire evacuation drills. Where a fire alarm system is
provided, emergency evacuation drills shall be initiated by
activating the fire alarm system. The fire alarm monitoring
company shall be notified prior to the activation of the fire
alarm system for drills proposed and again at the conclusion
of the transmission and restoration of the fire alarm system
to normal mode.
EXCEPTION: | Drills conducted between the hours of 9:00 p.m. and 6:00 a.m., in Group R-2 boarding homes, group homes, and residential treatment facilities licensed by the state of Washington. |
405.8 Accountability. As building occupants arrive at the
assembly point, efforts shall be made to determine if all
occupants have been successfully evacuated and/or have been
accounted for in the shelter-in-place.
405.9 Recall and reentry. The recall signal initiation shall
be manually operated and under the control of the person in
charge of the premises or the official in charge of the
incident. No one shall reenter the premises until authorized
to do so by the official in charge.
[]
406.1 General. Employees in the occupancies listed in Section
404.2.1 shall be trained in the emergency procedures described
in their emergency plans. Training shall be based on these
plans and as described in Section 404.2 and 404.3.
406.2 Frequency. Employees shall receive training in the
contents of the emergency plans and their duties as part of
new employee orientation and at least annually thereafter.
Records shall be kept and made available to the fire code
official upon request.
406.3 Employee training program. Employees shall be trained
in fire prevention, evacuation, sheltering-in-place, and fire
safety in accordance with Sections 406.3.1 through 406.3.4.
406.3.1 Fire prevention training. Employees shall be apprised
of the fire hazards of the materials and processes to which
they are exposed. Each employee shall be instructed in the
proper procedures for preventing fires in the conduct of their
assigned duties.
406.3.2 Evacuation training. Employees shall be familiarized
with the fire alarm and evacuation signals, their assigned
duties in the event of an alarm or emergency, evacuation
routes, areas of refuge, exterior assembly areas and
procedures for evacuation.
406.3.3 Emergency shelter-in-place training. Where a facility
has a shelter-in-place plan, employees shall be trained on the
alert and recall signals, communication system, location of
emergency supplies, the use of the incident notification and
alarm system, and their assigned duties and procedures in the
event of an alarm or emergency.
406.3.4 Fire safety training. Employees assigned firefighting
duties shall be trained to know the locations and proper use
of portable fire extinguishers or other manual firefighting
equipment and the protective clothing or equipment required
for its safe and proper use.
[]
407.1 General. The provisions of Sections 407.2 through 407.7
shall be applicable where hazardous materials subject to
permits under Section 2701.5 are located on the premises or
where required by the fire code official.
407.2 Material safety data sheets. Material safety data
sheets (MSDS) for all hazardous materials shall be either
readily available on the premises as a paper copy, or where
approved, shall be permitted to be readily retrievable by
electronic access.
407.3 Identification. Individual containers of hazardous
materials, cartons or packages shall be marked or labeled in
accordance with applicable federal regulations. Buildings,
rooms and spaces containing hazardous materials shall be
identified by hazard warning signs in accordance with Section
2703.5.
407.4 Training. Persons responsible for the operation of
areas in which hazardous materials are stored, dispensed,
handled or used shall be familiar with the chemical nature of
the materials and the appropriate mitigating actions necessary
in the event of a fire, leak or spill. Responsible persons
shall be designated and trained to be liaison personnel for
the fire department. These persons shall aid the fire
department in preplanning emergency responses and
identification of the locations where hazardous materials are
located, and shall have access to material safety data sheets
and be knowledgeable in the site emergency response
procedures.
407.5 Hazardous materials inventory statement. Where required
by the fire code official, each application for a permit shall
include a hazardous materials inventory statement (HMIS) in
accordance with Section 2701.5.2.
407.6 Hazardous materials management plan. Where required by
the fire code official, each application for a permit shall
include a hazardous materials management plan (HMMP) in
accordance with Section 2701.5.1. The fire code official is
authorized to accept a similar plan required by other
regulations.
407.7 Facility closure plans. The permit holder or applicant
shall submit to the fire code official a facility closure plan
in accordance with Section 2701.6.3 to terminate storage,
dispensing, handling or use of hazardous materials.
[]
408.1 General. In addition to the other requirements of this
chapter, the provisions of this section are applicable to
specific occupancies listed herein.
408.2 Group A occupancies. Group A occupancies shall comply
with the requirements of Sections 408.2.1 and 408.2.2 and
Sections 401 through 406.
408.2.1 Seating plan. The fire safety and evacuation plans
for assembly occupancies shall include the information
required by Section 404.3 and a detailed seating plan,
occupant load and occupant load limit. Deviations from the
approved plans shall be allowed provided the occupant load
limit for the occupancy is not exceeded and the aisles and
exit accessways remain unobstructed.
408.2.2 Announcements. In theaters, motion picture theaters,
auditoriums and similar assembly occupancies in Group A used
for noncontinuous programs, an audible announcement shall be
made not more than 10 minutes prior to the start of each
program to notify the occupants of the location of the exits
to be used in the event of a fire or other emergency.
EXCEPTION: | In motion picture theaters, the announcement is allowed to be projected upon the screen in a manner approved by the fire code official. |
408.3.1 First emergency evacuation drill. The first emergency
evacuation drill of each school year shall be conducted within
10 days of the beginning of classes.
408.3.2 Emergency evacuation drill deferral. In severe
climates, the fire code official shall have the authority to
modify the emergency evacuation drill frequency specified in
Section 405.2.
408.3.3 Time of day. Emergency evacuation drills shall be
conducted at different hours of the day or evening, during the
changing of classes, when the school is at assembly, during
the recess or gymnastic periods, or during other times to
avoid distinction between drills and actual fires. In Group
R-2 college and university buildings, one required drill shall
be held during hours after sunset or before sunrise.
408.3.4 Assembly points. Outdoor assembly areas shall be
designated and shall be located a safe distance from the
building being evacuated so as to avoid interference with fire
department operations. The assembly areas shall be arranged
to keep each class separate to provide accountability of all
individuals.
