WSR 15-16-109
PROPOSED RULES
BUILDING CODE COUNCIL
[Filed August 4, 2015, 1:01 p.m.]
Original Notice.
Preproposal statement of inquiry was filed as WSR 15-10-077.
Title of Rule and Other Identifying Information: Adoption and amendment of the 2015 International Fire Code (IFC), chapter 51-54A WAC.
Hearing Location(s): Fire Department Training Center, 1618 South Rebecca Street, Spokane, WA, on September 11, 2015, at 10:00 a.m.; and at the DES Presentation Room, 1500 Jefferson S.E., Olympia, WA 98504, on October 16, 2015, at 10:00 a.m.
Date of Intended Adoption: November 13, 2015.
Submit Written Comments to: Dave Kokot, Chair, State Building Code Council (SBCC), P.O. Box 41449, Olympia, WA 98504-1449, e-mail sbcc@ga.wa.gov, fax (360) 586-9088, by October 23, 2015.
Assistance for Persons with Disabilities: Contact Peggy Bryden by August 24, 2015, (360) 407-9280.
Purpose of the Proposal and Its Anticipated Effects, Including Any Changes in Existing Rules: The proposed rules adopt the 2015 edition of the International Code Council (ICC) Fire Code, with state amendments to incorporate proposed changes as adopted by the Washington SBCC. The rules will provide increased clarity and life safety measures.
WAC
Section
Changes in 2015
Discussion
51-54A-0105
 
 
 
 
105.6.4
CO2 systems.
New section.
 
105.6.4.9
Marijuana extraction systems - operational permits.
New; currently adopted as emergency rule.
 
105.7.19
Marijuana extraction systems - construction permits.
New; currently adopted as emergency rule.
 
105.7.20
Underground supply piping - automatic sprinkler system.
New section.
51-54A-0202
 
General definitions.
 
 
 
Assisted living facility.
Emergency drill.
New definition.
Deleted definition.
Deleted reference to R-2 Assisted living facility.
51-54A-0308
 
Open flames.
 
 
308.1.10
Decorative open flame tables.
New section.
51-54A-0402
 
Definitions.
 
 
 
Emergency drill.
Delete reference.
51-54A-0403
 
Emergency preparedness requirements.
New section.
 
403.3.1
403.5.4
403.10.2
403.10.2.4
403.10.3
403.12.3
Fire evacuation plan.
Assembly points and fire operations.
Group R-2 occupancies.
Group R-2 assisted living and residential care facilities.
Group R-4 occupancies. This section is not adopted.
Crowd managers for gatherings exceeding 1,000 people.
 
51-54A-0404
 
Fire safety and evacuation plans.
Section name changed.
 
404.1
General.
Deleted.
 
404.2
Fire safety and emergency plans.
Deleted.
 
404.2.1
Where required.
Deleted.
 
404.2.2
Contents.
Deleted.
 
404.2.2.1
Fire evacuation plans.
Deleted.
 
404.2.2.2
Fire safety plans.
Deleted.
 
404.2.3
Lockdown plans.
This section is not adopted.
 
404.3
Shelter-in-place plans.
Deleted.
 
404.3.1
Where required.
Deleted.
 
404.3.2
Shelter-in-place plan controls.
Deleted.
 
404.4
Maintenance.
Deleted.
 
404.5
Availability.
Deleted.
 
51-54A-0405
 
Emergency evacuation drills.
Modified to add "evacuation."
 
405.1
General.
Corrects reference.
 
405.2
Table 405.2 Fire and Evacuation Drill/Frequency and Participation.
Adds new occupancy groups and modifies requirements for drills.
 
405.6
Notification.
Adds evacuation.
 
405.7
Initiation.
Corrects reference.
 
405.7.1
Fire evacuation drills.
Reference to "assisted living facilities" added.
 
405.7.2
Shelter-in-place drills.
Corrects reference.
51-54A-0406
 
Employee training and response procedures.
 
 
406.1
General.
Corrects reference.
 
406.3.1
Fire prevention training.
New section.
 
406.3.2
Evacuation training.
New section.
 
406.3.3
Fire safety training.
New section.
 
406.3.4
Emergency shelter-in-place training.
Section renumbered.
 
406.4
Emergency lockdown training.
This section is not adopted.
51-54A-0408
 
Use and occupancy related requirements.
Section deleted; WAC number reserved.
51-54A-0507
 
Fire protection water supplies.
 
 
507.3
Fire flow.
Additional exception allowed.
51-54A-0605
 
Electrical equipment, wiring and hazards.
 
 
605.11
Solar photovoltaic power systems.
Modifies references; deletes exception.
 
605.11.1
Access and pathways.
 
 
605.11.1.1
Roof access points.
 
 
605.11.1.2
Solar photovoltaic systems for Group R-3 buildings.
(Note: remove duplicate section.)
 
605.11.1.2.1
Size of solar photovoltaic array.
 
 
605.11.1.2.2
Hip roof layouts.
 
 
605.11.1.2.3
Single ridge roofs.
 
 
605.11.1.2.4
Roofs with hips and valleys.
 
 
605.11.1.2.5
Allowance for smoke ventilation operations.
 
 
605.11.1.3
Other than Group R-3 buildings.
 
 
605.11.1.3.1
Access.
 
 
605.11.1.3.2
Pathways.
 
 
605.11.1.3.3
Smoke ventilation.
 
 
605.11.2
Locations of DC conductors.
Deleted.
 
605.11.3
Access and pathways.
Deleted.
 
605.11.3.2
Residential systems for one- and two-family dwellings.
Deleted.
 
605.11.3.2.3
Residential buildings with roof hips and valleys.
Deleted.
 
605.11.3.2.4
Residential building smoke ventilation.
Deleted.
 
605.11.2
Ground-mounted photovoltaic arrays.
Renumbered.
51-54A-0609
 
Commercial kitchen hoods.
 
 
Table 609.2.1
Reference to "assisted living facilities" added.
 
51-54A-0901
 
General.
New section.
 
901.4.2
Nonrequired fire protection systems.
 
 
901.8.2
Removal of existing occupant-use hose lines.
 
51-54A-0903
 
Automatic sprinkler systems.
 
 
903.2.1.6
Nightclub.
Renumbered/moved to 903.2.1.8.
 
903.2.1.6
Assembly occupancies on roofs.
New.
 
903.2.1.8
Nightclub.
Renumbered/moved from 903.2.1.6.
 
903.2.3
Group E.
Modified.
 
903.2.6
Group I.
New.
 
903.2.11.7
Relocatable buildings within buildings.
New.
 
903.3.5.3
Underground portions of fire protection system water supply piping.
New.
51-54A-0904
 
Alternative automatic fire-extinguishing systems.
New section.
 
904.12
Commercial cooking systems.
 
51-54A-0907
 
Fire alarm and detection systems.
 
 
907.2.6.1
Group I-1.
 
 
907.2.6.4
Group I-4 occupancies.
 
 
907.2.9.1.1
Group R-2 assisted living facilities.
Modified name and exceptions.
 
907.2.9.4
Group R-2 assisted living facilities.
 
 
907.5.2.1.2
Maximum sound pressure.
New.
 
907.10
NICET: National Institute for Certification in Engineering Technologies.
New.
 
907.10.1
Scope.
 
 
907.10.2
Design review.
 
 
907.10.3
Installation/maintenance.
 
51-54A-0908
 
Emergency alarm systems.
Section deleted; WAC number reserved.
51-54A-0909
 
Smoke control systems.
Section deleted; WAC number reserved.
51-54A-0915
 
Alerting systems.
Deleted; moved to WAC 51-54A-0916.
51-54A-0915
 
Carbon monoxide detection.
New.
 
915.1
General.
Modified.
 
915.1.1
Where required.
 
 
915.1.2
Fuel-burning appliances and fuel-burning fireplaces.
 
 
915.1.3
Forced-air furnaces.
 
 
915.1.4
Fuel-burning appliances outside of dwelling units, sleeping units and classrooms.
 
 
915.1.5
Private garages.
 
 
915.1.6
Exempt garages.
 
 
915.2
Locations.
Modified.
 
915.2.1
Dwelling units.
Modified.
 
915.2.2
Sleeping units.
Modified.
 
915.2.3
Group E occupancies.
New.
 
915.3
Duration of operation.
Deleted - moved to WAC 51-54A-0916.
 
915.4
Combination system.
Deleted - moved to WAC 51-54A-0916.
 
915.4.1
System priority.
Deleted - moved to WAC 51-54A-0916.
 
915.4.2
Fire alarm system.
Deleted - moved to WAC 51-54A-0916.
 
915.4.2.1
Signal priority.
Deleted - moved to WAC 51-54A-0916.
 
915.4.2.2
Temporary deactivation.
Deleted - moved to WAC 51-54A-0916.
 
915.4.2.3
Supervisory signal.
Deleted - moved to WAC 51-54A-0916.
 
915.5
Audibility.
Deleted - moved to WAC 51-54A-0916.
 
915.6
Visibility.
Deleted - moved to WAC 51-54A-0916.
51-54A-0916
 
Alerting systems.
New section - previously WAC 51-54A-0915.
 
916.1
General.
 
 
916.2
Power source.
 
 
916.3
Duration of operation.
 
 
916.4
Combination system.
 
 
916.4.1
System priority.
 
 
916.4.2
Fire alarm system.
 
 
916.4.2.1
Signal priority.
 
 
916.4.2.2
Temporary deactivation.
 
 
916.4.2.3
Supervisory signal.
 
 
916.5
Audibility.
 
 
916.6
Visibility.
 
51-54A-1007
 
Accessible means of egress.
Section deleted; WAC number reserved; chapter renumbered to WAC 51-54A-1009.
51-54A-1008
 
Doors, gates and turnstiles.
Section deleted; WAC number reserved; chapter renumbered to WAC 51-54A-1010.
51-54A-1009
 
Stairways and handrails.
Accessible means of egress.
Moved to WAC 51-54A-1011.
Moved from WAC 51-54A-1009.
51-54A-1010
 
Ramps.
Doors, gates and turnstiles.
Moved to WAC 51-54A-1012.
Moved from WAC 51-54A-1008.
51-54A-1011
 
Stairways.
New section – moved from WAC 51-54A-1009.
51-54A-1012
 
Ramps.
Moved from WAC 51-54A-1010.
51-54A-1018
 
Corridors.
Section chapter renumbered to WAC 51-54-1020.
 
1018.6
Corridor continuity.
Deleted.
51-54A-1020
 
Corridors.
New section to replace 1018.
 
1020.5
Air movement in corridors.
Renumbered.
51-54A-1021
 
Number of exits and exit configurations.
Section reserved.
51-54A-1028
 
Exit discharge.
New section.
 
1028.4.1
Width or capacity.
New section.
51-54A-1030
 
Emergency escape and rescue.
New section.
 
1030.1
General.
New section.
51-54A-1103
 
Fire safety requirements for existing buildings.
 
 
1103.4.2
Three to five stories.
New section.
 
1103.4.3
More than five stories.
Modified.
 
1103.5.5
Nightclub.
Renumbered from 1103.4.3.
 
1103.9
Carbon monoxide alarms.
Modifies references and exceptions.
51-54A-1105
 
Construction requirements for existing Group I-2.
New section.
 
1105.1
General.
Provides compliance with federal programs.
51-54A-3103
 
Temporary tents and membrane structures.
New section.
 
3103.5
Use period.
 
51-54A-3800
 
Marijuana processing or extraction facilities.
New chapter.
 
