PERMANENT RULES
Effective Date of Rule: July 1, 2013.
Purpose: Adoption and amendment of the 2012 International Mechanical Code, chapter 51-52 WAC. This also includes adoption and amendment of the 2012 International Fuel Gas Code, the 2012 Edition of the National Fuel Gas Code (NFPA 54), and the 2011 Edition of the Liquefied Petroleum Gas Code (NFPA 58) as noted in WAC 51-52-0101 and 51-52-21101.
Citation of Existing Rules Affected by this Order: Amending WAC 51-52-003, 51-52-004, 51-52-008, 51-52-0101, 51-52-0202, 51-52-0306, 51-52-0403, 51-52-0404, 51-52-0501, 51-52-0504, 51-52-0505, 51-52-0506, 51-52-0507, 51-52-0601, 51-52-1000, 51-52-1500, and 51-52-21101.
Statutory Authority for Adoption: RCW 19.27.031 and 19.27.074.
Other Authority: Chapters 19.27 and 34.05 RCW.
Adopted under notice filed as WSR 12-16-083 on July 31, 2012.
Changes Other than Editing from Proposed to Adopted Version: 1. WAC 51-52-0403, Table 403.3: Based on testimony received, the outdoor airflow rate under "Private dwellings, single and multiple," "living areas" was changed to reference the whole house ventilation requirements in Tables 403.8.1 and 403.8.5.1 and coordinate with that section.
2. WAC 51-52-0403, Section 403.8.2: The control requirements in item 5.5 of this section were adjusted to coordinate with the requirements in Section 403.8.5.1 to specify operation at a minimum of one out of every four hours.
3. WAC 51-52-0403, Section 403.8.5.2: The exception was moved from Item 6 to Item 7 of this section. Testimony received indicated the exception was appearing in the wrong location.
4. WAC 51-52-0403, Section 928.1: It was pointed out at the public hearing that Items 4 and 5 of this section had been erroneously combined. The list has been corrected.
5. WAC 51-52-1000, Chapter 10: Based on concerns voiced during public testimony, an informational note was added to the beginning of Chapter 10 to clarify that boilers and pressure vessels must meet labor and industry regulations. In addition, Exception 7 of 1001.1 was modified to indicate that, in addition to other state and federal requirements, any local inspection programs would take precedence over this code.
6. Under the proposed rule, amendments to the 2012 International Fuel Gas Code were erroneously placed into the WAC sections for the National Fuel Gas Code and LP Gas Code. WAC 51-52-22004 and 51-52-22006 were renumbered to be included in the International Fuel Gas Code section, as WAC 51-52-21401 and 51-52-21601.
7. Under the proposed rule, the amendment of piping identification appeared as WAC 51-52-0303, under the section title Equipment and Appliance Location. Testimony was received that this location was erroneous and should actually be placed in Section 301. The section was moved to WAC 51-52-0301, under section title General.
Number of Sections Adopted in Order to Comply with Federal Statute: New 0, Amended 0, Repealed 0; Federal Rules or Standards: New 0, Amended 0, Repealed 0; or Recently Enacted State Statutes: New 0, Amended 0, Repealed 0.
Number of Sections Adopted at Request of a Nongovernmental Entity: New 7, Amended 17, Repealed 0.
Number of Sections Adopted on the Agency's Own Initiative: New 0, Amended 0, Repealed 0.
Number of Sections Adopted in Order to Clarify, Streamline, or Reform Agency Procedures: New 0, Amended 0, Repealed 0.
Number of Sections Adopted Using Negotiated Rule Making: New 0, Amended 0, Repealed 0; Pilot Rule Making: New 0, Amended 0, Repealed 0; or Other Alternative Rule Making: New 7, Amended 17, Repealed 0.
Date Adopted: November 9, 2012.
C. Ray Allshouse
Council Chair
OTS-4920.4
STATE BUILDING CODE ADOPTION AND AMENDMENT OF THE ((2009))
2012 EDITION OF THE INTERNATIONAL MECHANICAL CODE
[Statutory Authority: RCW 19.27.190, 19.27.074, 19.27.031 and chapters 19.27 and 34.05 RCW. 10-03-099, § 51-52-003, filed 1/20/10, effective 7/1/10. Statutory Authority: RCW 19.27.190, 19.27.020, and chapters 19.27 and 34.05 RCW. 07-01-092, § 51-52-003, filed 12/19/06, effective 7/1/07. Statutory Authority: RCW 19.27.031 and 19.27.074. 04-01-104, § 51-52-003, filed 12/17/03, effective 7/1/04.]
[Statutory Authority: RCW 19.27.031 and 19.27.074. 04-01-104, § 51-52-004, filed 12/17/03, effective 7/1/04.]
[Statutory Authority: RCW 19.27.190, 19.27.074, 19.27.031 and chapters 19.27 and 34.05 RCW. 10-03-099, § 51-52-008, filed 1/20/10, effective 7/1/10. Statutory Authority: RCW 19.27.190, 19.27.020, and chapters 19.27 and 34.05 RCW. 07-01-092, § 51-52-008, filed 12/19/06, effective 7/1/07. Statutory Authority: RCW 19.27.031 and 19.27.074. 04-01-104, § 51-52-008, filed 12/17/03, effective 7/1/04.]
101.2 Scope. This code shall regulate the design,
installation, maintenance, alteration and inspection of
mechanical systems that are permanently installed and utilized
to provide control of environmental conditions and related
processes within buildings. This code shall also regulate
those mechanical systems, system components, equipment and
appliances specifically addressed herein. The installation of
fuel gas distribution piping and equipment, fuel gas-fired
appliances and fuel gas-fired appliance venting systems shall
be regulated by the International Fuel Gas Code.
EXCEPTIONS: | 1. Detached one- and two-family dwellings and multiple single-family dwellings (townhouses) not more than three stories high with separate means of egress and their accessory structures shall comply with the International Residential Code. |
2. The standards for liquefied petroleum gas installations shall be the (( |
[Statutory Authority: RCW 19.27.190, 19.27.074, 19.27.031 and chapters 19.27 and 34.05 RCW. 10-03-099, § 51-52-0101, filed 1/20/10, effective 7/1/10. Statutory Authority: RCW 19.27.190, 19.27.020, and chapters 19.27 and 34.05 RCW. 07-01-092, § 51-52-0101, filed 12/19/06, effective 7/1/07. Statutory Authority: RCW 19.27.031 and 19.27.074. 04-01-104, § 51-52-0101, filed 12/17/03, effective 7/1/04.]
102.4 Additions, alterations or repairs. Additions,
alterations, renovations or repairs to a mechanical system
shall conform to that required for a new mechanical system
without requiring the existing mechanical system to comply
with all of the requirements of this code. Additions,
alterations or repairs shall not cause an existing mechanical
system to become unsafe, hazardous or overloaded.
Minor additions, alterations, renovations and repairs to existing mechanical systems shall meet the provisions for new construction, unless such work is done in the same manner and arrangement as was in the existing system, is not hazardous and is approved.
EXCEPTION: | Additions, alterations, renovations or repairs to a mechanical system that is part of a building addition with less than 500 square feet of conditioned floor area are exempt from the requirements for whole house ventilation systems, Section 403.8.5. |
[]
((SOURCE SPECIFIC VENTILATION. A mechanical ventilation system
including all fans, controls, and ducting, which is dedicated
to exhausting contaminant-laden air to the exterior of the
building from the room or space in which the contaminant is
generated.
