PERMANENT RULES
Date of Adoption: November 17, 2000.
Purpose: To make changes to the Washington State Energy Code, chapter 51-11 WAC.
Citation of Existing Rules Affected by this Order: Chapter 51-11 WAC. Repealing sections 1201, 1210, 1701, 2000, 2001, 2002, 2003, 2004, 2005, 2006, 2007, 2008 and 2009; and amending sections 101, 201, 502, 503, 504, 505, 530, 601, 604, 605, 625, 626, 627, 628, 630, 701, 1001, 1002, 1003, 1004, 1005, 1006, 1007, 1008, 1009, 1132, 1313, 1322, 1323, 1331, 1334, 1410, 1411, 1412, 1414, 1415, 1416, 1423, 1433, 1435, 1438, 1439, 1443, 1512, 1513, 1521, 1530, 1531, 1532, 99902, 99903, and 99904.
Statutory Authority for Adoption: RCW 19.27A.025, 19.27A.045.
Adopted under notice filed as WSR 00-18-017 on August 28, 2000.
Changes Other than Editing from Proposed to Adopted Version: The proposed amendments to the following sections were not adopted: (502.1.5.1, exception 3), 504.5.2, (Tables 5-1, 6-2, 6-4, and 6-6), 602.5, 1312.1, 1412.4.1, (1412.8 and RS-29 Section 3.6.5), (1433 and 1401), (Tables 14-1, 14-2, and 14-3). In addition, the proposal to amend Section 502.1.1 and Table 10-5A (Section 1005) was altered to include the entire table (the roof values were lost in the proposed rule). Also, Table 10-6C (Section 1006) was altered to include a column of values for "Double Glazing with 1/4" Airspace." Also, Section 1411.1 was altered to add the words "nationally recognized" for clarification. Also, Section 1435, exception 1i was altered deleting the second and third sentence for simplicity. Finally, Section 1438 neither option was adopted, instead there was one word changed from "frequency" to "speed."
Number of Sections Adopted in Order to Comply with Federal Statute: New 0, Amended 0, Repealed 0; Federal Rules or Standards: New 0, Amended 0, Repealed 0; or Recently Enacted State Statutes: New 0, Amended 0, Repealed 0.
Number of Sections Adopted at Request of a Nongovernmental Entity: New 3, Amended 49, Repealed 13.
Number of Sections Adopted on the Agency's Own Initiative: New 0, Amended 0, Repealed 0.
Number of Sections Adopted in Order to Clarify, Streamline, or Reform Agency Procedures: New 0, Amended 0, Repealed 0.
Number of Sections Adopted Using Negotiated Rule Making: New 0, Amended 0, Repealed 0; Pilot Rule Making: New 0, Amended 0, Repealed 0; or Other Alternative Rule Making: New 3, Amended 49, Repealed 13. Effective Date of Rule: July 1, 2001.
January 3, 2001
Tim Nogler
for Jim Lewis
Council Vice Chair
OTS-4217.6
AMENDATORY SECTION(Amending WSR 98-24-078, filed 12/1/98,
effective 7/1/99)
WAC 51-11-0101
Section 101. Scope and general
requirements.
101.1 Title: Chapters 1 through 10 of this Code shall be
known as the "Washington State Residential Energy Code" and may
be cited as such; and will be referred to herein as "this Code."
101.2 Purpose and Intent: The purpose of this Code is to
provide minimum standards for new or altered buildings and
structures or portions thereof to achieve efficient use and
conservation of energy.
The purpose of this Code is not to create or otherwise
establish or designate any particular class or group of persons
who will or should be especially protected or benefitted by the
terms of this Code.
It is intended that these provisions provide flexibility to
permit the use of innovative approaches and techniques to achieve
efficient use and conservation of energy. These provisions are
structured to permit compliance with the intent of this Code by
any one of the following three paths of design:
1. A systems analysis approach for the entire building and
its energy-using sub-systems which may utilize renewable energy
sources, Chapter 4.
2. A component performance approach for various building
elements and mechanical systems and components, Chapter 5.
3. A prescriptive requirements approach, Chapter 6.
Compliance with any one of these approaches meets the intent
of this Code. This Code is not intended to abridge any safety or
health requirements required under any other applicable codes or
ordinances.
The provisions of this Code do not consider the efficiency
of various energy forms as they are delivered to the building
envelope. A determination of delivered energy efficiencies in
conjunction with this Code will provide the most efficient use of
available energy in new building construction.
101.3 Scope: This Code sets forth minimum requirements for
the design of new buildings and structures that provide
facilities or shelter for residential occupancies by regulating
their exterior envelopes and the selection of their HVAC, service
water heating systems and equipment for efficient use and
conservation of energy.
Buildings shall be designed to comply with the requirements
of either Chapter 4, 5, or 6 of this Code.
101.3.1 Exempt Buildings: Buildings and structures or
portions thereof meeting any of the following criteria shall be
exempt from the building envelope requirements of sections 502
and 602, but shall comply with all other requirements for
building mechanical systems, and service water heating.
101.3.1.1: Buildings and structures or portions thereof
whose peak design rate of energy usage is less than three and
four tenths (3.4) Btu/h per square foot or one point zero (1.0)
watt per square foot of floor area for space conditioning
requirements.
101.3.1.2: Buildings and structures or portions thereof
which are neither heated according to the definition of heated
space in Chapter 2, nor cooled by a nonrenewable energy source,
provided that the nonrenewable energy use for space conditioning
complies with requirements of section 101.3.1.1.
101.3.1.3: Greenhouses isolated from any conditioned space
and not intended for occupancy.
101.3.1.4: The provisions of this code do not apply to the
construction, alteration, or repair of temporary worker housing
except as provided by rule adopted under chapter 70.114A RCW or
chapter 37, Laws of 1998 (SB 6168). "Temporary worker housing"
means a place, area, or piece of land where sleeping places or
housing sites are provided by an employer for his or her
employees or by another person, including a temporary worker
housing operator, who is providing such accommodations for
employees, for temporary, seasonal occupancy, and includes "labor
camps" under RCW 70.54.110.
101.3.2 Application to Existing Buildings: Additions,
historic buildings, changes of occupancy or use, and alterations
or repairs shall comply with the requirements in the subsections
below.
EXCEPTION: | The building official may approve designs of alterations or repairs which do not fully conform with all of the requirements of this Code where in the opinion of the building official full compliance is physically impossible and/or economically impractical and: |
1. | The alteration or repair improves the energy efficiency of the building; or |
2. | The alteration or repair is energy efficient and is necessary for the health, safety, and welfare of the
general public. |
In no case, shall building envelope requirements or mechanical system requirements be less than those requirements in effect at the time of the initial construction of the building. |
EXCEPTION:
New additions which do not fully comply with the requirements of this Code and which have a floor area which
is less than seven hundred fifty square feet shall be approved provided that improvements are made to the
existing occupancy to compensate for any deficiencies in the new addition. Compliance shall be demonstrated
by either systems analysis or component performance calculations. The nonconforming addition and upgraded,
existing occupancy shall have an energy budget or ((
heat loss)) Target UA which is less than or equal to the
unimproved existing building (minus any elements which are no longer part of the building envelope once the
addition is added), with the addition designed to comply with this Code.
101.3.2.2 Historic Buildings: The building official may
modify the specific requirements of this Code for historic
buildings and require in lieu thereof alternate requirements
which will result in a reasonable degree of energy efficiency. This modification may be allowed for those buildings which have
been specifically designated as historically significant by the
state or local governing body, or listed in The National Register
of Historic Places or which have been determined to be eligible
for listing.
101.3.2.3 Change of Occupancy or Use:
Any Other than Group R Occupancy which is converted to Group
R Occupancy shall be brought into full compliance with this Code.
101.3.2.4 Alterations and Repairs: All alterations and
repairs to buildings or portions thereof originally constructed
subject to the requirements of this Code shall conform to the
provisions of this Code without exception. For all other
existing buildings, initial tenant alterations shall comply with
the new construction requirements of this Code. Other
alterations and repairs may be made to existing buildings and
moved buildings without making the entire building comply with
all of the requirements of this Code for new buildings, provided
the following requirements are met:
101.3.2.5 Building Envelope: The result of the alterations
or repairs both:
1. Improves the energy efficiency of the building, and
2. Complies with the overall average thermal transmittance
values of the elements of the exterior building envelope in Table
5-1 of Chapter 5 or the nominal R-values and glazing requirements
of the reference case in Tables 6-1 to 6-6.
EXCEPTIONS:
1. Untested storm windows may be installed over existing glazing for an assumed U-factor of 0.90, however,
where glass and sash are being replaced in Group R Occupancy, glazing shall comply with the appropriate
reference case in Table 6-1 through Table 6-6.
2. Where the structural elements of the altered portions of roof/ceiling, wall or floor are not being replaced,
these elements shall be deemed to comply with this Code if all existing framing cavities which are exposed
during construction are filled to the full depth with batt insulation or insulation having an equivalent nominal
R-value while, for roof/ceilings, maintaining the required space for ventilation. Existing walls and floors
without framing cavities need not be insulated. Existing roofs shall be insulated to the requirements of this
Code if
a. The roof is uninsulated or insulation is removed to the level of the sheathing, or
b. All insulation in the roof/ceiling was previously installed exterior to the sheathing or nonexistent.
101.3.2.6 Building Mechanical Systems: Those parts of
systems which are altered or replaced shall comply with section
503 of this Code.
101.3.2.7 Service Water Heating: Those parts of systems
which are altered or replaced shall comply with section 504.
101.3.2.8 ((Reserved.)) Lighting: Alterations shall comply
with section 1132.3.
EXCEPTION: | Group R-3 occupancy and the dwelling unit portions of Group R-1 occupancy. |
101.4 Amendments by Local Government: Except as provided in
RCW 19.27A.020(7), this Code shall be the maximum and minimum
energy code for Group R Occupancy in each town, city and county,
no later than July 1, 1991.
[Statutory Authority: RCW 19.27.031 and 19.27.074. 98-24-078, 51-11-0101, filed 12/1/98, effective 7/1/99. Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-0101, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-0101, filed 10/18/93, effective 4/1/94. Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, 51-11-0101, filed 12/19/90, effective 7/1/91.]
201.1 Application of Terms: For the purposes of this Code,
certain abbreviations, terms, phrases, words and their
derivatives, shall be as set forth in this chapter. Where terms
are not defined, they shall have their ordinary accepted meanings
within the context with which they are used. In the event there
is a question about the definition of a term, the definitions for
terms in the codes enumerated in RCW 19.27.031 and the edition of
Webster's dictionary referenced therein shall be considered as
the sources for providing ordinarily accepted meanings.
Addition: See the Washington State Building Code.
Advanced framed ceiling: Advanced framing assumes full and even depth of insulation extending to the outside edge of exterior walls. (See Standard Framing and Section 1007.2 of this Code.)
Advanced framed walls: Studs framed on twenty-four inch centers with double top plate and single bottom plate. Corners use two studs or other means of fully insulating corners, and one stud is used to support each header. Headers consist of double 2X material with R-10 insulation between the header and exterior sheathing. Interior partition wall/exterior wall intersections are fully insulated in the exterior wall. (See Standard Framing and Section 1005.2 of this Code.)
AFUE. Annual fuel utilization efficiency: Unlike steady state conditions, this rating is based on average usage including on and off cycling as set out in the standardized Department of Energy Test Procedures.
Air conditioning, comfort: The process of treating air to control simultaneously its temperature, humidity, cleanliness and distribution to meet requirements of the conditioned space.
ARI: Air-Conditioning and Refrigeration Institute.
ASHRAE: American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc.
ASTM: American Society for Testing and Materials
Automatic: Self-acting, operating by its own mechanism when actuated by some impersonal influence, as for example, a change in current strength, pressure, temperature or mechanical configuration. (See Manual.)
Below grade walls: Walls or the portion of walls which are entirely below the finish grade or which extend two feet or less above the finish grade.
((Building, existing: See the Washington State Building
Code.))
Boiler capacity: The rate of heat output in Btu/h measured at the boiler outlet, at the design inlet and outlet conditions and rated fuel/energy input.
Building envelope: For Group R occupancy, the elements of a building which enclose conditioned spaces through which thermal energy may be transferred to or from the exterior or to or from spaces exempted by the provisions of Section 101.3.1. For other than Group R occupancy, the elements of a building which enclose conditioned spaces through which thermal energy may be transferred to or from the exterior, or to or from unconditioned spaces, or to or from semi-heated spaces, or to or from spaces exempted by the provisions of Section 1301.
Building, existing: See the Washington State Building Code.
Building official: The official authorized to act in behalf of a jurisdiction code enforcement agency or its authorized representative.
Building project: A building or group of buildings, including on-site energy conversion or electric-generating facilities, which utilize a single submittal for a construction permit or are within the boundary of a contiguous area under one ownership.
((Comfort envelope: The area on a psychrometric chart
enclosing all those conditions described in Standard RS-4, Figure
No. 1, as being comfortable.))
Conditioned floor area: (See Gross conditioned floor area.)
Conditioned space: ((All spaces which are provided with
heated and/or cooled air or which are capable of being maintained
at temperatures over fifty degrees F during the heating season,
including adjacent connected spaces separated by an uninsulated
component (e.g., basements, utility rooms, garages, corridors).))
A cooled space, heated space (fully heated), heated space
(semi-heated) or indirectly conditioned space.
Cooled space: ((Space within a building which is provided
with a positive cooling supply.)) An enclosed space within a
building that is cooled by a cooling system whose sensible
capacity
a. exceeds 5 Btu/(h ft2), or
b. is capable of maintaining space dry bulb temperature of 90F or less at design cooling conditions.
COP - Coefficient of performance: The ratio of the rate of net heat output (heating mode) or heat removal (cooling mode) to the rate of total on-site energy input to the heat pump, expressed in consistent units and under designated rating conditions. (See Net Heat Output, Net Heat Removal, Total On-Site Energy Input.)
Daylighted zone:
a. Under overhead glazing: the area under overhead glazing whose horizontal dimension, in each direction, is equal to the overhead glazing dimension in that direction plus either the floor to ceiling height or the dimension to a ceiling height opaque partition, or one-half the distance to adjacent overhead or vertical glazing, whichever is least.
b. At vertical glazing: the area adjacent to vertical glazing which receives daylighting from the glazing. For purposes of this definition and unless more detailed daylighting analysis is provided, the daylighting zone depth is assumed to extend into the space a distance of 15 feet or to the nearest ceiling height opaque partition, whichever is less. The daylighting zone width is assumed to be the width of the window plus either two feet on each side (the distance to an opaque partition) or one-half the distance to adjacent overhead or vertical glazing, whichever is least.
Daylight sensing control (DS): A device that automatically regulates the power input to electric lighting near the glazing to maintain the desired workplace illumination, thus taking advantage of direct or indirect sunlight.
Deadband: The temperature range in which no heating or cooling is used.
((Degree day, heating: A unit, based upon temperature
difference and time, used in estimating fuel consumption and
specifying nominal heating load of a building in winter. For any
one day when the mean temperature is less than sixty-five degrees
F there exist as many degree days as there are Fahrenheit degrees
difference in temperature between the mean temperature for the
day and sixty-five degrees F.))
Design cooling conditions: The cooling outdoor design temperature from the 0.5% column for summer from the Puget Sound Chapter of ASHRAE publication "Recommended Outdoor Design Temperatures, Washington State, ASHRAE."
Design heating conditions: The heating outdoor design temperature from the 0.6% column for winter from the Puget Sound Chapter of ASHRAE publication "Recommended Outdoor Design Temperatures, Washington State, ASHRAE."
Door: ((An operable opening area in the shell of a
conditioned space, excluding sliding glass doors, which is
designed and used as a means of ingress and egress. A door may
also include a double door one of which is fixed and one of which
is operable.)) All operable opening areas, which are not glazing,
in the building envelope including swinging and roll-up doors,
fire doors, smoke vents and access hatches.
Door area: Total area of door measured using the rough opening and including the door and frame.
Dwelling unit: See the Washington State Building Code.
EER. Energy efficiency ratio: The ratio of net equipment cooling capacity in Btu/h to total rate of electric input in watts under designated operating conditions.
Economizer, air: A ducting arrangement and automatic control system that allows a cooling supply fan system to supply outside air to reduce or eliminate the need for mechanical refrigeration during mild or cold weather.
Economizer, water: A system by which the supply air of a cooling system is cooled directly, indirectly or both, by evaporation of water or by other appropriate fluid in order to reduce or eliminate the need for mechanical refrigeration.
Efficiency, HVAC system: The ratio of useful energy (at the point of use) to the energy input for a designated time period, expressed in percent.
Emissivity: The ability to absorb infrared radiation. A low emissivity implies a higher reflectance of infrared radiation.
Energy: The capacity for doing work; taking a number of forms which may be transformed from one into another, such as thermal (heat), mechanical (work), electrical and chemical; in customary units, measured in kilowatt-hours (kWh) or British thermal units (Btu). (See New energy.)
Energy, recovered: (See Recovered energy.)
Exterior envelope: (See Building envelope.)
Facade area: Vertical projected area including nonhorizontal roof area, overhangs, cornices, etc. measured in elevation in a vertical plane parallel to the plane of the building face.
Floor over unconditioned space: A floor which separates a conditioned space from an unconditioned space which is buffered from exterior ambient conditions including vented crawl spaces and unconditioned basements or other similar spaces, or exposed to exterior ambient conditions including open parking garages and enclosed garages which are mechanically ventilated.
F-Factor: The perimeter heat loss factor expressed in
Btu/hr ft F.
F-Value: (See F-Factor.)
Garden window: A multi-sided glazing product that projects beyond the plane of the wall.
Glazed wall system: A category of site assembled fenestration products used in the NFRC 100 and NFRC 200 rating procedures that include curtainwalls.
Glazing: All areas, including the frames, in the shell of a
conditioned space that let in natural light including windows,
clerestories, skylights, sliding or swinging glass doors and
glass block walls. ((The daylight opening area in all other
doors shall be considered glazing for the purpose of calculating
glazing area. The daylight opening area in all other doors is
included in the door U-factor and shall not be considered in
calculations of glazing U-factors.))
Glazing area: Total area of the glazing measured using the
rough opening, and including the glazing, sash, and frame. ((For
sliding glass doors the glazing area is the rough opening area. For all other doors the glazing area is the daylight opening
area.)) For doors where the daylight opening area is less than
50% of the door area, the glazing area is the daylight opening
area. For all other doors, the glazing area is the door area.
Gross conditioned floor area: The horizontal projection of that portion of interior space which is contained within exterior walls and which is conditioned directly or indirectly by an energy-using system, and which has an average height of five feet or greater, measured from the exterior faces.
Gross exterior wall area: The normal projection of the
building envelope wall area bounding interior space which is
conditioned by an energy-using system and which separates
conditioned space from: Unconditioned space, or semi-heated
space, or exterior ambient conditions or earth; includes opaque
wall, ((window)) vertical glazing and door areas. The gross area
of walls consists of all opaque wall areas, including foundation
walls, between floor spandrels, peripheral edges of floors,
((window)) vertical glazing areas ((including sash,)) and door
areas, where such surfaces are exposed to exterior ambient
conditions and enclose a conditioned space including interstitial
areas between two such spaces. (See Below grade wall.)
Gross floor area: The sum of the areas of the several floors of the building, including basements, cellars, mezzanine and intermediate floored tiers and penthouses of headroom height, measured from the exterior faces of exterior walls or from the center line of walls separating buildings, but excluding: Covered walkways, open roofed-over areas, porches and similar spaces. Pipe trenches, exterior terraces or steps, chimneys, roof overhangs and similar features.
Gross roof/ceiling area: ((The sum of the areas of the
roof/ceiling assembly, consisting of the total interior surface
area of all elements, including skylights, which enclose a
conditioned space.)) A roof/ceiling assembly shall be considered
as all components of the roof/ceiling envelope through which heat
flows, thus creating a building transmission heat loss or gain,
where such assembly is exposed to exterior ambient conditions and
encloses a conditioned space. The assembly does not include
those components that are separated from a heated and/or cooled
space by a vented airspace. The gross area of a roof/ceiling
assembly consists of the total interior surface of such assembly,
including overhead glazing.
Guest room: See the Washington State Building Code.