408.4 Group H-5 occupancies. Group H-5 occupancies shall
comply with the requirements of Sections 408.4.1 through
408.4.4 and Sections 401 through 407.
408.4.1 Plans and diagrams. In addition to the requirements
of Sections 404 and 407.6, plans and diagrams shall be
maintained in approved locations indicating the approximate
plan for each area, the amount and type of HPM stored, handled
and used, locations of shutoff valves for HPM supply piping,
emergency telephone locations and locations of exits.
408.4.2 Plan updating. The plans and diagrams required by
Section 408.4.1 shall be maintained up to date and the fire
code official and fire department shall be informed of all
major changes.
408.4.3 Emergency response team. Responsible persons shall be
designated the on-site emergency response team and trained to
be liaison personnel for the fire department. These persons
shall aid the fire department in preplanning emergency
responses, identifying locations where HPM is stored, handled
and used, and be familiar with the chemical nature of such
material. An adequate number of personnel for each work shift
shall be designated.
408.4.4 Emergency drills. Emergency drills of the on-site
emergency response team shall be conducted on a regular basis
but not less than once every three months. Records of drills
conducted shall be maintained.
408.5 Group I-1 occupancies. Group I-1 occupancies shall
comply with the requirements of Sections 408.5.1 through
408.5.5 and Sections 401 through 406.
408.5.1 Fire safety and evacuation plan. The fire safety and
evacuation plan required by Section 404 shall include special
staff actions including fire protection procedures necessary
for residents and shall be amended or revised upon admission
of any resident with unusual needs.
408.5.2 Staff training. Employees shall be periodically
instructed and kept informed of their duties and
responsibilities under the plan. Such instruction shall be
reviewed by the staff at least every two months. A copy of
the plan shall be readily available at all times within the
facility.
408.5.3 Resident training. Residents capable of assisting in
their own evacuation shall be trained in the proper actions to
take in the event of a fire. The training shall include
actions to take if the primary escape route is blocked. Where
the resident is given rehabilitation or habilitation training,
training in fire prevention and actions to take in the event
of a fire shall be a part of the rehabilitation training
program. Residents shall be trained to assist each other in
case of fire to the extent their physical and mental abilities
permit them to do so without additional personal risk.
408.5.4 Drill frequency. Emergency evacuation drills shall be
conducted at least six times per year, two times per year on
each shift. Twelve drills shall be conducted in the first
year of operation. Drills are not required to comply with the
time requirements of Section 405.4.
408.5.5 Resident participation. Emergency evacuation drills
shall involve the actual evacuation of residents to a selected
assembly point.
408.6 Group I-2 occupancies. Group I-2 occupancies shall
comply with the requirements of Sections 408.6.1 and 408.6.2
and Sections 401 through 406. Drills are not required to
comply with the time requirements of Section 405.4.
408.6.1 Evacuation not required. During emergency evacuation
drills, the movement of patients to safe areas or to the
exterior of the building is not required.
408.6.2 Coded alarm signal. When emergency evacuation drills
are conducted after visiting hours or when patients or
residents are expected to be asleep, a coded announcement is
allowed instead of audible alarms.
408.7 Group I-3 occupancies. Group I-3 occupancies shall
comply with the requirements of Sections 408.7.1 through
408.7.4 and Sections 401 through 406.
408.7.1 Employee training. Employees shall be instructed in
the proper use of portable fire extinguishers and other manual
fire suppression equipment. Training of new staff shall be
provided promptly upon entrance on duty. Refresher training
shall be provided at least annually.
408.7.2 Staffing. Group I-3 occupancies shall be provided
with 24-hour staffing. Staff shall be within three floors or
300 feet (91,440 mm) horizontal distance of the access door of
each resident housing area. In Use Conditions 3, 4 and 5, as
defined in Chapter 2, the arrangement shall be such that the
staff involved can start release of locks necessary for
emergency evacuation or rescue and initiate other necessary
emergency actions within 2 minutes of an alarm.
EXCEPTION: | Staff shall not be required to be within three floors or 300 feet (91,440 mm) in areas in which all locks are unlocked remotely and automatically in accordance with Section 408.4 of the International Building Code. |
408.7.4 Keys. Keys necessary for unlocking doors installed in
a means of egress shall be individually identifiable by both
touch and sight.
408.8 Group R-1 occupancies. Group R-1 occupancies shall
comply with the requirements of Sections 408.8.1 through
408.8.3 and Sections 401 through 406.
408.8.1 Evacuation diagrams. A diagram depicting two
evacuation routes shall be posted on or immediately adjacent
to every required egress door from each hotel, motel or
dormitory sleeping unit.
408.8.2 Emergency duties. Upon discovery of a fire or
suspected fire, hotel, motel and dormitory employees shall
perform the following duties:
1. Activate the fire alarm system, where provided.
2. Notify the public fire department.
3. Take other action as previously instructed.
408.8.3 Fire safety and evacuation instructions. Information
shall be provided in the fire safety and evacuation plan
required by Section 404 to allow guests to decide whether to
evacuate to the outside, evacuate to an area of refuge, remain
in place, or any combination of the three.
408.9 Group R-2 occupancies. Group R-2 occupancies shall
comply with the requirements of Sections 408.9.1 through
408.9.3 and Sections 401 through 406.
408.9.1 Emergency guide. A fire emergency guide shall be
provided which describes the location, function and use of
fire protection equipment and appliances accessible to
residents, including fire alarm systems, smoke alarms, and
portable fire extinguishers. The guide shall also include an
emergency evacuation plan for each dwelling unit.
408.9.2 Maintenance. Emergency guides shall be reviewed and
approved in accordance with Section 401.2.
408.9.3 Distribution. A copy of the emergency guide shall be
given to each tenant prior to initial occupancy.
408.10 Group R-4 occupancies. This section is not adopted.
408.11 Covered mall buildings. Covered mall buildings shall
comply with the provisions of Sections 408.11.1 through
408.11.3.