3801
Administration.
New section.
 
3802
Definitions.
New section.
 
3803
Processing or extraction of marijuana.
New section (drafting error assigned 3802 here).
51-54A-5307
 
Carbon dioxide (CO2 systems).
New section.
51-54A-8000
 
Referenced standards.
NFPA 720-15.
Note: Those not listed on the table above remain as adopted in 2012.
Reasons Supporting Proposal: RCW 19.27.031 and 19.27.074.
Statutory Authority for Adoption: RCW 19.27.031 and 19.27.074.
Statute Being Implemented: Chapters 19.27 and 34.05 RCW.
Rule is not necessitated by federal law, federal or state court decision.
Agency Comments or Recommendations, if any, as to Statutory Language, Implementation, Enforcement, and Fiscal Matters: SBCC is seeking comments on the issues proposed in the rules shown below.
Name of Proponent: SBCC, governmental.
Name of Agency Personnel Responsible for Drafting and Implementation: Joanne T. McCaughan, 1500 Jefferson Street, Olympia, (360) 407-9279.
A small business economic impact statement has been prepared under chapter 19.85 RCW.
Small Business Economic Impact Statement
Description: SBCC is filing a proposed rule to adopt the updated 2015 edition of the IFC (chapter 51-54A WAC). Since 1985 SBCC has been responsible to update new editions of the fire code per RCW 19.27.074.
The administrative compliance requirements are under the authority of the local government. RCW 19.27.050. Compliance activities including permit issuance, plan review and approval, and inspections occur at the local level. Requirements for construction document submittal and other reporting requirements are determined by the local jurisdiction and are consistent with previously established policies. The proposed amendments to chapter 51-54A WAC include specific technical requirements for life safety to be consistent with national standards.
The IFC is updated every three years by the ICC. The code development process conducted by the model code organization is open to all interest groups within the design and construction industry and from governmental organizations. See www.iccsafe.org for more information about the model code development process.
Professional Services: Washington state has had a statewide fire code in effect since 1974. The local enforcement authority having jurisdiction administers the codes through the building and/or fire departments. Administrative procedures for state building code compliance are established and will not be changed by the adoption of the update to the current building codes. Small businesses will employ the same types of professional services for the design and construction of buildings and systems to comply with the state building code.
The proposed rule updates the state fire code and does not require additional equipment, supplies, labor or other services. Services needed to comply with the fire code exist within the construction industry as required by the local authority having jurisdiction.
Costs of Compliance for Businesses: The cost of compliance incurred by Washington businesses includes training and educational materials. A complete set of the 2015 model codes on CD rom costs $985 for ICC members. The ICC chapters offer training for continuing education credits to architects, engineers and building inspectors for $285.
The 2015 edition of the IFC contains five amendments with a negative cost impact; an additional ten amendments will have a possible minor cost impact. These items were identified through the model code development process, and reviewed by the SBCC fire code technical advisory group (TAG) and the economic workgroup.
1. Section 403.2 Public safety plan. This provision will remove an exception for Group A and E occupancies from crowd management plans. This change will increase the cost of indoor/outdoor gatherings in Group A and E occupancies, where required by the fire code official to have a fire safety plan.
2. Section 903.2.1 will require fire sprinkler protection where there is more than one level of exit discharge for Group A occupancies. This change will increase the cost of construction for buildings with more than one level of exit discharge for Group A occupants.
3. Sections 903.2.1.1, 903.2.1.2, 903.2.1.3 and 903.2.1.4 re: Group A occupancy. Will require sprinkler systems to be added when more than three hundred occupants share an exit for separated assembly occupancies. The change will increase the cost of construction for certain buildings where exiting is shared for separated assembly occupancies.
4. Section 903.2.11.3 Buildings fifty-five feet or more in height, will require certain airport control towers to install automatic sprinkler systems, where there is any occupiable floor thirty-five feet or more above the lowest level of exit discharge. This change will increase the cost of construction for certain control towers.
5. Section 907.2.22, 907.2.22.1, and 907.2.22.2 Airport control towers, will clarify required locations of smoke detection equipment in airport traffic control towers. Will require sprinklers where an occupied floor is thirty-five feet or more above the lowest level of exit discharge. This change will increase the cost of construction for certain control towers.
6. Section 202 Definitions, will add new items to the list of decorative materials. This change will increase the cost of construction where such materials are used.
7. Section 315.6 Storage plenums in Group I occupancies will require cleanout of excess material in plenums and forbid plenums to be used for storage. Minimal construction cost increase for areas where plenums are installed.
8. Section 318.1 Laundry carts with a capacity of one cubic yard or more, adds Group E and M to occupancies required to comply with fire safety for laundry carts; day care is exempted. Minimal cost increase in Group E and M occupancies.
9. Section 806.2, 907.1, 807.1.2, 807.4.2.2 Artificial vegetation, will require certain test methods per NFPA 701 to be applied to artificial vegetation. Cost increase for projects where artificial vegetation is used.
10. Section 908.7 Carbon monoxide detection, will require CO detection in Group E. Minimal cost as a percentage of building valuation in Group E occupancies.
11. Section 909.5 Smoke barrier construction, clarifies requirements for passive smoke control systems, i.e., for leakage area calculation and testing; clarifies requirements for passive smoke control systems. Construction cost increase where these systems are installed.
12. 909.7 Airflow design method. References NFPA 92 Standard for Smoke Control systems; uses airflow method. Small cost impact for smoke control systems.
13. 3206.9.3 Dead ends, removes reference to Chapter 10; provides 50 foot limit for dead end aisles; allows certain exceptions. Will increase cost of construction for certain aisles.
14. 3304.2.1 Rubbish containers, adds certain safety requirements for rubbish containers exceeding 5.33 cu. ft. Will have a minimal cost impact on certain projects.
15. Table 5003.1.1(1) Maximum allowable quantity per control area of hazardous materials posing a physical hazard, limits NFPA standard amount of fireworks to one hundred twenty-five pounds net. Removes the allowance for an increase when sprinklers are provided. This may increase the cost of construction.
The fire code TAG and the SBCC economic workgroup determined there is a cost for compliance on businesses for the following proposed state amendments:
1. Proposal 14-003: IFC 507.3 Fireflow requirements: This amendment will allow local fire officials to use NFPA 1142 or the WUI code for fire flow requirements where necessary. There will be a small cost impact for fire flow testing in jurisdictions which choose to use these provisions.
2. Proposal 15-006 Group E daycare sprinklers: This amendment will specify that sprinkler systems are installed in Group E fire areas rather than Group E occupancies; exceptions for daycare/preschool when located at level of exit discharge. Construction costs may increase in some jurisdictions.
3. Proposal 15-013 Group R-2 assisted living: This amendment will specify smoke detection requirements in R-2. There will be a minor cost for alarm installations.
4. Proposal 15-021 Marijuana extraction systems: This proposal will require permits for marijuana extraction systems. A construction permit will be required to install a marijuana/cannabis extraction system, and an operational permit will be required to use a marijuana/cannabis extraction system regulated by WAC 314-55-104. The cost is estimated at up to $200 per permit.
5. Proposal 15-024 Vertical openings: This amendment will require fire resistant/smoke-rated construction or fire sprinklers in three- to five-story buildings; when more than five stories, smoke-rated construction is required. Where required the cost would be from $1000 to $5000 per floor/per elevator.
Proposal 15-051 Relocatable buildings within buildings: This amendment will require sprinkler systems be installed where job shacks or portable buildings are within buildings under construction. Where required, the estimated cost of construction is $250; an additional cost of $250 is estimated for enforcement.
6. Proposal 15-088 Commercial cooking systems: This amendment will amend section 904.12 to require signage that identifies appliances in commercial kitchens. The estimated cost impact is $10 per sign.
7. Proposal 15-090 Required fire protection: This amendment will amend section 901.4.1 to require signage for labeling required fire protection systems. The estimated cost impact is $10 per sign.
8. Proposal 15-091 Cannabis processing and extraction facilities: This amendment will create a new Chapter 38 in chapter 51-54A WAC to regulate cannabis processing and extraction facilities. The purpose is to provide additions or exceptions to applicable requirements of the fire code. The requirements of the chapter are retroactive for existing processing and extraction facilities effective July 1, 2016.
The cost impact of this proposal is indeterminate, as this is a new industry in Washington state. According to the July 29, 2015, Weekly Marijuana Report published by the Washington state liquor and cannabis board (LCB), there are currently a total of six hundred seventy-eight processor (forty-eight) and producer/processor (six hundred thirty) licenses issued.
These entities are already obligated to follow the requirements of WAC 314-55-104 Marijuana processor license extraction requirements, as adopted by LCB. Those rules already require specific health and safety measures, establish standards to be followed, require the services of a professional licensed engineer, and adherence to the requirements of the building and fire codes. The proposed rules in chapter 51-54A WAC will provide further direction on what actions are needed to comply with the fire code for extraction and processing of marijuana.
Loss of Sales or Revenue: The proposed rules make the state code for fire safety consistent with national standards. Businesses with new products or updated test or design standards are recognized in the updated fire code.
The update will result in some cost outlay for some small businesses for specific building projects, for a transition period. Other small businesses would see an increase in revenue. The amendments to the building codes affect over 25,000 small businesses in the state, where construction activity occurs. The primary intent of the amendments is to improve the safety features in buildings and provide consistency and fairness across the state, for a predictable business environment. The amendments should result in enhanced safety and value in buildings.
Cost of Compliance for Small Businesses: The majority of businesses affected by the updates to the building codes are small businesses; over ninety-five percent of those listed in the construction and related industries have under fifty employees. The costs per employee are comparable between the largest businesses and the majority of small businesses. The cost to comply with the updated codes is not a disproportionate impact on small business. Where SBCC found the cost of compliance for small businesses to be disproportionate, the proposed rule mitigates the cost. The proposed rules include a definition of small business and provide exceptions for compliance with the updated rule.
Reducing the Costs of the Rule on Small Businesses: The revision history for the 2015 model code amendments shows several hundred amendments proposed by industry and local governments which add flexibility and clarity to the code and coordinate rules, and represent a savings for small business building owners and operators. SBCC conducted a detailed review process, including participation at the national code development hearings, to document significant economic impacts of the proposed code amendments. These amendments are proposed to reduce the cost of compliance on small businesses.
Small Businesses Involved in the Development of the Rule: SBCC conducted fourteen open public meetings of the fire code TAG, available via telephone conference bridge and over the internet, and allowed comment on every item on every agenda. SBCC appointed over one hundred representatives of all segments of the business, construction, and fire safety community to serve on SBCC's seven TAGs.
List of Industries: Below is a list of industries required to comply with the fire code:
NAICS #
Type of Business
Businesses with 50 employees or less
Businesses with more than 50 employees
236115
New single-family housing construction
2523
18
236116
New multifamily housing construction
69
4
236118
Residential remodelers
4298
3
236210
Industrial building construction
88
8
236220
Commercial and institutional building construction
1151
40
238110
Poured concrete foundation and structure contractors
987
14
238120
Structural steel and precast concrete contractors
154
10
238130
Framing contractors
1866
17
238140
Masonry contractors
517
1
238150
Glass and glazing contractors
208
6
238160
Roofing contractors
925
11
238170
Siding contractors
558
1
238190
Other foundation, structure, and building exterior contractors
145
1
238220
Plumbing, heating, and air-conditioning contractors
2245
66
238290
Other building equipment contractors
315
6
238310
Drywall and insulation contractors
898
18
238990
All other specialty trade contractors
1141
15
321213
Engineered wood member (except truss) manufacturing
10
4
321214
Truss manufacturing
14
4
321911
Wood window and door manufacturing
31
1
327310
Cement manufacturing
3
1
327320
Ready-mix concrete manufacturing
41
7
327331
Concrete block and brick manufacturing
13
1
332311
Prefabricated metal building and component manufacturing
16
4
332312
Fabricated structural metal manufacturing
67
8
332321
Metal window and door manufacturing
10
1
332322
Sheet metal work manufacturing
69
8
333415
Air-conditioning and warm air heating equipment
13
2
335110
Electric lamp bulb and part manufacturing
3
 
335121
Residential electric lighting fixture manufacturing
14
 
335122
Commercial, industrial, and institutional electric light
2
1
335129
Other lighting equipment manufacturing
3
1
423310
Lumber, plywood, millwork, and wood panel merchant wholesale
196
12
423320
Brick, stone, and related construction material merchant
68
1
423330
Roofing, siding, and insulation material merchant wholesale
33
4
423390
Other construction material merchant wholesalers
78
 
423720
Plumbing and heating equipment and supplies (hydronics)
99
6
423730
Warm air heating and air-conditioning equipment and supplies
48
1
531110
Lessors of residential buildings and dwellings
1525
152
531120
Lessors of nonresidential buildings (except miniwarehouse)
2046
7
541310
Architectural services
579
19
541330
Engineering services
2351
82
541340
Drafting services
69
 
541350
Building inspection services
168
1
922160
Fire protection
246
31
 
Total
25,903
598
Estimate of the Number of Jobs That Will Be Created or Lost: The adoption of the latest code edition is not expected to significantly impact the number of jobs in the construction industry. These rules are likely to be job neutral overall, i.e., they will not result in any job gains or losses. The scheduled effective date of the new edition is July 1, 2016. Building permits issued prior to that date will be vested under the 2012 building code. Permits issued for projects under the 2015 code edition will start with the 2017 construction season.
The construction industry has experienced growth over the period June 2014 to June 2015.
Data from current employment statistics (CES):
Wage and salary workers
2015
2014
Residential building construction
25,600
22,400
Nonresidential building construction
18,700
16,500
Specialty trade contractors
114,200
101,400
Total
158,500
140,300
A copy of the statement may be obtained by contacting Tim Nogler, P.O. Box 41449, Olympia, WA 98504-1449, phone (360) 407-9277, fax (360) 407-9088, e-mail sbcc@ga.wa.gov.
A cost-benefit analysis is not required under RCW 34.05.328. SBCC is not one of the agencies identified as required to prepare an analysis. However, SBCC intends to prepare an analysis prior to the final adoption of these rules and a copy can be requested using the same information as provided for the small business economic impact statement.
August 4, 2015
David F. Kokot
Chair
AMENDATORY SECTION (Amending WSR 13-04-063, filed 2/1/13, effective 7/1/13)
WAC 51-54A-008 Implementation.
The International Fire Code adopted by chapter 51-54A WAC shall become effective in all counties and cities of this state on July 1, ((2013)) 2016.
AMENDATORY SECTION (Amending WSR 13-04-063, filed 2/1/13, effective 7/1/13)
WAC 51-54A-0105 Permits.
SECTION 105 SCOPE AND GENERAL REQUIREMENTS
105.1.1 Permits required. Any property owner or authorized agent who intends to conduct an operation or business, or install or modify systems and equipment, which is regulated by this code, or to cause any such work to be done shall first make application to the fire code official and obtain the required permit.
105.6.4 Carbon dioxide systems. An operational permit is required for carbon dioxide systems having more than 100 pounds of carbon dioxide.
105.6.4.9 Marijuana extraction systems. An operational permit is required to use a marijuana/cannabis extraction system regulated under WAC 314-55-104.
105.7.19 Marijuana extraction systems. A construction permit is required to install a marijuana/cannabis extraction system regulated under WAC 244-55-104.
105.7.20 Underground supply piping for automatic sprinkler system. A construction permit is required for the installation of the portion of the underground water supply piping, public or private, supplying a water-based fire protection system. The permit shall apply to all underground piping and appurtenances downstream of the first control valve on the lateral piping or service line from the distribution main to one foot above finished floor of the facility with the fire protection system. Maintenance performed in accordance with this code is not considered to be a modification and does not require a permit.
EXCEPTIONS:
1. When the underground piping is installed by the aboveground piping contractor.
 
2. Underground piping serves a fire protection system installed in accordance with NFPA 13D.
AMENDATORY SECTION (Amending WSR 14-24-090, filed 12/1/14, effective 5/1/15)
WAC 51-54A-0202 General definitions.
SECTION 202 GENERAL DEFINITIONS
ADULT FAMILY HOME. A dwelling, licensed by Washington state, in which a person or persons provide personal care, special care, room and board to more than one but not more than six adults who are not related by blood or marriage to the person or persons providing the services.
ALERT SIGNAL. A distinctive signal indicating the need for trained personnel and occupants to initiate a specific action, such as shelter-in-place.
ALERT SYSTEM. Approved devices, equipment and systems or combinations of systems used to transmit or broadcast an alert signal.
ASSISTED LIVING FACILITY. A home or other institution, licensed by the state of Washington, providing housing, basic services and assuming general responsibility for the safety and well-being of residents under chapters 18.20 RCW and 388-78A WAC. These facilities may provide care to residents with symptoms consistent with dementia requiring additional security measures.
CHILD CARE. For the purposes of these regulations, child care is the care of children during any period of a 24-hour day.
CHILD CARE, FAMILY HOME. A child care facility, licensed by Washington state, located in the dwelling of the person or persons under whose direct care and supervision the child is placed, for the care of twelve or fewer children, including children who reside at the home.
CLUSTER. Clusters are multiple portable school classrooms separated by less than the requirements of the building code for separate buildings.
COVERED BOAT MOORAGE. A pier or system of floating or fixed access ways to which vessels on water may be secured and any portion of which are covered by a roof.
ELECTRICAL CODE. The National Electrical Code, promulgated by the National Fire Protection Association, as adopted by rule or local ordinance under the authority of chapter 19.28 RCW.
((EMERGENCY DRILL. An exercise performed to train staff and occupants and to evaluate their efficiency and effectiveness in carrying out emergency procedures.))
EXISTING. Buildings, facilities or conditions that are already in existence, constructed or officially authorized prior to the adoption of this code.
GRAVITY-OPERATED DROP OUT VENTS. Automatic smoke and heat vents containing heat-sensitive glazing designed to shrink and drop out of the vent openings when exposed to fire.
HOSPICE CARE CENTER. A building or portion thereof used on a 24-hour basis for the provision of hospice services to terminally ill inpatients.
MOTOR VEHICLE. Includes, but not limited to, a vehicle, machine, tractor, trailer or semitrailer, or any combination thereof, propelled or drawn by mechanical power and designed for use upon the highways in the transportation of passengers or property. It does not include a vehicle, locomotive or car operated exclusively on a rail or rails, or a trolley bus operated by electric power derived from a fixed overhead wire, furnishing local passenger transportation similar to street-railway service. The term "motor vehicle" also includes freight containers or cargo tanks used, or intended for use, in connection with motor vehicles.
NIGHTCLUB. An A-2 Occupancy use under the 2006 International Building Code in which the aggregate area of concentrated use of unfixed chairs and standing space that is specifically designated and primarily used for dancing or viewing performers exceeds three hundred fifty square feet, excluding adjacent lobby areas. "Nightclub" does not include theaters with fixed seating, banquet halls, or lodge halls.
OCCUPANCY CLASSIFICATION. For the purposes of this code, certain occupancies are defined as follows:
Group I-2. This occupancy shall include buildings and structures used for medical care on a 24-hour basis for more than five persons who are incapable of self-preservation. This group shall include, but not be limited to, the following:
Foster care facilities
Detoxification facilities
Hospice care centers
Hospitals
Nursing homes
Psychiatric hospitals
Five or fewer persons receiving care. A facility such as the above with five or fewer persons receiving such care shall be classified as Group R-3 or shall comply with the International Residential Code provided an automatic sprinkler system is installed in accordance with Section 903.3.1.3 or with Section P2904 of the International Residential Code.
Licensed care facility. A facility such as the above providing licensed care to clients in one of the categories listed in Section 310.1 of the International Building Code licensed by Washington state shall be classified as Group R-2.
Family home child care. Family home child care licensed by Washington state for the care of twelve or fewer children shall be classified as Group R-3 or shall comply with the International Residential Code.
Adult care facility. A facility that provides accommodations for less than 24 hours for more than five unrelated adults and provides supervision and personal care services shall be classified as Group I-4.
EXCEPTION:
Where the occupants are capable of responding to an emergency situation without physical assistance from the staff, the facility shall be classified as Group R-3.
Child care facility. Child care facilities that provide supervision and personal care on a less than 24-hour basis for more than five children 2 1/2 years of age or less shall be classified as Group I-4.
EXCEPTIONS:
1. A child day care facility that provides care for more than five but no more than 100 children 2 1/2 years or less of age, where the rooms in which the children are cared for are located on a level of exit discharge serving such rooms and each of these child care rooms has an exit door directly to the exterior, shall be classified as Group E.
 