Heat: The form of energy that is transferred by virtue of a temperature difference.
Heat storage capacity: The physical property of materials (mass) located inside the building envelope to absorb, store, and release heat.
Heated space (Fully heated): ((Space within a building
which is provided with a positive heating supply. Finished
living space within a basement or registers or heating devices
designed to supply heat to a basement space shall automatically
define that space as heated space. (See Positive Heating
Supply.))) An enclosed space within a building, including
adjacent connected spaces separated by an uninsulated component
(e.g., basements, utility rooms, garages, corridors), which is
heated by a heating system whose output capacity is
a. Capable of maintaining a space dry-bulb temperature of 45F or greater at design heating conditions; or
b. 8 Btu/(h ft2) or greater in Climate Zone 1 and 12 Btu/(h ft2) or greater in Climate Zone 2.
Heated space (Semi-heated): An enclosed space within a building, including adjacent connected spaces separated by an uninsulated component (e.g., basements, utility rooms, garages, corridors), which is heated by a heating system
a. whose output capacity is 3 Btu/(h ft2) or greater in Climate Zone 1 and 5 Btu/(h ft2) or greater in Climate Zone 2; and
b. is not a Heated Space (Fully Heated).
HSPF. Heating season performance factor: The total heating
output (in Btu) of a heat pump during its normal annual usage
period for heating divided by the total (watt hour) electric
power input during the same period, as determined by test
procedures consistent with the U.S. Department of Energy "Test
Procedure for Central Air Conditioners, Including Heat Pumps"
published in ((the December 27, 1979, Federal Register, Vol 44,
No. 24, IOCFR. 430)) Standard RS-30. When specified in Btu per
watt hour an HSPF of 6.826 is equivalent to a COP of 2.0.
Humidistat: A regulatory device, actuated by changes in humidity, used for automatic control of relative humidity.
HVAC: Heating, ventilating and air conditioning.
HVAC system components: HVAC system components provide, in one or more factory-assembled packages, means for chilling and/or heating water with controlled temperature for delivery to terminal units serving the conditioned spaces of the buildings. Types of HVAC system components include, but are not limited to, water chiller packages, reciprocating condensing units and water source (hydronic) heat pumps. (See HVAC system equipment.)
HVAC system efficiency: (See Efficiency, HVAC system.)
HVAC system equipment: HVAC system equipment provides, in one (single package) or more (split system) factory-assembled packages, means for air circulation, air cleaning, air cooling with controlled temperature and dehumidification; and optionally, either alone or in combination with a heating plant, the functions of heating and humidifying. The cooling function may be either electrically or heat operated and the refrigerant condenser may be air, water or evaporatively cooled. Where the equipment is provided in more than one package, the separate packages shall be designed by the manufacturer to be used together. The equipment may provide the heating function as a heat pump or by the use of electric elements. (The word "equipment" used without modifying adjective may, in accordance with common industry usage, apply either to HVAC system equipment or HVAC system components.)
((Illumination: The density of the luminous flux incident
on a surface; it is the quotient of the luminous flux by the area
of the surface when the latter is uniformly illuminated.))
Indirectly conditioned space: An enclosed space within a building that is not a heated or cooled space, whose area weighted heat transfer coefficient to heated or cooled spaces exceeds that to the outdoors or to unconditioned spaces; or through which air from heated or cooled spaces is transferred at a rate exceeding three air changes per hour. Enclosed corridors between conditioned spaces shall be considered as indirectly conditioned space. (See Heated Space, Cooled Space and Unconditioned Space.)
Infiltration: The uncontrolled inward air leakage through cracks and interstices in any building element and around windows and doors of a building caused by the pressure effects of wind and/or the effect of differences in the indoor and outdoor air density.
Insulation baffle: A rigid material, resistant to wind driven moisture, the purpose of which is to allow air to flow freely into the attic or crawl space and to prevent insulation from blocking the ventilation of these spaces, or the loss of insulation. Example materials for this purpose are sheet metal, or wax impregnated cardboard.
Insulation position:
a. Exterior Insulation Position: a wall having all or nearly all of its mass exposed to the room air with the insulation on the exterior of the mass.
b. Integral Insulation Position: a wall having mass exposed to both room and outside air, with substantially equal amounts of mass on the inside and outside of the insulation layer.
c. Interior Insulation Position: a wall not meeting either of the above definitions; particularly a wall having most of its mass external to the insulation layer.
IPLV -- Integrated part-load value: A single number figure of merit based on part-load EER or COP expressing part-load efficiency for air conditioning and heat pump equipment on the basis of weighted operation at various load capacities for the equipment as specified in the Air-Conditioning and Refrigeration Institute (ARI) and Cooling Tower Institute (CTI) procedures.
Luminaire: A complete lighting unit consisting of a lamp or lamps together with the parts designed to distribute the light, to position and protect the lamps and to connect the lamps to the electric power supply.
Manual: Capable of being operated by personal intervention. (See Automatic.)
Microcell: A wireless communication facility consisting of an antenna that is either: (a) Four (4) feet in height and with an area of not more than 580 square inches; or (b) if a tubular antenna, no more than four (4) inches in diameter and no more than six (6) feet in length; and the associated equipment cabinet that is six (6) feet or less in height and no more than 48 square feet in floor area.
NFPA: National Fire Protection Association.
NFRC: National Fenestration Rating Council.
Net heat output: The change in the total heat content of the air entering and leaving the equipment (not including supplementary heat and heat from boilers).
Net heat removal: The total difference in heat content of the air entering and leaving the equipment (without heat) or the difference in total heat content of the water or refrigerant entering and leaving the component.
New energy: Energy, other than recovered energy, utilized for the purpose of heating or cooling. (See energy.)
Nominal R-value: The thermal resistance of insulation as specified by the manufacturer according to recognized trade and engineering standards.
Nonrenewable energy sources: All energy sources that are not renewable energy sources including natural gas, oil, coal, wood, liquified petroleum gas, steam, and any utility-supplied electricity.
Nonresidential: All buildings and spaces in the Uniform Building Code (UBC) occupancies other than Group R.
Occupancy: See the Washington State Building Code.
Occupancy sensor: A device that detects occupants within an area, causing any combination of lighting, equipment or appliances to be turned on or shut off.
Opaque envelope areas: All exposed areas of a building
envelope which enclose conditioned space, except openings for
((windows, skylights,)) doors, glazing and building service
systems.
Open blown: Loose fill insulation pneumatically installed in an unconfined attic space.
Outdoor air (outside air): Air taken from the outdoors and,
therefore, not previously circulated through ((the system)) a
building.
Overhead glazing: A glazing surface that has a slope of less than 60 from the horizontal plane.
Packaged terminal air conditioner: A factory-selected combination of heating and cooling components, assemblies or sections intended to serve a room or zone. (For the complete technical definition, see Standard RS-10.)
((Packaged terminal heat pump: A factory-selected
combination of heating and cooling components, assemblies or
sections intended for application in an individual room or zone. (For the complete technical definition, see Standard RS-21.)))
Permeance (perm): The ability of a material of specified
thickness to transmit moisture in terms of amount of moisture
transmitted per unit time for a specified area and differential
pressure (grains per hour ft2 inches of HG). Permeance may be
measured using ASTM E-96-72 or other approved dry cup method as
specified in ((RS-1)) RS-27.
Personal wireless service facility: A Wireless Communication Facility (WCF), including a microcell, which is a facility for the transmission and/or reception of radio frequency signals and which may include antennas, equipment shelter or cabinet, transmission cables, a support structure to achieve the necessary elevation, and reception and/or transmission devices or antennas.
Pool cover: A vapor-retardant cover which lies on or at the surface of the pool.
((Positive cooling supply: Mechanical cooling deliberately
supplied to a space, such as through a supply register. Also,
mechanical cooling indirectly supplied to a space through
uninsulated surfaces of space cooling components, such as
evaporator coil cases and cooling distribution systems which are
capable of maintaining air temperatures within the space of
eighty-five degrees F, or lower, at the exterior design
conditions specified in Section 302.1. To be considered exempt
from inclusion in this definition, such surfaces shall comply
with the insulation requirements of this Code.
Positive heating supply: Heat deliberately supplied to a space by design, such as a supply register, radiator or heating element. Also, heat indirectly supplied to a space through uninsulated surfaces of service water heaters and space heating components, such as furnaces, boilers and heating and cooling distributions systems which are capable of maintaining air temperature within the space of fifty degrees F, or higher, at the exterior design conditions specified in Section 302.1. To be considered exempt from inclusion in this definition, such surfaces shall comply with the insulation requirements of this Code.))
Power: In connection with machines, the time rate of doing work. In connection with the transmission of energy of all types, the rate at which energy is transmitted; in customary units, it is measured in watts (W) or British Thermal Units per hour (Btu/h).
((Public facility rest room: A rest room used by the
transient public on a regular (rather than casual) basis. Examples include rest rooms in service stations, airports, train
terminals and convention halls. Rest rooms incorporated with
private guest rooms in hotels, motels or dormitories and rest
room facilities intended for the use of employees and not usually
used by the general public are not considered public facility
rest rooms.)) Process energy: Energy consumed in support of a
manufacturing, industrial, or commercial process other than the
maintenance of building comfort or amenities for building
occupants.
Radiant slab floor: A slab floor assembly on grade or
below, containing heated pipes, ducts, or electric heating cables
that constitute a ((radiant slab)) floor or portion thereof for
((a)) complete or partial heating of the structure.
Readily accessible: See the Washington State Mechanical Code.
Recooling: The removal of heat by sensible cooling of the supply air (directly or indirectly) that has been previously heated above the temperature to which the air is to be supplied to the conditioned space for proper control of the temperature of that space.
Recovered energy: Energy utilized which would otherwise be wasted (i.e. not contribute to a desired end use) from an energy utilization system.
Reheat: The application of sensible heat to supply air that has been previously cooled below the temperature of the conditioned space by either mechanical refrigeration or the introduction of outdoor air to provide cooling.
Renewable energy sources: Renewable energy sources of energy (excluding minerals) are derived from: (1) incoming solar radiation, including but not limited to, natural daylighting and photosynthetic processes; (2) energy sources resulting from wind, waves and tides, lake or pond thermal differences; and (3) energy derived from the internal heat of the earth, including nocturnal thermal exchanges.
Reset: Adjustment of the set point of a control instrument to a higher or lower value automatically or manually to conserve energy.
Roof/ceiling assembly: ((A roof/ceiling assembly shall be
considered as all components of the roof/ceiling envelope through
which heat flows, thus creating a building transmission heat loss
or gain, where such assembly is exposed exterior ambient
conditions to and encloses a conditioned space. The gross area
of a roof/ceiling assembly consists of the total interior surface
of such assembly, including skylights.)) (See Gross roof/ceiling
area.)
SEER - Seasonal Energy Efficiency Ratio: The total cooling output of an air conditioner during its normal annual usage period, in Btu's, divided by the total electric energy input in watt-hours, during the same period, as determined by 10 CFR, Part 430.
Semi-heated space: Sub-category of Heated Space. (See Heated Space.)
Sequence: A consecutive series of operations.
Service systems: All energy-using systems in a building that are operated to provide services for the occupants or processes housed therein, including HVAC, service water heating, illumination, transportation, cooking or food preparation, laundering or similar functions.
Service water heating: Supply of hot water for domestic or commercial purposes other than comfort heating.
Shaded: Glazed area which is externally protected from direct solar radiation by use of devices permanently affixed to the structure or by an adjacent building, topographical feature, or vegetation.
Shading coefficient: The ratio of solar heat gain occurring through nonopaque portions of the glazing, with or without integral shading devices, to the solar heat gain occurring through an equivalent area of unshaded, 1/8 inch thick, clear, double-strength glass.
Note: | Heat gains to be compared under the same conditions. See Chapter 28 of Standard RS-27, listed in Chapter 7 of this Code. |
Single family: One and two family residential dwelling units with no more than two units in a single building.
Skylight: ((A glazing surface that has a slope of less than
sixty degrees from the horizontal plane.)) (See Overhead
glazing.)
Slab-below-grade: Any portion of a slab floor in contact with the ground which is more than 24 inches below the final elevation of the nearest exterior grade.
Slab-on-grade, exterior: Any portion of a slab floor in contact with the ground which is less than or equal to twenty-four inches below the final elevation of the nearest exterior grade.
((Slab-below-grade: Any portion of a slab floor in contact
with the ground which is more than twenty-four inches below the
final elevation of the nearest exterior grade.))
Small business: Any business entity (including a sole proprietorship, corporation, partnership, or other legal entity) which is owned and operated independently from all other businesses, which has the purpose of making a profit, and which has fifty or fewer employees, or which has a million dollars or less per year in gross sales, of window products.
Solar energy source: Source of natural daylighting and of thermal, chemical or electrical energy derived directly from conversion of incident solar radiation.
Solar heat gain coefficient (SHGC): The ratio of the solar heat gain entering the space through the glazing product to the incident solar radiation. Solar heat gain includes directly transmitted solar heat and absorbed solar radiation which is then reradiated, conducted or convected into the space.
Split system: Any heat pump or air conditioning unit which is provided in more than one assembly requiring refrigeration piping installed in the field.
Standard framing: All framing practices not defined as "intermediate" or "advanced" shall be considered standard. (See Advanced framed ceiling, Advanced framed walls, Intermediate framed wall and Section 1005.2 of this Code.)
Substantial contact: A condition where adjacent building materials are placed in a manner that proximal surfaces are contiguous, being installed and supported as to eliminate voids between materials, without compressing or degrading the thermal performance of either product.
System: A combination of central or terminal equipment or components and/or controls, accessories, interconnecting means, and terminal devices by which energy is transformed so as to perform a specific function, such as HVAC, service water heating or illumination.
Tapering: Installation of a reduced level of ceiling insulation at the eaves, due to reduced clearance.
Thermal by-pass: An area where the envelope surrounding the conditioned space is breached, or where an ineffective application compromises the performance of a thermal or infiltration barrier, increasing the structure's energy consumption by exposing finished surfaces to ambient conditions and additional heat transfer.
Thermal conductance (C): Time rate of heat flow through a body (frequently per unit area) from one of its bounding surfaces to the other for a unit temperature difference between the two surfaces, under steady conditions (Btu/hr ft2 F).
Thermal resistance (R): The reciprocal of thermal conductance (hr ft2 F/Btu).
Thermal transmittance (U): The coefficient of heat
transmission (air to air). It is the time rate of heat flow per
unit area and unit temperature difference between the warm side
and cold side air films (Btu/hr ft2 F). ((The U-factor applies
to the fractional combinations of different materials used in
series along the heat flow path.))
Thermal transmittance, overall (Uo): The overall (average)
heat transmission of a gross area of the exterior building
envelope (Btu/hr ft2 F). The Uo-factor applies to the combined
effect of the time rate of heat flows through the various
parallel paths, such as ((windows,)) glazing, doors and opaque
construction areas, comprising the gross area of one or more
exterior building components, such as walls, floors or
roof/ceiling.
Thermostat: An automatic control device actuated by temperature and designed to be responsive to temperature.
Total on-site energy input: The combination of all the energy inputs to all elements and accessories as included in the equipment components, including but not limited to, compressor(s), compressor sump heater(s), circulating pump(s), purge devices, fan(s), and the HVAC system component control circuit.
Transmission coefficient: The ratio of the solar heat gain through a glazing system to that of an unshaded single pane of double strength window glass under the same set of conditions.
U-factor: (See thermal transmittance.)
U-Value: (See U-factor.)
Uniform Building Code (UBC): ((The Washington State Uniform
Building Code as modified by the Washington State Building Code
Council.)) (See Washington State Building Code.)
Uniform Mechanical Code (UMC): ((The Washington State
Uniform Mechanical Code as modified by the Washington State
Building Code Council.)) (See Washington State Mechanical Code.)
Uniform Plumbing Code (UPC): (See Washington State Plumbing Code.)
Unitary cooling and heating equipment: One or more factory-made assemblies which include an evaporator or cooling coil, a compressor and condenser combination, and may include a heating function as well. Where such equipment is provided in more than one assembly, the separate assemblies shall be designed to be used together.
Unitary heat pump: One or more factory-made assemblies which include an indoor conditioning coil, compressor(s) and outdoor coil or refrigerant-to-water heat exchanger, including means to provide both heating and cooling functions. When such equipment is provided in more than one assembly, the separate assemblies shall be designed to be used together.
Vapor retarder: A layer of low moisture transmissivity
material (not more than 1.0 perm dry cup) placed over the warm
side (in winter) of insulation, over the exterior of below grade
walls, and under floors as ground cover to limit the transport of
water and water vapor through exterior walls, ceilings, and
floors. Vapor retarding paint, listed for this application, also
((complies with this Code)) meets this definition.
Vaulted ceilings: All ceilings where enclosed joist or rafter space is formed by ceilings applied directly to the underside of roof joists or rafters.
Ventilation: The process of supplying or removing air by natural or mechanical means to or from any space. Such air may or may not have been conditioned.
Ventilation air: That portion of supply air which comes from outside (outdoors) plus any recirculated air that has been treated to maintain the desired quality of air within a designated space.
Vertical glazing: A glazing surface that has a slope of 60 or greater from the horizontal plane.
Walls (exterior): Any member or group of members which defines the exterior boundaries or courts of a building and which have a slope of sixty degrees or greater with the horizontal plane, and separates conditioned from unconditioned space. Band joists between floors are to be considered a part of exterior walls.
Washington State Building Code: The building code as modified by the Washington State Building Code Council.
Washington State Mechanical Code: The mechanical code as modified by the Washington State Building Code Council.
Washington State Plumbing Code: The plumbing code as modified by the Washington State Building Code Council.
Zone: A space or group of spaces within a building with heating and/or cooling requirements sufficiently similar so that comfort conditions can be maintained throughout by a single controlling device. Each dwelling unit in residential buildings shall be considered a single zone.
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-0201, filed 1/8/98, effective 7/1/98. Statutory Authority: Chapters 19.27, 19.27A and 34.05 RCW. 94-05-059, 51-11-0201, filed 2/10/94, effective 4/1/94. Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-0201, filed 10/18/93, effective 4/1/94. Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, 51-11-0201, filed 12/19/90, effective 7/1/91.]
502.1 General:
502.1.1: The stated U- or F-factor of any component
assembly, listed in Table 5-1 or 5-2, such as roof/ceiling,
opaque wall or opaque floor may be increased and the U-factor for
other components decreased, provided that the total heat gain or
loss for the entire building envelope does not exceed the total
resulting from compliance to the U-factors specified in this
Section.
The U-factors for typical construction assemblies are
included in Chapter 10. These values shall be used for all
calculations. Where proposed construction assemblies are not
represented in Chapter 10, values shall be calculated in
accordance with Chapters 21-29 in Standard RS-1 listed in Chapter
7, using the framing factors listed in Chapter 10 where
applicable.
For envelope assemblies containing metal framing, the
U-factor shall be determined by one of the following methods:
1. Results of laboratory or field measurements.
2. Standard RS-25, listed in Chapter 7, where the metal
framing is bonded on one or both sides to a metal skin or
covering.
3. The zone method as provided in Chapter 24 of Standard
RS-1, listed in Chapter 7.
4. Results of parallel path correction factors effective
framing/cavity R-values as provided ((from the following table
for metal stud walls and roof ceilings:)) in Table 10-5A - EFFECTIVE R-VALUES FOR METAL FRAMING AND CAVITY ONLY for metal stud walls
and roof/ceilings.
Inches |
Inches |
R-Value |
16" o.c. |
24" o.c. |
|
R-11.4)) |
502.1.3: When return air ceiling plenums are employed, the
roof/ceiling assembly shall:
a. For thermal transmittance purposes, not include the
ceiling proper nor the plenum space as part of the assembly; and
b. For gross area purposes, be based upon the interior face
of the upper plenum surface.
502.1.4 Insulation:
502.1.4.1 General: All insulating materials shall comply
with sections 2602 and/or 707 of the Uniform Building Code. Substantial contact of the insulation with the surface being
insulated is required. All insulation materials shall be
installed according to the manufacturer's instructions to achieve
proper densities and maintain uniform R-values and shall be
installed in a manner which will permit inspection of the
manufacturer's R-value identification mark. To the maximum
extent possible, insulation shall extend over the full component
area to the intended R-value.