408.11.1 Lease plan. A lease plan shall be prepared for each
covered mall building. The plan shall include the following
information in addition to that required by Section 404.3.2:
1. Each occupancy, including identification of tenant.
2. Exits from each tenant space.
3. Fire protection features, including the following:
3.1. Fire department connections.
3.2. Fire command center.
3.3. Smoke management system controls.
3.4. Elevators, elevator machine rooms and controls.
3.5. Hose valve outlets.
3.6. Sprinkler and standpipe control valves.
3.7. Automatic fire-extinguishing system areas.
3.8. Automatic fire detector zones.
3.9. Fire barriers.
408.11.1.1 Submittal. The lease plan shall be submitted to
the fire code official, and shall be maintained on-site for
immediate reference by responding fire service personnel.
408.11.1.2 Revisions. The lease plans shall be reviewed and
revised annually or as often as necessary to keep them
current. Modifications or changes in tenants or occupancies
shall not be made without prior approval of the fire code
official and building official.
408.11.2 Tenant identification. Each occupied tenant space
provided with a secondary exit to the exterior or exit
corridor shall be provided with tenant identification by
business name and/or address. Letters and numbers shall be
posted on the corridor side of the door, be plainly legible
and shall contrast with their background.
EXCEPTION: | Tenant identification is not required for anchor stores. |
1. Kept free from the storage of any materials.
2. Separated from the remainder of the building by partitions of at least 0.5 inch-thick (12.7 mm) gypsum board or an approved equivalent to the underside of the ceiling of the adjoining tenant spaces.
3. Without doors or other access openings other than one door that shall be kept key locked in the closed position except during that time when opened for inspection.
4. Kept free from combustible waste and be broom swept clean.
[]
503.1 Where required. Fire apparatus access roads shall be
provided and maintained in accordance with locally adopted
street, road, and access standards.
503.1.1 Buildings and facilities, is not adopted.
503.1.2 Additional access, is not adopted.
503.1.3 High-piled storage, is not adopted.
503.2 Specifications. This section is not adopted.
503.3 Marking. This section is not adopted.
503.4 Obstruction of fire apparatus access roads. This
section is not adopted.
503.4.1 Traffic calming devices. This section is not adopted.
[]
507.3 Fire flow. Fire flow requirements for buildings or
portions of buildings and facilities shall be determined by an
approved method.
EXCEPTION: | Fire flow is not required for structures under 500 square feet with a B, U or R-1 occupancy where structures are at least 30 feet from any other structure and are used only for recreation. |
[]
508.1.2 Separation. The fire command center shall be
separated from the remainder of the building by not less than
a 2-hour fire barrier constructed in accordance with Section
707 of the International Building Code or horizontal assembly
constructed in accordance with Section 712 of the
International Building Code, or both.
[]
605.11 Solar photovoltaic power systems. This section is not
adopted.
[]
[M] 609.2 Where required. A Type I hood shall be installed at
or above all commercial cooking appliances and domestic
cooking appliances used for commercial purposes that produce
grease laden vapors.
EXCEPTIONS: | 1. A Type I hood shall not be required to be installed in R-2 occupancies licensed by the state of Washington. |
2. A Type I hood shall not be required for an electric cooking appliance where an approved testing agency provides documentation that the appliance effluent contains 5 mg/m3 or less of grease when tested at an exhaust flow rate of 500 cfm (0.236 m3/s) in accordance with Section 17 of UL 710B. | |
Type of Hood Required for Domestic Cooking Appliances in the Following Spacesa, b
Type of Space | Type of Cooking | Type of Hood |
Church | 1. Boiling, steaming and warming precooked food | Type II hood |
2. Roasting, pan frying and deep frying | Type I hood | |
Community or party room in apartment and condominium | 1. Boiling, steaming and warming precooked food | Residential hoodc or Type II hoodd |
2. Roasting, pan frying and deep frying | Type I hood | |
Day care | 1. Boiling, steaming and warming precooked food | Residential hoodc or Type II hoodd |
2. Roasting, pan frying and deep frying | Type I hood | |
Dormitory, boarding home, nursing home | 1. Boiling, steaming and warming precooked food | Type II hood |
2. Roasting, pan frying and deep frying | Type I hood | |
Office lunch room | 1. Boiling, steaming and warming precooked food | Residential hoodc or Type II hoodd |
2. Roasting, pan frying and deep frying | Type I hood |
a Commercial cooking appliances shall comply with Section 507.2. | |
b Requirements in this table apply to electric or gas fuel appliances only. Solid fuel appliances or charbroilers require Type I hoods. | |
c Residential hood shall ventilate to the outside. | |
d Type II hood required when more than one appliance is used. |
[]
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040.
NEW SECTION
WAC 51-54A-0806
Decorative vegetation in new and
existing buildings.
806.1.1 Restricted occupancies. Natural cut trees shall be
prohibited in the following occupancies:
1. Group I; and
2. R-2 occupancies providing licensed care to clients in one of the categories listed in IBC Section 310.1 licensed by Washington state.
806.1.2 Support devices. The support device that holds the
tree in an upright position shall be of a type that is stable
and that meets all of the following criteria:
1. The device shall hold the tree securely and be of adequate size to avoid tipping over of the tree.
2. The device shall be capable of containing a minimum supply of water in accordance with Table 806.1.2.
3. The water level, when full, shall cover the tree stem at least 2 inches (51 mm). The water level shall be maintained above the fresh cut and checked at least once daily.
Support Stand Water Capacity
Tree Stem Diameter (inches) | Minimum Support Stand Water Capacity (gallons) | Typical Daily Water Transpiration Amount (gallons) |
Up to 4 | 1 | 1/4 to 1 |
4 to 6 | 1 1/2 | 1 1/4 to 1 1/2 |
7 to 8 | 2 | 1 3/4 to 2 |
9 to 12 | 3 | 2 1/4 to 3 |
13 and over | 4 | Over 3 |
[]
903.2.1.6 Nightclub. An automatic sprinkler system shall be
provided throughout Group A-2 nightclubs as defined in this
code.
903.2.3 Group E. An automatic sprinkler system shall be
provided for Group E occupancies.