2. Family child care homes licensed by Washington state for the care of 12 or fewer children shall be classified as Group R-3.
Residential Group R. Residential Group R includes, among others, the use of a building or structure, or a portion thereof, for sleeping purposes when not classified as an Institutional Group I or when not regulated by the International Residential Code. This group shall include:
R-1 Residential occupancies containing sleeping units where the occupants are primarily transient in nature, including:
Boarding houses (transient) with more than 10 occupants
Congregate living facilities (transient) with more than 10 occupants
Hotels (transient)
Motels (transient)
R-2 Residential occupancies containing sleeping units or more than two dwelling units where the occupants are primarily permanent in nature, including:
Apartment houses
((Assisted living facilities as licensed by Washington state under chapter 388-78A WAC))
Boarding houses (nontransient) with more than 16 occupants
Congregate living facilities (nontransient) with more than 16 occupants
Convents
Dormitories
Fraternities and sororities
Hotels (nontransient)
Live/work units
Monasteries
Motels (nontransient)
Residential treatment facilities as licensed by Washington state under chapter 246-337 WAC
Vacation timeshare properties
R-3 Residential occupancies where the occupants are primarily permanent in nature and not classified as Group R-1, R-2, or I, including:
Buildings that do not contain more than two dwelling units.
Boarding houses (nontransient) with 16 or fewer occupants.
Boarding houses (transient) with 10 or fewer occupants.
Care facilities that provide accommodations for five or fewer persons receiving care.
Congregate living facilities (nontransient) with 16 or fewer occupants.
Congregate living facilities (transient) with 10 or fewer occupants.
Care facilities within a dwelling. Care facilities for five or fewer persons receiving care that are within a single-family dwelling are permitted to comply with the International Residential Code provided an automatic sprinkler system is installed in accordance with Section 903.3.1.3 or with Section P2904 of the International Residential Code.
Adult family homes, family home child care. Adult family homes and family home child care facilities that are within a single-family home are permitted to comply with the International Residential Code.
Foster family care homes. Foster family care homes licensed by Washington state are permitted to comply with the International Residential Code, as an accessory use to a dwelling, for six or fewer children including those of the resident family.
R-4 Classification is not adopted. Any reference in this code to R-4 does not apply.
PORTABLE SCHOOL CLASSROOM. A prefabricated structure consisting of one or more rooms with direct exterior egress from the classroom(s). The structure is transportable in one or more sections, and is designed to be used as an educational space with or without a permanent foundation. The structure shall be capable of being demounted and relocated to other locations as needs arise.
RECALL SIGNAL. An electrically or mechanically operated signal used to recall occupants after an emergency drill or to terminate a shelter-in-place event that shall be distinct from any alarm or alert signal used to initiate an emergency plan, or other signals.
SHELTER-IN-PLACE. An emergency response used to minimize exposure of facility occupants to chemical or environmental hazards by taking refuge in predetermined interior rooms or areas where actions are taken to isolate the interior environment from the exterior hazard.
AMENDATORY SECTION (Amending WSR 13-04-063, filed 2/1/13, effective 7/1/13)
WAC 51-54A-0308 Open flames.
308.1.4 Open-flame cooking devices. This section is not adopted.
308.1.7 Religious ceremonies. Participants in religious ceremonies shall not be precluded from carrying hand-held candles. See RCW 19.27.031(3).
308.1.9 Aisles and exits. Candles shall be prohibited in areas where occupants stand, or in an aisle or exit.
EXCEPTION:
Candles used in religious ceremonies.
308.1.10 Decorative open flame tables. Gas-fired portable or fixed open flame fire tables and fireplaces are required to be provided with fire code official approved design or protection devices to prevent occupants from using flame, and from flame being exposed to combustible material. A fire extinguisher shall be located within 75 feet of travel distance or a distance as approved by the fire code official. Where located indoors, the supply gas valve will be interlocked with building fire alarm and/or fire sprinklers, where provided.
AMENDATORY SECTION (Amending WSR 13-04-063, filed 2/1/13, effective 7/1/13)
WAC 51-54A-0402 Definitions.
The following terms are defined in Chapter 2:
ALARM SIGNAL
ALERT SIGNAL
ALERT SYSTEM
((EMERGENCY DRILL))
SHELTER-IN-PLACE
RECALL SIGNAL
NEW SECTION
WAC 51-54A-0403 Emergency preparedness requirements.
403.3.1 Fire evacuation plan. The fire safety and evacuation plan required by Section 404 shall include a description of special staff actions. This shall include a description for stabilizing patients in a staged evacuation or full evacuation in conjunction with the entire building, if part of a multitenant facility.
403.5.4 Assembly points and fire operations. Assembly points shall not be in areas likely to be utilized for fire service operations.
403.10.2 Group R-2 occupancies. Group R-2 occupancies shall comply with Sections 403.10.2.1 through 403.10.2.4.
403.10.2.4 Group R-2 assisted living and residential care facilities. Assisted living and residential care facilities licensed by the state of Washington shall comply with Section 403.8.1 as required for Group I-1 Condition 2 occupancies.
403.10.3 Group R-4 occupancies. This section not adopted.
403.12.3 Crowd managers for gatherings exceeding 1,000 people. Where facilities or events involve a gathering of more than 1,000 people, or as required by the fire code official, crowd managers shall be provided in accordance with Sections 403.12.3.1 through 403.12.3.3.
AMENDATORY SECTION (Amending WSR 13-04-063, filed 2/1/13, effective 7/1/13)
WAC 51-54A-0404 Fire safety and ((emergency)) evacuation plans.
((404.1 General. Fire safety, evacuation, shelter-in-place plans and associated drills shall comply with the requirements of Sections 404.2 through 404.5.1.
404.2 Fire safety and evacuation plans. Fire safety and evacuation plans shall comply with the requirements of Sections 404.2.1 through 404.2.2.2.
404.2.1 Where required. An approved fire safety and evacuation plan shall be prepared and maintained for the following occupancies and buildings.
1. Group A having an occupant load of 100 or more.
2. Group B buildings having an occupant load of 500 or more persons or more than 100 persons above or below the lowest level of exit discharge.
3. Group E.
4. Group F buildings having an occupant load of 500 or more persons or more than 100 persons above or below the lowest level of exit discharge.
5. Group H.
6. Group I.
7. Group R-1.
8. Group R-2 college and university buildings. Boarding homes, group homes, and residential treatment facilities licensed by the state of Washington.
9. High-rise buildings.
10. Group M buildings having an occupant load of 500 or more persons or more than 100 persons above or below the lowest level of exit discharge.
11. Covered malls exceeding 50,000 square feet (4645 m2) in aggregate floor area.
12. Open mall buildings exceeding 50,000 square feet (4645 m2) in aggregate area within perimeter line.
13. Underground buildings.
14. Buildings with an atrium and having an occupancy in Group A, E or M.
404.2.2 Contents. Fire evacuation and safety plan contents shall be in accordance with Sections 404.2.2.1 and 404.2.2.2.
404.2.2.1 Fire evacuation plans. Fire evacuation plans shall include the following:
1. Emergency egress or escape routes and whether evacuation of the building is to be complete or, where approved, by selected floors or areas only.
2. Procedures for employees who must remain to operate critical equipment before evacuating.
3. Procedures for assisted rescue for persons unable to use the general means of egress unassisted.
4. Procedures for accounting for employees and occupants after evacuation has been completed.
5. Identification and assignment of personnel responsible for rescue or emergency medical aid.
6. The preferred and any alternative means of notifying occupants of a fire.
7. The preferred and any alternative means of reporting fires and other emergencies to the fire department or designated emergency response organization.
8. Identification and assignment of personnel who can be contacted for further information or explanation of duties under the plan.
9. A description of the emergency voice/alarm communication system alert tone and preprogrammed voice messages, where provided.
404.2.2.2 Fire safety plans. Fire safety plans shall include the following:
1. The procedure for reporting a fire or other emergency.
2. The life safety strategy and procedures for notifying, relocating or evacuating occupants, including occupants who need assistance.
3. Site plans indicating the following:
3.1. The occupancy assembly point.
3.2. The locations of fire hydrants.
3.3. The normal routes of fire department vehicle access.
4. Floor plans identifying the locations of the following:
4.1. Exits.
4.2. Primary evacuation routes.
4.3. Secondary evacuation routes.
4.4. Accessible egress routes.
4.5. Areas of refuge.
4.6. Exterior areas for assisted rescue.
4.7. Manual fire alarm boxes.
4.8. Portable fire extinguishers.
4.9. Occupant-use hose stations.
4.10. Fire alarm annunciators and controls.
5. A list of major fire hazards associated with the normal use and occupancy of the premises, including maintenance and housekeeping procedures.
6. Identification and assignment of personnel responsible for maintenance of systems and equipment installed to prevent or control fires.
7. Identification and assignment of personnel responsible for maintenance, housekeeping and controlling fuel hazard sources.
404.3 Shelter-in-place plans. Shelter-in-place plans shall comply with the requirements of Sections 404.3.1 through 404.3.2.
404.3.1 Where required. A shelter-in-place plan shall be prepared and maintained for all Group E occupancies.
EXCEPTION:
Day cares not colocated on a Group E campus.
404.3.2 Shelter-in-place plan contents. Shelter-in-place plans shall include the following:
1. Identification of the procedures of initiating the shelter-in-place plan throughout the facility or campus.
2. Identification of prearranged alert and recall signals to notify all occupants.
3. Identification of procedures for reporting the facility is sheltering-in-place to the local emergency dispatch center.
4. A means of two-way communication between a central location and each secure area, and consideration for maintaining means of communication in absence of primary power.
5. Identification of protective security measures.
6. Location of emergency supplies.
7. Accountability procedures for staff to report the presence or absence of occupants.
8. Identification of crisis response team members in accordance with the National Incident Management System.
9. Actions to be taken in the event of a fire or medical emergency while sheltering-in-place.
404.4 Maintenance. Emergency plans shall be reviewed or updated annually or as necessitated by changes in staff assignments, occupancy or the physical arrangement of the building.
404.5 Availability. Emergency plans shall be available in the workplace for reference and review by employees, and copies shall be furnished to the fire code official for review upon request.)) 404.2.3 Lockdown plans. This section is not adopted.
AMENDATORY SECTION (Amending WSR 13-20-118, filed 10/1/13, effective 11/1/13)
WAC 51-54A-0405 Emergency evacuation drills.
405.1 General. Emergency drills complying with the provisions of this section shall be conducted at least annually in the occupancies listed in Section ((404.2.1)) 405.2.1 or when required by the fire code official. Drills shall be designed in cooperation with the local authorities.
405.2 Frequency. Required emergency drills shall be held at the intervals specified in Table 405.2 or more frequently where necessary to familiarize all occupants with the drill procedure.
405.2.1 Group E occupancies. The occupancy shall conduct at a minimum the following drills during the year:
1. One drill using the school mapping information system.
EXCEPTION:
Day cares not colocated on a school campus.
2. Three fire evacuation drills.
3. One shelter-in-place drill.
4. Additional drills shall be as required by RCW 28A.320.125.
Table 405.2
((Emergency)) Fire and Evacuation Drill Frequency and Participation
Group or Occupancy
Frequency
Participation
Group A
Quarterly
Employees
Group Bb
Annually
All Occupants
Group Bb,c
(Ambulatory Care Facilities)
Annually
Employees
Group Bb
(Clinic, outpatient)
Annually
Employees
Group E
Monthlya,e
All Occupants
Group F
Annually
Employees
Group I-1
((Quarterly)) Semiannually on each shift
((Employeesb))
All Occupants
Group I-2
Quarterly on each shifta
Employees
Group I-3
Quarterly on each shifta
Employees
Group I-4
Quarterly on each shifta
All Occupants
Group R-1
Quarterly on each shift
Employees
Group R-2f
Quarterly on each shift
Employees
Group R-2d
Four Annually
All Occupants
High-rise buildings
Annually
Employees
((a
The frequency shall be allowed to be modified in accordance with Section 408.3.2.
b
Fire and evacuation drills in residential care assisted living facilities shall include complete evacuation of the premises in accordance with Section 408.10.5. Where occupants receive habilitation or rehabilitation training, fire prevention and fire safety practices shall be included as part of the training program.
c
Group B buildings having an occupant load of 500 or more persons or more than 100 persons above or below the lowest level of exit discharge.))
a
In severe climates, the fire code official shall have the authority to modify the emergency evacuation drill frequency.
b
Emergency evacuation drills are required in Group B buildings having an occupant load of 500 or more persons or more than 100 persons above or below the level of exit discharge.
c
Emergency evacuation drills are required in ambulatory care facilities in accordance with Section 403.3.
d
((Applicable to)) Emergency evacuation drills in Group R-2 college and university buildings shall be in accordance with Section ((408.3)) 403.10.2.1. Other Group R-2 occupancies shall be in accordance with Section 403.10.2.2.
e
Day cares colocated on a Group E campus shall participate in emergency drills occurring on the campus.
f
Applicable to ((boarding homes,)) group homes((, and residential treatment facilities)) licensed by the state of Washington. Emergency evacuation drills for assisted living facilities and residential treatment facilities licensed by the state of Washington are required to meet the requirements of Group I-1.
405.4 Time. Drills shall be held at unexpected times and under varying conditions to simulate the unusual conditions that occur in case of an emergency.
405.5 Recordkeeping. Records shall be maintained of required emergency evacuation drills and include the following information:
1. Identity of the person conducting the drill.
2. Date and time of the drill.
3. Notification method used.
4. Staff members on duty and participating.
5. Number of occupants participating.
6. Special conditions simulated.
7. Problems encountered and corrective actions taken.
8. Weather conditions when occupants were evacuated.
9. Time required to accomplish complete evacuation, or shelter-in-place.
405.6 Notification. Where required by the fire code official, prior notification of emergency evacuation drills shall be given to the fire code official.
405.7 Initiation. Emergency drills shall be initiated in accordance with Sections 405.7.1 through ((405.7.2)) 405.7.3.
405.7.1 Fire evacuation drills. Where a fire alarm system is provided, emergency evacuation drills shall be initiated by activating the fire alarm system. The fire alarm monitoring company shall be notified prior to the activation of the fire alarm system for drills proposed and again at the conclusion of the transmission and restoration of the fire alarm system to normal mode.
EXCEPTION:
Drills conducted between the hours of 9:00 p.m. and 6:00 a.m., in ((Group R-2 boarding homes)) assisted living facilities, group homes, and residential treatment facilities licensed by the state of Washington.
405.7.2 Shelter-in-place drills. Shelter-in-place drills shall be initiated by the shelter-in-place alert signal, generated by ((the)) an alerting system in accordance with Section ((915)) 907.5.2.
405.8 Accountability. As building occupants arrive at the assembly point, efforts shall be made to determine if all occupants have been successfully evacuated and/or have been accounted for in the shelter-in-place.
405.9 Recall and reentry. The recall signal initiation shall be manually operated and under the control of the person in charge of the premises or the official in charge of the incident. No one shall reenter the premises until authorized to do so by the official in charge.
AMENDATORY SECTION (Amending WSR 13-04-063, filed 2/1/13, effective 7/1/13)
WAC 51-54A-0406 Employee training and response procedures.
406.1 General. Employees in the occupancies listed in Section ((404.2.1)) 403 shall be trained in the emergency procedures described in their emergency plans. Training shall be based on these plans and as described in Section 404.2 and 404.3.
406.2 Frequency. Employees shall receive training in the contents of the emergency plans and their duties as part of new employee orientation and at least annually thereafter. Records shall be kept and made available to the fire code official upon request.
406.3 Employee training program. Employees shall be trained in fire prevention, evacuation, sheltering-in-place, and fire safety in accordance with Sections 406.3.1 through 406.3.3.
((406.3.3)) 406.3.1 Fire prevention training. Employees shall be apprised of the fire hazards of the materials and processes to which they are exposed. Each employee shall be instructed in the proper procedures for preventing fires in the conduct of their assigned duties.
406.3.2 Evacuation training. Employees shall be familiarized with the fire alarm and evacuation signals, their assigned duties in the event of an alarm or emergency, evacuation routes, areas of refuge, exterior assembly areas and procedures for evacuation.
406.3.3 Fire safety training. Employees assigned firefighting duties shall be trained to know the locations and proper use of portable fire extinguishers or other manual firefighting equipment and the protective clothing or equipment required for its safe and proper use.
406.3.4 Emergency shelter-in-place training. Where a facility has a shelter-in-place plan, employees shall be trained on the alert and recall signals, communication system, location of emergency supplies, the use of the incident notification and alarm system, and their assigned duties and procedures in the event of an alarm or emergency.
406.4 Emergency lockdown training. This section is not adopted.
AMENDATORY SECTION (Amending WSR 13-04-063, filed 2/1/13, effective 7/1/13)
WAC 51-54A-0408 ((Use and occupancy-related requirements.)) Reserved.
((408.10 Group R-4 occupancies. This section is not adopted.))
AMENDATORY SECTION (Amending WSR 13-04-063, filed 2/1/13, effective 7/1/13)
WAC 51-54A-0507 Fire protection water supplies.
507.3 Fire flow. Fire flow requirements for buildings or portions of buildings and facilities shall be determined by an approved method.
EXCEPTIONS:
1. Fire flow is not required for structures under 500 square feet with a B, U or R-1 occupancy where structures are at least 30 feet from any other structure and are used only for recreation.
 