Alternatively, the thickness of roof/ceiling and wall insulation that is either blown in or spray-applied shall be identified by inches of thickness, density and R-value markers installed at least one for every 300 square feet (28 m2) through the attic, ceiling and/or wall space. In attics, the markers shall be affixed to the trusses or joists and marked with the minimum initial installed thickness and minimum settled thickness with numbers a minimum 1.0 inch (25 mm) in height. Each marker shall face the attic access. The thickness of installed attic insulation shall meet or exceed the minimum initial installed thickness shown by the marker. In cathedral ceilings and walls, the markers shall be affixed to the rafter and wall frame at alternating high and low intervals and marked with the minimum installed density and R-value with numbers a minimum 1.0 inch (25 mm) in height. Each marker shall face the conditioned room area.
502.1.4.2 Insulation Materials: All insulation materials
including facings such as vapor barriers or breather papers
installed within floor/ceiling assemblies, roof/ceiling
assemblies, walls, crawl spaces, or attics shall have a flame
spread rating of less than 25 and a smoke density not to exceed
450 when tested in accordance with UBC Standard 8-1.
EXCEPTIONS:
1. Foam plastic insulation shall comply with section 2602 of the Uniform Building Code.
2. When such materials are installed in concealed spaces of Types III, IV and V construction, the flame spread
and smoke developed limitations do not apply to facing, provided that the facing is installed in substantial
contact with the unexposed surface of the ceiling, floor or wall finish.
3. Cellulose insulation shall comply with section 707 of the Uniform Building Code.
502.1.4.3 Clearances: Where required, insulation shall be
installed with clearances according to manufacturer's
specifications. Insulation shall be installed so that required
ventilation is unobstructed. For blown or poured loose fill
insulation, clearances shall be maintained through installation
of a permanent retainer.
502.1.4.4 Access Hatches and Doors: Access doors from
conditioned spaces to unconditioned spaces (e.g., attics and
crawl spaces) shall be weatherstripped and insulated to a level
equivalent to the insulation on the surrounding surfaces. Access
shall be provided to all equipment which prevents damaging or
compressing the insulation. A wood framed or equivalent baffle
or retainer must be provided when loose fill insulation is
installed, the purpose of which is to prevent the loose fill
insulation from spilling into the living space when the attic
access is opened, and to provide a permanent means of maintaining
the installed R-value of the loose fill insulation.
502.1.4.5 Roof/Ceiling Insulation: Open-blown or poured
loose fill insulation may be used in attic spaces where the slope
of the ceiling is not more than 3 feet in 12 and there is at
least 30 inches of clear distance from the top of the bottom
chord of the truss or ceiling joist to the underside of the
sheathing at the roof ridge. When eave vents are installed,
baffling of the vent openings shall be provided so as to deflect
the incoming air above the surface of the insulation. Baffles
shall be, rigid material, resistant to wind driven moisture. Requirements for baffles for ceiling insulation shall meet the
Uniform Building Code section 1505.3 for minimum ventilation
requirements. When feasible, the baffles shall be installed from
the top of the outside of the exterior wall, extending inward, to
a point 6 inches vertically above the height of noncompressed
insulation, and 12 inches vertically above loose fill insulation.
502.1.4.6 Wall Insulation: Insulation installed in exterior
walls shall comply with the provisions of this section. All wall
insulation shall fill the entire framed cavity. Exterior wall
cavities isolated during framing shall be fully insulated to the
levels of the surrounding walls. All faced insulation shall be
face stapled to avoid compression.
502.1.4.7 Floor Insulation: Floor insulation shall be
installed in a permanent manner in substantial contact with the
surface being insulated. Insulation supports shall be installed
so spacing is no more than 24 inches on center. Foundation vents
shall be placed so that the top of the vent is below the lower
surface of the floor insulation.
EXCEPTION:
Insulation may be omitted from floor areas over heated basements, heated garages or underfloor areas used as
HVAC supply plenums. See Uniform Mechanical Code section 607 for underfloor supply plenum
requirements. When foundation walls are insulated, the insulation shall be attached in a permanent manner.
The insulation shall not block the airflow through foundation vents when installed. When foundation vents are
not placed so that the top of the vent is below the lower surface of the floor insulation, a permanently attached
baffle shall be installed at an angle of 30 from horizontal, to divert air flow below the lower surface of the
floor insulation.
502.1.4.8 Slab-On-Grade: Slab-on-grade insulation,
installed inside the foundation wall, shall extend downward from
the top of the slab for a minimum distance of 24 inches or
downward and then horizontally beneath the slab for a minimum
combined distance of 24 inches. Insulation installed outside the
foundation shall extend downward to a minimum of 24 inches or to
the frostline. Above grade insulation shall be protected.
EXCEPTION:
For monolithic slabs, the insulation shall extend downward from the top of the slab to the bottom of the
footing.
502.1.4.9 Radiant Slabs: The entire area of a radiant slab
shall be thermally isolated from the soil, with a minimum of R-10
insulation. The insulation shall be an approved product for its
intended use. If a soil gas control system is present below the
radiant slab, which results in increased convective flow below
the radiant slab, the radiant slab shall be thermally isolated
from the sub-slab gravel layer.
502.1.4.10 Below Grade Walls: Below grade exterior wall
insulation used on the exterior (cold) side of the wall shall
extend from the top of the below grade wall to the top of the
footing and shall be approved for below grade use. Above grade
insulation shall be protected.
Insulation used on the interior (warm) side of the wall
shall extend from the top of the below grade wall to the below
grade floor level.
502.1.5 Glazing and Door U-factors: Glazing and door
U-factors shall be determined in accordance with sections
502.1.5.1 and 502.1.5.2. All products shall be labeled with the
NFRC certified or default U-factor. The labeled U-factor shall
be used in all calculations to determine compliance with this
Code. Sealed insulating glass shall conform to, or be in test
for, ASTM E-774-81 class A.
EXCEPTIONS: | 1. For glazed wall systems, assemblies with all of the following features are deemed to satisfy the vertical
glazing U-factor requirement in Table 6-1 through 6-6 options with vertical glazing U-0.40 and greater: |
a. Double glazing with a minimum 1/2 inch gap width, having a low-emissivity coating with e=0.10 maximum,
with 90% minimum argon gas fill, and a non-aluminum spacer (as defined in footnote 1 to Table 10-6B), and |
|
b. Frame that is thermal break aluminum (as defined in footnote 9 to Table 10-6B), wood, aluminum clad
wood, vinyl, aluminum clad vinyl, or reinforced vinyl. |
|
The only labeling requirement for products using this exception shall be a description of the product and a label
stating: "This product is deemed to satisfy the Table 6-1 through 6-6 vertical glazing U-factor requirement
using the exception to Section 502.1.5 in the Washington State Energy Code." |
|
2. For overhead glazing, assemblies with all of the following features are deemed to satisfy the overhead
glazing U-factor requirement in all Table 6-1 through 6-6 options except the unlimited glazing area options
(Option VIII in Table 6-2, Option IX in Table 6-4, and Option VIII for Climate Zone 1 and Option IX for
Climate Zone 2 in Table 6-6): |
|
a. Either, double glazing with a minimum 1/2 inch gap width, having a low-emissivity coating with e=0.20
maximum, with 90% minimum argon gas fill, or, triple glazed plastic domes, and |
|
b. Frame that is thermal break aluminum (as defined in footnote 9 to Table 10-6B), wood, aluminum clad
wood, vinyl, aluminum clad vinyl, or reinforced vinyl. |
|
The only labeling requirement for products using this exception shall be a description of the product and a label
stating: "This product is deemed to satisfy the Table 6-1 through 6-6 overhead glazing U-factor requirement
using the exception to Section 502.1.5 in the Washington State Energy Code." |
|
3. For solariums with a floor area which does not exceed 300 square feet, assemblies which comply with the
features listed in exception 2 are deemed to satisfy the vertical glazing and overhead glazing U-factor
requirement in Table 6-1 through 6-6 options with vertical glazing U-0.40 and greater. |
|
The only labeling requirement for products using this exception shall be a description of the product and a label
stating: "This product is deemed to satisfy the Table 6-1 through 6-6 vertical glazing and overhead glazing
U-factor requirements using the exception to Section 502.1.5 in the Washington State Energy Code." |
EXCEPTIONS:
1. Glazing products without NFRC ratings may be assigned default U-factors from Table 10-6A for vertical
glazing and from Table 10-6E for overhead glazing.
2. Units without NFRC ratings produced by a small business may be assigned default U-factors from Table
10-6A for garden windows, from Table 10-6B for other vertical glazing, and from Table 10-6E for overhead
glazing.
502.1.5.2 Standard Procedure for Determination of Door
U-factors: ((Half-lite and full-lite doors, including fire
doors, shall be assigned default U-factors from Table 10-6D.)) All ((other)) doors, including fire doors, shall be assigned
default U-factors from Table 10-6C.
EXCEPTIONS:
1. U-factors determined, certified and labeled in accordance with the National Fenestration Rating Council
(NFRC) Product Certification Program (PCP), as authorized by an independent certification and inspection
agency licensed by the NFRC.
2. The default values for the opaque portions of doors shall be those listed in Table 10-6C, provided that the
U-factor listed for a door with a thermal break shall only be allowed if both the door and the frame have a
thermal break.
3. One unlabeled or untested exterior swinging door with the maximum area of 24 square feet may be installed
for ornamental, security or architectural purposes. Products using this exception shall not be included in either
the U-factor or glazing area calculation requirements.
502.1.6 Moisture Control:
502.1.6.1 Vapor Retarders: Vapor retarders shall be
installed on the warm side (in winter) of insulation as specified
in the following cases.
EXCEPTION: | Vapor retarder installed with not more than 1/3 of the nominal R-value between it and the conditioned space. |
502.1.6.3 Roof/Ceilings: Roof/ceiling assemblies where the
ventilation space above the insulation is less than an average of
12 inches shall be provided with a vapor retarder. Faced batt
insulation where used as a vapor retarder shall be face stapled. Single rafter joist vaulted ceiling cavities shall be of
sufficient depth to allow a minimum one inch vented air space
above the insulation.
502.1.6.4: Vapor retarders shall not be required in
roof/ceiling assemblies where the ventilation space above the
insulation averages 12 inches or greater.
502.1.6.5: Vapor retarders shall not be required where all
of the insulation is installed between the roof membrane and the
structural roof deck.
502.1.6.6 Walls: Walls separating conditioned space from
unconditioned space shall have a vapor retarder installed. Faced
batt insulation shall be face stapled.
502.1.6.7 Ground Cover: A ground cover of six mil (0.006
inch thick) black polyethylene or approved equal shall be laid
over the ground within crawl spaces. The ground cover shall be
overlapped 12 inches minimum at the joints and shall extend to
the foundation wall.
EXCEPTION: | The ground cover may be omitted in crawl spaces if the crawl space has a concrete slab floor with a minimum thickness of 3-1/2 inches. |
502.2.1 UA Calculations: The proposed UA as calculated
using Equations 2 and 3 shall not exceed the target UA as
calculated using Equation 1. For the purpose of determining
equivalent thermal performance, the glazing area for the target
UA shall be calculated using values in Table 5-1. The opaque
door area shall be the same in the target UA and the proposed UA.
EXCEPTION: | Log and solid timber walls that have a minimum average thickness of 3.5" and with space heat type other than electric resistance, are exempt from wall target UA and proposed UA calculations. |
1. Electric Resistance: Space heating systems which include
baseboard units, radiant units and forced air units as either the
primary or secondary heating system.
EXCEPTION: | Electric resistance systems for which the total electric heat capacity in each individual dwelling unit does not exceed the greater of: 1) One thousand watts (1000 w) per dwelling unit, or; 2) One watt per square foot (1 w/ft2) of the gross floor area. |
502.3 Reserved.
502.4 Air Leakage:
502.4.1 General: The requirements of this section shall
apply to all buildings and structures, or portions thereof, and
only to those locations separating outdoor ambient conditions
from interior spaces that are heated or mechanically cooled.
502.4.2 Doors and Windows, General: Exterior doors and
windows shall be designed to limit air leakage into or from the
building envelope. Site-constructed doors and windows shall be
sealed in accordance with Section 502.4.3.
502.4.3 Seals and Weatherstripping:
a. Exterior joints around windows and door frames, openings
between walls and foundation, between walls and roof and wall
panels; openings at penetrations of utility services through
walls, floors and roofs; and all other openings in the building
envelope for all occupancies and all other openings in between
units in R-1 occupancy shall be sealed, caulked, gasketed or
weatherstripped to limit air leakage. Other exterior joints and
seams shall be similarly treated, or taped, or covered with
moisture vapor permeable housewrap.
b. All exterior doors or doors serving as access to an
enclosed unheated area shall be weatherstripped to limit leakage
around their perimeter when in a closed position.
c. Site built windows are exempt from testing but shall be
made tight fitting. Fixed lights shall have glass retained by
stops with sealant or caulking all around. Operating sash shall
have weatherstripping working against overlapping trim and a
closer/latch which will hold the sash closed. The window frame
to framing crack shall be made tight with caulking, overlapping
membrane or other approved technique.
d. Openings that are required to be fire resistive are
exempt from this section.
502.4.4 Recessed Lighting Fixtures: When installed in the
building envelope, recessed lighting fixtures shall meet one of
the following requirements:
1. Type IC rated, manufactured with no penetrations between
the inside of the recessed fixture and ceiling cavity and sealed
or gasketed to prevent air leakage into the unconditioned space.
2. Type IC rated, installed inside a sealed box constructed
from a minimum 1/2 inch thick gypsum wall board, or constructed
from a preformed polymeric vapor barrier, or other air tight
assembly manufactured for this purpose.
3. Type IC rated, certified under ASTM E283 to have no more
than 2.0 cfm air movement from the conditioned space to the
ceiling cavity. The lighting fixture shall be tested at 75
Pascals or 1.57 lbs/ft2 pressure difference and have a label
attached, showing compliance.
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-0502, filed 1/8/98, effective 7/1/98. Statutory Authority: Chapters 19.27 and 19.27A RCW and 1994 c 226. 95-01-126, 51-11-0502, filed 12/21/94, effective 6/30/95. Statutory Authority: Chapters 19.27, 19.27A and 34.05 RCW. 94-05-059, 51-11-0502, filed 2/10/94, effective 4/1/94. Statutory Authority: Chapter 19.27A RCW. 92-01-140, 51-11-0502, filed 12/19/91, effective 7/1/92. Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, 51-11-0502, filed 12/19/90, effective 7/1/91.]
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040.
AMENDATORY SECTION(Amending WSR 98-24-075, filed 12/1/98,
effective 7/1/99)
WAC 51-11-0503
Building mechanical systems.
503.1 General: This section covers the determination of design requirements, system and component performance, control requirements, insulating systems and duct construction.
((
EXCEPTIONS:Special applications, including but not limited to hospitals, laboratories, thermally sensitive equipment, and
computer rooms may be exempted from the requirements of this section when approved by the building
official.))
503.2 Calculations of Heating and Cooling Loads, and System
Sizing Limits: The design parameters specified in Chapter 3
shall apply for all computations.
503.2.1 Calculation Procedures: Heating and cooling design
loads for the purpose of sizing HVAC systems are required and
shall be calculated in accordance with accepted engineering
practice, including infiltration and ventilation.
503.2.2 Space Heating and Space Cooling System Sizing
Limits: Building mechanical systems for all buildings which
provide space heating and/or space cooling shall be sized no
greater than two hundred percent (200%) of the heating and
cooling design loads as calculated above.
EXCEPTIONS:
The following limited exemptions from the sizing limit shall be allowed((
,)); however, in all cases heating
and/or cooling design load calculations shall be submitted.
1. For equipment which provides both heating and cooling in one package unit, including heat pumps with
electric heating and cooling and gas-pack units with gas heating and electric cooling, compliance need only be
demonstrated for either the space heating or space cooling system size.
2. Natural gas- or oil-fired space heating equipment whose total rated space heating output in any one dwelling
unit is ((
fifty-six thousand Btu/h or less))
a. 40,000 Btu/h or less is exempt from the sizing limit,
b. larger than 40,000 Btu/h may exceed the two hundred (200%) percent sizing limit provided that the installed
equipment has an annual fuel utilization efficiency (AFUE) of not less than ((
the sum of seventy-eight percent
plus one percent for every five thousand Btu/h that the space heating equipment output exceeds the design
heating load of the dwelling unit)) ninety (90%) percent.
3. Stand-by equipment may be installed if controls and other devices are provided which allow redundant
equipment to operate only when the primary equipment is not operating.
503.3 Simultaneous Heating and Cooling: Systems and
equipment that provide simultaneous heating and cooling shall
comply with the requirements in, as appropriate, Section 1422 or
Section 1435.
503.4 HVAC Equipment Performance Requirements:
503.4.1 Equipment Components:
503.4.1.1: The requirements of this section apply to
equipment and mechanical component performance for heating,
ventilating and air-conditioning systems. Equipment efficiency
levels are specified. Data furnished by the equipment supplier
or certified under a nationally recognized certification program
or rating procedure shall be used to satisfy these requirements. Equipment efficiencies shall be based on the standard rating
conditions in Tables 5-4, 5-5 or 5-6 as appropriate.
503.4.1.2: Where components from more than one manufacturer
are assembled into systems regulated under this section,
compliance for each component shall be as specified in sections
503.4.2 through 503.4.6 of this Code.
503.4.2: HVAC System Heating Equipment Heat Pump-heating
Mode. Heat pumps whose energy input is entirely electric shall
have a coefficient of performance (COP) heating, not less than
the values in Table 5-7. Heat Pumps with supplementary backup
heat other than electricity shall meet the requirements of Table
5-7.
503.4.2.1: These requirements apply to, but are not limited
to, unitary (central) heat pumps (air source and water source) in
the heating mode, water source (hydronic) heat pumps as used in
multiple-unit hydronic HVAC systems, and heat pumps in the
packaged terminal air-conditioner in the heating mode.
503.4.2.3 Supplementary Heater: The heat pump shall be
installed with a control to prevent supplementary backup heater
operation when the operating load can be met by the heat pump
compression cycle alone.
503.4.2.4 Heat Pump Controls: Requirements for heat pump
controls are listed in section 503.8.3.5 of this Code.
503.4.3 HVAC System Combustion Equipment: For Group R
Occupancy, all gas, oil, and propane central heating systems
shall have a minimum AFUE of 0.78*. All other Group R Occupancy
heating equipment fueled by gas, oil, or propane shall be
equipped with an intermittent ignition device, or shall comply
with the efficiencies as required in the 1987 National Appliances
Energy Conservation Act (Public Law 100-12).
*HVAC Heating system efficiency trade-offs shall be made
using Chapters 4 or 6 of this Code.
503.4.4 Packaged and Unitary HVAC System Equipment,
Electrically Operated, Cooling Mode: HVAC system equipment as
listed below, whose energy input in the cooling mode is entirely
electric, shall have an energy efficiency ratio (EER) or a
seasonal energy efficiency ratio (SEER) cooling not less than
values in Table 5-8.
503.4.4.1: These requirements apply to, but are not limited
to, unitary (central) and packaged terminal heat pumps (air
source and water source); packaged terminal air conditioners.
503.4.5 Other HVAC Equipment: HVAC equipment, other than
that addressed in Sections 503.4.2 through 503.4.4, shall have a
minimum performance at the specified rating conditions not less
than the values shown in Tables 14-1 through 14-3.
503.5 Reserved.
503.6 Balancing: The HVAC system design shall provide a
means for balancing air and water systems. Balancing the system
shall include, but not be limited to, dampers, temperature and
pressure test connections and balancing valves.
503.7 Cooling with Outdoor Air (Economizer Cycle): ((Each
fan system shall be designed to use up to and including 100% of
the fan system capacity for cooling with outdoor air
automatically whenever its use will result in lower usage of new
energy. Activation of economizer cycle shall be controlled by
sensing outdoor air enthalpy or outdoor air dry-bulb temperature
alone or alternate means approved by the building official.
((
EXCEPTIONS:))((
Cooling with outdoor air is not required under any one or more of the following conditions:))
((
))((
1. The fan system capacity is less than 3,500 cfm or total cooling capacity is less than 90,000 Btu/h.))
((
))((
2. The quality of the outdoor air is so poor as to require extensive treatment of the air and approval by the
building official.))