EXCEPTIONS: | 1. Portable school classrooms with an occupant load of 50 or less calculated in accordance with Table 1004.1.2, provided that the aggregate area of any cluster of portable classrooms does not exceed 5,000 square feet (1465 m2); and clusters of portable school classrooms shall be separated as required by the building code. |
2. Group E occupancies with an occupant load of 50 or less, calculated in accordance with Table 1004.1.2. |
EXCEPTION: | Group R-1 if all of the following conditions apply: |
1. The Group R fire area is no more than 500 square feet and is used for recreational use only. | |
2. The Group R fire area is on only one story. | |
3. The Group R fire area does not include a basement. | |
4. The Group R fire area is no closer than 30 feet from another structure. | |
5. Cooking is not allowed within the Group R fire area. | |
6. The Group R fire area has an occupant load of no more than 8. | |
7. A hand-held (portable) fire extinguisher is in every Group R fire area. |
[]
907.2.9.1.1 Group R-2 boarding homes. A manual fire alarm
system shall be installed in Group R-2 occupancies where the
building contains a boarding home licensed by the state of
Washington.
EXCEPTION: | In boarding homes licensed by the state of Washington, manual fire alarm boxes in resident sleeping areas shall not be required at exits if located at all constantly attended staff locations, provided such staff locations are visible, continuously accessible, located on each floor, and positioned so no portion of the story exceeds a horizontal travel distance of 200 feet to a manual fire alarm box. |
[]
908.7 Carbon monoxide alarms. Group I or Group R occupancies
shall be provided with single station carbon monoxide alarms
installed outside of each separate sleeping area in the
immediate vicinity of the bedrooms in dwelling units and on
each level of the dwelling. The carbon monoxide alarms shall
be listed as complying with UL 2034 and be installed and
maintained in accordance with NFPA 720-2009 and the
manufacturer's instructions.
EXCEPTIONS: | 1. For other than R-2 occupancies, the building does not contain a fuel-burning appliance, a fuel-burning fireplace, or an attached garage; or |
2. Sleeping units or dwelling units in I and R-1 occupancies and R-2 college dormitories, hotel, and DSHS licensed boarding home and residential treatment facility occupancies which do not themselves contain a fuel-burning appliance, or a fuel-burning fireplace, or have an attached garage, need not be provided with carbon monoxide alarms provided that: | |
a. The sleeping unit or dwelling unit is not adjacent to any room which contains a fuel-burning appliance, a fuel-burning fireplace, or an attached garage; and | |
b. The sleeping unit or dwelling unit is not connected by duct work or ventilation shafts with a supply or return register in the same room to any room containing a fuel-burning appliance, a fuel-burning fireplace, or an attached garage; and | |
c. The building is provided with a common area carbon monoxide detection system. | |
3. An open parking garage, as defined in Chapter 2 of the International Building Code, or enclosed parking garage ventilated in accordance with Section 404 of the International Mechanical Code shall not be considered an attached garage. |
[]
909.21.1 Pressurization requirements. Elevator hoistways
shall be pressurized to maintain a minimum positive pressure
of 0.10 inches of water (25 Pa) and a maximum positive
pressure of 0.25 inches of water (67 Pa) with respect to
adjacent occupied space on all floors. This pressure shall be
measured at the midpoint of each hoistway door, with all
elevator cars at the floor of recall and all hoistway doors on
the floor of recall open and all other hoistway doors closed.
The opening and closing of hoistway doors at each level must
be demonstrated during this test. The supply air intake shall
be from an outside uncontaminated source located a minimum
distance of 20 feet (6096 mm) from any air exhaust system or
outlet.
909.21.2 Rational analysis. A rational analysis complying
with Section 909.4 shall be submitted with the construction
documents.
909.21.3 Ducts for system. Any duct system that is part of
the pressurization system shall be protected with the same
fire-resistance rating as required for the elevator shaft
enclosure.
909.21.4 Fan system. The fan system provided for the
pressurization system shall be as required by Sections
909.21.4.1 through 909.21.4.4.
909.21.4.1 Fire resistance. When located within the building,
the fan system that provides the pressurization shall be
protected with the same fire-resistance rating required for
the elevator shaft enclosure.
909.21.4.2 Smoke detection. The fan system shall be equipped
with a smoke detector that will automatically shut down the
fan system when smoke is detected within the system.
909.21.4.3 Separate systems. A separate fan system shall be
used for each elevator hoistway.
909.21.4.4 Fan capacity. The supply fan shall either be
adjustable with a capacity of at least 1,000 cfm (0.4719 m3/s)
per door, or that specified by a registered design
professional to meet the requirements of a designed
pressurization system.
909.21.5 Standby power. The pressurization system shall be
provided with standby power from the same source as other
required emergency systems for the building.
909.21.6 Activation of pressurization system. The elevator
pressurization system shall be activated upon activation of
the building fire alarm system or upon activation of the
elevator lobby smoke detectors. Where both a building fire
alarm system and elevator lobby smoke detectors are present,
each shall be independently capable of activating the
pressurization system.
909.21.7 Special inspection. Special inspection for
performance shall be required in accordance with Section
909.18.8. System acceptance shall be in accordance with
Section 909.19.
909.21.8 Marking and identification. Detection and control
systems shall be marked in accordance with Section 909.14.
909.21.9 Control diagrams. Control diagrams shall be provided
in accordance with Section 909.15.
909.21.10 Control panel. A control panel complying with
Section 909.16 shall be provided.
909.21.11 System response time. Hoistway pressurization
systems shall comply with the requirements for smoke control
system response time in Section 909.17.
[]
915.1 General. An approved alerting system shall be provided
in buildings and structures as required in Chapter 4 and this
section, unless other requirements are provided by another
section of this code.
EXCEPTION: | Approved alerting systems in existing buildings, structures or occupancies. |
EXCEPTION: | Systems which do not require electrical power to operate. |
915.4 Combination system. Alerting system components and
equipment shall be allowed to be used for other purposes.