2. In rural and suburban areas in which adequate and reliable water supply systems do not exist, the fire code official is authorized to utilize NFPA 1142 or the International Wildland-Urban Interface Code.
AMENDATORY SECTION (Amending WSR 13-24-076, filed 12/2/13, effective 4/1/14)
WAC 51-54A-0605 Electrical equipment, wiring and hazards.
605.11 Solar photovoltaic power systems. Installation, modification, or alteration of solar photovoltaic power systems shall comply with this section. Due to the emerging technologies in the solar photovoltaic industry, it is understood fire code officials may need to amend prescriptive requirements of this section to meet the requirements for firefighter access and product installations. Section 104.9 Alternative materials and methods of this code shall be considered when approving the installation of solar photovoltaic power systems. Solar photovoltaic power systems shall be installed in accordance with Sections 605.11.1 through ((605.11.4)) 605.11.2, the International Building Code and ((NFPA 70)) chapter 19.28 RCW.
((EXCEPTION:
Detached, nonhabitable Group U structures shall not be subject to the requirements of Sections 605.11.2 through 605.11.3.3.3.
605.11.1.2 Marking content. The marking shall contain the words "PHOTOVOLTAIC POWER SOURCE."
605.11.2 Locations of DC conductors. Conduit, wiring systems, and raceways for photovoltaic circuits shall be located as close as possible to the ridge or hip or valley and from the hip or valley as directly as possible to an outside wall to reduce trip hazards and maximize ventilation opportunities. Conduit runs between sub arrays and to DC combiner boxes shall be installed in a manner that minimizes the total amount of conduit on the roof by taking the shortest path from the array to the DC combiner box. The DC combiner boxes shall be located such that conduit runs are minimized in the pathways between arrays. DC wiring shall be installed in metallic conduit or raceways when located within enclosed spaces in a building.
605.11.3 Access and pathways. Roof access, pathways, and spacing requirements shall be provided in accordance with Sections 605.11.3.1 through 605.11.3.3.3.
EXCEPTIONS:
1. Residential structures shall be designed so that each photovoltaic array is no greater than 150 feet (45,720 mm) by 150 feet (45,720 mm) in either axis.
 
2. Panels/modules shall be located up to the roof ridge where an alternative ventilation method approved by the fire code official has determined vertical ventilation techniques will not be employed.
605.11.3.2 Residential systems for one- and two-family dwellings. Access to residential systems for one- and two-family dwellings shall be provided in accordance with Sections 605.11.3.2.1 through 605.11.3.2.4.
EXCEPTIONS:
1. Residential dwellings with an approved automatic fire sprinkler system installed.
 
2. Residential dwellings with approved mechanical or passive ventilation systems.
 
3. Where the fire code official determines that the slope of the roof is too steep for emergency access.
 
4. Where the fire code official determines that vertical ventilation tactics will not be utilized.
 
5. These requirements shall not apply to roofs where the total combined area of the solar array does not exceed thirty-three percent as measured in plan view of the total roof area of the structure, where the solar array will measure 1,000 sq. ft. or less in area, and where a minimum eighteen inches unobstructed pathway shall be maintained along each side of any horizontal ridge.
605.11.3.2.3 Residential buildings with roof hips and valleys. Panels/modules installed on residential buildings with roof hips and valleys shall be located no closer than 18 inches (457 mm) to a hip or a valley where panels/modules are to be placed on both sides of a hip or valley. Where panels are to be located on only one side of a hip or valley, the panels shall be permitted to be placed directly adjacent to the hip or valley.
EXCEPTION:
These requirements shall not apply to roofs with slopes of two units vertical in 12 units horizontal (2:12) or less.
605.11.3.2.4 Residential building smoke ventilation. Panels/modules installed on residential buildings shall be located no higher than 18 inches (457 mm) below the ridge in order to allow for fire department rooftop operations.
605.11.4)) 605.11.1 Access and pathways. Roof access, pathways, and spacing requirements shall be provided in accordance with Sections 605.11.1.1 through 605.11.1.3.3.
EXCEPTIONS:
1. Detached, nonhabitable Group U structures including, but not limited to, parking shade structures, carports, solar trellises and similar structures.
 
2. Roof access, pathways and spacing requirements need not be provided where the fire chief has determined that rooftop operations will not be employed.
605.11.1.1 Roof access points. Roof access points shall be located in areas that do not require the placement of ground ladders over openings such as windows or doors, and located at strong points of building construction in locations where the access point does not conflict with overhead obstructions such as tree limbs, wires or signs.
605.11.1.2 Solar photovoltaic systems for Group R-3 buildings. Solar photovoltaic systems for Group R-3 buildings shall comply with Sections 605.11.1.2.1 through 605.11.1.2.5.
EXCEPTION:
These requirements shall not apply to structures designed and constructed in accordance with the International Residential Code. 1.1.1 Roof access points.
605.11.1.2.1 Size of solar photovoltaic array.
1. Each photovoltaic array shall be limited to 150 feet (45,720 mm) by 150 feet (45,720 mm). Multiple arrays shall be separated by a 3-foot wide (914 mm) clear access pathway.
2. Panels/modules shall be located up to the roof ridge where an alternative ventilation method approved by the fire code official has determined vertical ventilation techniques will not be employed.
605.11.1.2.2 Hip roof layouts. Panels and modules installed on Group R-3 buildings with hip roof layouts shall be located in a manner that provides a 3-foot wide (914 mm) clear access pathway from the eave to the ridge on each roof slope where panels and modules are located. The access pathway shall be at a location on the building capable of supporting the firefighters accessing the roof.
EXCEPTION:
These requirements shall not apply to roofs with slopes of two units vertical in 12 units horizontal (2:12) or less.
605.11.1.2.3 Single-ridge roofs. Panels and modules installed on Group R-3 buildings with a single ridge shall be located in a manner that provides two, 3-foot wide (914 mm) access pathways from the eave to the ridge on each roof slope where panels and modules are located.
EXCEPTION:
This requirement shall not apply to roofs with slopes of two units vertical in 12 units horizontal (2:12) or less.
605.11.1.2.4 Roofs with hips and valleys. Panels and modules installed on Group R-3 buildings with roof hips and valleys shall not be located closer than 18 inches (457 mm) to a hip or a valley where panels/modules are to be placed on both sides of a hip or valley. Where panels are to be located on only one side of a hip or valley that is of equal length, the panels shall be permitted to be placed directly adjacent to the hip or valley.
EXCEPTION:
These requirements shall not apply to roofs with slopes of two units vertical in 12 units horizontal (2:12) or less.
605.11.1.2.5 Allowance for smoke ventilation operations. Panels and modules installed on Group R-3 buildings shall be located not less than 18 inches (457 mm) from the ridge in order to allow for fire department smoke ventilation operations.
EXCEPTION:
Panels and modules shall be permitted to be located up to the roof ridge where an alternative ventilation method approved by the fire chief has been provided or where the fire chief has determined vertical ventilation techniques will not be employed.
605.11.1.3 Other than Group R-3 buildings. Access to systems for buildings, other than those containing Group R-3 occupancies, shall be provided in accordance with Sections 605.11.1.3.1 through 605.11.1.3.3.
EXCEPTION:
Where it is determined by the fire code official that the roof configuration is similar to that of a Group R-3 occupancy, the residential access and ventilation requirements in Sections 605.11.1.2.1 through 605.11.1.2.5 shall be permitted to be used.
605.11.1.3.1 Access. There shall be a minimum 6-foot wide (1829 mm) clear perimeter around the edges of the roof.
EXCEPTION:
Where either axis of the building is 250 feet (76,200 mm) or less, the clear perimeter around the edges of the roof shall be permitted to be reduced to a minimum 4 foot wide (1290 mm).
605.11.1.3.2 Pathways. The solar installation shall be designed to provide designated pathways. The pathways shall meet the following requirements:
1. The pathway shall be over areas capable of supporting firefighters accessing the roof.
2. The centerline axis pathways shall be provided in both axes of the roof. Centerline axis pathways shall run where the roof structure is capable of supporting firefighters accessing the roof.
3. Pathways shall be a straight line not less than 4 feet (1290 mm) clear to roof standpipes or ventilation hatches.
4. Pathways shall provide not less than 4 feet (1290 mm) clear around roof access hatch with not less than one singular pathway not less than 4 feet (1290 mm) clear to a parapet or roof edge.
605.11.1.3.3 Smoke ventilation. The solar installation shall be designed to meet the following requirements:
1. Arrays shall be not greater than 150 feet (45,720 mm) by 150 feet (45,720 mm) in distance in either axis in order to create opportunities for fire department smoke ventilation operations.
2. Smoke ventilation options between array sections shall be one of the following:
2.1. A pathway 8 feet (2438 mm) or greater in width.
2.2. A 4-foot (1290 mm) or greater in width pathway and bordering roof skylights or gravity-operated dropout smoke and heat vents on not less than one side.
2.3. A 4-foot (1290 mm) or greater in width pathway and bordering all sides of nongravity-operated dropout smoke and heat vents.
2.4. A 4-foot (1290 mm) or greater in width pathway and bordering 4-foot by 8-foot (1290 mm by 2438 mm) "venting cutouts" every 20 feet (6096 mm) on alternating sides of the pathway.
605.11.2 Ground-mounted photovoltaic arrays. Ground-mounted photovoltaic arrays shall comply with Section((s)) 605.11 ((through 605.11.2)) and this section. Setback requirements shall not apply to ground-mounted, free-standing photovoltaic arrays.
AMENDATORY SECTION (Amending WSR 13-04-063, filed 2/1/13, effective 7/1/13)
WAC 51-54A-0609 Commercial kitchen hoods.
[M] 609.2 Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease laden vapors.
EXCEPTIONS:
1. A Type I hood shall not be required for an electric cooking appliance where an approved testing agency provides documentation that the appliance effluent contains 5 mg/m3 or less of grease when tested at an exhaust flow rate of 500 cfm (0.236 m3/s) in accordance with Section 17 of UL 710B.
 
2. A Type I hood shall not be required to be installed in an R-2 occupancy with not more than 16 residents.
609.2.1 Domestic cooking appliances used for commercial purposes. Domestic cooking appliances utilized for commercial purposes shall be provided with Type I, Type II or residential hoods as required for the type of appliances and processes in accordance with Table 609.2.1 and Sections 507.2, 507.2.1 and 507.2.2 of the International Mechanical Code.
Table 609.2.1
Type of Hood Required for Domestic Cooking Appliances in the Following Spacesa,b
Type of Space
Type of
Cooking
Type of Hood
Church
1. Boiling, steaming and warming precooked food
Type II hood
 
2. Roasting, pan frying and deep frying
Type I hood
Community or party room in apartment and condominium
1. Boiling, steaming and warming precooked food
Residential hoodc or Type II hoodd
 
2. Roasting, pan frying and deep frying
Type I hood
Day care
1. Boiling, steaming and warming precooked food
Residential hoodc or Type II hoodd
 
2. Roasting, pan frying and deep frying
Type I hood
Dormitory, ((boarding home)) assisted living facility, nursing home
1. Boiling, steaming and warming precooked food
Type II hood
 
2. Roasting, pan frying and deep frying
Type I hood
Office lunch room
1. Boiling, steaming and warming precooked food
Residential hoodc or Type II hoodd
 
2. Roasting, pan frying and deep frying
Type I hood
 
a Commercial cooking appliances shall comply with Section 507.2 of the International Mechanical Code.
 
b Requirements in this table apply to electric or gas fuel appliances only. Solid fuel appliances or charbroilers require Type I hoods.
 
c Residential hood shall ventilate to the outside.
 
d Type II hood required when more than one appliance is used.
609.3 Operations, inspection and maintenance. Commercial cooking systems shall be operated, inspected and maintained in accordance with Sections 609.3.1 through 609.3.4 and Chapter 11 of NFPA 96.
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency.
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040.
NEW SECTION
WAC 51-54A-0901 General.
901.4.2 Nonrequired fire protection systems. A fire protection system or portion thereof not required by this code or the International Building Code shall be allowed to be furnished for partial or complete protection provided such installed system meets the applicable requirements of this code and the International Building Code. Such systems or portion of system shall be provided with signage stating "NON-REQUIRED SYSTEM." Signage shall be durable and permanent in nature, with contrasting color and background, and with lettering of not less than 1 inch in height. Location of such signage shall be approved.
901.8.2 Removal of existing occupant-use hose lines. The fire code official is authorized to permit the removal of existing occupant-use hose lines where all of the following conditions exist:
1. Installation is not required by this code, the International Building Code, or a previously approved alternative method.
2. The hose line would not be utilized by trained personnel or the fire department.
3. The remaining outlets are compatible with local fire department fittings.
AMENDATORY SECTION (Amending WSR 14-24-090, filed 12/1/14, effective 5/1/15)
WAC 51-54A-0903 Automatic sprinkler systems.
903.2.1.6 ((Nightclub. An automatic sprinkler system shall be provided throughout Group A-2 nightclubs as defined in this code.)) Assembly occupancies on roofs. Where an occupied roof has an assembly occupancy with an occupant load exceeding 100 for Group A-2, and 300 for other Group A occupancies, the building shall be equipped with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2.
EXCEPTION:
Open parking garages of Type I or Type II construction.
903.2.1.8 Nightclub. An automatic sprinkler system shall be provided throughout Group A-2 nightclubs as defined in this code.
903.2.3 Group E. An automatic sprinkler system shall be provided for Group E ((occupancies)) fire areas.
EXCEPTIONS:
1. Portable school classrooms with an occupant load of 50 or less calculated in accordance with Table 1004.1.2, provided that the aggregate area of any cluster of portable classrooms does not exceed 6,000 square feet (557 m2); and clusters of portable school classrooms shall be separated as required by the building code; or
 
2. Portable school classrooms with an occupant load from 51 through 98, calculated in accordance with Table 1004.1.2, and provided with two means of direct independent exterior egress from each classroom in accordance with Chapter 10, and one exit from each class room shall be accessible, provided that the aggregate area of any cluster of portable classrooms does not exceed 6,000 square feet (557 m2); and clusters of portable school classrooms shall be separated as required by the building code; or
 
3. An automatic sprinkler system is not required in Group E occupancies with an occupant load of 50 or less within the Group E occupancy, calculated in accordance with Table 1004.1.2.
 