((
))((
3. The need for humidification or dehumidification requires the use of more energy than is conserved by the
outdoor air cooling on an annual basis.))
((
))((
4. The use of outdoor air cooling may affect the operation of other systems so as to increase the overall energy
consumption of the building.))
((
))((
5. When energy recovered from an internal/external zone heat recovery system exceeds the energy conserved by
outdoor air cooling on an annual basis.))
((
))((
6. When all space cooling is accomplished by a circulating liquid which transfers space heat directly or
indirectly to a heat rejection device such as a cooling tower without use of a refrigeration system.))
((
))((
7. When the use of 100% outside air will cause coil frosting, controls may be added to reduce the quantity of
outside air. However, the intent of this exception is to use 100% air in lieu of mechanical cooling when less
energy usage will result and this exception applies only to direct expansion systems when the compressor is
running.))
Systems and equipment that provide mechanical cooling shall
comply with Section 1413 and, as appropriate, Section 1423 or
1433.
503.8 Controls:
503.8.1 Temperature Control: Each system shall be provided
with at least one adjustable thermostat for the regulation of
temperature. Each thermostat shall be capable of being set by
adjustment or selection of sensors as follows:
503.8.1.1: When used to control heating only: Fifty-five
degrees to seventy-five degrees F.
503.8.1.2: When used to control cooling only: Seventy
degrees to eighty-five degrees F.
503.8.1.3: When used to control both heating and cooling,
it shall be capable of being set from fifty-five degrees to
eighty-five degrees F and shall be capable of operating the
system heating and cooling in sequence. The thermostat and/or
control system shall have an adjustable deadband of not less than
ten degrees F.
503.8.2 Humidity Control: If a system is equipped with a
means for adding moisture to maintain specific selected relative
humidities in space or zones, a humidistat shall be provided. Humidistats shall be capable of being set to prevent new energy
from being used to produce space-relative humidity above thirty
percent.
EXCEPTION:
Special uses requiring different relative humidities may be permitted when approved by the building official.
503.8.3 Zoning for Temperature Control:
503.8.3.1 One- and Two-Family Dwellings: At least one
thermostat for regulation of space temperature shall be provided
for each separate system. In addition, a readily accessible
manual or automatic means shall be provided to partially restrict
or shut off the heating and/or cooling input to each zone or
floor.
503.8.3.2 Multifamily Dwellings: For multifamily dwellings,
each individual dwelling unit shall have at least one thermostat
for regulation of space temperature. A readily accessible manual
or automatic means shall be provided to partially restrict or
shut off the heating and/or cooling input to each room. Spaces
other than living units shall meet the requirements of 503.8.3.3.
503.8.3.3 Reserved.
503.8.3.4 Control Setback and Shut-off:
Residential Occupancy Groups. One- and Two-Family and
Multifamily dwellings -- The thermostat required in section
503.8.3.1 or section 503.8.3.2, or an alternate means such as a
switch or clock, shall provide a readily accessible, manual or
automatic means for reducing the energy required for heating and
cooling during the periods of non-use or reduced need, such as,
but not limited to unoccupied periods and sleeping hours. Lowering thermostat set points to reduce energy consumption of
heating systems shall not cause energy to be expended to reach
the reduced setting.
503.8.3.5 Heat Pump Controls: Programmable thermostats are
required for all heat pump systems. The cut-on temperature for
the compression heating shall be higher than the cut-on
temperature for the supplementary heat, and the cut-off
temperature for the compression heating shall be higher than the
cut-off temperature for the supplementary heat. Heat pump
thermostats will be capable of providing at least two
programmable setback periods per day. The automatic setback
thermostat shall have the capability of limiting the use of
supplemental heat during the warm-up period.
503.9 Air Handling Duct System Insulation: Ducts, plenums
and enclosures installed in or on buildings shall be thermally
insulated per Table 5-11.
EXCEPTIONS:
Duct insulation (except where required to prevent condensation) is not required in any of the following cases:
1. When the heat gain or loss of the ducts, without insulation, will not increase the energy requirements of the
building.
2. Within the HVAC equipment.
3. Exhaust air ducts.
4. Supply or return air ducts installed in unvented crawl spaces with insulated walls, basements, or cellars in
one-and two-family dwellings.
503.10 Duct Construction: All duct work shall be
constructed in accordance with Standards RS-15, RS-16, RS-17,
RS-18, RS-19 or RS-20, as applicable, and the Uniform Mechanical
Code.
503.10.1 Leakage Testing: High-pressure and medium-pressure
ducts shall be leak tested in accordance with the applicable
standards in Chapter 7 of this Code with the rate of air leakage
not to exceed the maximum rate specified in that standard.
503.10.2 Seams and Joints: ((When low-pressure supply air
ducts are located outside of the conditioned space, all HVAC
ductwork seams and joints, both longitudinal and transverse,
shall be taped and sealed with products approved by the building
official only. Ductwork joints shall be mechanically fastened
with a minimum of three fasteners per joint for a cylindrical
duct. Use Table 5-11 for duct insulation requirements.)) All
low-pressure supply and return, including enclosed stud bays or
joist cavities/space used to transport air, shall be securely
fastened and sealed with welds, gaskets, mastics (adhesives),
mastic-plus-embedded-fabric systems or tapes installed in
accordance with the manufacturer's installation instructions.
Tapes and mastics used with rigid fibrous glass ducts shall be
listed and labeled in accordance with UL 181A. Tapes and mastics
used with flexible air ducts shall be listed and labeled in
accordance with UL 181B. Duct tape is not permitted as a sealant
on any ducts.
EXCEPTION: | Ducts or building cavities used for air distribution that are located entirely within the conditioned space of the building are exempt from this section. |
503.10.4 Duct Insulation: Ducts shall meet the insulation
requirements specified in Table 5-11.
503.11 ((Piping)) Pipe Insulation: All piping ((installed
to serve buildings (and within))) shall be thermally insulated in
accordance with Table 5-12. ((For service hot water systems see
section 504.7. If water pipes are outside of conditioned space
then the pipe insulation requirement shall be R-3 minimum for
nonrecirculating hot and cold water pipes. For recirculating
service hot and cold water pipes use Table 5-12 for pipe sizes
and temperatures.))
EXCEPTION:
Piping ((
insulation is not required)) installed within unitary HVAC equipment.
Cold water pipes outside the conditioned space shall be insulated
in accordance with the Washington State Plumbing Code (chapter 51-46 WAC).
[Statutory Authority: RCW 19.27A.020, 19.27A.045, and 19.27.020. 98-24-075, 51-11-0503, filed 12/1/98, effective 7/1/99. Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-0503, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-0503, filed 10/18/93, effective 4/1/94. Statutory Authority: Chapter 19.27A RCW. 92-01-140, 51-11-0503, filed 12/19/91, effective 7/1/92. Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, 51-11-0503, filed 12/19/90, effective 7/1/91.]
504.1 Scope: The purpose of this section is to provide
criteria for design and equipment selection that will produce
energy savings when applied to service water heating.
504.2 Water Heaters, Storage Tanks and Boilers:
504.2.1 Performance Efficiency: All Storage water heaters
shall meet the requirements of the 1987 National Appliance Energy
Conservation Act and be so labeled. All electric water heaters
in unheated spaces or on concrete floors shall be placed on an
incompressible, insulated surface with a minimum thermal
resistance of R-10.
For combination space and service water heaters with a
principal function of providing space heat, the Combined Annual
Efficiency (CAE) may be calculated by using ASHRAE Standard
124-1991. Storage water heaters used in combination space heat
and water heat applications shall have either an Energy Factor
(EF) or a Combined Annual Efficiency (CAE) of not less than the
following:
Energy Factor (EF) | Combined Annual Efficiency (CAE) | |
<50 gallon storage | 0.58 | 0.71 |
50 to 70 gallon storage | 0.57 | 0.71 |
>70 gallon storage | 0.55 | 0.70 |
504.2.3 Combination Service Water Heating/Space Heating
Boilers: Service water heating equipment shall not be dependent
on year round operation of space heating boilers.
EXCEPTIONS: | 1. Systems with service/space heating boilers having a standby loss Btu/h less than: | ||
(13.3 pmd+ 400)/n | |||
determined by the fixture count method where: | |||
pmd = probably maximum demand in gallons/hour as determined in accordance with Chapter 37 of Standard RS-11. |
|||
n = fraction of year when outdoor daily mean temperature exceeds 64.9 F. |
|||
The standby loss is to be determined for a test period of twenty-four-hour duration while maintaining a boiler water temperature of ninety degrees F above an ambient of sixty degrees F and a five foot stack on appliance. | |||
2. For systems where the use of a single heating unit will lead to energy savings, such unit shall be utilized. |
504.4 Shutdown: A separate switch shall be provided to
permit turning off the energy supplied to electric service water
heating systems. A separate valve shall be provided to permit
turning off the energy supplied to the main burner(s) of all
other types of service water heater systems.
504.5 Swimming Pools:
504.5.1: All pool heaters shall be equipped with readily
accessible ON/OFF switch to allow shutting off the operation of
the heater without adjusting the thermostat setting. Controls
shall be provided to allow the water temperature to be regulated
from the maximum design temperature down to sixty-five degrees F.
504.5.2 Pool Covers: Heated swimming pools shall be
equipped with a pool cover, approved by the building official.
504.6 Pump Operation: Circulating hot water systems shall
be controlled so that the circulation pump(s) can be conveniently
turned off, automatically or manually, when the hot water system
is not in operation.
504.7 Pipe Insulation: ((For recirculating and
non-recirculating systems,)) Piping shall be thermally insulated
in accordance with section 503.11 ((and Table 5-12)).
504.8 Conservation of Hot Water:
504.8.1 Showers and Lavatories: Showers and lavatories used
for other than safety reasons shall be equipped with flow control
devices or specially manufactured showerheads or aerators to
limit the total water flow rate as set forth in chapter 51-26 WAC, as measured with both hot and cold faucets turned on to
their maximum flow.
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-0504, filed 1/8/98, effective 7/1/98. Statutory Authority: Chapter 19.27A RCW. 92-01-140, 51-11-0504, filed 12/19/91, effective 7/1/92. Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, 51-11-0504, filed 12/19/90, effective 7/1/91.]
505.1 Lighting Controls: Hotel and motel guest rooms and
guest suites shall have a master control device at the main room
entry that controls all permanently installed luminaires and
switched receptacles.
505.2 Lighting Power: Lighting shall comply with the
Prescriptive Lighting Option in Section 1520 or the Lighting
Power Allowance Option in Section 1530.
EXCEPTIONS: | 1. Group R-3 occupancy and the dwelling unit portions of Group R-1 occupancy. |
2. Lighting exempted by Section 1512. |
[Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-0505, filed 10/18/93, effective 4/1/94. Statutory Authority: Chapter 19.27A RCW. 92-01-140, 51-11-0505, filed 12/19/91, effective 7/1/92. Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, 51-11-0505, filed 12/19/90, effective 7/1/91.]
TABLE 5-1
TARGET COMPONENT VALUES FOR GROUP R OCCUPANCY
Electric Resistance | Other Fuels | |||
Climate Zone | Climate Zone | |||
Component | 1 | 2 | 1 | 2 |
Glazing % Floor Area | 15% | 15% | 15% | 15% |
Vertical Glazing U-Factor | U = 0.400 | U = 0.400 | U = 0.650 | U = 0.600 |
Overhead Glazing U-Factor | U = 0. 58 | U = 0. 58 | U = 0. 68 | U = 0.64 |
Doors | U = 0.200 (R-5) |
U = 0.200 (R-5) |
U = 0.400 (R-2.5) |
U = 0.400 (R-2.5) |
Ceilings Attic Single Rafter/ Joist Vaulted |
U = 0.031 (R-38) U = 0.034 (R-30) |
U = 0.031 (R-38) U = 0.034 (R-30) |
U = 0.036 (R-30) U = 0.034 (R-30) |
U = 0.031 (R-38) U = 0.034 (R-30) |
Walls | U = 0.058 (R-19A) |
U = 0.044 (R-19+5A) |
U = 0.0621 (R-19) |
U = 0.0621 (R-19(( |
Floors | U = 0.029 (R-30) |
U = 0.029 (R-30) |
U = 0.041 (R-19) |
U = 0.029 (R-30) |
Slab on Grade Slab R-Value |
F = 0.54 (R-10) |
F = 0.54 (R-10) |
F = 0.54 (R-10) |
F = 0.54 (R-10) |
Below Grade Interior | ||||
Wall R-Value | R-19 | R-19 | R-19 | R-19 |
2' Depth: Walls Slab |
U = 0.043 F = 0.69 |
U = 0.043 F = 0.69 |
U = 0.043 F = 0.69 |
U = 0.043 F = 0.69 |
3.5' Depth: Walls Slab |
U = 0.041 F = 0.64 |
U = 0.041 F = 0.64 |
U = 0.041 F = 0.64 |
U = 0.041 F = 0.64 |
7' Depth: Walls Slab |
U = 0.037 F = 0.57 |
U = 0.037 F = 0.57 |
U = 0.037 F = 0.57 |
U = 0.037 F = 0.57 |
Below Grade Exterior | ||||
Wall R-Value | R-10 | R-12 | R-10 | R-12 |
2' Depth: Walls Slab |
U = 0.070 F = 0.60 |
U = 0.061 F = 0.60 |
U = 0.070 F = 0.60 |
U = 0.061 F = 0.60 |
3.5' Depth: Walls Slab |
U = 0.064 F = 0.57 |
U = 0.057 F = 0.57 |
U = 0.064 F = 0.57 |
U = 0.057 F = 0.57 |
7' Depth: Walls Slab |
U = 0.056 F = 0.42 |
U = 0.050 F = 0.42 |
U = 0.056 F = 0.42 |
U = 0.050 F = 0.42 |
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-0530, filed 1/8/98, effective 7/1/98. Statutory Authority: Chapters 19.27 and 19.27A RCW and 1994 c 226. 95-01-126, 51-11-0530, filed 12/21/94, effective 6/30/95. Statutory Authority: Chapter 19.27A RCW. 92-01-140, 51-11-0530, filed 12/19/91, effective 7/1/92.]
601.1 General: This chapter establishes design criteria in
terms of prescribed requirements for building construction.
The provisions of this chapter are applicable to all Group R
Occupancies. Occupancies shall comply with all the requirements
of Chapter 5 except for the modifications herein specified.
For wood frame assemblies, the building envelope
requirements of this chapter may be met by installing one of the
prescriptive packages in Tables 6-1 to 6-6. Installed components
shall meet the requirements of section 602 ((and 605)). Compliance with nominal R-Values shall be demonstrated for the
thermal resistance of the added insulation in framing cavities
and/or insulated sheathing only and shall not include the thermal
transmittance of other building materials or air films, but shall
permit interruption by occasional framing members. Other than
wood frame assemblies with continuous insulation uninterrupted by
framing shall also be allowed to comply with nominal R-values.
For metal frame assemblies, compliance shall be demonstrated
in accordance with Chapter 4 or Chapter 5 based on the assemblies
in Chapter 10. Compliance with nominal R-values is not allowed,
unless the full nominal R-value of the insulation is installed
either inside or outside of the framing and is uninterrupted by
framing.
[Statutory Authority: Chapters 19.27, 19.27A and 34.05 RCW. 94-05-059, 51-11-0601, filed 2/10/94, effective 4/1/94. Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, 51-11-0601, filed 12/19/90, effective 7/1/91.]
((604.1: All electrical power and lighting systems shall
comply with the requirements of section 505.))
[Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, 51-11-0604, filed 12/19/90, effective 7/1/91.]
[Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-0605, filed 10/18/93, effective 4/1/94. Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, 51-11-0605, filed 12/19/90, effective 7/1/91.]
TABLE 6-1
PRESCRIPTIVE REQUIREMENTS1 **FOR GROUP R OCCUPANCY
CLIMATE ZONE 1 HEATING BY ELECTRIC RESISTANCE
Option | Glazing
Area10: % of Floor |
Glazing U-Factor | Door 9 U- Factor |
Ceiling2 | Vaulted Ceiling3 | Wall Above Grade | Wall int4 Below Grade | Wall ext4 Below Grade | Floor5 | Slab4 on Grade |
|
Vertical | Overhead11 | ||||||||||
I. | 10% | 0.46 | 0. 58 | 0.40 | R-38 | R-30 | R-21 | R-21 | R-10 | R-30 | R-10 |
II. | 12% | 0.43 | 0. 58 | 0.20 | R-38 | R-30 | R-19 | R-19 | R-10 | R-30 | R-10 |
III. | 12% | 0.40 | 0. 58 | 0.40 | R-38 | R-30 | R-21 | R-21 | R-10 | R-30 | R-10 |
IV.* | 15% | 0.40 | 0. 58 | 0.20 | R-38 | R-30 | R-19 | R-19 | R-10 | R-30 | R-10 |
V. | 18% | 0.39 | 0. 58 | 0.20 | R-38 | R-30 | R-21 | R-21 | R-10 | R-30 | R-10 |
VI. | 21% | 0.36 | 0. 58 | 0.20 | R-38 | R-30 | R-21 | R-21 | R-10 | R-30 | R-10 |
VII.7 | 25% | 0.327 | 0. 58 | 0.20 | R-38 | R-30 | R-19 +R-58 |
R-21 | R-10 | R-30 | R-10 |
VIII.7 | 30% | 0.297 | 0. 58 | 0.20 | R-38 | R-30 | R-19 +R-58 |
R-21 | R-10 | R-30 | R-10 |
* | Reference Case |
** | Nominal R-values are for wood frame assemblies only or assemblies built in accordance with Section 601.1. |
1. | Minimum requirements for each option listed. For example, if a proposed design has a glazing ratio to the conditioned floor area of 19%, it shall comply with all of the requirements of the 21% glazing option (or higher). Proposed designs which cannot meet the specific requirements of a listed option above may calculate compliance by Chapters 4 or 5 of this Code. |
2. | Requirement applies to all ceilings except single rafter or joist vaulted ceilings. 'Adv' denotes Advanced Framed Ceiling. |
3. | Requirement applicable only to single rafter or joist vaulted ceilings. |
4. | Below grade walls shall be insulated either on the exterior to a minimum level of R-10, or on the interior to the same level as walls above grade. Exterior insulation installed on below grade walls shall be a water resistant material, manufactured for its intended use, and installed according to the manufacturer's specifications. See Section 602.2. |
5. | Floors over crawl spaces or exposed to ambient air conditions. |
6. | Required slab perimeter insulation shall be a water resistant material, manufactured for its intended use, and installed according to manufacturer's specifications. See Section 602.4. |
7. | The following options shall be applicable to buildings less than three stories: 0.35 maximum for glazing areas of 25% or less; 0.32 maximum for glazing areas of 30% or less. |
8. | This wall insulation requirement denotes R-19 wall cavity insulation plus R-5 foam sheathing. |
9. | Doors, including all fire doors, shall be assigned default U-factors from Table 10-6C (( |
10. | Where a maximum glazing area is listed, the total glazing area (combined vertical plus overhead) as a percent of gross conditioned floor area shall be less than or equal to that value. Overhead glazing with U-factor of U=0.040 or less is not included in glazing area limitations. |
11. | Overhead glazing shall have U-factors determined in accordance with NFRC 100 or as specified in Section 502.1.5. |
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-0625, filed 1/8/98, effective 7/1/98. Statutory Authority: Chapters 19.27 and 19.27A RCW and 1994 c 226. 95-01-126, 51-11-0625, filed 12/21/94, effective 6/30/95. Statutory Authority: Chapters 19.27, 19.27A and 34.05 RCW. 94-05-059, 51-11-0625, filed 2/10/94, effective 4/1/94. Statutory Authority: Chapter 19.27A RCW. 92-01-140, 51-11-0625, filed 12/19/91, effective 7/1/92.]