915.4.1 System priority. The alerting system use shall take
precedence over any other use.
915.4.2 Fire alarm system. Fire alarm systems sharing
components and equipment with alerting systems must be in
accordance with Section 6.8.4 of NFPA 72.
915.4.2.1 Signal priority. Recorded or live alert signals
generated by an alerting system that shares components with a
fire alarm system shall, when actuated, take priority over
fire alarm messages and signals.
915.4.2.2 Temporary deactivation. Should the fire alarm
system be in the alarm mode when such an alerting system is
actuated, it shall temporarily cause deactivation of all fire
alarm-initiated audible messages or signals during the time
period required to transmit the alert signal.
915.4.2.3 Supervisory signal. Deactivation of fire alarm
audible and visual notification signals shall cause a
supervisory signal for each notification zone affected in the
fire alarm system.
915.5 Audibility. Audible characteristics of the alert signal
shall be in accordance with Section 7.4.1 of NFPA 72
throughout the area served by the alerting system.
EXCEPTION: | Areas served by approved visual or textual notification, where the visible notification appliances are not also used as a fire alarm signal, are not required to be provided with audibility complying with Section 915.6. |
[]
1007.1 Accessible means of egress required. Accessible means
of egress shall comply with this section. Accessible spaces
shall be provided with not less than one accessible means of
egress. Where more than one means of egress are required by
Section 1015.1 or 1021.1 from any accessible space, each
accessible portion of the space shall be served by not less
than two accessible means of egress.
EXCEPTIONS: | 1. Accessible means of egress are not required in alterations to existing buildings. |
2. One accessible means of egress is required from an accessible mezzanine level in accordance with Section 1007.3, 1007.4 or 1007.5. | |
3. In assembly areas with sloped or stepped aisles, one accessible means of egress is permitted where the common path of travel is accessible and meets the requirements in Section 1028.8. | |
4. In parking garages, accessible means of egress are not required to serve parking areas that do not contain accessible parking spaces. |
[]
1008.1.9.3 Locks and latches. Locks and latches shall be
permitted to prevent operation of doors where any of the
following exists:
1. Places of detention or restraint.
2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided:
2.1. The locking device is readily distinguishable as locked;
2.2. A readily visible sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background; and
2.3. The use of the key-operated locking device is revocable by the building official for due cause.
3. Where egress doors are used in pairs, approved automatic flush bolts shall be permitted to be used, provided that the door leaf having the automatic flush bolts has no doorknob or surface-mounted hardware.
4. Doors from individual dwelling or sleeping units of Group R occupancies having an occupant load of 10 or less are permitted to be equipped with a night latch, dead bolt, or security chain, provided such devices are openable from the inside without the use of a key or a tool.
5. Fire doors after the minimum elevated temperature has disabled the unlatching mechanism in accordance with listed fire door test procedures.
6. Approved, listed locks without delayed egress shall be permitted in Group R-2 boarding homes licensed by Washington state, provided that:
6.1. The clinical needs of one or more patients require specialized security measures for their safety.
6.2. The doors unlock upon actuation of the automatic sprinkler system or automatic fire detection system.
6.3. The doors unlock upon loss of electrical power controlling the lock or lock mechanism.
6.4. The lock shall be capable of being deactivated by a signal from a switch located in an approved location.
6.5. There is a system, such as a keypad and code, in place that allows visitors, staff persons and appropriate residents to exit. Instructions for exiting shall be posted within six feet of the door.
1008.1.9.6 Special locking arrangements in Group I-2.
Approved special egress locks shall be permitted in a Group
I-2 Occupancy where the clinical needs of persons receiving
care require such locking. Special egress locks shall be
permitted in such occupancies where the building is equipped
throughout with an automatic sprinkler system in accordance
with Section 903.3.1.1 or an approved automatic smoke or heat
detection system installed in accordance with Section 907,
provided that the doors unlock in accordance with Items 1
through 7.
1. The doors unlock upon actuation of the automatic
sprinkler system or automatic fire detection system.
2. The doors unlock upon loss of power controlling
the lock or lock mechanism.
3. The door locks shall have the capability of being
unlocked by a signal from the fire command center, a nursing station or other approved location.
4. A building occupant shall not be required to pass through more than one door equipped with a special egress lock before entering an exit.
5. The procedures for the operation(s) of the unlocking system shall be described and approved as part of the emergency planning and preparedness required by Chapter 4 of the International Fire Code.
6. There is a system, such as a keypad and code, in place that allows visitors, staff persons and appropriate residents to exit. Instructions for exiting shall be posted within six feet of the door.
7. Emergency lighting shall be provided at the door.
EXCEPTION: | Items 1, 2, 3, and 6 shall not apply to doors to areas where persons, which because of clinical needs, require restraint or containment as part of the function of a psychiatric treatment area provided that all clinical staff shall have the keys, codes or other means necessary to operate the locking devices. |
[]
1009.3 Exit access stairways. Floor openings between stories
created by exit access stairways shall be enclosed.
EXCEPTIONS: | 1. In other than Group I-2 and I-3 occupancies, exit access stairways that serve, or atmospherically communicate between, only two stories are not required to be enclosed. Such interconnected stories shall not be open to other stories. |
2. Exit access stairways serving and contained within a single residential dwelling unit or sleeping unit in Group R-1, R-2 or R-3 occupancies are not required to be enclosed. | |
3. In Group B or M occupancies, exit access stairways that are designed exclusively for circulation are not required to be enclosed provided that the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, the area of the floor opening between stories does not exceed twice the horizontal projected area of the exit access stairway, and the opening is protected by a draft curtain and closely spaced sprinklers in accordance with NFPA 13. | |
4. In other than Group B and M occupancies, exit access stairways that are designed exclusively for circulation are not required to be enclosed provided that the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, the floor opening does not connect more than four stories, the area of the floor opening between stories does not exceed twice the horizontal projected area of the exit access stairway, and the opening is protected by a draft curtain and closely spaced sprinklers in accordance with NFPA 13. |
[]
1010.1 Scope. The provisions of this section shall apply to
ramps used as a component of a means of egress.