UNUSUALLY TIGHT CONSTRUCTION. Construction meeting the following
requirements:
1. Walls exposed to the outdoor atmosphere having a continuous water vapor retarder with a rating of 1 perm (57 ng/s·m2·Pa) or less with openings gasketed or sealed; and
2. Operable windows and doors meeting the air leakage requirements of the International Energy Conservation Code, Section 502.1.4; and
3. Caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines, and at other openings; or
4. Buildings built in compliance with the 1986 or later editions of the Washington State Energy Code, chapter 51-11 WAC, Northwest Energy Code, or Super Good Cents weatherization standards or equivalent.)) LOCAL EXHAUST. An exhaust system that uses one or more fans to exhaust air from a specific room or rooms within a dwelling.
WHOLE HOUSE VENTILATION SYSTEM. A mechanical ventilation system,
including fans, controls, and ducts, which replaces, by direct
or indirect means, air from the habitable rooms with outdoor
air.
[Statutory Authority: RCW 19.27.190, 19.27.074, 19.27.031 and chapters 19.27 and 34.05 RCW. 10-03-099, § 51-52-0202, filed 1/20/10, effective 7/1/10. Statutory Authority: RCW 19.27.190, 19.27.020, and chapters 19.27 and 34.05 RCW. 07-01-092, § 51-52-0202, filed 12/19/06, effective 7/1/07. Statutory Authority: RCW 19.27.031 and 19.27.074. 04-01-104, § 51-52-0202, filed 12/17/03, effective 7/1/04.]
301.3 Identification. Each length of pipe and tubing and each
pipe fitting utilized in a mechanical system shall bear the
identification of the manufacturer.
EXCEPTION: | The manufacturer identification for fittings and pipe nipples shall be on each piece or shall be printed on the fitting or nipple packaging or provided documentation. |
[]
306.5 Equipment and appliances on roofs or elevated
structures. Where equipment requiring access ((and)) or
appliances are ((installed on roofs or elevated structures at
a height exceeding)) located on an elevated structure or the
roof of a building such that personnel will have to climb
higher than 16 feet (4877 mm) above grade to access such
equipment or appliances, ((such access shall be provided by a
permanent approved means of access, the extent of which shall
be from grade or floor level to the equipment and appliances'
level service space)) an interior or exterior means of access
shall be provided. Such access shall not require climbing
over obstructions greater than 30 inches (762 mm) ((high)) in
height or walking on roofs having a slope greater than 4 units
vertical in 12 units horizontal (33 percent slope). Such
access shall not require the use of portable ladders. Where
access involves climbing over parapet walls, the height shall
be measured to the top of the parapet wall.
Permanent ladders installed to provide the required
access shall comply with the following minimum design
criteria:
1. The side railing shall extend above the parapet or roof edge not less than 42 inches (1067 mm).
2. Ladders shall have rung spacing not to exceed 12 inches (305 mm) on center. The uppermost rung shall be a maximum of 24 inches below the upper edge of the roof hatch, roof or parapet, as applicable.
3. Ladders shall have a toe spacing not less than 7 inches (178 mm) deep.
4. There shall be a minimum of 18 inches (457 mm) between rails.
5. Rungs shall have a minimum 0.75-inch (19 mm) diameter and be capable of withstanding a 300-pound (136.1 kg) load.
6. Ladders over 30 feet (9144 mm) in height shall be provided with offset sections and landings capable of withstanding 100 pounds (488.2 kg/m2) per square foot. Landing dimensions shall be not less than 18 inches and not less than the width of the ladder served. A guardrail shall be provided on all open sides of the landing.
7. Climbing clearances. The distance from the centerline of the rungs to the nearest permanent object on the climbing side of the ladder shall be a minimum of 30 inches measured perpendicular to the rungs. This distance shall be maintained from the point of ladder access to the bottom of the roof hatch. A minimum clear width of 15 inches shall be provided on both sides of the ladder measured from the midpoint of and parallel with the rungs except where cages or wells are installed.
8. Landing required. The ladder shall be provided with a clear and unobstructed bottom landing area having a minimum dimension of 30 inches by 30 inches centered in front of the ladder.
9. Ladders shall be protected against corrosion by approved means.
10. Access to ladders shall be provided at all times.
Catwalks installed to provide the required access shall
be not less than 24 inches (610 mm) wide and shall have
railings as required for service platforms.
EXCEPTION: | This section shall not apply to Group R-3 occupancies. |
[Statutory Authority: RCW 19.27.190, 19.27.074, 19.27.031 and chapters 19.27 and 34.05 RCW. 10-03-099, § 51-52-0306, filed 1/20/10, effective 7/1/10.]
307.2.3 Auxiliary and secondary drain systems. In addition to
the requirements of Section 307.2.1, where damage to any
building components could occur as a result of overflow from
the equipment primary condensate removal system, one of the
following auxiliary protection methods shall be provided for
each cooling coil or fuel-fired appliance that produces
condensate:
1. An auxiliary drain pan with a separate drain shall be provided under the coils on which condensation will occur. The auxiliary pan drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The pan shall have a minimum depth of 1 1/2 inches (38 mm), shall not be less than 3 inches (76 mm) larger than the unit or the coil dimensions in width and length and shall be constructed of corrosion-resistant material. Galvanized sheet steel pans shall have a minimum thickness of not less than 0.0236 inch (0.6010 mm) (No. 24 gage). Nonmetallic pans shall have a minimum thickness of not less than 0.0625 inch (1.6 mm).
2. A separate overflow drain line shall be connected to the drain pan provided with the equipment. Such overflow drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The overflow drain line shall connect to the drain pan at a higher level than the primary drain connection.
3. An auxiliary drain pan without a separate drain line shall be provided under the coils on which condensate will occur. Such pan shall be equipped with a water-level detection device conforming to UL 508 that will shut off the equipment served prior to overflow of the pan. The auxiliary drain pan shall be constructed in accordance with Item 1 of this section.
4. A water-level detection device conforming to UL 508 shall be provided that will shut off the equipment served in the event that the primary drain is blocked. The device shall be installed in the primary drain line, the overflow drain line, or in the equipment-supplied drain pan, located at a point higher than the primary drain line connection and below the overflow rim of such pan.
EXCEPTIONS: | 1. Fuel-fired appliances that automatically shut down operation in the event of a stoppage in the condensate drainage system. |
2. Unducted fan coil units where there is no factory option available for water-level detection devices and which are installed directly within the occupied space. |
[]
403.2 Outdoor air required. The minimum ventilation rate of
outdoor air shall be determined in accordance with Section
403.3.
EXCEPTIONS: | 1. Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding that obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design. |
2. Alternate systems designed in accordance with ASHRAE Standard 62.1 Section 6.2, Ventilation Rate Procedure, shall be permitted. |
1. Ventilation air shall not be recirculated from one dwelling to another or to dissimilar occupancies.
2. Supply air to a swimming pool and associated deck areas shall not be recirculated unless such air is dehumidified to maintain the relative humidity of the area at 60 percent or less. Air from this area shall not be recirculated to other spaces where 10 percent or more of the resulting supply airstream consists of air recirculated from these spaces.
3. Where mechanical exhaust is required by Note b in Table 403.3, recirculation of air from such spaces shall be prohibited. All air supplied to such spaces shall be exhausted, including any air in excess of that required by Table 403.3.
(Item 4 is not adopted.)
403.3 Outdoor airflow rate. Ventilation systems shall be
designed to have the capacity to supply the minimum outdoor
airflow rate determined in accordance with this section. The
occupant load utilized for design of the ventilation system
shall not be less than the number determined from the
estimated maximum occupant load rate indicated in Table 403.3.
Ventilation rates for occupancies not represented in Table
403.3 shall be those for a listed occupancy classification
that is most similar in terms of occupant density, activities
and building construction; or shall be determined by an
approved engineering analysis. The ventilation system shall
be designed to supply the required rate of ventilation air
continuously during the period the building is occupied,
except as otherwise stated in other provisions of the code.