4. An automatic sprinkler system is not required in Group E day care and preschool facilities with an occupant load of 100 or less, when located at the level of exit discharge, where every room in which care is provided has not fewer than one exterior exit door.
903.2.6 Group I. An automatic sprinkler system shall be provided throughout buildings with a Group I fire area.
EXCEPTIONS:
1. An automatic sprinkler system installed in accordance with Section 903.3.1.2 shall be permitted in Group I-1 Condition 1 facilities.
 
2. An automatic sprinkler system is not required in Group I-4 day care facilities with an occupant load of 100 or less, when located at the level of exit discharge, where every room in which care is provided has not fewer than one exterior exit door.
 
3. In buildings where Group I-4 day care is provided on levels other than the level of exit discharge, an automatic sprinkler system in accordance with Section 903.3.1.1 shall be installed on the entire floor where care is provided, all floors between the level of care and the level of exit discharge, and all floors below the level of exit discharge other than areas classified as an open parking garage.
 
4. Where new construction or additions house less than sixteen persons receiving care, an automatic sprinkler system installed in accordance with Section 903.2.8.3 shall be permitted for Group I-1, Condition 2, assisted living facilities licensed under chapter 388-78A WAC and residential treatment facilities licensed under chapter 246-337 WAC.
903.2.8 Group R. An automatic sprinkler system installed in accordance with Section 903.3 shall be provided throughout all buildings with a Group R fire area.
EXCEPTION:
Group R-1 if all of the following conditions apply:
 
1. The Group R fire area is no more than 500 square feet and is used for recreational use only.
 
2. The Group R fire area is on only one story.
 
3. The Group R fire area does not include a basement.
 
4. The Group R fire area is no closer than 30 feet from another structure.
 
5. Cooking is not allowed within the Group R fire area.
 
6. The Group R fire area has an occupant load of no more than 8.
 
7. A hand-held (portable) fire extinguisher is in every Group R fire area.
903.2.11.1.3 Basements. Where any portion of a basement is located more than 75 feet (22,860 mm) from openings required by Section 903.2.11.1, or where new walls, partitions or other similar obstructions are installed that increase the exit access travel distance to more than 75 feet, the basement shall be equipped throughout with an approved automatic sprinkler system.
903.2.11.7 Relocatable buildings within buildings. Relocatable buildings or structures located within a building with an approved fire sprinkler system shall be provided with fire sprinkler protection within the occupiable space of the building and the space underneath the relocatable building.
EXCEPTIONS:
1. Sprinkler protection is not required underneath the building when the space is separated from the adjacent space by construction resisting the passage of smoke and heat and combustible storage will not be located there.
 
2. If the building or structure does not have a roof or ceiling obstructing the overhead sprinklers.
903.3.5.3 Underground portions of fire protection system water supply piping. The installation or modification of an underground water main, public or private, supplying a water-based fire protection system shall be in accordance with NFPA 24 and chapter 18.160 RCW. Piping and appurtenances downstream of the first control valve on the lateral or service line from the distribution main to one-foot above finished floor shall be approved by the fire code official. Such underground piping shall be installed by a fire sprinkler system contractor licensed in accordance with chapter 18.160 RCW and holding either a Level U or a Level 3 license. For underground piping supplying systems installed in accordance with Section 903.3.1.2, a Level 2, 3, or U licensed contractor is acceptable.
EXCEPTION:
Portions of underground piping supplying automatic sprinkler systems installed in accordance with NFPA 13D.
NEW SECTION
WAC 51-54A-0904 Alternative automatic fire-extinguishing systems.
904.12 Commercial cooking systems. The automatic fire-extinguishing system for commercial cooking systems shall be of a type recognized for protection of commercial cooking equipment and exhaust systems of the type and arrangement protected. Preengineered automatic dry and wet chemical extinguishing systems shall be tested in accordance with UL 300 and listed and labeled for the intended application. Other types of automatic fire-extinguishing systems shall be listed and labeled for specific use as protection for commercial cooking operations. The system shall be installed in accordance with this code, its listing and the manufacturer's installation instructions. Signage shall be provided on the exhaust hood or system cabinet, indicating the type and arrangement of cooking appliances protected by the automatic fire-extinguishing system. Signage shall indicate appliances from left to right, be durable, and the size, color, and lettering shall be approved. Automatic fire-extinguishing systems of the following types shall be installed in accordance with the referenced standard indicated, as follows:
1. Carbon dioxide extinguishing systems, NFPA 12;
2. Automatic sprinkler systems, NFPA 13;
3. Foam-water sprinkler systems or foam-water spray systems, NFPA 16;
4. Dry-chemical extinguishing systems, NFPA 17;
5. Wet-chemical extinguishing systems, NFPA 17A.
EXCEPTION:
Factory-built commercial cooking recirculating systems that are tested in accordance with UL 710B and listed, labeled and installed in accordance with Section 304.1 of the International Mechanical Code.
AMENDATORY SECTION (Amending WSR 14-24-091, filed 12/1/14, effective 5/1/15)
WAC 51-54A-0907 Fire alarm and detection systems.
907.2.3 Group E. A manual fire alarm system that initiates the occupant notification signal utilizing an emergency voice/alarm communication system meeting the requirements of Section 907.5.2.2 and installed in accordance with Section 907.6 shall be installed in Group E occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alarm system.
EXCEPTIONS:
1. A manual fire alarm system is not required in Group E occupancies with an occupant load of 50 or less.
 
2. Emergency voice/alarm communication systems meeting the requirements of Section 907.5.2.2 and installed in accordance with Section 907.6 shall not be required in Group E occupancies with occupant loads of 100 or less, provided that activation of the manual fire alarm system initiates an approved occupant notification signal in accordance with Section 907.5.
 
3. Manual fire alarm boxes are not required in Group E occupancies where all of the following apply:
 
3.1 Interior corridors are protected by smoke detectors.
 
3.2 Auditoriums, cafeterias, gymnasiums and similar areas are protected by heat detectors or other approved detection devices.
 
3.3 Shops and laboratories involving dusts or vapors are protected by heat detectors or other approved detection devices.
 
4. Manual fire alarm boxes shall not be required in Group E occupancies where the building is equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, the emergency voice/alarm communication system will activate on sprinkler water flow and manual activation.
907.2.6.1 Group I-1. An automatic smoke detection system shall be installed in corridors, waiting areas open to corridors and habitable spaces other than sleeping units and kitchens. The system shall be activated in accordance with Section 907.4.
EXCEPTIONS:
1. For Group I-1 Condition 1 occupancies, smoke detection in habitable spaces is not required where the facility is equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1.
 
2. Smoke detection is not required for exterior balconies.
907.2.6.4 Group I-4 occupancies. A manual fire alarm system that initiates the occupant notification signal utilizing an emergency voice/alarm communication system meeting the requirements of Section 907.5.2.2 and installed in accordance with Section 907.6 shall be installed in Group I-4 occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alarm system.
EXCEPTIONS:
1. A manual fire alarm system is not required in Group I-4 occupancies with an occupant load of 50 or less.
 
2. Emergency voice alarm communication systems meeting the requirements of Section 907.5.2.2 and installed in accordance with Section 907.6 shall not be required in Group I-4 occupancies with occupant loads of 100 or less, provided that activation of the manual fire alarm system initiates an approved occupant notification signal in accordance with Section 907.5.
907.2.9.1.1 Group R-2 ((boarding homes)) assisted living facilities. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in Group R-2 occupancies where the building contains ((a boarding home)) an assisted living facility licensed by the state of Washington.
((EXCEPTION:
In boarding homes licensed by the state of Washington, manual fire alarm boxes in resident sleeping areas shall not be required at exits if located at all constantly attended staff locations, provided such staff locations are visible, continuously accessible, located on each floor, and positioned so no portion of the story exceeds a horizontal travel distance of 200 feet to a manual fire alarm box.))
EXCEPTIONS:
1. Manual fire alarm boxes in resident sleeping areas shall not be required at exits if located at all care providers' control stations or other constantly attended staff locations, provided such staff locations are visible and continuously accessible and that the distances of travel required in Section 907.4.2.1 are not exceeded.
 
2. The manual fire alarm system that activates the occupant notification system is not required to be activated where private mode signaling installed in accordance with NFPA 72 is approved by the fire code official and staff evacuation responsibilities are included in the fire safety and evacuation plan required by Section 404.
907.2.9.4 Group R-2 assisted living facilities. An automatic smoke detection system that activates the occupant notification system in accordance with Section 907.5 shall be installed in corridors, waiting areas open to corridors and habitable spaces other than sleeping units and kitchens located in Group R-2 assisted living facilities licensed by the state of Washington.
EXCEPTIONS:
1. Smoke detection is not required for exterior balconies.
 
2. Occupant notification systems are not required to be activated where private mode signaling installed in accordance with NFPA 72 is approved by the fire code official and staff evacuation responsibilities are included in the fire safety and evacuation plan required by Section 404.
907.5.2.1.2 Maximum sound pressure. The maximum sound pressure level for audible alarm notification appliances shall be 110 dBA at the minimum hearing distance from the audible appliance. For systems operating in public mode, the maximum sound pressure level shall not exceed 30 dBA over the average ambient sound level. Where the average ambient noise is greater than 95 dBA, visible alarm notification appliances shall be provided in accordance with NFPA 72 and audible alarm notification appliances shall be required.
907.10 NICET: National Institute for Certification in Engineering Technologies.
907.10.1 Scope. This section shall apply to new and existing fire alarm systems.
907.10.2 Design review: All construction documents shall be reviewed by a NICET III in fire alarms or a licensed professional engineer (PE) in Washington prior to being submitted for permitting. The reviewing professional shall submit a stamped, signed, and dated letter; or a verification method approved by the local authority having jurisdiction indicating the system has been reviewed and meets or exceeds the design requirements of the state of Washington and the local jurisdiction (effective July 1, 2017).
907.10.3 Installation/maintenance: All installation, inspection, testing, maintenance and programing not defined as "Electrical Work" by chapter 19.28 RCW shall be completed by a NICET II in fire alarms (effective July 1, 2017).
AMENDATORY SECTION (Amending WSR 13-24-017, filed 11/21/13, effective 4/1/14)
WAC 51-54A-0908 ((Emergency alarm systems.)) Reserved.
((908.7 Carbon monoxide alarms. Group I or Group R occupancies shall be provided with single station carbon monoxide alarms installed outside of each separate sleeping area in the immediate vicinity of the bedrooms in dwelling units or sleeping units and on each level of the dwelling. The carbon monoxide alarms shall be listed as complying with UL 2034 and be installed and maintained in accordance with NFPA 720-2012 and the manufacturer's instructions.
EXCEPTIONS:
1. For other than R-2 occupancies, the building does not contain a fuel-burning appliance, a fuel-burning fireplace, or an attached garage; or
 
2. Sleeping units or dwelling units in I and R-1 occupancies and R-2 college dormitories, hotel, DOC prisons and work releases and DSHS licensed boarding home and residential treatment facility occupancies which do not themselves contain a fuel-burning appliance, or a fuel-burning fireplace, or have an attached garage, need not be provided with carbon monoxide alarms provided that:
 
a. The sleeping unit or dwelling unit is not adjacent to any room which contains a fuel-burning appliance, a fuel-burning fireplace, or an attached garage; and
 
b. The sleeping unit or dwelling unit is not connected by duct work or ventilation shafts with a supply or return register in the same room to any room containing a fuel-burning appliance, a fuel-burning fireplace, or an attached garage; and
 
c. The building is provided with a common area carbon monoxide detection system.
 
3. An open parking garage, as defined in Chapter 2 of the International Building Code, or enclosed parking garage ventilated in accordance with Section 404 of the International Mechanical Code shall not be considered an attached garage.
908.7.1 Carbon monoxide detection systems. Carbon monoxide detection systems, that include carbon monoxide detectors and audible notification appliances, installed and maintained in accordance with this section for carbon monoxide alarms and NFPA 720-2012 shall be permitted. The carbon monoxide detectors shall be listed as complying with UL 2075.))
AMENDATORY SECTION (Amending WSR 13-04-063, filed 2/1/13, effective 7/1/13)
WAC 51-54A-0909 ((Smoke control systems.)) Reserved.
((909.21 Elevator hoistway pressurization alternative. Where elevator hoistway pressurization is provided in lieu of required enclosed elevator lobbies, the pressurization system shall comply with Sections 909.21.1 through 909.21.13.
909.21.1 Pressurization requirements. Elevator hoistways shall be pressurized to maintain a minimum positive pressure of 0.10 inches of water (25 Pa) and a maximum positive pressure of 0.25 inches of water (67 Pa) with respect to adjacent occupied space on all floors. This pressure shall be measured at the midpoint of each hoistway door, with all elevator cars at the floor of recall and all hoistway doors on the floor of recall open and all other hoistway doors closed. The opening and closing of hoistway doors at each level must be demonstrated during this test. The supply air intake shall be from an outside uncontaminated source located a minimum distance of 20 feet (6096 mm) from any air exhaust system or outlet.
909.21.2 Rational analysis. A rational analysis complying with Section 909.4 shall be submitted with the construction documents.
909.21.3 Ducts for system. Any duct system that is part of the pressurization system shall be protected with the same fire-resistance rating as required for the elevator shaft enclosure.
909.21.4 Fan system. The fan system provided for the pressurization system shall be as required by Sections 909.21.4.1 through 909.21.4.4.
909.21.4.1 Fire resistance. When located within the building, the fan system that provides the pressurization shall be protected with the same fire-resistance rating required for the elevator shaft enclosure.
909.21.4.2 Smoke detection. The fan system shall be equipped with a smoke detector that will automatically shut down the fan system when smoke is detected within the system.
909.21.4.3 Separate systems. A separate fan system shall be used for each elevator hoistway.
909.21.4.4 Fan capacity. The supply fan shall either be adjustable with a capacity of at least 1,000 cfm (0.4719 m3/s) per door, or that specified by a registered design professional to meet the requirements of a designed pressurization system.
909.21.5 Standby power. The pressurization system shall be provided with standby power from the same source as other required emergency systems for the building.
909.21.6 Activation of pressurization system. The elevator pressurization system shall be activated upon activation of the building fire alarm system or upon activation of the elevator lobby smoke detectors. Where both a building fire alarm system and elevator lobby smoke detectors are present, each shall be independently capable of activating the pressurization system.
909.21.7 Special inspection. Special inspection for performance shall be required in accordance with Section 909.18.8. System acceptance shall be in accordance with Section 909.19.
909.21.8 Marking and identification. Detection and control systems shall be marked in accordance with Section 909.14.
909.21.9 Control diagrams. Control diagrams shall be provided in accordance with Section 909.15.
909.21.10 Control panel. A control panel complying with Section 909.16 shall be provided.
909.21.11 System response time. Hoistway pressurization systems shall comply with the requirements for smoke control system response time in Section 909.17.
909.21.12 Hoistway venting. Hoistway venting required by Section 3004 of the International Building Code need not be provided for pressurized elevator shafts.
909.21.13 Machine rooms. Elevator machine rooms shall be pressurized in accordance with this section unless separated from the hoistway shaft by construction in accordance with Section 707 of the International Building Code.))
AMENDATORY SECTION (Amending WSR 13-04-063, filed 2/1/13, effective 7/1/13)
WAC 51-54A-0915 ((Alerting systems.)) Carbon monoxide detection.
((915.1 General. An approved alerting system shall be provided in buildings and structures as required in Chapter 4 and this section, unless other requirements are provided by another section of this code.
EXCEPTION:
Approved alerting systems in existing buildings, structures or occupancies.
915.2 Power source. Alerting systems shall be provided with power supplies in accordance with Section 4.4.1 of NFPA 72 and circuit disconnecting means identified as "EMERGENCY ALERTING SYSTEM."
EXCEPTION:
Systems which do not require electrical power to operate.
915.3 Duration of operation. The alerting system shall be capable of operating under nonalarm condition (quiescent load) for a minimum of 24 hours and then shall be capable of operating during an emergency condition for a period of 15 minutes at maximum connected load.
915.4 Combination system. Alerting system components and equipment shall be allowed to be used for other purposes.
915.4.1 System priority. The alerting system use shall take precedence over any other use.
915.4.2 Fire alarm system. Fire alarm systems sharing components and equipment with alerting systems must be in accordance with Section 6.8.4 of NFPA 72.
915.4.2.1 Signal priority. Recorded or live alert signals generated by an alerting system that shares components with a fire alarm system shall, when actuated, take priority over fire alarm messages and signals.
915.4.2.2 Temporary deactivation. Should the fire alarm system be in the alarm mode when such an alerting system is actuated, it shall temporarily cause deactivation of all fire alarm-initiated audible messages or signals during the time period required to transmit the alert signal.
915.4.2.3 Supervisory signal. Deactivation of fire alarm audible and visual notification signals shall cause a supervisory signal for each notification zone affected in the fire alarm system.
915.5 Audibility. Audible characteristics of the alert signal shall be in accordance with Section 7.4.1 of NFPA 72 throughout the area served by the alerting system.
EXCEPTION:
Areas served by approved visual or textual notification, where the visible notification appliances are not also used as a fire alarm signal, are not required to be provided with audibility complying with Section 915.6.
915.6 Visibility. Visible and textual notification appliances shall be permitted in addition to alert signal audibility.)) 915.1 General. Carbon monoxide detection shall be installed in new buildings in accordance with Sections 915.1.1 through 915.6. Carbon monoxide detection shall be installed in existing buildings in accordance with Chapter 11 of the International Fire Code.
915.1.1 Where required. Carbon monoxide detection shall be provided in Group I and R occupancies and in classrooms in Group E occupancies in the locations specified in Section 915.2 where any of the conditions in Sections 915.1.2 through 915.1.6 exist.
EXCEPTIONS:
1. R-2 occupancies, with the exception of R-2 college dormitories, are required to install carbon monoxide detectors without exception.
 