EXCEPTIONS: | 1. Other than ramps that are part of the accessible routes providing access in accordance with Sections 1108.2 through 1108.2.4 and 1108.2.6, ramped aisles within assembly rooms or spaces shall conform with the provisions in Section 1028.11. |
2. Curb ramps shall comply with ICC A117.1. | |
3. Vehicle ramps in parking garages for pedestrian exit access shall not be required to comply with Sections 1010.4 through 1010. when they are not an accessible route serving accessible parking spaces or other required accessible elements. | |
4. In a parking garage where one accessible means of egress serving accessible parking spaces or other accessible elements is provided, a second accessible means of egress serving that area may include a vehicle ramp that does not comply with Sections 1010.5, 1010.6, and 1010.9. A landing complying with Sections 1010.7.1 and 1010.7.4 shall be provided at any change of direction in the accessible means of egress. |
[]
1018.5 Air movement in corridors. Corridors shall not serve
as supply, return, exhaust, relief or ventilation air ducts.
EXCEPTIONS: | 1. Use of a corridor as a source of makeup air for exhaust systems in rooms that open directly onto such corridors, including toilet rooms, bathrooms, dressing rooms, smoking lounges and janitor closets, shall be permitted provided that each such corridor is directly supplied with outdoor air at a rate greater than the rate of makeup air taken from the corridor. |
2. Where located within a dwelling unit, the use of corridors for conveying return air shall not be prohibited. | |
3. Where located within tenant spaces of one thousand square feet (93 m2) or less in area, utilization of corridors for conveying return air is permitted. | |
4. Incidental air movement from pressurized rooms within health care facilities, provided that a corridor is not the primary source of supply or return to the room. | |
5. Where such air is part of an engineered smoke control system. | |
6. Air supplied to corridors serving residential occupancies shall not be considered as providing ventilation air to the dwelling units subject to the following: | |
6.1. The air supplied to the corridor is one hundred percent outside air; and | |
6.2. The units served by the corridor have conforming ventilation air independent of the air supplied to the corridor; and | |
6.3. For other than high-rise buildings, the supply fan will automatically shut off upon activation of corridor smoke detectors which shall be spaced at no more than thirty feet (9144 mm) on center along the corridor; or | |
6.4. For high-rise buildings, corridor smoke detector activation will close required smoke/fire dampers at the supply inlet to the corridor at the floor receiving the alarm. |
EXCEPTIONS: | 1. Foyers, lobbies or reception rooms constructed as required for corridors shall not be construed as intervening rooms. |
2. In Group R-2 boarding homes and residential treatment facilities licensed by Washington state, seating areas shall be allowed to be open to the corridor provided: | |
2.1. The seating area is constructed as required for the corridor; | |
2.2. The floor is separated into at least two compartments complying with Section 407.5; | |
2.3. Each individual seating area does not exceed 150 square feet, excluding the corridor width; | |
2.4. The combined total space of seating areas per compartment does not exceed 300 square feet, excluding the corridor width; | |
2.5. Combustible furnishings located within the seating area shall be in accordance with the International Fire Code Section 805; and | |
2.6. Emergency means of egress lighting is provided as required by Section 1006 to illuminate the area. |
[]
1021.3.1 Access to exits at adjacent levels. Access to exits
at other levels shall be by stairways or ramps. Where access
to exits occurs from adjacent building levels, the horizontal
and vertical exit access travel distance to the closest exit
shall not exceed that specified in Section 1016.1. The path
of egress travel to an exit shall not pass through more than
one adjacent story.
EXCEPTION: | Landing platforms or roof areas for helistops that are less than 60 feet (18,288 mm) long, or less than 2,000 square feet (186 m2) in area, shall be permitted to access the second exit by a fire escape, alternating tread device or ladder leading to the story or level below. |
[]
1103.4.3 Nightclub. An automatic sprinkler system shall be
provided throughout A-2 nightclubs as defined in this code.
No building shall be constructed for, used for, or converted
to occupancy as a nightclub except in accordance with this
section.
1103.9 Carbon monoxide alarms. Existing Group I or Group R
occupancies shall be provided with single station carbon
monoxide alarms in accordance with Section 908.7. An
inspection will occur when alterations, repairs or additions
requiring a permit occur, or when one or more sleeping rooms
are added or created. The carbon monoxide alarms shall be
listed as complying with UL 2034 and be installed and
maintained in accordance with NFPA 720-2009 and the
manufacturer's instructions.
EXCEPTIONS: | 1. For other than R-2 occupancies, if the building does not contain a fuel-burning appliance, a fuel-burning fireplace, or an attached garage. |
2. Work involving the exterior surfaces of dwellings, such as the replacement of roofing or siding, or the addition or replacement of windows or doors, or the addition of a porch or deck, or electrical permits. | |
3. Installation, alteration or repairs of noncombustion plumbing or mechanical systems. | |
4. Sleeping units or dwelling units in I and R-1 occupancies and R-2 college dormitories, hotel, and DSHS licensed boarding home and residential treatment facility occupancies which do not themselves contain a fuel-burning appliance, a fuel-burning fireplace, or have an attached garage, need not be provided with carbon monoxide alarms provided that: | |
a. The sleeping units or dwelling unit is not adjacent to any room which contains a fuel-burning appliance, a fuel-burning fireplace, or an attached garage; and | |
b. The sleeping units or dwelling unit is not connected by duct work or ventilation shafts with a supply or return register in the same room to any room containing a fuel-burning appliance, a fuel-burning fireplace, or to an attached garage; and | |
c. The building is provided with a common area carbon monoxide detection system. | |
5. An open parking garage, as defined in the International Building Code, or enclosed parking garage ventilated in accordance with Section 404 of the International Mechanical Code shall not be considered an attached garage. |
[]
OPTION ONE: (Requiring PLM for existing buildings)
1104.1 General. Means of egress in existing buildings shall
comply with Section 1030 and 1104.2 through 1104.24.