With the exception of smoking lounges, the ventilation
rates in Table 403.3 are based on the absence of smoking in
occupiable spaces. Where smoking is anticipated in a space
other than a smoking lounge, the ventilation system serving
the space shall be designed to provide ventilation over and
above that required by Table 403.3 in accordance with accepted
engineering practice.
EXCEPTION: | Where occupancy density is known and documented in the plans, the outside air rate may be based on the design occupant density. Under no circumstance shall the occupancies used result in outside air less than one-half that resulting from application of Table 403.3 estimated maximum occupancy rates. |
REQUIRED OUTDOOR VENTILATION AIR
(( |
cfm/Person |
cfm/ft2a |
||||
private |
||||||
Occupancy Classification | Occupant Density #/1000 ft2a | People Outdoor
Airflow Rate in
Breathing Zone Rp cfm/Person |
Area Outdoor
Airflow Rate in
Breathing Zone
Ra cfm/ft2a |
Exhaust Airflow Rate cfm/ft2 | |
Offices | |||||
Conference rooms | 50 | 5 | 0.06 | -- | |
Kitchenettes | -- | -- | -- | 0.30 | |
Office spaces | 5 | 5 | 0.06 | -- | |
Reception areas | 30 | 5 | 0.06 | -- | |
Telephone/data entry | 60 | 5 | 0.06 | -- | |
Main entry lobbies | 10 | 5 | 0.06 | -- | |
Private dwellings, single and multiple | |||||
Garages, common for multiple unitsb | -- | -- | -- | 0.75 | |
Garages, separate for each dwellingb | -- | -- | -- | 100 cfm per car | |
Kitchensb | -- | -- | -- | 25/100f | |
Living areasc | Based on the number of bedrooms. First bedroom, 2; each additional bedroom, 1 | See Tables 403.8.1 and 403.8.5.1 | -- | -- | |
Toilet rooms, bathrooms and laundry areasg, i | -- | -- | -- | 20/50f | |
Sports and amusement | |||||
Disco/dance floors | 100 | 20 | 0.06 | -- | |
Bowling alleys (seating areas) | 40 | 10 | 0.12 | -- | |
Game arcades | 20 | 7.5 | 0.18 | -- | |
Ice arenas, without combustion enginesj | -- | -- | 0.30 | 0.5 | |
Gym, stadium, arena (play area)j | -- | -- | 0.30 | -- | |
Spectator areas | 150 | 7.5 | 0.06 | -- | |
Swimming pools (pool and deck area) | -- | -- | 0.48 | -- | |
Health club/aerobics room | 40 | 20 | 0.06 | -- | |
Health club/weight room | 10 | 20 | 0.06 | -- | |
Storage | |||||
Janitor closets, trash rooms, recycling rooms | -- | -- | -- | 1.0 | |
Repair garages, enclosed parking garageb, d | -- | -- | -- | 0.75 | |
Storage rooms, chemical | -- | -- | -- | 1.5 | |
Warehouses | -- | -- | 0.06 | -- |
For SI: | 1 cubic foot per minute = 0.0004719 m3/s, 1 ton = 908 kg, 1 cubic foot per minutes per square foot = 0.00508 m3/(s•m2), °C = [(°F) -32]/1.8, 1 square foot - 0.0929 m2. |
a. | Based upon net occupiable floor area. |
b. | Mechanical exhaust required and the recirculation of air from such spaces is prohibited (see Section 403.2.1, Item 3). |
c. | Spaces unheated or maintained below 50°F are not covered by these requirements unless the occupancy is continuous. |
d. | Ventilation systems in enclosed parking garages shall comply with Section 404. |
e. | Rates are per water closet or urinal. The higher rate shall be provided where (( |
f. | Rates are per room unless otherwise indicated. The higher rate shall be provided where the exhaust system is
designed to operate intermittently. The lower rate shall be permitted only where the exhaust system is
designed to operate continuously (( |
g. | (( |
h. | For nail salons, (( |
i. | A laundry area within a kitchen or bathroom is not required to have (( |
j. | When combustion equipment is intended to be used on the playing surface, additional dilution ventilation and/or source control shall be provided. |
403.8.1 Minimum ventilation performance. Ventilation systems
shall be designed and installed to satisfy the ventilation
requirements of Table 403.3 or Table 403.8.1. Breathing zone
ventilation rates from Table 403.3 shall be calculated per
Section 403.3.1.1 and corrected per zone air distribution
effectiveness requirements per Section 403.3.1.2.
VENTILATION RATES FOR ALL GROUP R PRIVATE DWELLINGS, SINGLE AND MULTIPLE
(CONTINUOUSLY OPERATING SYSTEMS)
Floor Area | Bedrooms1 | ||||||||||
(ft2) | 0-1 | 2-3 | 4-5 | 6-7 | >7 | ||||||
<1500 | 30 | 45 | 60 | 75 | 90 | ||||||
1501 - 3000 | 45 | 60 | 75 | 90 | 105 | ||||||
3001 - 4500 | 60 | 75 | 90 | 105 | 120 | ||||||
4501 - 6000 | 75 | 90 | 105 | 120 | 135 | ||||||
6001 - 7500 | 90 | 105 | 120 | 135 | 150 | ||||||
>7500 | 105 | 120 | 135 | 150 | 165 |
1Ventilation rates in table are minimum outdoor airflow rates measured in cfm. |
1. Location of controls. Controls for all ventilation systems shall be readily accessible by the occupant.
2. Instructions. Operating instructions for whole house ventilation systems shall be provided to the occupant by the installer of the system.
3. ((Source specific)) Local exhaust ventilation systems.
((Source specific)) Local exhaust ventilation systems shall
be controlled by manual switches, dehumidistats, timers, or
other approved means.
4. Continuous whole house ventilation systems. Continuous whole house ventilation systems shall operate continuously. Exhaust fans, forced-air system fans, or supply fans shall be equipped with "fan on" as override controls. Controls shall be capable of operating the ventilation system without energizing other energy-consuming appliances. A label shall be affixed to the controls that reads "Whole House Ventilation (see operating instructions)."
5. Intermittent whole house ventilation systems. Intermittent whole house ventilation systems shall comply with the following:
5.1 They shall be capable of operating intermittently and continuously.
5.2 They shall have controls capable of operating the exhaust fans, forced-air system fans, or supply fans without energizing other energy-consuming appliances.
5.3 The ventilation rate shall be adjusted according to the exception in Section 403.8.5.1.
5.4 The system shall be designed so that it can operate automatically based on the type of control timer installed.
5.5 The intermittent mechanical ventilation system shall
operate at least one hour out of every ((twelve)) four.
5.6 The system shall have a manual control and automatic control, such as a 24-hour clock timer.
5.7 At the time of final inspection, the automatic control shall be set to operate the whole house fan according to the schedule used to calculate the whole house fan sizing.
5.8 A label shall be affixed to the control that reads "Whole House Ventilation (see operating instructions)."
EXCEPTION: | Engineered central ventilation systems serving dwelling units or sleeping units are not required to have individual controls for each dwelling unit or sleeping unit when designed for continuous operation and approved by the code official. |
1. Openings for mechanical air intakes shall comply with Section 401.4. Operable openings shall comply with Section 401.4 items 2 and 4 only.
2. Intake openings shall not be located closer than 10 feet from an appliance vent outlet unless such vent outlet is 3 feet above the outdoor air inlet. The vent shall be permitted to be closer if specifically allowed by Chapter 8 or by the International Fuel Gas Code.
3. Intake openings shall be located where they will not pick up objectionable odors, fumes, or flammable vapors.
4. Intake openings shall be located where they will not take air from a hazardous or unsanitary location.
5. Intake openings shall be located where they will not take air from a room or space having a fuel-burning appliances.
6. Intake openings shall not be located closer than 10 feet from a vent opening of a plumbing drainage system unless the vent opening is at least 3 feet above the air inlet.