2. Sleeping units or dwelling units in I and R-1 occupancies and R-2 college dormitories, hotel, DOC prisons and work releases and assisted living facilities and residential treatment facilities licensed by the state of Washington, which do not themselves contain a fuel-burning appliance, a fuel-burning fireplace, or have an attached garage, need not be provided with carbon monoxide alarms provided that they comply with the exceptions of Section 915.1.4.
915.1.2 Fuel-burning appliances and fuel-burning fireplaces. Carbon monoxide detection shall be provided in dwelling units, sleeping units and classrooms that contain a fuel-burning appliance or a fuel-burning fireplace.
915.1.3 Forced-air furnaces. Carbon monoxide detection shall be provided in dwelling units, sleeping units and classrooms served by a fuel-burning, forced-air furnace.
EXCEPTION:
Carbon monoxide detection shall not be required in dwelling units, sleeping units and classrooms where carbon monoxide detection is provided in the first room or area served by each main duct leaving the furnace, and the carbon monoxide alarm signals are automatically transmitted to an approved location.
915.1.4 Fuel-burning appliances outside of dwelling units, sleeping units and classrooms. Carbon monoxide detection shall be provided in dwelling units, sleeping units and classrooms located in buildings that contain fuel-burning appliances or fuel-burning fireplaces.
EXCEPTIONS:
1. Carbon monoxide detection shall not be required in dwelling units, sleeping units and classrooms where there are no communicating openings between the fuel-burning appliance or fuel-burning fireplace and the dwelling unit, sleeping unit or classroom.
 
2. Carbon monoxide detection shall not be required in dwelling units, sleeping units and classrooms where carbon monoxide detection is provided in one of the following locations:
 
2.1 In an approved location between the fuel burning appliance or fuel burning fireplace, and the dwelling unit, sleeping unit or classroom.
 
2.2 On the ceiling of the room containing the fuel burning appliance or fuel burning fireplace.
915.1.5 Private garages. Carbon monoxide detection shall be provided in dwelling units, sleeping units and classrooms in buildings with attached private garages.
EXCEPTIONS:
1. Carbon monoxide detection shall not be required where there are no communicating openings between the private garage and the dwelling unit, sleeping unit or classroom.
 
2. Carbon monoxide detection shall not be required in dwelling units, sleeping units and classrooms located more than one story above or below a private garage.
 
3. Carbon monoxide detection shall not be required where the private garage connects to the building through an open-ended corridor.
 
4. Where carbon monoxide detection is provided in an approved location between openings to a private garage and dwelling units, sleeping units or classrooms, carbon monoxide detection shall not be required in the dwelling units, sleeping units or classrooms.
915.1.6 Exempt garages. For determining compliance with Section 915.1.5, an open parking garage complying with Section 406.5 of the International Building Code or an enclosed parking garage complying with Section 406.6 of the International Building Code shall not be considered a private garage.
915.2 Locations. Where required by Section 915.1.1, carbon monoxide detection shall be installed in the locations specified in Sections 915.2.1 through 915.2.3.
915.2.1 Dwelling units. Carbon monoxide detection shall be installed outside of each separate sleeping area in the immediate vicinity of the bedrooms and on each level of the dwelling. Where a fuel-burning appliance or a fuel-burning fireplace is located within a bedroom or its attached bathroom, carbon monoxide detection shall be installed within the bedroom.
915.2.2 Sleeping units. Carbon monoxide detection shall be installed in sleeping units.
EXCEPTION:
Carbon monoxide detection shall be allowed to be installed outside of each separate sleeping area in the immediate vicinity of the sleeping unit where the sleeping unit or its attached bathroom does not contain a fuel-burning appliance or fuel-burning fireplace and is not served by a forced air furnace.
915.2.3 Group E occupancies. When required by Section 915.1 in new buildings, or by Chapter 11 of the International Fire Code, carbon monoxide detection shall be installed in classrooms in Group E occupancies. Carbon monoxide alarm signals shall be automatically transmitted to an on-site location that is staffed by school personnel.
EXCEPTIONS:
1. Carbon monoxide alarm signals shall not be required to be automatically transmitted to an on-site location that is staffed by school personnel in Group E occupancies with an occupant load of 50 or less.
 
2. Carbon monoxide alarm signals shall not be required to be automatically transmitted to an on-site location that is staffed by school personnel in Group E occupancies where an exception contained in Section 915.1 applies, or in Group E occupancies where signals are transmitted to an off-site service monitored by a third party, such as a service that monitors fire protection systems in the building.
NEW SECTION
WAC 51-54A-0916 Alerting systems.
916.1 General. An approved alerting system shall be provided in buildings and structures as required in Chapter 4 and this section, unless other requirements are provided by another section of this code.
EXCEPTION:
Approved alerting systems in existing buildings, structures or occupancies.
916.2 Power source. Alerting systems shall be provided with power supplies in accordance with Section 4.4.1 of NFPA 72 and circuit disconnecting means identified as "EMERGENCY ALERTING SYSTEM."
EXCEPTION:
Systems which do not require electrical power to operate.
916.3 Duration of operation. The alerting system shall be capable of operating under nonalarm condition (quiescent load) for a minimum of 24 hours and then shall be capable of operating during an emergency condition for a period of 15 minutes at maximum connected load.
916.4 Combination system. Alerting system components and equipment shall be allowed to be used for other purposes.
916.4.1 System priority. The alerting system use shall take precedence over any other use.
916.4.2 Fire alarm system. Fire alarm systems sharing components and equipment with alerting systems must be in accordance with Section 6.8.4 of NFPA 72.
916.4.2.1 Signal priority. Recorded or live alert signals generated by an alerting system that shares components with a fire alarm system shall, when actuated, take priority over fire alarm messages and signals.
916.4.2.2 Temporary deactivation. Should the fire alarm system be in the alarm mode when such an alerting system is actuated, it shall temporarily cause deactivation of all fire alarm-initiated audible messages or signals during the time period required to transmit the alert signal.
916.4.2.3 Supervisory signal. Deactivation of fire alarm audible and visual notification signals shall cause a supervisory signal for each notification zone affected in the fire alarm system.
916.5 Audibility. Audible characteristics of the alert signal shall be in accordance with Section 7.4.1 of NFPA 72 throughout the area served by the alerting system.
EXCEPTION:
Areas served by approved visual or textual notification, where the visible notification appliances are not also used as a fire alarm signal, are not required to be provided with audibility complying with Section 916.6.
916.6 Visibility. Visible and textual notification appliances shall be permitted in addition to alert signal audibility.
AMENDATORY SECTION (Amending WSR 13-04-063, filed 2/1/13, effective 7/1/13)
WAC 51-54A-1007 ((Accessible means of egress.)) Reserved.
((1007.1 Accessible means of egress required. Accessible means of egress shall comply with this section. Accessible spaces shall be provided with not less than one accessible means of egress. Where more than one means of egress are required by Section 1015.1 or 1021.1 from any accessible space, each accessible portion of the space shall be served by not less than two accessible means of egress.
EXCEPTIONS:
1. Accessible means of egress are not required in alterations to existing buildings.
 
2. One accessible means of egress is required from an accessible mezzanine level in accordance with Section 1007.3, 1007.4 or 1007.5.
 
3. In assembly areas with sloped or stepped aisles, one accessible means of egress is permitted where the common path of travel is accessible and meets the requirements in Section 1028.8.
 
4. In parking garages, accessible means of egress are not required to serve parking areas that do not contain accessible parking spaces.
1007.8.1 System requirements. Two-way communication systems shall provide communication between each required location and the fire command center or a central control point location approved by the fire department. Where the central control point is not constantly attended, a two-way communication system shall have a timed automatic telephone dial-out capability to a monitoring location. The two-way communication system shall include both audible and visible signals. The two-way communication system shall have a battery backup or an approved alternate source of power that is capable of 90 minutes use upon failure of the normal power source.))
AMENDATORY SECTION (Amending WSR 13-04-063, filed 2/1/13, effective 7/1/13)
WAC 51-54A-1008 ((Doors, gates and turnstiles.)) Reserved.
((1008.1.9.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists:
1. Places of detention or restraint.
2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided:
2.1. The locking device is readily distinguishable as locked;
2.2. A readily visible sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background; and
2.3. The use of the key-operated locking device is revocable by the building official for due cause.
3. Where egress doors are used in pairs, approved automatic flush bolts shall be permitted to be used, provided that the door leaf having the automatic flush bolts has no doorknob or surface-mounted hardware.
4. Doors from individual dwelling or sleeping units of Group R occupancies having an occupant load of 10 or less are permitted to be equipped with a night latch, dead bolt, or security chain, provided such devices are openable from the inside without the use of a key or a tool.
5. Fire doors after the minimum elevated temperature has disabled the unlatching mechanism in accordance with listed fire door test procedures.
6. Approved, listed locks without delayed egress shall be permitted in Group R-2 boarding homes licensed by Washington state, provided that:
6.1. The clinical needs of one or more patients require specialized security measures for their safety.
6.2. The doors unlock upon actuation of the automatic sprinkler system or automatic fire detection system.
6.3. The doors unlock upon loss of electrical power controlling the lock or lock mechanism.
6.4. The lock shall be capable of being deactivated by a signal from a switch located in an approved location.
6.5. There is a system, such as a keypad and code, in place that allows visitors, staff persons and appropriate residents to exit. Instructions for exiting shall be posted within six feet of the door.
1008.1.9.6 Special locking arrangements in Group I-2. Approved special egress locks shall be permitted in a Group I-2 Occupancy where the clinical needs of persons receiving care require such locking. Special egress locks shall be permitted in such occupancies where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or an approved automatic smoke or heat detection system installed in accordance with Section 907, provided that the doors unlock in accordance with Items 1 through 7.
1. The doors unlock upon actuation of the automatic
sprinkler system or automatic fire detection system.
2. The doors unlock upon loss of power controlling
the lock or lock mechanism.
3. The door locks shall have the capability of being
unlocked by a signal from the fire command center, a nursing station or other approved location.
4. A building occupant shall not be required to pass through more than one door equipped with a special egress lock before entering an exit.
5. The procedures for the operation(s) of the unlocking system shall be described and approved as part of the emergency planning and preparedness required by Chapter 4 of the International Fire Code.
6. There is a system, such as a keypad and code, in place that allows visitors, staff persons and appropriate residents to exit. Instructions for exiting shall be posted within six feet of the door.
7. Emergency lighting shall be provided at the door.
EXCEPTION:
Items 1, 2, 3, and 6 shall not apply to doors to areas where persons, which because of clinical needs, require restraint or containment as part of the function of a psychiatric treatment area provided that all clinical staff shall have the keys, codes or other means necessary to operate the locking devices.))
AMENDATORY SECTION (Amending WSR 13-04-063, filed 2/1/13, effective 7/1/13)
WAC 51-54A-1009 ((Stairways and handrails.)) Accessible means of egress.
((1009.3 Exit access stairways. Floor openings between stories created by exit access stairways shall be enclosed.
EXCEPTIONS:
1. In other than Group I-2 and I-3 occupancies, exit access stairways that serve, or atmospherically communicate between, only two stories are not required to be enclosed. Such interconnected stories shall not be open to other stories.
 
2. Exit access stairways serving and contained within a single residential dwelling unit or sleeping unit in Group R-1, R-2 or R-3 occupancies are not required to be enclosed.
 
3. In Group B or M occupancies, exit access stairways that are designed exclusively for circulation are not required to be enclosed provided that the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, the area of the floor opening between stories does not exceed twice the horizontal projected area of the exit access stairway, and the opening is protected by a draft curtain and closely spaced sprinklers in accordance with NFPA 13.
 
4. In other than Group B and M occupancies, exit access stairways that are designed exclusively for circulation are not required to be enclosed provided that the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, the floor opening does not connect more than four stories, the area of the floor opening between stories does not exceed twice the horizontal projected area of the exit access stairway, and the opening is protected by a draft curtain and closely spaced sprinklers in accordance with NFPA 13.
 
5. Exit access stairways with an atrium complying with the provisions of Section 404 of the International Building Code are not required to be enclosed.
 
6. Exit access stairways and ramps in open parking garages that serve only the parking garage are not required to be enclosed.
 
7. Stairways serving outdoor facilities where all portions of the means of egress are essentially open to the outside are not required to be enclosed.
 
8. Exit access stairways serving stages, platforms and technical production areas in accordance with Sections 410.6.2 and 410.6.3 of the International Building Code are not required to be enclosed.
 
9. Stairways are permitted to be open between the balcony, gallery or press box and the main assembly floor in occupancies such as theaters, places of religious worship, auditoriums and sports facilities.
 
10. In Group I-3 occupancies, exit access stairways constructed in accordance with Section 408.5 of the International Building Code, are not required to be enclosed.
1009.18 Stairways in individual dwelling units. Stairs or ladders within an individual dwelling unit used for access to areas of 200 square feet (18.6 m2) or less, and not containing the primary bathroom or kitchen, are exempt from the requirements of Section 1009.)) 1009.1 Accessible means of egress required. Accessible means of egress shall comply with this section. Accessible spaces shall be provided with not less than one accessible means of egress. Where more than one means of egress is required by Section 1006.2 or 1006.3 from any accessible space, each accessible portion of the space shall be served by not less than two accessible means of egress.
EXCEPTIONS:
1. Accessible means of egress are not required in alterations to existing buildings.
 
2. One accessible means of egress is required from an accessible mezzanine level in accordance with Section 1009.3, 1009.4 or 1009.5.
 
3. In assembly areas with ramped aisles or stepped aisles one accessible means of egress is permitted where the common path of egress travel is accessible and meets the requirements in Section 1029.8.
 