TABLE 6-2
PRESCRIPTIVE REQUIREMENTS1 **FOR GROUP R OCCUPANCY
CLIMATE ZONE 1 HEATING BY OTHER FUELS
Option | HVAC9 Equip. Effic. |
Glazing Area11: % of Floor |
Glazing U-Factor | Door10 U-Factor |
Ceiling2 | Vaulted Ceiling3 |
Wall Above Grade |
Wall int4 Below Grade |
Wall ext4 Below Grade |
Floor5 | Slab6 on Grade |
|
Vertical | Overhead12 | |||||||||||
I. | Med. | 10% | 0.70 | 0.68 | 0.40 | R-30 | R-30 | R-15 | R-15 | R-10 | R-19 | R-10 |
II. | Med. | 12% | 0.65 | 0.68 | 0.40 | R-30 | R-30 | R-15 | R-15 | R-10 | R-19 | R-10 |
III. | High | 21% | 0.75 | 0.68 | 0.40 | R-30 | R-30 | R-19 | R-19 | R-10 | R-19 | R-10 |
IV.* | Med. | 21% | 0.65 | 0.68 | 0.40 | R-30 | R-30 | R-19 | R-19 | R-10 | R-19 | R-10 |
V. | Low | 21% | 0.60 | 0.68 | 0.40 | R-30 | R-30 | R-19 | R-19 | R-10 | R-19 | R-10)) |
VI.7 | Med. | 25% | 0.457 | 0.68 | 0.40 | R-38 | R-30 | R-19 | R-19 | R-10 | R-25 | R-10 |
VII.7 | Med. | 30% | 0.407 | 0.68 | 0.40 | R-30 | R-30 | R-19 | R-19 | R-10 | R-25 | R-10 |
VIII. | Med. | unlimited | 0.25 | 0.40 | 0.40 | R-30 | R-30 | R-19 | R-19 | R-10 | R-25 | R-10 |
* | Reference Case |
** | Nominal R-values are for wood frame assemblies only or assemblies built in accordance with Section 601.1. |
1 | Minium requirements for each option listed. For example, if a proposed design has a glazing ratio to the conditioned floor
area of 19%, it shall comply with all of the requirements of the 21% glazing option (or higher). Proposed designs which
cannot meet the specific requirements of a listed option above may calculate compliance by Chapters 4 or 5 of this Code. |
2 | Requirement applies to all ceilings except single rafter or joist vaulted ceilings. 'Adv' denotes Advanced Framed Ceiling. |
3 | Requirement applicable only to single rafter or joist vaulted ceilings. |
4 | Below grade walls shall be insulated either on the exterior to a minimum level of R-10, or on the interior to the same level
as walls above grade. Exterior insulation installed on below grade walls shall be a water resistant material, manufactured
for its intended use, and installed according to the manufacturer's specifications. See Section 602.2. |
5 | Floors over crawl spaces or exposed to ambient air conditions. |
6 | Required slab perimeter insulation shall be a water resistant material, manufactured for its intended use, and installed
according to manufacturer's specifications. See Section 602.4. |
7 | The following options shall be applicable to buildings less than three stories: 0.50 maximum for glazing areas of 25% or
less; 0.45 maximum for glazing areas of 30% or less. |
8 | (( |
9 | Minimum HVAC Equipment efficiency requirement. 'Low' denotes an AFUE of 0.74. 'Med.' denotes an AFUE of 0.78.
'High' denotes an AFUE of 0.88. Minimum HVAC Equipment efficiency requirement for heat pumps. 'Low' denotes an
HSPF of 6.35. 'Med' denotes an HSPF of 6.8. 'High' an HSPF of 7.7. Water and ground source heat pumps shall be
considered as medium efficiency and have a minimum COP as required in Table 5-7. |
10 | Doors, including all fire doors, shall be assigned default U-factors from Table 10-6C (( |
11. | Where a maximum glazing area is listed, the total glazing area (combined vertical plus overhead) as a percent of gross
conditioned floor area shall be less than or equal to that value. Overhead glazing with U-factor of U= 0.040 or less is not
included in glazing area limitations. |
12. | Overhead glazing shall have U-factors determined in accordance with NFRC 100 or as specified in Section 502.1.5. |
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-0626, filed 1/8/98, effective 7/1/98. Statutory Authority: Chapters 19.27 and 19.27A RCW and 1994 c 226. 95-01-126, 51-11-0626, filed 12/21/94, effective 6/30/95. Statutory Authority: Chapters 19.27, 19.27A and 34.05 RCW. 94-05-059, 51-11-0626, filed 2/10/94, effective 4/1/94. Statutory Authority: Chapter 19.27A RCW. 92-01-140, 51-11-0626, filed 12/19/91, effective 7/1/92.]
TABLE 6-3
PRESCRIPTIVE REQUIREMENTS1 **FOR GROUP R OCCUPANCY
CLIMATE ZONE 2 HEATING BY ELECTRIC RESISTANCE
Option | Glazing
Area11: % of Floor |
Glazing U-Factor | Door10 U- Factor |
Ceiling2 | Vaulted Ceiling3 |
Wall Above Grade |
Wall int4 Below Grade |
Wall ext4 Below Grade |
Floor5 | Slab6 on Grade |
|
Vertical | Over- head12 |
||||||||||
I. | 10% | 0.38 | 0.58 | 0.20 | R-38 | R-30 | R-21 | R-21 | R-12 | R-30 | R-10 |
II. | 12% | 0.40 | 0.58 | 0.20 | R-38 | R-30 | R-19+R-58 | R-21 | R-12 | R-25 | R-10 |
III.* | 15% | 0.40 | 0.58 | 0.20 | R-38 | R-30 | R-19+R-58 | R-21 | R-12 | R-30 | R-10 |
IV. | 18% | 0.38 | 0.58 | 0.20 | R-38 | R-30 | R-19+R-58 | R-21 | R-12 | R-30 | R-10 |
V. | 21% | 0.35 | 0.58 | 0.20 | R-38Adv | R-38 | R-19+R-58 | R-21 | R-12 | R-30 | R-10 |
VI.7 | 25% | 0.307 | 0.58 | 0.20 | R-49Adv | R-38 | R-19+R-58 | R-21 | R-12 | R-30 | R-10 |
VII.7 | 30% | 0.287 | 0.58 | 0.20 | R-60Adv | R-38 | R-21+R-7.59 | R-21 | R-12 | R-30 | R-10 |
* | Reference Case |
** | Nominal R-values are for wood frame assemblies only or assemblies built in accordance with Section 601.1. |
1 | Minimum requirements for each option listed. For example, if a proposed design has a glazing ratio to the conditioned floor area of 19%, it shall comply with all of the requirements of the 21% glazing option (or higher). Proposed designs which cannot meet the specific requirements of a listed option above may calculate compliance by Chapters 4 or 5 of this Code. |
2 | Requirement applies to all ceilings except single rafter or joist vaulted ceilings. 'Adv' denotes Advanced Framed Ceiling. |
3 | Requirement applicable only to single rafter or joist vaulted ceilings. |
4 | Below grade walls shall be insulated either on the exterior to a minimum level of R-12, or on the interior to the same level as walls above grade. Exterior insulation installed on below grade walls shall be a water resistant material, manufactured for its intended use, and installed according to the manufacturer's specifications. See Section 602.2. |
5 | Floors over crawl spaces or exposed to ambient air conditions. |
6 | Required slab perimeter insulation shall be a water resistant material, manufactured for its intended use, and installed according to manufacturer's specifications. See Section 602.4. |
7 | The following options shall be applicable to buildings less than three stories: 0.33 maximum for glazing areas of 25% or less; 0.31 maximum for glazing areas of 30% or less. |
8 | This wall insulation requirement denotes R-19 wall cavity insulation plus R-5 foam sheathing. |
9 | This wall insulation requirement denotes R-21 wall cavity insulation plus R-7.5 foam sheathing. |
10 | Doors, including all fire doors, shall be assigned default U-factors from Table 10-6C (( |
11. | Where a maximum glazing area is listed, the total glazing area (combined vertical plus overhead) as a percent of gross conditioned floor area shall be less than or equal to that value. Overhead glazing with U-factor of U=0.040 or less is not included in glazing area limitations. |
12. | Overhead glazing shall have U-factors determined in accordance with NFRC 100 or as specified in Section 502.1.5. |
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-0627, filed 1/8/98, effective 7/1/98. Statutory Authority: Chapters 19.27 and 19.27A RCW and 1994 c 226. 95-01-126, 51-11-0627, filed 12/21/94, effective 6/30/95. Statutory Authority: Chapters 19.27, 19.27A and 34.05 RCW. 94-05-059, 51-11-0627, filed 2/10/94, effective 4/1/94. Statutory Authority: Chapter 19.27A RCW. 92-01-140, 51-11-0627, filed 12/19/91, effective 7/1/92.]
Option | HVAC9 Equip. Effic. | Glazing
Area11: % of Floor |
Glazing U-Factor | Door10 U-Factor | Ceiling2 | Vaulted Ceiling3 | Wall Above Grade | Wall int4 Below Grade |
Wall ext4 Below Grade |
Floor5 | Slab6 on Grade |
|
Vertical | Overhead12 | |||||||||||
I. | Med. | 10% | 0.70 | 0.64 | 0.40 | R-38 | R-30 | R-19 | R-19 | R-12 | R-25 | R-10 |
II. | Med. | 12% | 0.65 | 0.64 | 0.40 | R-38 | R-30 | R-19 | R-19 | R-12 | R-25 | R-10 |
III. | High | 17% | 0.65 | 0.64 | 0.40 | R-38 | R-30 | R-19 | R-19 | R-12 | R-25 | R-10 |
IV.* | Med. | 17% | 0.60 | 0.64 | 0.40 | R-38 | R-30 | R-19 | R-19 | R-12 | R-30 | R-10 |
V. | Low | 17% | 0.50 | 0.64 | 0.40 | R-38 | R-30 | R-19 | R-19 | R-12 | R-30 | R-10 |
VI. | Med. | 21% | 0.50 | 0.64 | 0.40 | R-38 | R-30 | R-19 | R-19 | R-12 | R-30 | R-10 |
VII.7 | Med. | 25% | 0.407 | 0.64 | 0.40 | R-38 | R-30 | R-19 | R-19 | R-12 | R-30 | R-10 |
VIII.7 | Med. | 30% | 0.407 | 0.64 | 0.40 | R-38 | R-30 | R-19 | R-19 | R-12 | R-30 | R-10 |
IX. | Med. | unlimited | 0.25 | 0.40 | 0.40 | R-38 | R-30 | R-19 | R-19 | R-12 | R-30 | R-10 |
** Nominal R-values are for wood frame assemblies only or assemblies built in accordance with Section 601.1.
1 | Minimum requirements for each option listed. For example, if a proposed design has a glazing ratio to the conditioned floor area of 19%, it shall comply with all of the requirements of the 21% glazing option (or higher). Proposed designs which cannot meet the specific requirements of a listed option above may calculate compliance by Chapters 4 or 5 of this Code. |
2 | Requirement applies to all ceilings except single rafter or joist vaulted ceilings. 'Adv' denotes Advanced Framed Ceiling. |
3 | Requirement applicable only to single rafter or joist vaulted ceilings. |
4 | Below grade walls shall be insulated either on the exterior to a minimum level of R-12, or on the interior to the same level as walls above grade. Exterior insulation installed on below grade walls shall be a water resistant material, manufactured for its intended use, and installed according to the manufacturer's specifications. See Section 602.2. |
5 | Floors over crawl spaces or exposed to ambient air conditions. |
6 | Required slab perimeter insulation shall be a water resistant material, manufactured for its intended use, and installed according to manufacturer's specifications. See Section 602.4. |
7 | The following options shall be applicable to buildings less than three stories: 0.45 maximum for glazing areas of 25% or less; 0.40 maximum for glazing areas of 30% or less. |
8 | (( |
9 | Minimum HVAC Equipment efficiency requirement. 'Low' denotes an AFUE of 0.74. 'Med.' denotes an AFUE of 0.78. 'High' denotes an AFUE of 0.88. Minimum HVAC Equipment efficiency requirement for heat pumps. 'Low' denotes an HSPF of 6.35. 'Med' denotes an HSPF of 6.8. 'High' an HSPF of 7.7. Water and ground source heat pumps shall be considered as medium efficiency and have a minimum COP as required in Table 5-7. |
10 | Doors, including all fire doors, shall be assigned default U-factors from Table 10-6C (( |
11. | Where a maximum glazing area is listed, the total glazing area (combined vertical plus overhead) as a percent of gross conditioned floor area shall be less than or equal to that value. Overhead glazing with U-factor of U=0.040 or less is not included in glazing area limitations. |
12. | Overhead glazing shall have U-factors determined in accordance with NFRC 100 or as specified in Section 502.1.5. |
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-0628, filed 1/8/98, effective 7/1/98. Statutory Authority: Chapters 19.27 and 19.27A RCW and 1994 c 226. 95-01-126, 51-11-0628, filed 12/21/94, effective 6/30/95. Statutory Authority: Chapters 19.27, 19.27A and 34.05 RCW. 94-05-059, 51-11-0628, filed 2/10/94, effective 4/1/94. Statutory Authority: Chapter 19.27A RCW. 92-01-140, 51-11-0628, filed 12/19/91, effective 7/1/92.]
TABLE 6-6
LOG HOMES PRESCRIPTIVE REQUIREMENTS1**
HEATING BY OTHER FUELS
Option | HVAC9
Equip. Effic. |
Glazing
Area12: % of Floor |
Glazing U-Factor | Door 10 U- Factor |
Ceiling2 | Vaulted Ceiling3 |
Wall11 Above Grade |
Wall int4 Below Grade |
Wall ext4 Below Grade |
Floor5 | Slab6 on Grade |
|
Vert- ical |
Over- head13 |
|||||||||||
Climate Zone 1 | ||||||||||||
I. | Med. | 10% | 0.70 | 0.68 | 0.40 | R-30 | R-30 | R-15 | R-15 | R-10 | R-19 | R-10 |
II. | Med. | 12% | 0.65 | 0.68 | 0.40 | R-30 | R-30 | R-15 | R-15 | R-10 | R-19 | R-10 |
III. | High | 21% | 0.75 | 0.68 | 0.40 | R-30 | R-30 | R-19 | R-19 | R-10 | R-19 | R-10 |
IV.* | Med. | 21% | 0.65 | 0.68 | 0.40 | R-30 | R-30 | R-19 | R-19 | R-10 | R-19 | R-10 |
V. | Low | 21% | 0.60 | 0.68 | 0.40 | R-30 | R-30 | R-19 | R-19 | R-10 | R-19 | R-10 |
VI.7 | Med. | 25% | 0.457 | 0.68 | 0.40 | R-38 | R-30 | R-19 | R-19 | R-10 | R-25 | R-10 |
VII.7 | Med. | 30% | 0.407 | 0.68 | 0.40 | R-30 | R-30 | R-19 | R-19 | R-10 | R-25 | R-10 |
VIII. | Med. | unlimited | 0.25 | 0.40 | 0.40 | R-30 | R-30 | R-19 | R-19 | R-10 | R-25 | R-10 |
Climate Zone 2 | ||||||||||||
I. | Med. | 10% | 0.70 | 0.64 | 0.40 | R-38 | R-30 | R-19 | R-19 | R-12 | R-25 | R-10 |
II. | Med. | 12% | 0.65 | 0.64 | 0.40 | R-38 | R-30 | R-19 | R-19 | R-12 | R-25 | R-10 |
III. | High | 17% | 0.65 | 0.64 | 0.40 | R-38 | R-30 | R-19 | R-19 | R-12 | R-25 | R-10 |
IV.* | Med. | 17% | 0.60 | 0.64 | 0.40 | R-38 | R-30 | R-19 | R-19 | R-12 | R-30 | R-10 |
V. | Low | 17% | 0.50 | 0.64 | 0.40 | R-38 | R-30 | R-19 | R-19 | R-12 | R-30 | R-10 |
VI. | Med. | 21% | 0.50 | 0.64 | 0.40 | R-38 | R-30 | R-19 | R-19 | R-12 | R-30 | R-10 |
VII. | Med. | 25% | 0.408 | 0.64 | 0.40 | R-38 | R-30 | R-19 | R-19 | R-12 | R-30 | R-10 |
VIII. | Med. | 30% | 0.408 | 0.64 | 0.40 | R-38 | R-30 | R-19 | R-19 | R-12 | R-30 | R-10 |
IX. | Med. | unlimited | 0.25 | 0.40 | 0.40 | R-38 | R-30 | R-19 | R-19 | R-12 | R-30 | R-10 |
* | Reference Case |
** | Nominal R-values are for wood frame assemblies only or assemblies built in accordance with Section 601.1. |
1 | Minimum requirements for each option listed. For example, if a proposed design has a glazing ratio to the conditioned floor area of 19%, it shall comply with all of the requirements of the 21% glazing option (or higher). Proposed designs which cannot meet the specific requirements of a listed option above may calculate compliance by Chapters 4 or 5 of this Code. |
2 | Requirement applies to all ceilings except single rafter or joist vaulted ceilings. 'Adv' denotes Advanced Framed Ceiling. |
3 | Requirement applicable only to single rafter or joist vaulted ceilings. |
4 | Below grade walls shall be insulated either on the exterior to a minimum level of R-10, or on the interior to the same level as walls above grade. Exterior insulation installed on below grade walls shall be a water resistant material, manufactured for its intended use, and installed according to the manufacturer's specifications. See Section 602.2. |
5 | Floors over crawl spaces or exposed to ambient air conditions. |
6 | Required slab perimeter insulation shall be a water resistant material, manufactured for its intended use, and installed according to manufacturer's specifications. See Section 602.4. |
7 | The following options shall be applicable to buildings less than three stories: 0.50 maximum for glazing areas of 25% or less; 0.45 maximum for glazing areas of 30% or less. |
8 | The following options shall be applicable to buildings less than three stories: 0.45 maximum for glazing areas of 25% or less; 0.40 maximum for glazing areas of 30% or less. |
9 | Minimum HVAC Equipment efficiency requirement. 'Low' denotes an AFUE of 0.74. 'Med.' denotes an AFUE of 0.78. 'High' denotes an AFUE of 0.88. Minimum HVAC Equipment efficiency requirement for heat pumps. 'Low' denotes an HSPF of 6.35. 'Med' denotes an HSPF of 6.8. 'High' an HSPF of 7.7. Water and ground source heat pumps shall be considered as medium efficiency and have a minimum COP as required in Table 5-7. |
10 | Doors, including all fire doors, shall be assigned default U-factors from Table 10-6C (( |
11 | Log and solid timber walls with a minimum average thickness of 3.5" are exempt from this insulation requirement. |
12. | Where a maximum glazing area is listed, the total glazing area (combined vertical plus overhead) as a percent of gross conditioned floor area shall be less than or equal to that value. Overhead glazing with U-factor of U=0.040 or less is not included in glazing area limitations. |
13. | Overhead glazing shall have U-factors determined in accordance with NFRC 100 or as specified in Section 502.1.5. |
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-0630, filed 1/8/98, effective 7/1/98. Statutory Authority: Chapters 19.27 and 19.27A RCW and 1994 c 226. 95-01-126, 51-11-0630, filed 12/21/94, effective 6/30/95. Statutory Authority: Chapters 19.27, 19.27A and 34.05 RCW. 94-05-059, 51-11-0630, filed 2/10/94, effective 4/1/94. Statutory Authority: Chapter 19.27A RCW. 92-01-140, 51-11-0630, filed 12/19/91, effective 7/1/92.]