7. Intake openings shall not be located where they will take air from an attic, crawl space, or garage.
403.8.4 ((Source specific)) Local exhaust ventilation
requirements. ((Source specific)) Local exhaust ventilation
systems shall exhaust at least the volume of air required for
exhaust in Table 403.3. Exhaust shall be provided in each
kitchen, bathroom, water closet, laundry area, indoor swimming
pool, spa, and other room where water vapor or cooking odor is
produced.
403.8.4.1 ((Source specific)) Local exhaust systems. Exhaust
systems shall be designed and installed to meet all of the
criteria below:
1. ((Source specific)) Local exhaust shall be discharged
outdoors.
2. Exhaust outlets shall comply with Section ((501.2))
501.3.
3. Pressure equalization shall comply with Section
((501.3)) 501.4.
4. Exhaust ducts in systems which are designed to operate intermittently shall be equipped with back-draft dampers.
5. All exhaust ducts in unconditioned spaces shall be insulated to a minimum of R-4.
6. Terminal outlet elements shall have at least the equivalent net free area of the ductwork.
7. Terminal outlet elements shall be screened or
otherwise protected as required by Section ((501.2.2))
501.3.2.
8. Exhaust fans in separate dwelling units or ((guest
rooms)) sleeping units shall not share common exhaust ducts
unless the system is engineered for this operation.
9. Where permitted by Chapter 5, multiple ((source
specific)) local exhaust ducts may be combined. If more than
one of the exhaust fans in a dwelling unit or ((guest room))
sleeping unit shares a common exhaust duct then each exhaust
fan shall be equipped with a back-draft damper to prevent the
recirculation of exhaust air from one room to another room via
the exhaust ducting system.
403.8.4.2 ((Source specific)) Local exhaust fans. Exhaust fan
construction and sizing shall meet the following criteria.
1. Exhaust fans shall be tested and rated in accordance with the airflow and sound rating procedures of the Home Ventilating Institute (HVI 915, HVI Loudness Testing and Rating Procedure, HVI 916, HVI Airflow Test Procedure, and HVI 920, HVI Product Performance Certification Procedure).
EXCEPTION: | Where a range hood or down draft exhaust fan is used for (( |
3. Fan airflow rating and duct system shall be designed and installed to deliver at least the exhaust airflow required by Table 403.3. The airflows required refer to the delivered airflow of the system as installed and tested using a flow hood, flow grid, or other airflow measurement device.
EXCEPTIONS: | 1. An exhaust airflow rating at a pressure of 0.25 in. w.g. may be used, provided the duct sizing meets the prescriptive requirements of Table 403.8.4.2. |
2. Where a range hood or down draft exhaust fan is used to satisfy the (( |
PRESCRIPTIVE EXHAUST DUCT SIZING
Fan Tested cfm at 0.25 inches w.g. | Minimum Flex Diameter | Maximum Length in Feet |
Minimum Smooth Diameter | Maximum Length in Feet | Maximum Elbows1 | ||||
50 | 4 inches | 25 | 4 inches | 70 | 3 | ||||
50 | 5 inches | 90 | 5 inches | 100 | 3 | ||||
50 | 6 inches | No Limit | 6 inches | No Limit | 3 | ||||
80 | 4 inches2 | NA | 4 inches | 20 | 3 | ||||
80 | 5 inches | 15 | 5 inches | 100 | 3 | ||||
80 | 6 inches | 90 | 6 inches | No Limit | 3 | ||||
100 | 5 inches2 | NA | 5 inches | 50 | 3 | ||||
100 | 6 inches | 45 | 6 inches | No Limit | 3 | ||||
125 | 6 inches | 15 | 6 inches | No Limit | 3 | ||||
125 | 7 inches | 70 | 7 inches | No Limit | 3 |
1. | For each additional elbow, subtract 10 feet from length. |
2. | Flex ducts of this diameter are not permitted with fans of this size. |
403.8.5.1 Outdoor air. Outdoor air shall be distributed to
each habitable space.
Where outdoor air supply intakes are separated from exhaust vents by doors, means shall be provided to ensure airflow to all separated habitable spaces by installing distribution ducts, installed grilles, transoms, doors undercut to a minimum of 1/2-inch above the surface of the finish floor covering, or other similar means where permitted by the International Building Code.
The mechanical system shall operate continuously to supply at least the volume of outdoor air required in Table 403.3 or Table 403.8.1.
EXCEPTION: | Intermittently operating ventilation systems: (( |
(( |
||
The whole house mechanical ventilation system is permitted to operate intermittently where the system has controls that enable operation for not less than 25 percent of each 4-hour segment and the ventilation rate prescribed in Table 403.3 or Table 403.8.1 is multiplied by the factor determined in accordance with Table 403.8.5.1. |
((VENTILATION EFFECTIVENESS FOR)) INTERMITTENT ((FANS)) WHOLE HOUSE MECHANICAL VENTILATION RATE
FACTORSa, b
(( |
||
RUN-TIME PERCENTAGE
IN EACH 4-HOUR SEGMENT |
25% | 33% | 50% | 66% | 75% | 100% |
Factora | 4 | 3 | 2 | 1.5 | 1.3 | 1.0 |
a For ventilation system run-time values between those given, the factors are permitted to be determined by interpolation. | |
b Extrapolation beyond the table is prohibited. |
1. Outdoor air louvers shall be adequately sized for the required airflow and shall comply with Section 401.5. Outdoor air intake locations shall comply with mechanical air intakes requirements of Section 403.8.3.
2. Outdoor air ducts for dedicated or central supply systems and exhaust ducts for heat or energy recovery systems shall be provided with a means for balancing the system to the required airflow via balance dampers or other devices.
3. Outdoor air ducts((,)) for dedicated or central
systems shall be provided with motorized dampers.
EXCEPTIONS: | 1. Outdoor air ducts at heat or energy recovery ventilation systems are not required to have motorized dampers. |
2. Outdoor air ducts at continuous ventilation systems are not required to have motorized dampers. |
5. All outdoor air ducts shall be designed and installed to deliver at least the outdoor airflow required by Section 403.8.5.1. The airflows required refer to the delivered airflow of the system as installed and tested using a flow hood, flow grid, or other airflow measurement device.
EXCEPTION: | The outdoor air duct for supply fan systems and heat or energy recovery systems may be prescriptively sized per Table 403.8.5.2 for dedicated outdoor air ducts upstream of the supply fan. Supply fans shall have the capacity to provide the amount of outdoor air required by Section 403.8.5.1 at 0.40 in. w.g. as per HVI 916 (April 1995). When prescriptively sized the system shall be tested and balanced using a flow hood, flow-grid, or other airflow measurement device. |
6. Whole house ventilation controls for ((continuous
and)) intermittent operation shall ((be provided at both))
allow concurrent operation of the forced-air fan and the
associated outdoor air motorized damper.
7. Whole house ventilation controls for continuous operation shall be provided at the forced-air fan.
EXCEPTION: | Engineered central ventilation systems serving dwelling units or sleeping units are not required to have individual controls for each dwelling or sleeping unit when designed for continuous operation and approved by the code official. |
PRESCRIPTIVE SUPPLY FAN DUCT SIZING
Supply Fan Tested cfm at 0.40" w.g. | ||||
Specified Volume from Table 408.1 | Minimum Smooth Duct Diameter | Minimum Flexible Duct Diameter | ||
50 - 90 cfm | 4 inch | 5 inch | ||
90 - 150 cfm | 5 inch | 6 inch | ||
150 - 250 cfm | 6 inch | 7 inch | ||
250 - 400 cfm | 7 inch | 8 inch |
403.8.6.1 Outdoor air. Exhaust fan only ventilation systems
shall provide outdoor air to each occupiable space through one
of the following methods:
1. Outdoor air may be drawn through air inlets installed
in exterior walls or windows. ((For interior spaces without
openings to the outdoor, air inlets cannot be used unless a
transfer fan is provided in compliance with Section 403.8.6.1
Item 3.)) The air inlets shall comply with all of the
following:
((a)) 1.1. Inlets shall have controllable, secure
openings and shall be designed to not compromise the thermal
properties of the building envelope.