EXCEPTION: | Means of egress conforming to the requirements of the building code under which they were constructed and Section 1030 shall not be required to comply with 1104.2 through 1104.22. |
[]
OPTION 2: (Matching the existing emergency rule)
1104.1 General. Means of egress in existing buildings shall
comply with Section 1030 and 1104.2 through 1104.24.
EXCEPTION: | Means of egress conforming to the requirements of the building code under which they were constructed and Section 1030 shall not be required to comply with 1104.2 through 1104.22 and 1104.24. |
[]
3601.1.2 Permits. For permits to operate marine motor
fuel-dispensing stations, application of flammable or
combustible finishes, and hot works, see Section 105.6.
[]
3602.1 Definitions. The following terms are defined in
Chapter 2:
COVERED BOAT MOORAGE.
FLOAT.
GRAVITY-OPERATED DROP OUT VENTS.
MARINA.
PIER.
VESSEL.
WHARF.
[]
3604.2 Standpipes. Marinas shall be equipped throughout with
Class I manual, dry standpipe systems in accordance with NFPA
303. Systems shall be provided with outlets located such that
no point on the marina pier or float system exceeds 150 feet
from a standpipe outlet.
3604.3 Access and water supply. Piers and wharves shall be
provided with fire apparatus access roads and water-supply
systems with on-site fire hydrants when required and approved
by the fire code official. At least one fire hydrant capable
of providing the required fire flow shall be provided within
an approved distance of standpipe supply connections.
3604.4 Portable fire extinguishers. One 4A40BC fire
extinguisher shall be provided at each standpipe outlet.
Additional fire extinguishers, suitable for the hazards
involved, shall be provided and maintained in accordance with
Section 906.
3604.7 Smoke and heat vents. Approved automatic smoke and
heat vents shall be provided in covered boat moorage areas
exceeding 2,500 sq. ft. (232 m2) in area, excluding roof
overhangs.
EXCEPTION: | Smoke and heat vents are not required in areas protected by automatic sprinklers. |
3604.7.1.1 Smoke and heat vents. Smoke and heat vents shall
operate automatically by actuation of a heat-responsive device
rated at between 100ºF (56ºC) above ambient.
EXCEPTION: | Gravity-operated drop out vents. |
3604.8 Draft curtains. Draft curtains shall be provided in
covered boat moorage areas exceeding 2,500 sq. ft. (232 m2) in
area, excluding roof overhangs.
EXCEPTION: | Draft curtains are not required in areas protected by automatic sprinklers. |
3604.8.2 Draft curtain location and depth. The maximum area
protected by draft curtains shall not exceed 2,000 sq. ft.
(186 m2) or two slips or berths, whichever is smaller. Draft
curtains shall not extend past the piling line. Draft
curtains shall have a minimum depth of 4 feet and shall not
extend closer than 8 feet (2438 mm) to the walking surface of
the pier.
[]
5306.1 General. Compressed gases at hospitals and similar
facilities intended for inhalation or sedation including, but
not limited to, analgesia systems for dentistry, podiatry,
veterinary and similar uses shall comply with Sections 5306.2
through 5306.4 in addition to other requirements of this
chapter.
EXCEPTION: | All new distribution piping, supply manifolds, connections, regulators, valves, alarms, sensors and associated equipment shall be in accordance with the Plumbing Code. |
[]
5601.1 Scope. The provisions of this chapter shall govern the
possession, manufacture, storage, handling, sale and use of
explosives, explosive materials, and small arms ammunition.
The manufacture, storage, handling, sale and use of fireworks
shall be governed by chapter 70.77 RCW, and by chapter 212-17 WAC and local ordinances consistent with chapter 212-17 WAC.
EXCEPTIONS: | 1. The Armed Forces of the United States, Coast Guard or National Guard. |
2. Explosives in forms prescribed by the official United States Pharmacopoeia. | |
3. The possession, storage and use of small arms ammunition when packaged in accordance with DOT packaging requirements. | |
4. The possession, storage and use of not more than 1 pound (0.454 kg) of commercially manufactured sporting black powder, 20 pounds (9 kg) of smokeless powder and 10,000 small arms primers for hand loading of small arms ammunition for personal consumption. | |
5. The use of explosive materials by federal, state and local regulatory, law enforcement and fire agencies acting in their official capacities. | |
6. Special industrial explosive devices in which the aggregate contain less than 50 pounds (23 kg) of explosive materials. | |
7. The possession, storage and use of blank industrial-power load cartridges when packaged in accordance with DOT packaging regulations. | |
8. Transportation in accordance with DOT 49 C.F.R. Parts 100-178. | |
9. Items preempted by federal regulations. |
[]
5704.2.11 Underground tanks. Underground storage of flammable
and combustible liquids in tanks shall comply with Section
3404.2 and Sections 3404.2.11.1 through 3404.2.11.5.2.
Corrosion protection shall comply with WAC 173-360-305.
[]
5706.5.4.5 Commercial, industrial, governmental or
manufacturing. Dispensing of Class II and III motor vehicle
fuel from tank vehicles into the fuel tanks of motor vehicles
located at commercial, industrial, governmental or
manufacturing establishments is allowed where permitted,
provided such dispensing operations are conducted in
accordance with the following: (Those sections not noted here
remain unchanged.)
12. Fuel delivery vehicles shall be equipped with spill clean-up supplies in accordance with the department of ecology's Source Control Best Management Practices. Such supplies shall be readily available for deployment by the operator at all times and include nonwater absorbents capable of absorbing 15 gallons (56.76 L) of diesel fuel, storm drain plug or cover kit, a nonwater absorbent containment boom of a minimum 10 foot long (3038 mm) length with a 12-gallon (45.41 L) absorbent capacity, a nonmetallic shovel, and two 5-gallon (19 L) buckets with lids.
[]
6108.1 Scope. Storage, handling and transportation of
liquefied petroleum gas (LP-gas) and the installation of
LP-gas equipment pertinent to systems for such uses shall
comply with this chapter and NFPA 58. Properties of LP-gas
shall be determined in accordance with Appendix B of NFPA 58.