(( STANDARD NO. |
TITLE AND SOURCE |
RS-1 | (( |
RS-2 | through RS-3 (Reserved.) |
RS-4 | ASHRAE Standard 55-92 Thermal Environmental Conditions for Human Occupancy. |
RS-5 | through RS-8 (Reserved.) |
RS-9 | ASHRAE/IES Standard 90.1-1989, Efficient Design of New Buildings Except New Low-Rise Residential Buildings. |
RS-10 | Standard for Packaged Terminal Air Conditioners and Heat Pumps, ARI Standard 310/380-93. |
RS-11 | (( |
RS-12 | through RS-14 (Reserved.) |
RS-15 | 1996 ASHRAE System and Equipment Handbook. |
RS-16 | SMACNA, Installation Standards for Residential Heating and Air Conditioning Systems, 6th Edition, 1988. |
RS-17 | (( |
RS-18 | (( |
RS-19 | SMACNA, Fibrous Glass Duct Construction Standards, 6th Edition, 1992. |
RS-20 | (( |
RS-21 | Same as Standard RS-10. |
RS-22 | through RS-24 (Reserved.) |
RS-25 | (( |
RS-26 | Super Good Cents Technical Reference (Builder's Field Guide). |
RS-27 | 1997 ASHRAE Fundamentals Handbook. |
RS-28 | (Reserved.) |
RS-29 | Nonresidential Building Design by Systems Analysis. |
RS-30 | Title 10, Code of Federal Regulations (CFR), Part 430 (March 14, 1988). |
RS-31 | National Fenestration Rating Council (NFRC) Standard 100-1997. |
Phone (212) 642-4900 Fax (212) 398-0023, Internet www.ansi.org
ARI refers to the Air Conditioning and Refrigeration
Institute, 4301 N. Fairfax Dr., Suite 425, Arlington, VA 22203
Phone (703) 524-8800 Fax (703) 528-3816, Internet www.ari.org
ASHRAE refers to the American Society of Heating,
Refrigerating, and Air Conditioning Engineers, Inc., 1791 Tullie
Circle, N.E., Atlanta, GA 30329
Phone (404) 636-8400 Fax (404) 321-5478, Internet www.ashrae.org
ASTM refers to the American Society for Testing and
Materials, 100 Barr Harbor Drive, West Conshohocken, PA
19428-2959
Phone (610) 832-9585 Fax (610) 832-9555, Internet www.astm.org
CTI refers to the Cooling Tower Institute, 530 Wells Fargo
Drive, Suite 218, Houston, TX 77090
Phone (281) 583-4087 Fax (281) 537-1721, Internet www.cti.org
IES refers to the Illuminating Engineering Society, 120 Wall
Street, Floor 17, New York, NY 10005-4001
Phone (212) 248-5000 Fax (212) 248-5017, Internet ((www.ies.org))
www.iesna.org
NFRC refers to the National Fenestration Rating Council,
Incorporated, 1300 Spring Street, Suite ((120)) 500, Silver
Spring, Maryland 20910
Phone (301) 589-NFRC Fax (301) 588-0854, Internet www.nfrc.org
SMACNA refers to the Sheet Metal and Air Conditioning
Contractors National Association, Inc., 4201 Lafayette Center
Drive, P.O. Box 221230, Chantilly, VA 20153-1230
Phone (703) 803-2980 Fax (703) 803-3732, Internet www.smacna.org
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-0701, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, 51-11-0701, filed 12/19/90, effective 7/1/91.]
1001.1 Scope: The following defaults shall apply to
Chapters 1 through 20. This chapter includes tables of seasonal
average heat-loss coefficients for specified nominal insulation. The heat-loss coefficients may also be used for heating system
sizing.
1001.2 Description: These coefficients were developed
primarily from data and procedures from Standard ((RS-1)) RS-27,
and taken specifically from Standard RS-26, listed in Chapter 7.
Coefficients not contained in this chapter may be computed
using the procedures listed in these references if the
assumptions in the following sections and Standard RS-26, listed
in Chapter 7, are used, along with data from the sources
referenced above.
1001.3 Air Films: Default R-values used for air films shall
be as follows:
R-Value | Condition |
0.17 | All exterior surfaces |
0.61 | Interior horizontal surfaces, heat flow up |
0.92 | Interior horizontal surfaces, heat flow down |
0.68 | Interior vertical surfaces |
TABLE 10-A
R-Value of Fiberglass Batts Compressed within Various Depth Cavities
Insulation R-Value at Standard Thickness | ||||||||||||
R-Value | 38 | 30 | 22 | 21 | 19 | 15 | 13 | 11 | 8 | 5 | 3 | |
Standard Thickness | 12" | 9-1/2" | 6-3/4" | 5-1/2" | 6-1/4" | 3-1/2" | 3-5/8" | 3-1/2" | 2-1/2" | 1-1/2" | 3/4" | |
Nominal Lumber Sizes, Inches | Actual Depth of Cavity, Inches | Insulation R-Values when Installed in a Confined Cavity | ||||||||||
2 x 12 | 11-1/4 | 37 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- |
2 x 10 | 9-1/4 | 32 | 30 | -- | -- | -- | -- | -- | -- | -- | -- | -- |
2 x 8 | 7-1/4 | 27 | 26 | -- | -- | -- | -- | -- | -- | -- | -- | -- |
2 x 6 | 5-1/2 | -- | 21 | 20 | 21 | 18 | -- | -- | -- | -- | -- | -- |
2 x 4 | 3-1/2 | -- | -- | 14 | -- | 13 | 15 | 13 | 11 | -- | -- | -- |
2 x 3 | 2-1/2 | -- | -- | -- | -- | -- | -- | 9.8 | -- | -- | -- | -- |
2 x 2 | 1-1/2 | -- | -- | -- | -- | -- | -- | 6.3 | 6.0 | 5.7 | 5.0 | -- |
2 x 1 | 3/4 | -- | -- | -- | -- | -- | -- | -- | -- | -- | 3.2 | 3.0 |
[Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, 51-11-1001, filed 12/19/90, effective 7/1/91.]
1002.1 General: Table 10-1 lists heat-loss coefficients for
below-grade walls and floors.
Coefficients for below-grade walls are given as U-factors
(Btu/hrft2F ((per square foot)) of wall area). Coefficients
for below-grade slabs are listed as F-factors (Btu/hrftF per
lineal foot of slab perimeter).
Below-grade wall U-factors are only valid when used with the
accompanying below-grade slab F-factors, and vice versa.
1002.2 Component Description: All below-grade walls are
assumed to be eight-inch concrete. The wall is assumed to extend
from the slab upward to the top of the mud sill for the distance
specified in Table 10-1, with six inches of concrete wall
extending above grade.
Interior insulation is assumed to be fiberglass batts placed
in the cavity formed by 2x4 framing on twenty-four inch centers
with one-half inch of gypsum board as the interior finish
material. Exterior insulation is assumed to be applied directly
to the exterior of the below-grade wall from the top of the wall
to the footing. The exterior case does not assume any interior
framing or sheetrock.
In all cases, the entire wall surface is assumed to be
insulated to the indicated nominal level with the appropriate
framing and insulation application. Coefficients are listed for
wall depths of two, three and one-half, and seven feet below
grade. Basements shallower than two feet should use on-grade
slab coefficients.
Heat-loss calculations for wall areas above grade should use
above-grade wall U-factors, beginning at the mudsill.
1002.3 Insulation Description: Coefficients are listed for
the following four configurations:
1. Uninsulated: No insulation or interior finish.
2. Interior insulation: Interior 2x4 insulated wall without
a thermal break between concrete wall and slab.
3. Interior insulation w/thermal break: Interior 2x4
insulated wall with R-5 rigid board providing a thermal break
between the concrete wall and the slab.
4. Exterior insulation: Insulation applied directly to the
exterior surface of the concrete wall.
Below Grade Wall U-factor | Below Grade Slab F-factor | |
2-Foot Depth Below Grade | ||
Uninsulated | 0.350 | 0.59 |
R-11 Interior | 0.066 | 0.68 |
R-11 Interior w/tb | 0.070 | 0.60 |
R-19 Interior | 0.043 | 0.69 |
R-19 Interior w/tb | 0.045 | 0.61 |
R-10 Exterior | 0.070 | 0.60 |
R-12 Exterior | 0.061 | 0.60 |
3.5-Foot Depth Below Grade | ||
Uninsulated | 0.278 | 0.53 |
R-11 Interior | 0.062 | 0.63 |
R-11 Interior w/tb | 0.064 | 0.57 |
R-19 Interior | 0.041 | 0.64 |
R-19 Interior w/tb | 0.042 | 0.57 |
R-10 Exterior | 0.064 | 0.57 |
R-12 Exterior | 0.057 | 0.57 |
7-Foot Depth Below Grade | ||
Uninsulated | 0.193 | 0.46 |
R-11 Interior | 0.054 | 0.56 |
R-11 Interior w/tb | 0.056 | 0.42 |
R-19 Interior | 0.037 | 0.57 |
R-19 Interior w/tb | 0.038 | 0.43 |
R-10 Exterior | 0.056 | 0.42 |
R-12 Exterior | 0.050 | 0.42 |
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-1002, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, 51-11-1002, filed 12/19/90, effective 7/1/91.]
1003.1 General: Table 10-2 lists heat-loss coefficients for
heated on-grade slab floors, in units of Btu/hF((hr)) per
lineal foot of perimeter.
1003.2 Component Description: All on-grade slab floors are
assumed to be six-inch concrete poured directly onto the earth. The bottom of the slab is assumed to be at grade line. Monolithic and floating slabs are not differentiated.
Soil is assumed to have a conductivity of 0.75
Btu/hrFft2. Slabs two-feet or more below grade should use
basement coefficients.
1003.3 Insulation Description: Coefficients are provided
for the following three configurations:
Two-Foot (or four-foot) vertical: Insulation is applied
directly to the slab exterior, extending downward from the top of
the slab to a depth of two-feet (or four-feet) below grade.
Two-Foot (or four-foot) horizontal: Insulation is applied
directly to the underside of the slab, and run horizontally from
the perimeter inward for two-feet or four-feet. The slab edge is
exposed in this configuration.
Note: | A horizontal installation with a thermal break of at least R-5 at the slab edge should use the vertical-case F-factors. |
TABLE 10-2
DEFAULT F-FACTORS FOR ON-GRADE SLABS
Insulation type | R-0 | R-5 | R-10 | R-15 |
Unheated Slab | ||||
Uninsulated slab | 0.73 | |||
2-ft Horizontal (No thermal break) | 0.70 | 0.70 | 0.69 | |
4-ft Horizontal (No thermal break) | 0.67 | 0.64 | 0.63 | |
2-ft Vertical | 0.58 | 0.54 | 0.52 | |
4-ft Vertical | 0.54 | 0.48 | 0.45 | |
Fully insulated slab | 0.36 | |||
Heated Slab | ||||
Uninsulated slab | 0.84 | |||
Fully insulated slab | 0.74 | 0.55 | 0.44 | |
R-5 Center (With perimeter insulation) | 0.66 | 0.62 | ||
R-10 Center (With perimeter insulation) | 0.51 | |||
3-ft Vertical | 0.78 |
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-1003, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, 51-11-1003, filed 12/19/90, effective 7/1/91.]
1004.1 General: Tables 10-3 ((and)), 10-4 and 10-4a list
heat-loss coefficients for floors over ((crawlspaces))
unconditioned spaces in units of Btu/hft2F((hr per square
foot of floor)).
They are derived from procedures listed in ((RS-1)) RS-27,
listed in Chapter 7, assuming an average outdoor temperature of
45 F, an average indoor temperature of 65 F, and a crawlspace
area of ((one thousand three hundred fifty)) 1350 ft2 and ((one
hundred fifty)) 100 ft of perimeter. The crawlspace is assumed
to be 2.5((-))feet high, with ((twenty-four)) 24 inches below
grade and ((six)) 6 inches above grade.
1004.2 Crawlspace Description: Four ((crawlspace))
configurations are considered: Vented crawlspace, unvented
crawlspace, ((enclosed and)) heated plenum crawlspace and exposed
floor.
Vented crawlspaces: Assumed to have ((three)) 3.0
air-changes per hour, with at least ((one)) 1.0 ft2 of net-free
ventilation in the foundation for every three hundred ft2 of
crawlspace floor area. The crawlspace is not actively heated.
Floors over unheated areas, such as garages, may only use
those values which have R-0 perimeter insulation.
Unvented crawlspaces: Assumed to have 1.5 air changes per
hour, with less than ((one)) 1.0 ft2 of net-free ventilation in
the foundation for every three hundred ft2 of crawlspace floor
area. The crawlspace is not actively heated. Floors over
unheated basements may only use those values which have R-0
perimeter insulation.
Heated-plenum crawlspaces: Assumed to have 0.25 air-changes
per hour, with no foundation vents. Heated supply air from
central furnace is blown into a crawlspace and allowed to enter
the living space unducted via holes cut into the floor.
Enclosed floors: Assumes no buffer space, and a covering of
one-half inch of T1-11 on the exterior of the cavity exposed to
the outside air or rigid insulation below a concrete floor, such
as over parking garages.
1004.3 Construction Description: Floors are assumed to be
either joisted floors framed on sixteen inch centers, or post and
beam on four by eight foot squares. Insulation is assumed to be
installed under the subflooring between the joists or beams with
no space between the insulation and the subfloor. Insulation is
assumed to be uncompressed. Exposed floors also include concrete
with continuous rigid insulation assumed.
Perimeter insulation is assumed to extend from the top of
the rim joist to the crawlspace floor and then inward along the
ground (on top of the ground cover) for at least twenty-four
inches.
Floor coverings are assumed to be light carpet with rubber
pad.
Nominal R-value |
U-factor |
|||
Floor | Perimeter | Post & Beam | Joists | |
0 | 0 11 19 30 |
0.112 0.100 0.098 0.093 |
0.134 0.116 0.114 0.107 |
|
11 | 0 11 |
0.052 0.048 |
0.056 0.052 |
|
19 | 0 11 |
0.038 0.036 |
0.041 0.038 |
|
22 | 0 11 |
0.034 0.033 |
0.037 0.035 |
|
25 | 0 11 |
0.032 0.031 |
0.034 0.033 |
|
30 | 0 11 |
0.028 0.027 |
0.029 0.028 |
|
38 | 0 11 |
0.024 0.024 |
0.025 0.024 |
Nominal R-value Perimeter |
U-factor |
11 | 0.085 |
19 | 0.075 |
30 | 0.069 |
TABLE 10-4A
EXPOSED FLOOR
Nominal R-value |
U-factor | ||
Concrete | Wood Joist | Metal Joist | |
R-11 | 0.077 | 0.088 | 0.14 |
R-15 | 0.059 | 0.076 | 0.12 |
R-19 | 0.048 | 0.062 | 0.11 |
R-21 | 0.043 | 0.057 | 0.11 |
R-25 | 0.037 | 0.051 | 0.10 |
R-30 | 0.031 | 0.040 | 0.09 |
R-38 | 0.025 | 0.034 | 0.08 |
Note: | Crawlspaces used as heated plenums have approximately 30% higher heat-loss rate than unvented crawlspaces with the same assumed ACH. Default U-values in Table 10-4 reflect this higher rate of heat loss. |
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-1004, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, 51-11-1004, filed 12/19/90, effective 7/1/91.]
Section 1005.1 General: Table 10-5, 10-5A and 10-5B
list((s)) heat-loss coefficients for the opaque portion of
above-grade wood stud frame walls (((Btu/Fhr per square
foot))), metal stud frame walls and concrete masonry walls
(Btu/hft2F) respectively. They are derived from procedures
listed in ((RS-1)) RS-27, listed in Chapter 7((, assuming
exterior air films at 7.5-mph wind speed)). For intermediate
floor slabs which penetrate the insulated wall, use the concrete
wall U-factors in Table 10-5B.
Insulation is assumed to uniformly fill the entire cavity
and to be installed as per manufacturer's directions. All walls
are assumed to be finished on the inside with one-half inch
gypsum wallboard, and on the outside with either beveled wood
siding over one-half inch plywood sheathing or with five-eighths
inch T1-11 siding. Insulated sheathing (either interior or
exterior) is assumed to cover the entire opaque wall surface.
1005.2 Framing Description: For wood stud frame walls,
three framing types are considered, and defined as follows:
Standard: Studs framed on sixteen inch centers with double
top plate and single bottom plate. Corners use three studs and
each opening is framed using two studs. Headers consist of
double 2X or single 4X material with an air space left between
the header and the exterior sheathing. Interior partition
wall/exterior wall intersections use two studs in the exterior
wall.
Framing weighting factors: | Studs and plates | .19 |
Insulated cavity | .77 | |
Headers | .04 |
Framing weighting factors: | Studs and plates | .18 |
Insulated cavity | .78 | |
Headers | .04 |
Framing weighting factors: | Studs and plates | .13 |
Insulated cavity | .83 | |
Headers | .04 |
Single-Stud Wall: Assumes either 2x4 or 2x6 studs framed on
sixteen or twenty-four inch centers. Headers are solid for 2x4
walls and double 2x for 2x6 walls, with either dead-air or
rigid-board insulation in the remaining space.
Metal Stud Wall: Assumes metal studs spaced on 16 or 24
inch centers with insulation installed to fill wall cavities.
Continuous rigid board insulation is applied without creating
uninsulated voids in the wall assembly.
Strap Wall: Assumes 2x6 studs framed on sixteen or twenty-four inch centers. 2x3 or 2x4 strapping is run horizontally along the interior surface of the wall to provide additional space for insulation.
Double-Stud Wall: Assumes an exterior structural wall and a
separate interior, non-structural wall. Insulation is placed in
both wall cavities and in the space between the ((two)) 2 walls. Stud spacing is assumed to be on ((twenty-four)) 24 inch centers
for both walls.