((b)) 1.2. Inlets shall be accessible to occupants,
including compliance with Section 1109.13 of the International
Building Code for designated accessible units, Type A units
and Type B units.
((c)) 1.3. Inlets shall be screened or otherwise
protected from entry by insects, leaves, or other material.
((d)) 1.4. Inlets shall provide not less than 4 square
inches of net free area of opening for each 10 cfm of outdoor
air required in Table 403.3 or Table 403.8.1.
((e)) 1.5. Any inlet or combination of inlets which
provide 10 cfm at 10 Pascals as determined by the Home
Ventilation Institute Air Flow Test Standard (HVI 901
(November 1996)) are deemed equivalent to 4 square inches of
net free area.
((f)) 1.6. Each occupiable space shall have a minimum of
one air inlet that has a minimum of 4 square inches of net
free area.
2. In high-rise buildings, outdoor air may be drawn in
through operable windows, doors, louvers or other operable
openings to the outdoors. Exterior spaces shall have a
minimum openable area of 4 percent of the total floor area
being ventilated. Doors exiting to a corridor, court or
public way shall not be used to provide outdoor air. ((For
interior spaces without openings to the outdoors, the opening
to the adjoining room shall be unobstructed and shall have an
area of not less than 8 percent of the floor area of the
interior room or space, but not less than 25 square feet.)) The operable openings shall comply with the following:
((a)) 2.1. Openings shall be controllable, securable, and
shall be designed to not compromise the thermal properties of
the building envelope.
((b)) 2.2. Openings shall be accessible to occupants,
including compliance with Section 1109.13 of the International
Building Code for designated accessible units, Type A units
and Type B units.
3. For interior adjoining spaces((, in buildings with air
inlets in accordance with Section 403.8.6.1 Item 1 or in
high-rise building without operable openings in accordance
with Section 403.8.6.1 Item 2 shall have a whole house
transfer fan sized to provide a minimum of the ventilation
rate required per Section 403.8.5.1. The transfer fan shall
circulate air between the interior room or space and the
adjacent habitable space. The transfer fan may operate
continuously or intermittently using controls per Section
403.8.2)) without outdoor air openings, one of the following
two options shall be used to ventilate the interior adjoining
space:
3.1. Provide a whole house transfer fan at the interior adjoining space sized to provide a minimum of the ventilation rate required per Section 403.8.5.1. The transfer fan shall circulate air between the interior room or space and the adjacent habitable space. The transfer fan may operate continuously or intermittently using controls per Section 403.8.2.
3.2. Provide a permanent opening to the interior adjoining space. Opening shall be unobstructed and shall have an area of not less than 8 percent of the floor area of the interior adjoining space, but not less than 25 square feet.
403.8.6.2 Outside air intake locations. All outside air
intake opening types described in Section 403.8.6.1 shall be
classified operable openings and shall not be classified as
mechanical air intakes. The intake locations shall comply
with Section 403.8.3.
403.8.6.3 Whole house exhaust system. Whole house exhaust
system shall be designed and installed to meet all of the
applicable criteria below:
1. Whole house ventilation exhaust shall be discharged outdoors.
2. Exhaust outlets shall comply with Section 501.2.
3. Exhaust ducts in systems which are designed to operate intermittently shall be equipped with back-draft dampers.
4. All exhaust ducts in unconditioned spaces shall be insulated to a minimum of R-4.5. Terminal outlet elements shall have at least the equivalent net free area of the ductwork.
5. Terminal outlet elements shall be screened or otherwise protected as required by Section 501.2.2.
6. One of the required ((source specific)) local exhaust
fans for the laundry room or bathroom may be designated as the
whole house exhaust fan.
7. Exhaust fans in separate dwelling units or ((guest
rooms)) sleeping units shall not share common exhaust ducts
unless the system is engineered for this operation.
8. Where permitted by Chapter 5 whole house exhaust ducts
may be combined with other ((source specific)) local exhaust
ducts. If more than one of the exhaust fans in a dwelling
unit or ((guest room)) sleeping unit shares a common exhaust
duct then each exhaust fan shall be equipped with a back-draft
damper to prevent the recirculation of exhaust air from one
room to another room via the exhaust ducting system.
403.8.6.4 Whole house exhaust and transfer fans. Exhaust fan
construction and sizing shall meet the following criteria.
1. Exhaust and transfer fans shall be tested and rated in accordance with the airflow and sound rating procedures of the Home Ventilating Institute (HVI 915, HVI Loudness Testing and Rating Procedure, HVI 916, HVI Airflow Test Procedure, and HVI 920, HVI Product Performance Certification Procedure).
2. Installation of system or equipment shall be carried out in accordance with manufacturers' design requirements and installation instructions.
3. Fan airflow rating and duct system shall be designed and installed to deliver at least the outdoor airflow required by Table 403.3 or Table 403.8.1. The airflows required refer to the delivered airflow of the system as installed and tested using a flow hood, flow grid, or other airflow measurement device.
EXCEPTION: | An airflow rating at a pressure of 0.25 in. w.g. may be used, provided the duct sizing meets the prescriptive requirements of Table 403.8.5.2. |
403.8.7 Whole house ventilation integrated with forced-air
systems. This section establishes minimum requirements for
mechanical whole house ventilation systems using forced-air
system fans.
403.8.7.1 Outdoor air. Forced-air system fan ventilation
systems shall provide outdoor air through one of the following
methods:
1. A dedicated outdoor air louver and outdoor air duct
for each dwelling unit or ((guest room)) sleeping unit shall
supply outdoor air to the return side of the forced-air system
fan; or
2. A central outdoor air delivery system that supplies
multiple dwelling units or ((guest rooms)) sleeping units
shall supply outdoor air to the return side of the forced air
system fan.
403.8.7.2 Whole house forced-air system. Where outdoor air is
provided to each habitable dwelling unit or ((guest room))
sleeping unit by a forced-air system, the outdoor air duct
shall be connected to the return air stream at a point within
4 feet upstream of the forced-air unit. It shall not be
connected directly to the forced-air unit cabinet in order to
prevent thermal shock to the heat exchanger. At a minimum,
filtration of the outdoor air shall be provided at the
forced-air unit. The filter shall be accessible for regular
maintenance and replacement. The filter shall have a Minimum
Efficiency Rating Value (MERV) of at least 6.
403.8.8 Whole house ventilation with supply fan systems. This
section establishes minimum requirements for mechanical whole
house ventilation systems using supply fan systems.
403.8.8.1 Outdoor air. Supply fan ventilation systems shall
provide outdoor air through one of the following methods:
1. A dedicated outdoor air louver and outdoor air duct
for each dwelling unit or ((guest room)) sleeping unit shall
supply outdoor air to a supply fan; or
2. A central outdoor air supply fan system shall
distribute unconditioned or conditioned air to multiple
dwelling units or ((guest rooms)) sleeping units.
403.8.8.2 Whole house supply system. Where outdoor air is
provided to each habitable dwelling unit or ((guest room))
sleeping unit by supply fan systems the outdoor air shall be
filtered.
The system filter may be located at the intake device or inline with the fan. The filter shall be accessible for regular maintenance and replacement. The filter shall have a Minimum Efficiency Rating Value (MERV) of at least 6.