EXCEPTION: | The use and storage of listed propane fired barbeque grills on R-2 decks and balconies with an approved container not exceeding a water capacity of 20 pounds (9 kg) that maintain a minimum clearance of 18 inches on all sides, unless listed for lesser clearances. |
[]
NFPA 9607 Standard for Ventilation Control and Fire Protection
of Commercial Cooking Operations. . . . . . . . . . . . 609.3
[]
K101.5 Additions or alterations. Additions or alterations may
be made to any building or structure without requiring the
existing building or structure to comply with all of the
requirements of this code, provided the addition or alteration
conforms to that required for a new building or structure.
EXCEPTION: | Provisions of this code that specifically apply to existing conditions are retroactive. See Sections 402.3, 601.1 and Appendix A. |
K108.3 Site plan. In addition to the requirements for plans
in the International Building Code, the code official may
require site plans which include topography, width and percent
of grade of access roads, landscape and vegetation details,
locations of structures or building envelopes, existing or
proposed overhead utilities, occupancy classification of
buildings, types of ignition resistant construction of
buildings, structures and their appendages, roof
classification of buildings, and site water supply systems.
The code official is authorized to waive or modify the
requirement for a site plan.
K108.4 Vegetation management plans. When required by the code
official or when utilized by the permit applicant pursuant to
Section 502, vegetation management plans shall be prepared and
shall be submitted to the code official for review and
approval as part of the plans required for a permit. See
Appendix B.
K108.7 Vicinity plan. When required by the code official, the
requirements for site plans shall include details regarding
the vicinity within 300 feet (91,440 mm) of property lines,
including other structures, slope, vegetation, fuel breaks,
water supply systems and access roads.
K402.1.1 Access. New subdivisions, as determined by this
jurisdiction, shall be provided with fire apparatus access
roads in accordance with the International Fire Code.
K402.1.2 Water supply. New subdivisions as determined by this
jurisdiction shall be provided with water supply in accordance
with the International Fire Code.
K402.2 Individual structures. Individual structures shall
comply with Sections 402.2.1 and 402.2.2.
K402.2.1 Access. Individual structures hereafter constructed
or relocated into or within wildland-urban interface areas
shall be provided with fire apparatus access in accordance
with the International Fire Code.
K402.2.2 Water supply. Individual structures hereafter
constructed or relocated into or within wildland-urban
interface areas shall be provided with a conforming water
supply in accordance with the International Fire Code.
EXCEPTIONS: | 1. Structures constructed to meet the requirements for the class of ignition-resistant construction specified in Table 503.1 for a nonconforming water supply. |
2. Buildings containing only private garages, carports, sheds and agricultural buildings with a floor area of not more than 600 square feet (56 m2). | |
Ignition-Resistant Constructiona
Fire Hazard Severity | ||||||
Moderate Hazard | High Hazard | Extreme Hazard | ||||
Water Supplyb | Water Supplyb | Water Supplyb | ||||
Defensible Spacec | Conforming | Nonconforming | Conforming | Nonconforming | Conforming | Nonconforming |
Nonconforming | IR 2 | IR 1 | IR 1 | IR 1 N.C. | IR 1 N.C. | Not Permitted |
Conforming | IR 3 | IR 2 | IR 2 | IR 1 | IR 1 | IR 1 N.C. |
1.5 x Conforming | Not Required | IR 3 | IR 3 | IR 2 | IR 2 | IR 1 |
aAccess shall be in accordance with Section 402. | |
bWater supply shall be in accordance with Section 402.1. | |
IR 1 = Ignition-resistant construction in accordance with Section 504. | |
IR 2 = Ignition-resistant construction in accordance with Section 505. | |
IR 3 = Ignition-resistant construction in accordance with Section 506. | |
N.C. = Exterior walls shall have a fire-resistance rating of not less than 1 hour and the exterior surfaces of such walls shall be noncombustible. Usage of log wall construction is allowed. | |
c Conformance based on Section 603. |
K404 Water supply. This section not adopted.
APPENDIX B-VEGETATION MANAGEMENT PLAN - THIS APPENDIX IS ADOPTED.
APPENDIX C-FIRE DANGER RATING SYSTEM - THIS APPENDIX IS ADOPTED.
[]
OTS-4947.1
REPEALER
The following chapter of the Washington Administrative Code is repealed:
WAC 51-54-001 | Authority. |
WAC 51-54-002 | Purpose. |
WAC 51-54-003 | International Fire Code. |
WAC 51-54-007 | Exceptions. |
WAC 51-54-008 | Implementation. |
WAC 51-54-0100 | Chapter 1 -- Administration. |
WAC 51-54-0200 | Chapter 2 -- Definitions. |
WAC 51-54-0300 | Chapter 3 -- General precautions against fire. |
WAC 51-54-0400 | Chapter 4 -- Emergency planning and preparedness. |
WAC 51-54-0500 | Chapter 5 -- Fire service features. |
WAC 51-54-0600 | Chapter 6 -- Building services and systems. |
WAC 51-54-0800 | Chapter 8 -- Interior finish, decorative materials and furnishings. |
WAC 51-54-0900 | Chapter 9 -- Fire protection systems. |
WAC 51-54-1000 | Chapter 10 -- Means of egress. |
WAC 51-54-1100 | Aircraft-fueling vehicles. |
WAC 51-54-2200 | Chapter 22 -- Motor fuel-dispensing facilities and repair garages. |
WAC 51-54-3000 | Chapter 30 -- Compressed gasses. |
WAC 51-54-3300 | Chapter 33 -- Explosives and fireworks. |
WAC 51-54-3400 | Chapter 34 -- Flammable and combustible liquids. |
WAC 51-54-3800 | Chapter 38 -- Liquefied petroleum gases. |
WAC 51-54-4500 | Chapter 45 -- Marinas. |
WAC 51-54-4600 | Chapter 46 -- Existing buildings. |
WAC 51-54-4700 | Chapter 47 -- Referenced standards. |
WAC 51-54-4800 | Appendix K -- Wildland and Urban Interface Code. |