TABLE 10-5
DEFAULT U-FACTORS FOR ABOVE-GRADE WALLS
2 x 4 Single Wood Stud: R-11 Batt | ||||||
Siding Material/Framing Type | ||||||
Lapped Wood | T1-11 | |||||
R-value of Foam Board |
STD | ADV | STD | ADV | ||
NOTE:
R-11 at 3.5 inch thickness Installed Batt R-value: R-11 in 3.5 inch cavity |
0 | 0.088 | 0.084 | 0.094 | 0.090 | |
1 | 0.080 | 0.077 | 0.085 | 0.082 | ||
2 | 0.074 | 0.071 | 0.078 | 0.075 | ||
3 | 0.069 | 0.066 | 0.072 | 0.070 | ||
4 | 0.064 | 0.062 | 0.067 | 0.065 | ||
5 | 0.060 | 0.058 | 0.063 | 0.061 | ||
6 | 0.056 | 0.055 | 0.059 | 0.057 | ||
7 | 0.053 | 0.052 | 0.055 | 0.054 | ||
8 | 0.051 | 0.049 | 0.052 | 0.051 | ||
9 | 0.048 | 0.047 | 0.050 | 0.049 | ||
10 | 0.046 | 0.045 | 0.047 | 0.046 | ||
11 | 0.044 | 0.043 | 0.045 | 0.044 | ||
12 | 0.042 | 0.041 | 0.043 | 0.042 | ||
2 x 4 Single Wood Stud: R-13 Batt | ||||||
Siding Material/Framing Type | ||||||
Lapped Wood | T1-11 | |||||
R-value of Foam Board |
STD | ADV | STD | ADV | ||
NOTE:
R-13 at 3.63 inch thickness Installed Batt R-value: R-12.7 in 3.5 inch cavity |
0 | 0.082 | 0.078 | 0.088 | 0.083 | |
1 | 0.075 | 0.072 | 0.080 | 0.076 | ||
2 | 0.069 | 0.066 | 0.073 | 0.070 | ||
3 | 0.065 | 0.062 | 0.068 | 0.065 | ||
4 | 0.060 | 0.058 | 0.063 | 0.061 | ||
5 | 0.057 | 0.055 | 0.059 | 0.057 | ||
6 | 0.053 | 0.052 | 0.056 | 0.054 | ||
7 | 0.051 | 0.049 | 0.052 | 0.051 | ||
8 | 0.048 | 0.047 | 0.050 | 0.048 | ||
9 | 0.046 | 0.045 | 0.047 | 0.046 | ||
10 | 0.044 | 0.043 | 0.045 | 0.044 | ||
11 | 0.042 | 0.041 | 0.043 | 0.042 | ||
12 | 0.040 | 0.039 | 0.041 | 0.040 | ||
2 x 4 Single Wood Stud: R-15 Batt | ||||||
Siding Material/Framing Type | ||||||
Lapped Wood | T1-11 | |||||
R-value of Foam Board |
STD | ADV | STD | ADV | ||
NOTE: Nominal Batt R-value: R-15 at 3.5 inch thickness Installed Batt R-value: R-15 in 3.5 inch cavity |
0 | 0.076 | 0.071 | 0.081 | 0.075 | |
1 | 0.069 | 0.065 | 0.073 | 0.069 | ||
2 | 0.064 | 0.061 | 0.068 | 0.069 | ||
3 | 0.060 | 0.057 | 0.063 | 0.059 | ||
4 | 0.056 | 0.053 | 0.059 | 0.056 | ||
5 | 0.053 | 0.051 | 0.055 | 0.052 | ||
6 | 0.050 | 0.048 | 0.052 | 0.050 | ||
7 | 0.047 | 0.046 | 0.049 | 0.047 | ||
8 | 0.045 | 0.044 | 0.047 | 0.045 | ||
9 | 0.043 | 0.042 | 0.044 | 0.043 | ||
10 | 0.041 | 0.040 | 0.042 | 0.041 | ||
11 | 0.039 | 0.038 | 0.041 | 0.039 | ||
12 | 0.038 | 0.037 | 0.039 | 0.038 | ||
2 x 6 Single Wood Stud: R-19 Batt | ||||||||
Siding Material/Framing Type | ||||||||
Lapped Wood | T1-11 | |||||||
R-value of Foam Board |
STD | INT | ADV | STD | INT | ADV | ||
NOTE: Nominal Batt R-value: R-19 at 6 inch thickness Installed Batt R-value: R-18 in 5.5 inch cavity |
0 | 0.062 | 0.058 | 0.055 | 0.065 | 0.061 | 0.058 | |
1 | 0.058 | 0.055 | 0.052 | 0.060 | 0.057 | 0.055 | ||
2 | 0.054 | 0.052 | 0.050 | 0.056 | 0.054 | 0.051 | ||
3 | 0.051 | 0.049 | 0.047 | 0.053 | 0.051 | 0.049 | ||
4 | 0.048 | 0.046 | 0.045 | 0.050 | 0.048 | 0.046 | ||
5 | 0.046 | 0.044 | 0.043 | 0.048 | 0.046 | 0.044 | ||
6 | 0.044 | 0.042 | 0.041 | 0.045 | 0.044 | 0.042 | ||
7 | 0.042 | 0.040 | 0.039 | 0.043 | 0.042 | 0.040 | ||
8 | 0.040 | 0.039 | 0.038 | 0.041 | 0.040 | 0.039 | ||
9 | 0.038 | 0.037 | 0.035 | 0.039 | 0.038 | 0.037 | ||
10 | 0.037 | 0.036 | 0.035 | 0.038 | 0.037 | 0.036 | ||
11 | 0.036 | 0.035 | 0.034 | 0.036 | 0.035 | 0.035 | ||
12 | 0.034 | 0.033 | 0.033 | 0.035 | 0.034 | 0.033 | ||
2 x 6 Single Wood Stud: R-21 Batt | ||||||||
Siding Material/Framing Type | ||||||||
Lapped Wood | T1-11 | |||||||
R-value of Foam Board |
STD | INT | ADV | STD | INT | ADV | ||
NOTE: Nominal Batt R-value: R-21 at 5.5 inch thickness Installed Batt R-value: R-21 in 5.5 inch cavity |
0 | 0.057 | 0.054 | 0.051 | 0.060 | 0.056 | 0.053 | |
1 | 0.054 | 0.051 | 0.048 | 0.056 | 0.053 | 0.050 | ||
2 | 0.050 | 0.048 | 0.045 | 0.052 | 0.050 | 0.047 | ||
3 | 0.048 | 0.045 | 0.043 | 0.049 | 0.047 | 0.045 | ||
4 | 0.045 | 0.043 | 0.041 | 0.047 | 0.045 | 0.043 | ||
5 | 0.043 | 0.041 | 0.040 | 0.044 | 0.042 | 0.041 | ||
6 | 0.041 | 0.039 | 0.038 | 0.042 | 0.041 | 0.039 | ||
7 | 0.039 | 0.038 | 0.036 | 0.040 | 0.039 | 0.037 | ||
8 | 0.038 | 0.036 | 0.035 | 0.039 | 0.037 | 0.036 | ||
9 | 0.036 | 0.035 | 0.034 | 0.037 | 0.036 | 0.035 | ||
10 | 0.035 | 0.034 | 0.033 | 0.036 | 0.035 | 0.033 | ||
11 | 0.033 | 0.033 | 0.032 | 0.034 | 0.033 | 0.032 | ||
12 | 0.032 | 0.031 | 0.031 | 0.033 | 0.032 | 0.031 | ||
2 x 6 Single Wood Stud: R-22 Batt | ||||||||
Siding Material/Framing Type | ||||||||
Lapped Wood | T1-11 | |||||||
R-value of Foam Board |
STD | INT | ADV | STD | INT | ADV | ||
NOTE: Nominal Batt R-value: R-22 at 6.75 inch thickness Installed Batt R-value: R-20 in 5.5 inch cavity |
0 | 0.059 | 0.055 | 0.052 | 0.062 | 0.058 | 0.054 | |
1 | 0.055 | 0.052 | 0.049 | 0.057 | 0.054 | 0.051 | ||
2 | 0.052 | 0.049 | 0.047 | 0.054 | 0.051 | 0.048 | ||
3 | 0.049 | 0.046 | 0.044 | 0.050 | 0.048 | 0.046 | ||
4 | 0.046 | 0.044 | 0.042 | 0.048 | 0.046 | 0.044 | ||
5 | 0.044 | 0.042 | 0.041 | 0.045 | 0.043 | 0.042 | ||
6 | 0.042 | 0.040 | 0.039 | 0.043 | 0.042 | 0.040 | ||
7 | 0.040 | 0.039 | 0.037 | 0.041 | 0.040 | 0.038 | ||
8 | 0.038 | 0.037 | 0.036 | 0.039 | 0.038 | 0.037 | ||
9 | 0.037 | 0.036 | 0.035 | 0.038 | 0.037 | 0.035 | ||
10 | 0.035 | 0.034 | 0.033 | 0.036 | 0.035 | 0.034 | ||
11 | 0.034 | 0.033 | 0.032 | 0.035 | 0.034 | 0.033 | ||
12 | 0.033 | 0.032 | 0.031 | 0.034 | 0.033 | 0.032 | ||
2 x 6 Single Wood Stud: Two R-11 Batts | ||||||||
Siding Material/Framing Type | ||||||||
Lapped Wood | T1-11 | |||||||
R-value of Foam Board |
STD | INT | ADV | STD | INT | ADV | ||
NOTE:
R-22 at 7 inch thickness Installed Batt R-value: R-18.9 in 5.5 inch cavity |
0 | 0.060 | 0.057 | 0.054 | 0.063 | 0.059 | 0.056 | |
1 | 0.056 | 0.053 | 0.051 | 0.059 | 0.056 | 0.053 | ||
2 | 0.053 | 0.050 | 0.048 | 0.055 | 0.052 | 0.050 | ||
3 | 0.050 | 0.048 | 0.046 | 0.052 | 0.049 | 0.047 | ||
4 | 0.047 | 0.045 | 0.044 | 0.049 | 0.047 | 0.045 | ||
5 | 0.045 | 0.043 | 0.042 | 0.046 | 0.045 | 0.043 | ||
6 | 0.043 | 0.041 | 0.040 | 0.044 | 0.043 | 0.041 | ||
7 | 0.041 | 0.040 | 0.038 | 0.042 | 0.041 | 0.039 | ||
8 | 0.039 | 0.038 | 0.037 | 0.040 | 0.039 | 0.038 | ||
9 | 0.038 | 0.037 | 0.036 | 0.039 | 0.038 | 0.036 | ||
10 | 0.036 | 0.035 | 0.034 | 0.037 | 0.036 | 0.035 | ||
11 | 0.035 | 0.034 | 0.033 | 0.036 | 0.035 | 0.034 | ||
12 | 0.034 | 0.033 | 0.032 | 0.034 | 0.034 | 0.033 | ||
2 x 8 Single Stud: R-25 Batt | ||||||||
Siding Material/Framing Type | ||||||||
Lapped Wood | T1-11 | |||||||
R-value of Foam Board |
STD | INT | ADV | STD | INT | ADV | ||
NOTE:
R-25 at 8 inch thickness Installed Batt R-value: R-23.6 in 7.25 inch cavity |
0 | 0.051 | 0.047 | 0.045 | 0.053 | 0.049 | 0.046 | |
1 | 0.048 | 0.045 | 0.043 | 0.049 | 0.046 | 0.044 | ||
2 | 0.045 | 0.043 | 0.041 | 0.047 | 0.044 | 0.042 | ||
3 | 0.043 | 0.041 | 0.039 | 0.044 | 0.042 | 0.040 | ||
4 | 0.041 | 0.039 | 0.037 | 0.042 | 0.040 | 0.038 | ||
5 | 0.039 | 0.037 | 0.036 | 0.040 | 0.038 | 0.037 | ||
6 | 0.037 | 0.036 | 0.035 | 0.038 | 0.037 | 0.036 | ||
7 | 0.036 | 0.035 | 0.033 | 0.037 | 0.035 | 0.034 | ||
8 | 0.035 | 0.033 | 0.032 | 0.035 | 0.034 | 0.033 | ||
9 | 0.033 | 0.032 | 0.031 | 0.034 | 0.033 | 0.032 | ||
10 | 0.032 | 0.031 | 0.030 | 0.033 | 0.032 | 0.031 | ||
11 | 0.031 | 0.030 | 0.029 | 0.032 | 0.031 | 0.030 | ||
12 | 0.030 | 0.029 | 0.028 | 0.031 | 0.030 | 0.029 | ||
2 x 6: Strap Wall | ||||||
Siding Material/Frame Type | ||||||
Lapped Wood | T1-11 | |||||
STD | ADV | STD | ADV | |||
R-19 + R-11 Batts | 0.036 | 0.035 | 0.038 | 0.036 | ||
R-19 + R-8 Batts | 0.041 | 0.039 | 0.042 | 0.040 | ||
Siding Material/Frame Type | ||||||
Batt Configuration | Lapped Wood | T1-11 | ||||
Exterior | Middle | Interior | STD | ADV | STD | ADV |
R-19 | ------- | R-11 | 0.040 | 0.037 | 0.041 | 0.038 |
R-19 | ------- | R-19 | 0.034 | 0.031 | 0.035 | 0.032 |
R-19 | R-8 | R-11 | 0.029 | 0.028 | 0.031 | 0.029 |
R-19 | R-11 | R-11 | 0.027 | 0.026 | 0.028 | 0.027 |
R-19 | R-11 | R-19 | 0.024 | 0.023 | 0.025 | 0.023 |
R-19 | R-19 | R-19 | 0.021 | 0.020 | 0.021 | 0.020 |
2 x 4 + 2 x 4: Double Wood Stud | ||||||||
Siding Material/Frame Type | ||||||||
Batt Configuration | Lapped Wood | T1-11 | ||||||
Exterior | Middle | Interior | STD | ADV | STD | ADV | ||
R-11 | -------- | R-11 | 0.050 | 0.046 | 0.052 | 0.048 | ||
R-19 | -------- | R-11 | 0.039 | 0.037 | 0.043 | 0.039 | ||
R-11 | R-8 | R-11 | 0.037 | 0.035 | 0.036 | 0.036 | ||
R-11 | R-11 | R-11 | 0.032 | 0.031 | 0.033 | 0.032 | ||
R-13 | R-13 | R-13 | 0.029 | 0.028 | 0.029 | 0.028 | ||
R-11 | R-19 | R-11 | 0.026 | 0.026 | 0.027 | 0.026 |
Log Walls |
|||
Average
Log Diameter, Inches |
U-factor | ||
NOTE: | |||
R-value of wood: R-1.25 per inch thickness Average wall thickness 90% average log diameter |
6 | 0.148 | |
8 | 0.111 | ||
10 | 0.089 | ||
12 | 0.074 | ||
14 | 0.063 | ||
16 | 0.056 | ||
Stress Skin Panel |
|||
Panel Thickness, Inches |
U-factor | ||
NOTE: | |||
R-value of expanded
polystyrene: R-3.85 per
inch Framing: 6% Spline: 8% |
3 1/2 | 0.071 | |
5 1/2 | 0.048 | ||
7 1/4 | 0.037 | ||
9 1/4 | 0.030 | ||
11 1/4 | 0.025 | ||
No thermal bridging between interior and exterior splines |
Metal Stud Walls: The nominal R-values in Table 10-5A may
be used for purposes of calculating metal stud wall section
U-factors in lieu of the ASHRAE zone calculation method as
provided in Chapter 24 of Standard RS-27.
TABLE 10-5A
Default U-factors for Overall Assembly Metal Stud Walls, Effective R-values for Metal Framing and Cavity Only, and Default Metal Building U-factors
OVERALL ASSEMBLY U-FACTORS FOR METAL STUD WALLS
Metal | R-Value of | ||||||
Framing | Continuous | Cavity Insulation | |||||
Foam Board | |||||||
Insulation | R-11 | R-13 | R-15 | R-19 | R-21 | R-25 | |
16" o.c. |
R-0 (none) |
U-0.14 |
U-0.13 |
U-0.12 |
U-0.10 |
U-0.097 |
U-0.091 |
R-1 | U-0.12 | U-0.12 | U-0.11 | U-0.094 | U-0.089 | U-0.083 | |
R-2 | U-0.11 | U-0.010 | U-0.099 | U-0.086 | U-0.081 | U-0.077 | |
R-3 | U-0.10 | U-0.095 | U-0.090 | U-0.079 | U-0.075 | U-0.071 | |
R-4 | U-0.091 | U-0.087 | U-0.082 | U-0.073 | U-0.070 | U-0.067 | |
R-5 | U-0.083 | U-0.080 | U-0.076 | U-0.068 | U-0.065 | U-0.062 | |
R-6 | U-0.077 | U-0.074 | U-0.071 | U-0.064 | U-0.061 | U-0.059 | |
R-7 | U-0.071 | U-0.069 | U-0.066 | U-0.060 | U-0.058 | U-0.055 | |
R-8 | U-0.067 | U-0.064 | U-0.062 | U-0.057 | U-0.055 | U-0.053 | |
R-9 | U-0.062 | U-0.060 | U-0.058 | U-0.054 | U-0.052 | U-0.050 | |
R-10 | U-0.059 | U-0.057 | U-0.055 | U-0.051 | U-0.049 | U-0.048 |
24" o.c |
R-0 (none) |
U-0.13 |
U-0.12 |
U-0.11 |
U-0.091 |
U-0.085 |
U-0.079 |
R-1 | U-0.11 | U-0.10 | U-0.098 | U-0.084 | U-0.078 | U-0.073 | |
R-2 | U-0.10 | U-0.091 | U-0.089 | U-0.077 | U-0.073 | U-0.068 | |
R-3 | U-0.092 | U-0.083 | U-0.082 | U-0.072 | U-0.068 | U-0.064 | |
R-4 | U-0.084 | U-0.077 | U-0.076 | U-0.067 | U-0.063 | U-0.060 | |
R-5 | U-0.078 | U-0.071 | U-0.070 | U-0.063 | U-0.060 | U-0.057 | |
R-6 | U-0.072 | U-0.067 | U-0.066 | U-0.059 | U-0.056 | U-0.054 | |
R-7 | U-0.067 | U-0.063 | U-0.062 | U-0.056 | U-0.053 | U-0.051 | |
R-8 | U-0.063 | U-0.059 | U-0.058 | U-0.053 | U-0.051 | U-0.048 | |
R-9 | U-0.059 | U-0.056 | U-0.055 | U-0.050 | U-0.048 | U-0.046 | |
R-10 | U-0.056 | U-0.053 | U-0.052 | U-0.048 | U-0.046 | U-0.044 |
EFFECTIVE R-VALUES FOR METAL FRAMING AND CAVITY ONLY
Cavity | Insulation | ||||
Nominal Depth, Inches |
Actual Depth, Inches |
Nominal R-Value |
Effective R-Value | ||
16" O.C. | 24" O.C. | ||||
Air Cavity | any | any | R-0.91 (air) | 0.79 | 0.91 |
4 | 3-1/2 | R-11 | 5.5 | 6.6 | |
4 | 3-1/2 | R-13 | 6.0 | 7.2 | |
Wall | 4 | 3-1/2 | R-15 | 6.4 | 7.8 |
6 | 5-1/2 | R-19 | 7.1 | 8.6 | |
6 | 5-1/2 | R-21 | 7.4 | 9.0 | |
8 | 7-1/4 | R-25 | 7.8 | 9.6 | |
Roof | Insulation is uncompressed | R-11 | 5.5 | 6.1 | |
R-19 | 7.0 | 9.1 | |||
R-30 | 9.3 | 11.4 |
DEFAULT METAL BUILDING U-FACTORS
R-10 | R-11 | R-13 | R-19 | R-24 | R-30 | |
Faced fiber glass blanket insulation rolled over and perpendicular to structural frame. Metal covering sheets fastened to the frame, holding insulation in place. | 0.133 | 0.127 | 0.114 | 0.091 | na | na |
Faced fiber glass batt insulation suspended between structural frame. Metal covering sheets fastened directly to frame. | 0.131 | 0.123 | 0.107 | 0.079 | 0.065 | 0.057 |
Faced fiber glass blanket insulation rolled over and perpendicular to structural frame. Rigid insulation blocks placed over insulation to align with structural frame. | 0.102 | 0.096 | 0.084 | 0.065 | na | na |
Faced fiber glass batt insulation suspended between structural frame. Rigid insulation blocks placed over insulation to align with structural frame. | 0.099 | 0.093 | 0.080 | 0.059 | 0.048 | 0.041 |
TABLE 10-5B
Default U-Factors for Concrete and Masonry Walls
8" CONCRETE MASONRY | ||||
WALL DESCRIPTION | CORE TREATMENT | |||
Partial Grout with Ungrouted Cores | Solid Grout | |||
Empty | Loose-fill insulated | |||
Perlite | Vermiculite | |||
Exposed Block, Both Sides | 0.40 | 0.23 | 0.24 | 0.43 |
R-5 Interior Insulation, Wood Furring | 0.14 | 0.11 | 0.12 | 0.15 |
R-6 Interior Insulation, Wood Furring | 0.14 | 0.11 | 0.11 | 0.14 |
R-10.5 Interior Insulation, Wood Furring | 0.11 | 0.09 | 0.09 | 0.11 |
R-8 Interior Insulation, Metal Clips | 0.11 | 0.09 | 0.09 | 0.11 |
R-6 Exterior Insulation | 0.12 | 0.10 | 0.10 | 0.12 |
R-10 Exterior Insulation | 0.08 | 0.07 | 0.07 | 0.08 |
R-9.5 Rigid Polystyrene Integral Insulation, Two Webbed Block | 0.11 | 0.09 | 0.09 | 0.12 |
12" CONCRETE MASONRY | ||||
CORE TREATMENT | ||||
Partial Grout with Ungrouted Cores | Solid Grout | |||
Empty | Loose-fill insulated | |||
Perlite | Vermiculite | |||
Exposed Block, Both Sides | 0.35 | 0.17 | 0.18 | 0.33 |
R-5 Interior Insulation, Wood Furring | 0.14 | 0.10 | 0.10 | 0.13 |
R-6 Interior Insulation, Wood Furring | 0.13 | 0.09 | 0.10 | 0.13 |
R-10.5 Interior Insulation, Wood Furring | 0.11 | 0.08 | 0.08 | 0.10 |
R-8 Interior Insulation, Metal Clips | 0.10 | 0.08 | 0.08 | 0.09 |
R-6 Exterior Insulation | 0.11 | 0.09 | 0.09 | 0.11 |
R-10 Exterior Insulation | 0.08 | 0.06 | 0.06 | 0.08 |
R-9.5 Rigid Polystyrene Integral Insulation, Two Webbed Block | 0.11 | 0.08 | 0.09 | 0.12 |
8" CLAY BRICK | ||||
WALL DESCRIPTION | CORE TREATMENT | |||
Partial Grout with Ungrouted Cores | Solid Grout | |||
Empty | Loose-fill insulated | |||
Perlite | Vermiculite | |||
Exposed Block, Both Sides | 0.50 | 0.31 | 0.32 | 0.56 |
R-5 Interior Insulation, Wood Furring | 0.15 | 0.13 | 0.13 | 0.16 |
R-6 Interior Insulation, Wood Furring | 0.15 | 0.12 | 0.12 | 0.15 |
R-10.5 Interior Insulation, Wood Furring | 0.12 | 0.10 | 0.10 | 0.12 |
R-8 Interior Insulation, Metal Clips | 0.11 | 0.10 | 0.10 | 0.11 |
R-6 Exterior Insulation | 0.12 | 0.11 | 0.11 | 0.13 |
R-10 Exterior Insulation | 0.08 | 0.08 | 0.08 | 0.09 |
6" CONCRETE POURED OR PRECAST | ||||
WALL DESCRIPTION | CORE TREATMENT | |||
Partial Grout with Ungrouted Cores | Solid Grout | |||
Empty | Loose-fill insulated | |||
Perlite | Vermiculite | |||
Exposed Concrete, Both Sides | NA | NA | NA | 0.61 |
R-5 Interior Insulation, Wood Furring | NA | NA | NA | 0.16 |
R-6 Interior Insulation, Wood Furring | NA | NA | NA | 0.15 |
R-10.5 Interior Insulation, Wood Furring | NA | NA | NA | 0.12 |
R-8 Interior Insulation, Metal Clips | NA | NA | NA | 0.12 |
R-6 Exterior Insulation | NA | NA | NA | 0.13 |
R-10 Exterior Insulation | NA | NA | NA | 0.09 |
Notes for Default Table 10-5B |
1. | Grouted cores at 40" x 48" on center vertically and horizontally in partial grouted walls. |
2. | Interior insulation values include 1/2" gypsum board on the inner surface. |
3. | Furring and stud spacing is 16" on center. Insulation is assumed to fill furring space and is not compressed. |
4. | Intermediate values may be interpolated using this table. Values not contained in this table may be computed using the procedures listed in Standard RS-27. |
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-1005, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, 51-11-1005, filed 12/19/90, effective 7/1/91.]