403.8.9 Whole house ventilation with heat recovery or energy
recovery ventilation systems. This section establishes
minimum requirements for mechanical whole house ventilation
systems using heat recovery or energy recovery ventilation
systems.
403.8.9.1 Outdoor air. Heat recovery or energy recovery
ventilation systems shall provide outdoor air through one of
the following methods:
1. A dedicated outdoor air louver and outdoor air duct
for each dwelling unit or ((guest room)) sleeping unit shall
supply outdoor air to the heat recovery or energy recovery
ventilator; or
2. A central outdoor air heat recovery or energy recovery
unit shall distribute conditioned air to multiple dwelling
units or ((guest rooms)) sleeping units.
403.8.9.2 Whole house heat recovery ventilator system. Where
outdoor air is provided to each habitable dwelling unit or
((guest room)) sleeping unit by heat recovery or energy
recovery ventilator the outdoor air shall be filtered. The
filter shall be located on the upstream side of the heat
exchanger in both the intake and exhaust airstreams with a
Minimum Efficiency Rating Value (MERV) of at least 6. The
system filter may be located at the intake device or inline
with the fan. The filter shall be accessible for regular
maintenance and replacement.
403.8.10 ((Source specific)) Local exhaust ventilation and
whole house ventilation alternate performance or design
requirements. In lieu of complying with Sections 403.8.4 or
403.8.5 compliance with the section shall be demonstrated
through engineering calculations by an engineer licensed to
practice in the state of Washington or by performance testing.
Documentation of calculations or performance test results
shall be submitted to and approved by the building official. Performance testing shall be conducted in accordance with
approved test methods.
403.8.11 Alternate systems. When approved by the code
official, systems designed in accordance with ASHRAE Standard
62.2((-2007)) shall be permitted.
[Statutory Authority: RCW 19.27.031, 19.27.035, 19.27.074, and chapters 19.27 and 34.05 RCW. 12-07-020, § 51-52-0403, filed 3/12/12, effective 4/12/12. Statutory Authority: RCW 19.27.190, 19.27.074, 19.27.031 and chapters 19.27 and 34.05 RCW. 10-03-099, § 51-52-0403, filed 1/20/10, effective 7/1/10. Statutory Authority: RCW 19.27.190, 19.27.020, and chapters 19.27 and 34.05 RCW. 07-01-092, § 51-52-0403, filed 12/19/06, effective 7/1/07. Statutory Authority: RCW 19.27.020, 19.27.031, 19.27.074 and chapters 19.27 and 34.05 RCW. 05-01-015, § 51-52-0403, filed 12/2/04, effective 7/1/05.]
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040.
AMENDATORY SECTION(Amending WSR 10-03-099, filed 1/20/10,
effective 7/1/10)
WAC 51-52-0404
Section 404 -- Enclosed parking garages and
automobile repair facilities.
((404.5)) 404.4 Automobile repair facilities. In buildings
used for the repair of automobiles, each repair stall shall be
equipped with an exhaust extension duct, extending to the
outside of the building. Exhaust extension duct over 10 feet
in length shall mechanically exhaust at least 300 cfm. Connecting offices and waiting rooms shall be supplied with
conditioned air under positive pressure.
[Statutory Authority: RCW 19.27.190, 19.27.074, 19.27.031 and chapters 19.27 and 34.05 RCW. 10-03-099, § 51-52-0404, filed 1/20/10, effective 7/1/10.]
((501.2 Exhaust discharge. The air removed by every
mechanical exhaust system shall be discharged outdoors at a
point where it will not cause a nuisance and not less than the
distances specified in Section 501.2.1. The air shall be
discharged to a location from which it cannot again be readily
drawn in by a ventilating system. Air shall not be exhausted
into an attic or crawlspace.
1. For ducts conveying explosive or flammable vapors, fumes or dusts: 30 feet (9144 mm) from the property line; 10 feet (3048 mm) from operable openings into the building; 6 feet (1829 mm) from exterior walls and roofs; 30 feet (9144 mm) from combustible walls and operable openings into the building which are in the direction of the exhaust discharge; 10 feet (3048 mm) above adjoining grade.
2. For other product-conveying outlets: 10 feet (3048 mm) from property lines; 3 feet (914 mm) from exterior walls and roofs; 10 feet (3048 mm) from operable openings into the building; 10 feet (3048 mm) above adjoining grade.
3. For environmental air exhaust other than enclosed parking garage and transformer vault exhaust: 3 feet (914 mm) from property lines, 3 feet (914 mm) from operable openings into buildings for all occupancies other that Group U, and 10 feet (3048 mm) from mechanical air intakes. Such exhaust shall not be considered hazardous or noxious.
EXCEPTIONS: | 1. The separation between an air intake and exhaust outlet on a single listed package HVAC unit. |
2. Exhaust from environmental air systems other than garages may be discharged into an open parking garage. | |
3. Except for Group I occupancies, where ventilation system design circumstances require building HVAC air to be relieved, such as during economizer operation, such air may be relieved into an open or enclosed parking garage within the same building. |
5. For enclosed parking garage exhaust system outlets and
transformer vault exhaust system outlets: 10 feet (3048 mm)
from property lines which separate one lot from another; 10
feet (3048 mm) from operable openings into buildings; 10 feet
(3048 mm) above adjoining ((grade)) finished sidewalk.
6. For elevator machinery rooms in enclosed or open parking garages: Exhaust outlets may discharge air directly into the parking garage.
7. For specific systems see the following sections:
7.1. Clothes dryer exhaust, Section 504.4.
7.2. Kitchen hoods and other kitchen exhaust equipment,
Sections ((506.3)) 506.3.13, 506.4 and 506.5.
7.3. Dust stock and refuse conveying systems, Section
((511)) 511.2.
7.4. Subslab soil exhaust systems, Section 512.4.
7.5. Smoke control systems, Section 513.10.3.
7.6. Refrigerant discharge, Section 1105.7.
7.7. Machinery room discharge, Section 1105.6.1.
501.4 Pressure equalization. Mechanical exhaust systems shall
be sized to remove the quantity of air required by this
chapter to be exhausted. The system shall operate when air is
required to be exhausted. Where mechanical exhaust is
required in a room or space, such space shall be maintained
with a neutral or negative pressure. If a greater quantity of
air is supplied by a mechanical ventilating supply system than
is removed by a mechanical exhaust for a room, adequate means
shall be provided for the natural or mechanical exhaust of the
excess air supplied. If only a mechanical exhaust system is
installed for a room or if a greater quantity of air is
removed by a mechanical exhaust system than is supplied by a
mechanical ventilating supply system for a room, adequate
makeup air consisting of supply air, transfer air or outdoor
air shall be provided to satisfy the deficiency. The
calculated building infiltration rate shall not be used to
satisfy the requirements of this section.
EXCEPTION: | R-3 occupancies and dwelling units in R-2 occupancies are excluded from the pressure equalization requirement unless required by Section 504.5 or Section 505.2. |
[Statutory Authority: RCW 19.27.190, 19.27.074, 19.27.031 and chapters 19.27 and 34.05 RCW. 10-03-099, § 51-52-0501, filed 1/20/10, effective 7/1/10. Statutory Authority: RCW 19.27.190, 19.27.020, and chapters 19.27 and 34.05 RCW. 07-01-092, § 51-52-0501, filed 12/19/06, effective 7/1/07. Statutory Authority: RCW 19.27.020, 19.27.031, 19.27.074 and chapters 19.27 and 34.05 RCW. 05-01-015, § 51-52-0501, filed 12/2/04, effective 7/1/05.]
504.6.4.1 Specified length. The maximum length of the exhaust
duct shall be 35 feet (10668 mm) from the connection to the
transition duct from the dryer to the outlet terminal. Where
fittings are used, the maximum length of the exhaust duct
shall be reduced in accordance with Table 504.6.4.1.