4. In parking garages, accessible means of egress are not required to serve parking areas that do not contain accessible parking spaces.
1009.8 Two-way communication. A two-way communication system complying with Sections 1009.8.1 and 1009.8.2 shall be provided at the landing serving each elevator or bank of elevators on each accessible floor that is one or more stories above or below the level of exit discharge.
EXCEPTIONS:
1. Two-way communication systems are not required at the landing serving each elevator or bank of elevators where the two-way communication system is provided within areas of refuge in accordance with Section 1009.6.5.
 
2. Two-way communication systems are not required on floors provided with ramps that provide a direct path of egress travel to grade or the level of exit discharge conforming to the provisions of Section 1012.
 
3. Two-way communication systems are not required at the landings serving only service elevators that are not designated as part of the accessible means of egress or serve as part of the required accessible route into a facility.
 
4. Two-way communication systems are not required at the landings serving only freight elevators.
 
5. Two-way communication systems are not required at the landing serving a private residence elevator.
1009.8.1 System requirements. Two-way communication systems shall provide communication between each required location and the fire command center or a central control point location approved by the fire department. Where the central control point is not a constantly attended location, a two-way communication system shall have a timed automatic telephone dial-out capability to a monitoring location. The two-way communication system shall include both audible and visible signals. The two-way communication system shall have a battery backup or an approved alternate source of power that is capable of 90 minutes use upon failure of the normal power source.
AMENDATORY SECTION (Amending WSR 13-04-063, filed 2/1/13, effective 7/1/13)
WAC 51-54A-1010 ((Ramps.)) Doors, gates and turnstiles.
((1010.1 Scope. The provisions of this section shall apply to ramps used as a component of a means of egress.
EXCEPTIONS:
1. Other than ramps that are part of the accessible routes providing access in accordance with Sections 1108.2 through 1108.2.4 and 1108.2.6, ramped aisles within assembly rooms or spaces shall conform with the provisions in Section 1028.11.
 
2. Curb ramps shall comply with ICC A117.1.
 
3. Vehicle ramps in parking garages for pedestrian exit access shall not be required to comply with Sections 1010.4 through 1010.10 when they are not an accessible route serving accessible parking spaces or other required accessible elements.
 
4. In a parking garage where one accessible means of egress serving accessible parking spaces or other accessible elements is provided, a second accessible means of egress serving that area may include a vehicle ramp that does not comply with Sections 1010.5, 1010.6, and 1010.9. A landing complying with Sections 1010.7.1 and 1010.7.4 shall be provided at any change of direction in the accessible means of egress.))
1010.1.9.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists:
1. Places of detention or restraint.
2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M, and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided:
2.1. The locking device is readily distinguishable as locked;
2.2. A readily visible sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background; and
2.3. The use of the key-operated locking device is revocable by the building official for due cause.
3. Where egress doors are used in pairs, approved automatic flush bolts shall be permitted to be used, provided that the door leaf having the automatic flush bolts has no doorknob or surface-mounted hardware.
4. Doors from individual dwelling or sleeping units of Group R occupancies having an occupant load of 10 or less are permitted to be equipped with a night latch, dead bolt, or security chain, provided such devices are openable from the inside without the use of a key or a tool.
5. Fire doors after the minimum elevated temperature has disabled the unlatching mechanism in accordance with listed fire door test procedures.
6. Approved, listed locks without delayed egress shall be permitted in Group R-2 assisted living facilities licensed by the state of Washington, provided that:
6.1. The clinical needs of one or more patients require specialized security measures for their safety.
6.2. The doors unlock upon actuation of the automatic sprinkler system or automatic fire detection system.
6.3. The doors unlock upon loss of electrical power controlling the lock or lock mechanism.
6.4. The lock shall be capable of being deactivated by a signal from a switch located in an approved location.
6.5. There is a system, such as a keypad and code, in place that allows visitors, staff persons and appropriate residents to exit. Instructions for exiting shall be posted within six feet of the door.
1010.1.9.6 Special locking arrangements in Group I-2. Approved special egress locks shall be permitted in a Group I-2 occupancy where the clinical needs of persons receiving care require such locking. Special egress locks shall be permitted in such occupancies where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or an approved automatic smoke or heat detection system installed in accordance with Section 907, provided that the doors unlock in accordance with Items 1 through 7.
1. The doors unlock upon actuation of the automatic sprinkler system or automatic fire detection system.
2. The doors unlock upon loss of power controlling the lock or lock mechanism.
3. The door locks shall have the capability of being unlocked by a signal from the fire command center, a nursing station, or other approved location.
4. A building occupant shall not be required to pass through more than one door equipped with a special egress lock before entering an exit.
5. The procedures for the operation(s) of the unlocking system shall be described and approved as part of the emergency planning and preparedness required by Chapter 4 of the International Fire Code.
6. There is a system, such as a keypad and code, in place that allows visitors, staff persons and appropriate residents to exit. Instructions for exiting shall be posted within 6 feet of the door.
7. Emergency lighting shall be provided at the door.
EXCEPTION:
Items 1, 2, 3, and 6 shall not apply to doors to areas where persons, which because of clinical needs, require restraint or containment as part of the function of a psychiatric treatment area provided that all clinical staff shall have the keys, codes, or other means necessary to operate the locking devices.
NEW SECTION
WAC 51-54A-1011 Stairways.
1011.17 Stairways in individual dwelling units. Stairs or ladders within an individual dwelling unit used for access to areas of 200 square feet (18.6 m2) or less, and not containing the primary bathroom or kitchen, are exempt from the requirements of Section 1009.
NEW SECTION
WAC 51-54A-1012 Ramps.
1012.1 Scope. The provisions of this section shall apply to ramps used as a component of a means of egress.
EXCEPTIONS:
1. Other than ramps that are part of the accessible routes providing access in accordance with Sections 1108.2 through 1108.2.4 and 1108.2.6, ramped aisles within assembly rooms or spaces shall conform with the provisions in Section 1029.13.
 
2. Curb ramps shall comply with ICC A117.1.
 
3. Vehicle ramps in parking garages for pedestrian exit access shall not be required to comply with Sections 1010.4 through 1010.10 when they are not an accessible route serving accessible parking spaces or other required accessible elements.
 
4. In a parking garage where one accessible means of egress serving accessible parking spaces or other accessible elements is provided, a second accessible means of egress serving that area may include a vehicle ramp that does not comply with Sections 1010.5, 1010.6, and 1010.9. A landing complying with Sections 1010.7.1 and 1010.7.4 shall be provided at any change of direction in the accessible means of egress.
AMENDATORY SECTION (Amending WSR 13-04-063, filed 2/1/13, effective 7/1/13)
WAC 51-54A-1018 ((Corridors.)) Reserved.
((1018.5 Air movement in corridors. Corridors shall not serve as supply, return, exhaust, relief or ventilation air ducts.
EXCEPTIONS:
1. Use of a corridor as a source of makeup air for exhaust systems in rooms that open directly onto such corridors, including toilet rooms, bathrooms, dressing rooms, smoking lounges and janitor closets, shall be permitted provided that each such corridor is directly supplied with outdoor air at a rate greater than the rate of makeup air taken from the corridor.
 
2. Where located within a dwelling unit, the use of corridors for conveying return air shall not be prohibited.
 
3. Where located within tenant spaces of one thousand square feet (93 m2) or less in area, utilization of corridors for conveying return air is permitted.
 
4. Incidental air movement from pressurized rooms within health care facilities, provided that a corridor is not the primary source of supply or return to the room.
 
5. Where such air is part of an engineered smoke control system.
 
6. Air supplied to corridors serving residential occupancies shall not be considered as providing ventilation air to the dwelling units subject to the following:
 
6.1. The air supplied to the corridor is one hundred percent outside air; and
 
6.2. The units served by the corridor have conforming ventilation air independent of the air supplied to the corridor; and
 
6.3. For other than high-rise buildings, the supply fan will automatically shut off upon activation of corridor smoke detectors which shall be spaced at no more than thirty feet (9144 mm) on center along the corridor; or
 
6.4. For high-rise buildings, corridor smoke detector activation will close required smoke/fire dampers at the supply inlet to the corridor at the floor receiving the alarm.
1018.6 Corridor continuity. Fire-resistance-rated corridors shall be continuous from the point of entry to an exit, and shall not be interrupted by intervening rooms.
EXCEPTIONS:
1. Foyers, lobbies or reception rooms constructed as required for corridors shall not be construed as intervening rooms.
 
2. In Group R-2 boarding homes and residential treatment facilities licensed by Washington state, seating areas shall be allowed to be open to the corridor provided:
 
2.1. The seating area is constructed as required for the corridor;
 
2.2. The floor is separated into at least two compartments complying with Section 407.5 of the International Building Code;
 
2.3. Each individual seating area does not exceed 150 square feet, excluding the corridor width;
 
2.4. The combined total space of seating areas per compartment does not exceed 300 square feet, excluding the corridor width;
 
2.5. Combustible furnishings located within the seating area shall be in accordance with Section 805; and
 
2.6. Emergency means of egress lighting is provided as required by Section 1006 to illuminate the area.))
NEW SECTION
WAC 51-54A-1020 Corridors.
1020.5 Air movement in corridors. Corridors shall not serve as supply, return, exhaust, relief or ventilation air ducts.
EXCEPTIONS:
1. Use of a corridor as a source of makeup air for exhaust systems in rooms that open directly onto such corridors, including toilet rooms, bathrooms, dressing rooms, smoking lounges and janitor closets, shall be permitted provided that each such corridor is directly supplied with outdoor air at a rate greater than the rate of makeup air taken from the corridor.
 
2. Where located within a dwelling unit, the use of corridors for conveying return air shall not be prohibited.
 
3. Where located within tenant spaces of one thousand square feet (93 m2) or less in area, utilization of corridors for conveying return air is permitted.
 
4. Incidental air movement from pressurized rooms within health care facilities, provided that a corridor is not the primary source of supply or return to the room.
 
5. Where such air is part of an engineered smoke control system.
 
6. Air supplied to corridors serving residential occupancies shall not be considered as providing ventilation air to the dwelling units subject to the following:
 
6.1. The air supplied to the corridor is one hundred percent outside air; and
 
6.2. The units served by the corridor have conforming ventilation air independent of the air supplied to the corridor; and
 
6.3. For other than high-rise buildings, the supply fan will automatically shut off upon activation of corridor smoke detectors which shall be spaced at no more than thirty feet (9144 mm) on center along the corridor; or
 
6.4. For high-rise buildings, corridor smoke detector activation will close required smoke/fire dampers at the supply inlet to the corridor at the floor receiving the alarm.
AMENDATORY SECTION (Amending WSR 13-04-063, filed 2/1/13, effective 7/1/13)
WAC 51-54A-1021 ((Number of exits and exit configurations.)) Reserved.
((1021.3.1 Access to exits at adjacent levels. Access to exits at other levels shall be by stairways or ramps. Where access to exits occurs from adjacent building levels, the horizontal and vertical exit access travel distance to the closest exit shall not exceed that specified in Section 1016.1. The path of egress travel to an exit shall not pass through more than one adjacent story.
EXCEPTION:
Landing platforms or roof areas for helistops that are less than 60 feet (18,288 mm) long, or less than 2,000 square feet (186 m2) in area, shall be permitted to access the second exit by a fire escape, alternating tread device or ladder leading to the story or level below.))
NEW SECTION
WAC 51-54A-1028 Exit discharge.
1028.4.1 Width or capacity. The required capacity of egress courts shall be determined as specified in Section 1005.1, but the minimum width shall be not less than 44 inches (1118 mm), except as specified herein. Egress courts serving Group R-3 and U occupancies shall be not less than 36 inches (914 mm) in width. The required capacity and width of egress courts shall be unobstructed to a height of 7 feet (2134 mm).
EXCEPTION:
Encroachments complying with Section 1005.7.
NEW SECTION
WAC 51-54A-1030 Emergency escape and rescue.
1030.1 General. In addition to the means of egress required by this chapter, provisions shall be made to emergency escape and rescue openings in Group R-2 occupancies in accordance with Tables 1006.3.2(1) and 1006.3.2(2) and Group R-3 occupancies. Basements and sleeping rooms below the fourth story above grade plane shall have at least one exterior emergency escape and rescue opening in accordance with this section. Where basements contain one or more sleeping rooms, emergency escape and rescue openings shall be required in each sleeping room, but shall not be required in adjoining areas of the basement. Such openings shall open directly into a public way or to a yard or court that opens to a public way.
EXCEPTIONS:
1. Basements with a ceiling height of less than 80 inches (2032 mm) shall not be required to have emergency escape and rescue openings.
 
2. Emergency escape and rescue openings are not required from basements or sleeping rooms that have an exit door or exit access door that opens directly into a public way or to a yard, court or exterior balcony that opens to a public way.
 
3. Basements without habitable spaces and having not more than 200 square feet (18.6 m2) in floor area shall not be required to have emergency escape and rescue openings.
 
4. Within individual dwelling and sleeping units in Groups R-2 and R-3, where the building is equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3, sleeping rooms in basements shall not be required to have emergency escape and rescue openings provided that the basement has one of the following:
 
a. One means of egress and one emergency escape and rescue opening.
 
b. Two means of egress.
AMENDATORY SECTION (Amending WSR 13-24-017, filed 11/21/13, effective 4/1/14)
WAC 51-54A-1103 Fire safety requirements for existing buildings.
((1103.4.3)) 1103.4.2 Three to five stories. In other than Group I occupancies, interior vertical openings connecting three to five stories shall be protected by either a one-hour fire-resistant and smoke-rated construction or an automatic sprinkler system shall be installed throughout the building in accordance with Section 903.3.1.1 or 903.3.1.2.
EXCEPTIONS:
1. Vertical opening protection is not required for Group R-3 occupancies.
 
2. Vertical opening protection is not required for open parking garages and ramps.
 
3. Vertical opening protection for escalators shall be in accordance with Section 1103.4.5, 1103.4.6 or 1103.4.7.
1103.4.3 More than five stories. In other than Group I occupancies, interior vertical openings connecting more than five stories shall be protected by fire-resistant and smoke-rated construction.
EXCEPTIONS:
1. Vertical opening protection is not required for Group R-3 occupancies.
 
2. Vertical opening protection is not required for open parking garages and ramps.
 
3. Vertical opening protection for escalators shall be in accordance with Section 1103.4.8.
1103.5.5 Nightclub. An automatic sprinkler system shall be provided throughout A-2 nightclubs as defined in this code. No building shall be constructed for, used for, or converted to occupancy as a nightclub except in accordance with this section.
1103.9 Carbon monoxide alarms. Existing Group I or Group R occupancies shall be provided with single station carbon monoxide alarms in accordance with Section ((908.7)) 915.4.3. An inspection will occur when alterations, repairs or additions requiring a permit occur, or when one or more sleeping rooms are added or created. The carbon monoxide alarms shall be listed as complying with UL 2034 and be installed and maintained in accordance with NFPA 720-((2012)) 2015 and the manufacturer's instructions.
EXCEPTIONS:
1. For other than R-2 occupancies, if the building does not contain a fuel-burning appliance, a fuel-burning fireplace, or an attached garage.
 
2. Work involving the exterior surfaces of dwellings, such as the replacement of roofing or siding, or the addition or replacement of windows or doors, or the addition of a porch or deck, or electrical permits.
 