The maximum length of the duct may be increased in an engineered exhaust system when a listed and labeled exhaust booster fan is installed in accordance with the manufacturer's installation instructions.
504.7.1 Protection required. Protective shield plates shall
be provided in accordance with Section 504.6.7.
504.8 Common exhaust systems for clothes dryers located in
multistory structures. Where a common multistory duct system
is designed and installed to convey exhaust from multiple
clothes dryers, the construction of the system shall be in
accordance with all of the following:
1. The shaft in which the duct is installed shall be constructed and fire-resistance rated as required by the International Building Code.
2. Dampers shall be prohibited in the exhaust duct. Penetrations of the shaft and ductwork shall be protected in accordance with Section 607.5.5, Exception 2.
3. Rigid metal ductwork shall be installed within the shaft to convey the exhaust. The ductwork shall be constructed of sheet steel having a minimum thickness of 0.0187 inch (0.4712 mm) (No. 26 gage) and in accordance with SMACNA Duct Construction Standards.
4. The ductwork within the shaft shall be designed and installed without offsets.
5. The exhaust fan motor design shall be in accordance with Section 503.2.
6. The exhaust fan motor shall be located outside of the airstream.
7. The exhaust fan shall run continuously, and shall be connected to a standby power source.
8. Exhaust fan operation shall be monitored in an approved location and shall initiate an audible or visual signal when the fan is not in operation.
9. Makeup air shall be provided for the exhaust system to maintain the minimum flow for the exhaust fan when the dryers are not operating. Additionally, makeup air shall be provided when required by Section 504.5.
10. A cleanout opening shall be located at the base of the shaft to provide access to the duct to allow for cleaning and inspection. The finished opening shall be not less than 12 inches by 12 inches (305 mm by 305 mm).
11. Screens shall not be installed at the termination.
12. The common multistory duct system shall serve only clothes dryers and shall be independent of other exhaust systems.
[Statutory Authority: RCW 19.27.190, 19.27.074, 19.27.031 and chapters 19.27 and 34.05 RCW. 10-03-099, § 51-52-0504, filed 1/20/10, effective 7/1/10. Statutory Authority: RCW 19.27.190, 19.27.020, and chapters 19.27 and 34.05 RCW. 07-01-092, § 51-52-0504, filed 12/19/06, effective 7/1/07.]
505.1 Domestic systems. Where domestic range hoods and
domestic appliances equipped with downdraft exhaust are
located within dwelling units, such hoods and appliances shall
discharge to the outdoors through sheet metal ducts
constructed of galvanized steel, stainless steel, aluminum or
copper. Such ducts shall have smooth inner walls ((and)),
shall be air tight ((and)), shall be equipped with a backdraft
damper((. Domestic range hood duct systems shall not be
combined with other environmental air exhaust systems)) and
shall be independent of all other exhaust systems.
Listed and labeled exhaust booster fans shall be permitted when installed in accordance with the manufacturer's installation instructions.
EXCEPTIONS: | 1. Where installed in accordance with the manufacturer's installation instructions and where mechanical ventilation is otherwise provided in accordance with Chapter 4, listed and labeled ductless range hoods shall not be required to discharge to the outdoors. |
2. Ducts for domestic kitchen cooking appliances equipped with downdraft exhaust systems shall be permitted to be constructed of Schedule 40 PVC pipe and fittings provided that the installation complies with all of the following: | |
2.1. The duct shall be installed under a concrete slab poured on grade. | |
2.2. The underfloor trench in which the duct is installed shall be completely backfilled with sand or gravel. | |
2.3. The PVC duct shall extend not more than 1 inch (25 mm) above the indoor concrete floor surface. | |
2.4. The PVC duct shall extend not more than 1 inch (25 mm) above grade outside of the building. | |
2.5. The PVC ducts shall be solvent cemented. |
[Statutory Authority: RCW 19.27.190, 19.27.074, 19.27.031 and chapters 19.27 and 34.05 RCW. 10-03-099, § 51-52-0505, filed 1/20/10, effective 7/1/10.]
506.3.9 Grease duct cleanout location, spacing and
installation.
506.3.9.1 Grease duct horizontal cleanout. Cleanouts located
on horizontal sections of ducts shall:
1. Be spaced not more than 20 feet (6096 mm) apart.
((The cleanouts shall)) 2. Be located ((on the side of
the duct with the opening not less than 1 1/2 inches (38 mm)
above the bottom of the duct, and not less)) not more than 10
feet (3048 mm) from changes in direction that are greater than
45 degrees (0.79 rad).
3. Be located on the bottom only where other locations are not available and shall be provided with internal damming of the opening such that grease will flow past the opening without pooling. Bottom cleanouts and openings shall be approved for the application and installed liquid-tight.
4. Not be closer than 1 inch (((25)) 25.4 mm) ((below the
top of the duct. The opening minimum)) from the edges of the
duct.
5. Have dimensions ((shall be)) of not less than 12
inches by 12 inches (305 mm by 305 mm) ((on each side)). Where ((the)) such dimensions ((of the side of the duct
prohibit the cleanout)) preclude installation ((prescribed
herein)), the openings shall ((be on the top of the duct or
the bottom of the duct. Where located on the top of the duct,
the opening edges shall be a minimum of 1 inch (25 mm) from
the edges of the duct. Where located in the bottom of the
duct, cleanout openings shall be designed to provide internal
damming around the opening, shall be provided with gasketing
to preclude grease leakage, shall provide for drainage of
grease down the duct around the dam and shall be approved for
the application. Where the dimensions of the sides, top or
bottom of the duct preclude the installation of the prescribed
minimum-size cleanout opening, the cleanout shall be located
on the duct face that affords the largest opening dimension
and shall be installed with the opening edges at the
prescribed distances from the duct edges as previously set
forth in this section)) be not less than 12 inches (305 mm) on
one side and shall be large enough to provide access for
cleaning and maintenance.
6. Shall be located at grease reservoirs.
506.3.9.2 Grease duct vertical cleanouts. Where ducts pass
vertically through floors, cleanouts shall be provided. A
minimum of one cleanout shall be provided on each floor.
Cleanout openings shall be not less than 1 1/2 inches (38 mm)
from all outside edges of the duct or welded seams.
506.3.11 Grease duct enclosures. A grease duct serving a Type
I hood that penetrates a ceiling, wall, floor or any concealed
spaces shall be enclosed from the point of penetration to the
outlet terminal. A duct shall penetrate exterior walls only
at locations where unprotected openings are permitted by the
International Building Code. The duct enclosure shall serve a
single grease duct and shall not contain other ducts, piping
or wiring systems. Duct enclosures shall be either
field-applied or factory-built. Duct enclosures shall have a
fire-resistance rating of not less than that of the assembly
penetrated. The duct enclosure need not exceed 2 hours but
shall not be less than 1 hour. Duct enclosures shall be as
prescribed by Section 506.3.11.1, 506.3.11.2 or 506.3.11.3.
[Statutory Authority: RCW 19.27.190, 19.27.074, 19.27.031 and chapters 19.27 and 34.05 RCW. 10-03-099, § 51-52-0506, filed 1/20/10, effective 7/1/10. Statutory Authority: RCW 19.27.190, 19.27.020, and chapters 19.27 and 34.05 RCW. 07-01-092, § 51-52-0506, filed 12/19/06, effective 7/1/07.]
507.2.1 Type I hoods. Type I hoods shall be installed where
cooking appliances produce grease or smoke. Type I hoods
shall be installed over medium-duty, heavy-duty and
extra-heavy-duty cooking appliances. Type I hoods shall be
installed over light-duty cooking appliances that produce
grease or smoke.