3. Installation, alteration or repairs of noncombustion plumbing or mechanical systems.
 
4. Sleeping units or dwelling units in I and R-1 occupancies and R-2 college dormitories, hotel, DOC prisons and work releases and ((DSHS licensed boarding home)) assisted living facilities and residential treatment ((facility occupancies)) facilities licensed by the state of Washington which do not themselves contain a fuel-burning appliance, a fuel-burning fireplace, or have an attached garage, need not be provided with carbon monoxide alarms provided that:
 
4.1. The sleeping units or dwelling unit is not adjacent to any room which contains a fuel-burning appliance, a fuel-burning fireplace, or an attached garage; and
 
4.2. The sleeping units or dwelling unit is not connected by duct work or ventilation shafts with a supply or return register in the same room to any room containing a fuel-burning appliance, a fuel-burning fireplace, or to an attached garage; and
 
4.3. The building is provided with a common area carbon monoxide detection system.
 
5. An open parking garage, as defined in the International Building Code, or enclosed parking garage ventilated in accordance with Section 404 of the International Mechanical Code shall not be considered an attached garage.
NEW SECTION
WAC 51-54A-1105 Construction requirements for existing Group I-2.
1105.1 General. This section shall be applied by jurisdictions conducting surveys for compliance with the federal centers for medicare and medicaid reimbursement program. Existing Group I-2 shall meet all of the following requirements:
1. The minimum fire safety requirements in Section 1103.
2. The minimum means of egress requirements in Section 1104.
3. The additional egress and construction requirements in Section 1105.
Where the provisions of this chapter conflict with the construction requirements that applied at the time of construction, the most restrictive provisions shall apply.
NEW SECTION
WAC 51-54A-3103 Temporary tents and membrane structures.
3103.5 Use period. Temporary tents, air-supported, air-inflated or tensioned membrane structures are permitted to be erected for a period of less than 180 days within a 12-month period on a single premises. Such structures erected for 180 days or more within a 12-month period shall comply with the IBC.
NEW SECTION
WAC 51-54A-3800 Marijuana processing or extraction facilities.
SECTION 3801ADMINISTRATION
3801.1 Scope. Marijuana processing or extraction facilities shall comply with this chapter and the International Building Code. The extraction process includes the act of extraction of the oils and fats by use of a solvent, desolventizing of the raw material and production of the miscella, distillation of the solvent from the miscella and solvent recovery. The use, storage, transfilling, and handling of hazardous materials in these facilities shall comply with this chapter, other applicable provisions of this code and the International Building Code.
3801.2 Application. The requirements set forth in this chapter are requirements specific only to marijuana processing and extraction facilities and shall be applied as exceptions or additions to applicable requirements set forth elsewhere in this code.
3801.3 Multiple hazards. Where a material, its use or the process it is associated with poses multiple hazards, all hazards shall be addressed in accordance with Section 5001.1 and other material specific chapters.
3801.4 Existing buildings or facilities. Existing buildings or facilities used for the processing of marijuana shall comply with this chapter. Existing buildings or facilities used for marijuana extraction shall comply with the requirements of this chapter by July 1, 2016.
3801.5 Permits. Permits shall be required as set forth in Section 105.6 and 105.7.
SECTION 3802DEFINITIONS
Marijuana extraction facility (MEF): A building used for the solvent-based extraction process of marijuana.
Marijuana extraction equipment (MEE): Equipment or appliances used for the extraction of botanical material such as essential oils, from marijuana.
Marijuana extraction room (MER): The room or space in which the solvent–based extractions occur.
Finding: The results of an inspection, examination, analysis or review.
Observation: A practice or condition not technically noncompliant with other regulations or requirements, but could lead to noncompliance if left unaddressed.
Desolventizing: The act of removing a solvent from a material.
Miscella: A mixture, in any proportion, of the extracted oil or fat and the extracting solvent.
Transfilling: The process of taking a gas source, either compressed or in liquid form (usually in bulk containers), and transferring it into a different container (usually a smaller compressed cylinder).
SECTION 3803PROCESSING OR EXTRACTION OF MARIJUANA
3803.1 Location. Marijuana processing shall be located in a building complying with the International Building Code and this code. The marijuana extraction process shall be located in a room dedicated to the extraction process. The extraction room shall not be used for any other purpose including storage.
3803.2 Staffing. The extraction process shall be continuously staffed by personnel trained in the extraction process, the transfer of LP-gas where applicable, and all emergency procedures. All staff training records shall be maintained on-site by the owner and made available upon request from the fire code official.
3803.3 Systems, equipment and processes. Systems, equipment, and processes shall be in accordance with Sections 3802.3.1 through 3802.3.3.7.
3803.3.1 Application. Systems, equipment and processes shall include, but are not limited to, vessels, chambers, containers, cylinders, tanks, piping, tubing, valves, fittings, and pumps.
3803.3.2 General requirements. In addition to the requirements in Section 3802, systems, equipment and processes shall also comply with Section 5003.2, other applicable provisions of this code, the International Building Code, and the International Mechanical Code.
3803.3.3 Additional requirements for marijuana extraction. In addition to the requirements of Section 3802.3, marijuana extraction systems, equipment and process shall comply with this section.
3803.3.3.1 General requirements. The requirements set forth in Section 5003.2 shall apply to vessels, chambers, containers, cylinders, tanks, piping, tubing, valves, fittings, and pumps used in the extraction process. The use of ovens in post-process purification or winterization shall comply with Section 3802.3.3.7.
3803.3.3.2 Systems and equipment. Systems or equipment used for the extraction of marijuana/cannabis oils from plant material shall be listed for the specific use. If the system used for extraction of marijuana/cannabis oils and products from plant material is not listed, then the system shall have a designer of record. If the designer of record is not a licensed Washington professional engineer, then the system shall be peer reviewed by a licensed Washington professional engineer. In reviewing the system, the licensed professional engineer shall review and consider any information provided by the system's designer or manufacturer. For systems and equipment not listed for the specific use, a technical report documenting the design or peer review as outlined in Section 3802.3.3.4.2 shall be prepared and submitted to the fire code official for review and approval for systems and equipment used for the extraction of marijuana/cannabis oils and products from plant material. The firm or individual performing the engineering analysis for the technical report shall be approved by the fire code official prior to performing the analysis.
3803.3.3.3 Change of extraction medium. Where the medium of extraction or solvent is changed from the material indicated in the technical report or as required by the manufacturer, the technical report shall be revised at the cost of the facility owner, submitted for review and approval by the fire code official prior to the use of the equipment with the new medium or solvent. If the original engineer of record is not available, then new engineer of record shall comply with Section 3802.3.3.4.1.
3803.3.3.4 Required technical report. The technical report documenting the design or peer review shall be submitted for review and approval by the fire code official prior to the equipment being located or installed at the facility.
3803.3.3.4.1 Approval of the engineer of record. Where a technical report is required to be submitted for review and approval by the fire code official to meet the requirements of 3802.3.3.2, the following actions shall occur:
1. Prior to submittal of the technical report, the engineer shall submit educational background and professional experience specific to the review and approval of system, equipment and processes with like hazards of those associated with the marijuana extraction system to the fire code official.
2. Once the proof of qualifications are found acceptable by the fire code official, the engineer of record shall produce the technical report and the report shall be signed and sealed in accordance with Washington state requirements.
The proof of qualifications shall include documentation indicating the person is a professional engineer licensed in Washington state.
3803.3.3.4.2 Content of technical report and engineering analysis. All, but not limited to, the items listed below shall be included in the technical report:
1. Manufacturer information.
2. Engineer of record information.
3. Date of review and report revision history.
4. Signature page shall include:
a. Author of the report;
b. Date of report;
c. Seal, date and signature of engineer of record performing the design or peer review; and
d. Date, signature, and stamp of the professional engineer performing the engineering document review of the report. The engineering document review cannot be performed by the authoring engineer.
5. Model number of the item evaluated. If the equipment is provided with a serial number, the serial number shall be included for verification at time of site inspection.
6. Methodology of the design or peer review process used to determine minimum safety requirements. Methodology shall consider the basis of design, and shall include a code analysis and code path to demonstrate the reason as to why specific code or standards are applicable or not.
7. Equipment description. A list of every component and subassembly (clamp, fittings, hose, quick disconnects, gauges, site glass, gaskets, valves, pumps, vessels, containers, switches, etc.) of the system or equipment, indicating the manufacturer, model number, material, and solvent compatibility. Vendor cut sheets shall be provided.
8. A general flow schematic or general process flow diagram (PFD) of the process. Post-processing or winterization may be included in this diagram. All primary components of the process equipment shall be identified and match the aforementioned list. Operating temperatures, pressures, and solvent state of matter shall be identified in each primary step or component. A piping and instrumentation diagram (PID or PI&D) may be provided but is not required.
9. Analysis of the vessel(s) if pressurized beyond standard atmospheric pressure. Analysis shall include purchased and fabricated components.
10. Structural analysis for the frame system supporting the equipment.
11. Process safety analysis of the extraction system, from the introduction of raw product to the end of the extraction process.
12. Comprehensive process hazard analysis considering failure modes and points of failure throughout the process. This portion of the review should include review of emergency procedure information provided by the manufacturer of the equipment or process and not that of the facility, building or room.
13. Review of the assembly instructions, operational and maintenance manuals provided by the manufacturer.
14. Report shall include findings and observations of the analysis.
15. List of references used in the analysis.
3803.3.3.5 Building analysis. If the technical report, or manufacturer's literature indicate specific requirements for the location, room, space or building, where the extraction process is to occur, the engineer of record, as approved in 3802.3.3.4.1 shall review the construction documents of such location, room, space or building and provide a report of their findings and observations to the fire code official.
Analysis shall include:
1. Process safety analysis of the entire process from raw material to finished product.
2. Comprehensive process hazard analysis considering failure modes and points throughout the process. Should include review of emergency procedures as related to the equipment or process, and the facility.
3803.3.3.6 Site inspection. Prior to operation of the extraction equipment, if required by the fire code official, the engineer of record, as approved in Section 3802.3.3.4.1 shall inspect the site of the extraction process once equipment has been installed for compliance with the technical report and the building analysis. The engineer of record shall provide a report of findings and observations of the site inspection to the fire code official prior to the approval of the extraction process. The field inspection report authored by engineer of record shall include the serial number of the equipment used in the process and shall confirm the equipment installed is the same model and type of equipment identified in the technical report.
3803.3.3.7 Post-process purification and winterization. Post-processing and winterization involving the heating or pressurizing of the miscella to other than normal pressure or temperature shall be approved and performed in an appliance listed for such use. Domestic or commercial cooking appliances shall not be used. The use of industrial ovens shall comply with Chapter 30.
EXCEPTION:
An automatic fire extinguishing system shall not be required for batch-type Class A ovens having less than 3.0 cubic feet of work space.
3803.4 Construction requirements.
3803.4.1 Location. Marijuana extraction shall not be located in any building containing a Group A, E, I or R occupancy.
3803.4.1.1 Extraction room. The extraction equipment and extraction process shall be located in a room dedicated to extraction.
3803.4.2 Egress. Each marijuana extraction room shall be provided with at least one exit, swinging in the direction of travel provided with an automatic closer and panic hardware.
3803.4.2.1 Facility egress. The marijuana extraction room shall not enter directly into an exit, exit passageway, horizontal exit or along the sole egress path from another portion of the building.
3803.4.3 Ventilation. Each marijuana extraction room shall be provided with a dedicated hazardous exhaust system complying with Section 5004.3 for all solvents other than water. The operation of the hazardous exhaust system shall be continuous.
3803.4.4 Control area. Each marijuana extraction room shall be considered a single control area and comply with Section 5003.8.3.
3803.4.5 Ignition source control. Extraction equipment and extraction processes using a hydrocarbon-based liquid or gas solvent shall be provided with ventilation rates for the room to maintain the concentration of flammable constituents in air below 25 percent of the lower flammability limit of the respective solvent. If not provided with the required ventilation rate, then Class I Division II electrical requirements shall apply to the entire room.
3803.4.6 Interlocks. All electrical components within the extraction room shall be interlocked with the hazardous exhaust system and when provided, the gas detection system. When the hazardous exhaust system is not operational, then light switches and electrical outlets shall be disabled. Activation of the gas detection system shall disable all light switches and electrical outlets.
3803.4.7 Emergency power.
3803.4.7.1 Emergency power for extraction process. Where power is required for the operation of the extraction process, an automatic emergency power source shall be provided. The emergency power source shall have sufficient capacity to allow safe shutdown of the extraction process plus an additional 2 hours of capacity beyond the shutdown process.
3803.4.7.2 Emergency power for other than extraction process. An automatic emergency power system shall be provided for the following items when installed.
3803.4.7.2.1 Required electrical systems.
1. Extraction room lighting.
2. Extraction room ventilation system.
3. Solvent gas detection system.
4. Emergency alarm systems.
5. Automatic fire extinguishing systems.
3803.4.8 Continuous gas detection system. For extraction processes utilizing gaseous hydrocarbon-based solvents, a continuous gas detection system shall be provided. The gas detection threshold shall be no greater than 25 percent of the LEL/LFL limit of the materials.
3803.4.9 Liquefied-petroleum gases shall not be released to the atmosphere.
3803.5 Carbon dioxide enrichment or extraction. Extraction processes using carbon dioxide shall comply with the section.
3803.5.1 Scope. Carbon dioxide systems with more than 100 pounds of carbon dioxide shall comply with Sections 3802.5 through 3802.5.8. This section is applicable to carbon dioxide systems utilizing compressed gas systems, liquefied-gas system, dry ice, or on-site carbon dioxide generation.
3803.5.2 Permits. Permits shall be required as set forth in Sections 105.6 and 105.7.
3803.5.3 Equipment. The storage, use, and handling of liquid carbon dioxide shall be in accordance with Chapter 54 and the applicable requirements of NFPA 55, Chapter 13. Insulated liquid carbon dioxide system shall have pressure relief devices in accordance with NFPA 55.
3803.5.5 Protection from damage. Carbon dioxide systems shall be installed so the storage tanks, cylinders, piping and fittings are protected from damage by occupants or equipment during normal facility operations.
3803.5.7 Signage. At the entrance to each area using or storing carbon dioxide, signage shall be posted indicating the hazard. Signs shall be durable and permanent in nature and not less than 7 inches wide by 10 inches tall. Signs shall bear the "skull and crossbones" emblem with the warning "DANGER! POTENTIAL OXYGEN DEFICIENT ATMOSPHERE." NFPA 704 signage shall be provided at the building main entry and the rooms where the carbon dioxide is used and stored.
3803.5.8 Ventilation. Mechanical ventilation shall be in accordance with the International Mechanical Code and shall comply with all of the following:
1. Mechanical ventilation in the room or area shall be at a rate of not less than 1 cubic foot per minute per square foot.
2. The exhaust system intake shall be taken from a point within 12 inches of the floor.
3. The ventilation system shall be designed to operate at a negative pressure in relation to the surrounding area.
3803.6 Flammable or combustible liquid. The use of a flammable or combustible liquid for the extraction of oils and fats from marijuana shall comply with this section.
3803.6.1 Scope. The use of flammable and combustible liquids for liquid extraction process where the liquid is boiled, distilled, or evaporated shall comply with this section and NFPA 30.
3803.6.2 Location. The process using a flammable or combustible liquid shall be located within a hazardous exhaust fume hood, rated for exhausting flammable vapors. Electrical equipment used within the hazardous exhaust fume hood shall be rated for use in flammable atmospheres. Heating of flammable or combustible liquids over an open flame is prohibited.
EXCEPTION:
The use of a heating element not rated for flammable atmospheres may be approved where documentation from the manufacturer or an approved testing laboratory indicates it is rated for heating of flammable liquids.
NEW SECTION
WAC 51-54A-5307 Carbon dioxide (CO2) systems.
5307.1 General. Carbon dioxide systems with more than 100 pounds (45.4 kg) of carbon dioxide shall comply with Sections 5307.2 through 5307.5.2.
AMENDATORY SECTION (Amending WSR 13-04-063, filed 2/1/13, effective 7/1/13)
WAC 51-54A-8000 Referenced standards.
NFPA 96-07 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations . . . . 609.3
NFPA 720-((12)) 15 Standard for the Installation of Carbon Monoxide (CO) Warning Equipment in Dwelling
Units . . . . 908.7, 1103.9