EXCEPTIONS: | 1. A Type I hood shall not be required for an electric cooking appliance where an approved testing agency provides documentation that the appliance effluent contains 5 mg/m3 or less of grease when tested at an exhaust flow rate of 500 cfm in accordance with Section 17 of UL 710B. |
2. A Type I hood shall not be required in an R-2 type occupancy with not more than 16 residents. |
TYPE OF HOOD REQUIRED FOR DOMESTIC COOKING APPLIANCES IN THE FOLLOWING SPACESa, b
Type of Space | Type of Cooking | Type of Hood |
Church | 1. Boiling, steaming and warming precooked food | Type II hood |
2. Roasting, pan frying and deep frying | Type I hood | |
Community or party room in apartment and condominium | 1. Boiling, steaming and warming precooked food | Residential hoodc or Type II hoodd |
2. Roasting, pan frying and deep frying | Type I hood | |
Day care | 1. Boiling, steaming and warming precooked food | Residential hoodc or Type II hoodd |
2. Roasting, pan frying and deep frying | Type I hood | |
Dormitory, boarding home, nursing home | 1. Boiling, steaming and warming precooked food | Type II hood |
2. Roasting, pan frying and deep frying | Type I hood | |
Office lunch room | 1. Boiling, steaming and warming precooked food | Residential hoodc or Type II hoodd |
2. Roasting, pan frying and deep frying | Type I hood |
a Commercial cooking appliances shall comply with Section 507.2. | |
b Requirements in this table apply to electric or gas fuel appliances only. Solid fuel appliances or charbroilers require Type I hoods. | |
c Residential hood shall ventilate to the outside. | |
d Type II hood required when more than one appliance is used. |
[Statutory Authority: RCW 19.27.190, 19.27.074, 19.27.031 and chapters 19.27 and 34.05 RCW. 10-03-099, § 51-52-0507, filed 1/20/10, effective 7/1/10.]
601.2 Air movement in egress elements. Corridors shall not
serve as supply, return, exhaust, relief or ventilation air
ducts.
EXCEPTIONS: | 1. Use of a corridor as a source of makeup air for exhaust systems in rooms that open directly onto
such corridors, including toilet rooms, bathrooms, dressing rooms, smoking lounges and janitor closets,
shall be permitted provided that each such corridor is directly supplied with (( |
2. Where located within a dwelling unit, the use of corridors for conveying return air shall not be prohibited. | |
3. Where located within tenant spaces of one thousand square feet (93 m2) or less in area, utilization of corridors for conveying return air is permitted. | |
4. Incidental air movement from pressurized rooms within health care facilities, provided that the corridor is not the primary source of supply or return to the room. | |
5. Where such air is part of an engineered smoke control system. | |
6. Air supplied to corridors serving residential occupancies shall not be considered as providing ventilation air to the dwelling units subject to the following: | |
6.1 The air supplied to the corridor is one hundred percent outside air; and | |
6.2 The units served by the corridor have conforming ventilation air independent of the air supplied to the corridor; and | |
6.3 For other than high-rise buildings, the supply fan will automatically shut off upon activation of corridor smoke detectors which shall be spaced at no more than thirty feet (9,144 mm) on center along the corridor; or | |
6.4 For high-rise buildings, corridor smoke detector activation will close required smoke/fire dampers at the supply inlet to the corridor at the floor receiving the alarm. |
[Statutory Authority: RCW 19.27.190, 19.27.074, 19.27.031 and chapters 19.27 and 34.05 RCW. 10-03-099, § 51-52-0601, filed 1/20/10, effective 7/1/10. Statutory Authority: RCW 19.27.190, 19.27.020, and chapters 19.27 and 34.05 RCW. 07-01-092, § 51-52-0601, filed 12/19/06, effective 7/1/07. Statutory Authority: RCW 19.27.031 and 19.27.074. 04-01-104, § 51-52-0601, filed 12/17/03, effective 7/1/04.]
605.4 Particulate matter removal. Particulate matter filters
or air cleaners having a minimum efficiency reporting value
(MERV) of not less than 6 for ducted air handlers and not less
than 4 for unducted air handlers shall be provided upstream of
all cooling coils or other devices with wetted surfaces
through which air is supplied to an occupiable space.
[]
928.1 General. Evaporative cooling equipment shall:
1. Be installed in accordance with the manufacturer's instructions.
2. Be installed on level platforms in accordance with Section 304.10.
3. Have openings in exterior walls or roofs flashed in accordance with the International Building Code.
4. Be provided with potable water backflow protection in accordance with backflow requirements in the plumbing code.
5. Have air intake opening locations in accordance with Section 401.4.
[]
((SECTIONS 1003 THROUGH 1011, are not adopted.
Boilers and Unfired Pressure Vessels are regulated by
chapter 70.79 RCW.))
Informational Note: | Boilers and pressure vessels are regulated by chapter 70.79 RCW and chapter 296-104 WAC in addition to the requirements of this code. |
EXCEPTIONS: | 1. Pressure vessels used for unheated water supply. |
2. Portable unfired pressure vessels and Interstate Commerce Commission containers. | |
3. Containers for bulk oxygen and medical gas. | |
4. Unfired pressure vessels having a volume of 5 cubic feet (0.14 m3) or less operating at pressures not exceeding 250 pounds per square inch (psi) (1724 kPa) and located within occupancies of Groups B, F, H, M, R, S and U. | |
5. Pressure vessels used in refrigeration systems that are regulated by Chapter 11 of this code. | |
6. Pressure tanks used in conjunction with coaxial cables, telephone cables, power cables and other similar humidity control systems. | |
7. Any boiler or pressure vessel subject to inspection by federal or state inspection programs. |
[Statutory Authority: RCW 19.27.190, 19.27.074, 19.27.031 and chapters 19.27 and 34.05 RCW. 10-03-099, § 51-52-1000, filed 1/20/10, effective 7/1/10. Statutory Authority: RCW 19.27.190, 19.27.020, and chapters 19.27 and 34.05 RCW. 07-01-092, § 51-52-1000, filed 12/19/06, effective 7/1/07. Statutory Authority: RCW 19.27.031 and 19.27.074. 04-01-104, § 51-52-1000, filed 12/17/03, effective 7/1/04.]
ASHRAE
62.2-((2007)) 2010 Ventilation and Acceptable Indoor Air
Quality in Low-Rise Residential Buildings
[Statutory Authority: RCW 19.27.190, 19.27.074, 19.27.031 and chapters 19.27 and 34.05 RCW. 10-03-099, § 51-52-1500, filed 1/20/10, effective 7/1/10.]
101.2 Scope. This code shall apply to the installation of
fuel gas piping systems, fuel gas utilization equipment,
gaseous hydrogen systems and regulated accessories in
accordance with Section 101.2.1 through 101.2.5.
EXCEPTIONS: | 1. Detached one- and two-family dwellings and multiple single-family dwellings (townhouses) not more than three stories high with separate means of egress and their accessory structures shall comply with the International Residential Code. |
2. The standards for liquefied petroleum gas installations shall be the (( |
[Statutory Authority: RCW 19.27.190, 19.27.074, 19.27.031 and chapters 19.27 and 34.05 RCW. 10-03-099, § 51-52-21101, filed 1/20/10, effective 7/1/10. Statutory Authority: RCW 19.27.190, 19.27.020, and chapters 19.27 and 34.05 RCW. 07-01-092, § 51-52-21101, filed 12/19/06, effective 7/1/07.]
401.9 Identification. Each length of pipe and tubing and each
pipe fitting utilized in a mechanical system shall bear the
identification of the manufacturer.
EXCEPTION: | The manufacturer identification for fittings and pipe nipples shall be on each piece or shall be printed on the fitting or nipple packaging or provided documentation. |
[]
614.7.1 Protection required. Protective shield plates shall
be provided in accordance with Section 614.6.3.
[]