1006.1 ((Untested)) Glazing and Doors without NFRC
Certification: ((Untested)) Glazing and doors that do not have
NFRC certification shall be assigned the ((U-factors from Tables
10-6A, 10-6B, 10-6C, 10-6D, or 10-6E as appropriate.)) following
U-factors:
TABLE 10-6
Other than Group R Occupancy: DEFAULT
U-FACTORS FOR VERTICAL GLAZING,
OVERHEAD GLAZING AND OPAQUE DOORS
Vertical Glazing | ||
U-Factor | ||
Any Frame | Vinyl/Wood Frame |
|
Single | 1.45 | 1.45 |
Double | 0.90 | 0.75 |
1/2 Inch Air, Fixed | 0.75 | 0.60 |
1/2 Inch Air, Low-e(0.40), Fixed |
0.60 | 0.50 |
1/2 Inch Argon, Low-e(0.10), Fixed |
0.50 | 0.40 |
Overhead Glazing | ||
U-Factor | ||
Any Frame | Vinyl/Wood Frame |
|
Single | 2.15 | 2.15 |
Double | 1.45 | 1.00 |
Low-e(0.40) or Argon | 1.40 | 0.95 |
Low-e(0.40)+ Argon | 1.30 | 0.85 |
Low-e(0.20) Air | 1.30 | 0.90 |
Low-e(0.20)+ Argon | 1.25 | 0.80 |
Triple | 1.25 | 0.80 |
Opaque Doors | |
U-Factor | |
Uninsulated Metal | 1.20 |
Insulated Metal (Including Fire Door and Smoke Vent) | 0.60 |
Wood | 0.50 |
Where a gap width is listed (i.e.: 1/2 inch), that is the minimum allowed.
Where a low-emissivity emittance is listed (i.e.: 0.40, 0.20, 0.10), that is the maximum allowed.
Where a gas other than air is listed (i.e.: Argon), the gas fill shall be a minimum of 90%.
Where an operator type is listed (i.e.: Fixed), the default is only allowed for that operator type.
Where a frame type is listed (i.e.: Wood/vinyl), the default is only allowed for that frame type. Wood/vinyl frame includes reinforced vinyl and aluminum-clad wood.
Description1,2,3,4 | Frame Type5,6 | ||||
Aluminum | Aluminum Thermal Break7 |
Wood/Vinyl | |||
Windows | Single | 1.20 | 1.20 | 1.20 | |
Double, < 1/2" | Clear | 0.92 | 0.75 | 0.63 | |
Clear+ Argon | 0.87 | 0.71 | 0.60 | ||
Low-e | 0.85 | 0.69 | 0.58 | ||
Low-e+Argon | 0.79 | 0.62 | 0.53 | ||
Double, > 1/2" | Clear | 0.86 | 0.69 | 0.58 | |
Clear+ Argon | 0.83 | 0.67 | 0.55 | ||
Low-e | 0.78 | 0.61 | 0.51 | ||
Low-e+Argon | 0.75 | 0.58 | 0.48 | ||
Triple, | Clear | 0.70 | 0.53 | 0.43 | |
Clear+ Argon | 0.69 | 0.52 | 0.41 | ||
Low-e | 0.67 | 0.49 | 0.40 | ||
Low-e+Argon | 0.63 | 0.47 | 0.37 | ||
Garden | Single | 2.60 | n.a. | 2.31 | |
Windows | Double | Clear | 1.81 | n.a. | 1.61 |
Clear+ Argon | 1.76 | n.a. | 1.56 | ||
Low-e | 1.73 | n.a. | 1.54 | ||
Low-e+Argon | 1.64 | n.a. | 1.47 |
1 | <1/2"= a minimum dead air space of less than 0.5 inches between the panes of glass. | |
> 1/2"= a minimum dead air space of 0.5 inches or greater between the panes of glass. | ||
Where no gap width is listed, the minimum gap width is 1/4". | ||
2 | Any low-e (emissivity) coating (0.1, 0.2 or 0.4). | |
3 | U-factors listed for argon shall consist of sealed, gas-filled insulated units for argon, C02, SF6, argon/SF6 mixtures and Krypton. | |
4 | "Glass block” assemblies may use a U-factor of 0.51. | |
5 | Insulated fiberglass framed products shall use wood/vinyl U-factors. | |
6 | Aluminum clad wood windows shall use the U-factors listed for wood/vinyl windows. | |
7 | Aluminum Thermal Break= An aluminum thermal break framed window shall incorporate the following minimum design characteristics: | |
a) | The thermal conductivity of the thermal break material shall be not more than 3.6 Btu-in/h/ft2/F; | |
b) | The thermal break material must produces a gap in the frame material of not less than 0.210 inches; and, | |
c) | All metal framing members of the products exposed to interior and exterior air shall incorporate a thermal break meeting the criteria in a) and b) above. |
FRAME TYPE7,8 | ||||
DESCRIPTION2,3,4,5,6 | ALUMINUM | ALUM. THERMAL BREAK9 |
WOOD/VINYL | ALUM. CLAD WOOD/REINFORCED VINYL10 |
Double, Clear 1/4" | 0.82 | 0.66 | 0.56 | 0.59 |
Double, Clear 1/4"+ argon | 0.77 | 0.63 | 0.53 | 0.56 |
Double, Low-e4 1/4" | 0.76 | 0.61 | 0.52 | 0.54 |
Double, Low-e2 1/4" | 0.73 | 0.58 | 0.49 | 0.51 |
Double, Low-e1 1/4" | 0.70 | 0.55 | 0.47 | 0.49 |
Double, Low-e4 1/4"+ argon | 0.70 | 0.55 | 0.47 | 0.49 |
Double, Low-e2 1/4"+ argon | 0.66 | 0.52 | 0.43 | 0.46 |
Double, Low-e1 1/4"+ argon | 0.64 | 0.50 | 0.41 | 0.43 |
Double, Clear 3/8" | 0.78 | 0.63 | 0.54 | 0.57 |
Double, Clear 3/8"+ argon | 0.75 | 0.60 | 0.51 | 0.54 |
Double, Low-e4 3/8" | 0.72 | 0.57 | 0.48 | 0.51 |
Double, Low-e2 3/8" | 0.69 | 0.54 | 0.45 | 0.48 |
Double, Low-e1 3/8" | 0.66 | 0.51 | 0.43 | 0.46 |
Double, Low-e4 3/8"+ argon | 0.68 | 0.53 | 0.44 | 0.47 |
Double, Low-e2 3/8"+ argon | 0.63 | 0.49 | 0.41 | 0.44 |
Double, Low-e1 3/8"+ argon | 0.61 | 0.47 | 0.39 | 0.41 |
Double, Clear 1/2" | 0.75 | 0.60 | 0.50 | 0.54 |
Double, Clear 1/2"+ argon | 0.72 | 0.58 | 0.48 | 0.51 |
Double, Low-e4 1/2" | 0.68 | 0.53 | 0.44 | 0.47 |
Double, Low-e2 1/2" | 0.64 | 0.50 | 0.41 | 0.44 |
Double, Low-e1 1/2" | 0.61 | 0.47 | 0.39 | 0.42 |
Double, Low-e4 1/2"+ argon | 0.65 | 0.50 | 0.42 | 0.44 |
Double, Low-e2 1/2"+ argon | 0.60 | 0.46 | 0.37 | 0.40 |
Double, Low-e1 1/2"+ argon | 0.58 | 0.43 | 0.35 | 0.38 |
Triple, Clear 1/4" | 0.66 | 0.52 | 0.42 | 0.44 |
Triple, Clear 1/4"+ argon | 0.63 | 0.49 | 0.39 | 0.42 |
Triple, Low-e4 1/4" | 0.64 | 0.50 | 0.40 | 0.40 |
Triple, Low-e2 1/4" | 0.62 | 0.48 | 0.39 | 0.41 |
Triple, Low-e1 1/4" | 0.61 | 0.47 | 0.38 | 0.40 |
Triple, Low-e4 1/4"+ argon | 0.60 | 0.46 | 0.37 | 0.39 |
Triple, Low-e2 1/4"+ argon | 0.58 | 0.43 | 0.34 | 0.37 |
Triple, Low-el 1/4" + argon | 0.57 | 0.42 | 0.34 | 0.36 |
Triple, Clear 1/2" | 0.61 | 0.46 | 0.37 | 0.40 |
Triple, Clear 1/2"+ argon | 0.59 | 0.45 | 0.36 | 0.38 |
Triple, Low-e4 1/2" | 0.58 | 0.43 | 0.35 | 0.37 |
Triple, Low-e2 1/2" | 0.55 | 0.41 | 0.32 | 0.35 |
Triple, Low-e1 1/2" | 0.54 | 0.39 | 0.31 | 0.33 |
Triple, Low-e4 1/2"+ argon | 0.55 | 0.41 | 0.32 | 0.35 |
Triple, Low-e2 1/2"+ argon | 0.52 | 0.38 | 0.30 | 0.32 |
Triple, Low-e1 1/2"+ argon | 0.51 | 0.37 | 0.29 | 0.31 |
Footnotes to Table 10-6B
1 | Subtract 0.02 from the listed default U-factor for non-aluminum spacer. Acceptable spacer materials may
include but is not limited to fiberglass, wood and butyl or other material with an equivalent thermal
performance. |
2 | 1/4"= a minimum dead air space of 0.25 inches between the panes of glass. 3/8"= a minimum dead air space of 0.375 inches between the panes of glass. 1/2"= a minimum dead air space of 0.5 inches between the panes of glass. Product with air spaces different than those listed above shall use the value for the next smaller air space;
i.e. 3/4 inch= 1/2 inch U-factors, 7/16 inch= 3/8 inch U-factors, 5/16 inch= 1/4 inch U-factors. |
3 | Low-e4 (emissivity) shall be 0.4 or less. Low-e2 (emissivity) shall be 0.2 or less. Low-e1 (emissivity) shall be 0.1 or less. |
4 | U-factors listed for argon shall consist of sealed, gas-filled insulated units for argon, CO2, SF6, and
argon/SF6 mixtures. The following conversion factor shall apply to Krypton gas-filled units: 1/4" or
greater with krypton is equivalent to 1/2" argon. |
5 | Dividers placed between glazing: The U-factor listed shall be used where the divider has a minimum gap
of 1/8 inch between the divider and lite of each inside glass surface. Add 0.03 to the listed U-factor for
True Divided Lite windows. |
6 | "Glass block” assemblies may use a U-factor of 0.51. |
7 | Insulated fiberglass framed products shall use wood/vinyl U-factors. |
8 | Subtract 0.02 from the listed default values for solariums. |
9 | Aluminum Thermal Break= An aluminum thermal break framed window shall incorporate the following
minimum design characteristics: |
a) | The thermal conductivity of the thermal break material shall be not more than 3.6 Btu-in/h/ft2/F; |
b) | The thermal break material must produce a gap in the frame material of not less than 0.210 inches; and, |
c) | All metal framing members of the products exposed to interior and exterior air shall incorporate a thermal break meeting the criteria in a) and b) above. |
10 | Aluminum clad wood windows shall use the U-factors listed for Aluminum Clad Wood/Reinforced Vinyl windows. Vinyl clad wood window shall use the U-factors listed for Wood/Vinyl windows. Any vinyl frame window with metal reinforcement in more than one rail shall use the U-factors listed for Aluminum Clad Wood/Reinforced Vinyl window. |
Door Thickness, Inches |
Storm Door |
Storm Doorc |
Storm Doord |
|
Doorsb |
||||
Doorsb |
||||
(18 gage commercial steel)f |
||||
(18 gage commercial steel)f |
||||
(24 gage commercial steel)f |
||||
(24 gage commercial steel)f |
||||
0.17)) |
The U-factors in Table 6C are for exterior wood and steel doors. The values given for wood doors were calculated, and those for steel doors were
taken from hotbox tests (Sabine et al. 1975: Yellot 1965) or from manufacturer's test reports. An outdoor surface conductance of 6.0
Btu/hft2F was used, and the indoor surface conductance was taken as 1.4 Btu/hft2F for vertical surfaces with horizontal heat flow. All
values given are for exterior doors without glazing. If an exterior door contains glazing, refer to Table 10-6D.))
TABLE 10-6C
Group R Occupancy: DEFAULT U-FACTORS FOR DOORS
Door Type | No Glazing | Single Glazing | Double Glazing with 1/4 in. Airspace | Double Glazing with 1/2 in. Airspace | Double Glazing with e=0.10, 1/2 in. Argon |
SWINGING DOORS (Rough opening - 38 in. x 82 in.) | |||||
Slab Doors | |||||
Wood slab in wood framea | 0.46 | ||||
6% glazing (22 in. x 8 in. lite) | - | 0.48 | 0.47 | 0.46 | 0.44 |
25% glazing (22 in. x 36 in. lite) | - | 0.58 | 0.48 | 0.46 | 0.42 |
45% glazing (22 in. x 64 in. lite) | - | 0.69 | 0.49 | 0.46 | 0.39 |
More than 50% glazing | Use Table 10-6A | ||||
Insulated steel slab with wood edge in wood framea | 0.16 | ||||
6% glazing (22 in. x 8 in. lite) | - | 0.21 | 0.20 | 0.19 | 0.18 |
25% glazing (22 in. x 36 in. lite) | - | 0.39 | 0.28 | 0.26 | 0.23 |
45% glazing (22 in. x 64 in. lite) | - | 0.58 | 0.38 | 0.35 | 0.26 |
More than 50% glazing | Use Table 10-6A | ||||
Foam insulated steel slab with metal edge in steel frameb | 0.37 | ||||
6% glazing (22 in. x 8 in. lite) | - | 0.44 | 0.42 | 0.41 | 0.39 |
25% glazing (22 in. x 36 in. lite) | - | 0.55 | 0.50 | 0.48 | 0.44 |
45% glazing (22 in. x 64 in. lite) | - | 0.71 | 0.59 | 0.56 | 0.48 |
More than 50% glazing | Use Table 10-6A | ||||
Cardboard honeycomb slab with metal edge in steel frameb | 0.61 | ||||
Style and Rail Doors | |||||
Sliding glass doors/French doors | Use Table 10-6A | ||||
Site-Assembled Style and Rail Doors | |||||
Aluminum in aluminum frame | - | 1.32 | 0.99 | 0.93 | 0.79 |
Aluminum in aluminum frame with thermal break | - | 1.13 | 0.80 | 0.74 | 0.63 |
REVOLVING DOORS (Rough opening - 82 in. x 84 in.) | |||||
Aluminum in aluminum frame | |||||
Open | - | 1.32 | - | - | - |
Closed | - | 0.65 | - | - | - |
SECTIONAL OVERHEAD DOORS (Nominal - 10 ft x 10 ft) | |||||
Uninsulated steel (nominal U =1.15)c | 1.15 | - | - | - | - |
Insulated steel (nominal U =0.11)c | 0.24 | - | - | - | - |
Insulated steel with thermal break (nominal U = 0.08)c | 0.13 | - | - | - | - |
a. | Thermally broken sill (add 0.03 for nonthermally broken sill) |
b. | Nonthermally broken sill |
c. | Nominal U-factors are through the center of the insulated panel before consideration of thermal bridges around the edges of the door sections and due to the frame. |
3/8"= a minimum dead air space of 0.375 inches between the panes of glass. 1/2"= a minimum dead air space of 0.5 inches between the panes of glass. Products with air spaces different than those listed above shall use the value for next smaller air space;
i.e. 3/4 inch= 1/2 inch U-factors, 7/16 inch= 3/8 inch U-factors, 5/16 inch= 1/4 inch U-factors. |
|
Low-e2 (emissivity) shall be 0.2 or less. Low-e1 (emissivity) shall be 0.1 or less. |
|
The following conversion factor shall apply to Krypton gas-filled units: 1/4 inch or greater airspace of Krypton gas-fill= 1/2 inch air space Argon gas-fill. |
|
a) The thermal conductivity of the thermal break material shall be not more than 3.6 Btu-in/hft2F; and b) The thermal break material shall not be less than 0.210 inches. |
|
Add 0.06 to the listed U-factor for Half-Lite values if the insulated door does not have a thermal break.)) |
Frame Type | ||||
Aluminum | Aluminum | Reinforced | Wood or Vinyl- | |
Glazing Type | without | with | Vinyl/ | Clad Wood/ |
Thermal | Thermal | Aluminum-Clad | Vinyl without | |
Break | Break | Wood or Vinyl | Reinforcing | |
Single Glazing | ||||
glass | U-1.58 | U-1.51 | U-1.40 | U-1.18 |
acrylic/polycarb | U-1.52 | U-1.45 | U-1.34 | U-1.11 |
Double Glazing | ||||
air | U-1.05 | U-0.89 | U-0.84 | U-0.67 |
argon | U-1.02 | U-0.86 | U-0.80 | U-0.64 |
Double Glazing, e=0.20 | ||||
air | U-0.96 | U-0.80 | U-0.75 | U-0.59 |
argon | U-0.91 | U-0.75 | U-0.70 | U-0.54 |
Double Glazing, e=0.10 | ||||
air | U-0.94 | U-0.79 | U-0.74 | U-0.58 |
argon | U-0.89 | U-0.73 | U-0.68 | U-0.52 |
Double Glazing, e=0.05 | ||||
air | U-0.93 | U-0.78 | U-0.73 | U-0.56 |
argon | U-0.87 | U-0.71 | U-0.66 | U-0.50 |
Triple Glazing | ||||
air | U-0.90 | U-0.70 | U-0.67 | U-0.51 |
argon | U-0.87 | U-0.69 | U-0.64 | U-0.48 |
Triple Glazing, e=0.20 | ||||
air | U-0.86 | U-0.68 | U-0.63 | U-0.47 |
argon | U-0.82 | U-0.63 | U-0.59 | U-0.43 |
Triple Glazing, e=0.20 on 2 surfaces | ||||
air | U-0.82 | U-0.64 | U-0.60 | U-0.44 |
argon | U-0.79 | U-0.60 | U-0.56 | U-0.40 |
Triple Glazing, e=0.10 on 2 surfaces | ||||
air | U-0.81 | U-0.62 | U-0.58 | U-0.42 |
argon | U-0.77 | U-0.58 | U-0.54 | U-0.38 |
Quadruple Glazing, e=0.10 on 2 surfaces | ||||
air | U-0.78 | U-0.59 | U-0.55 | U-0.39 |
argon | U-0.74 | U-0.56 | U-0.52 | U-0.36 |
krypton | U-0.70 | U-0.52 | U-0.48 | U-0.32 |
1. | U-factors are applicable to both glass and plastic, flat and domed units, all spacers and gaps. |
2. | Emissivities shall be less than or equal to the value specified. |
3. | Gap fill shall be assumed to be air unless there is a minimum of 90% argon or krypton. |
4. | Aluminum frame with thermal break is as defined in footnote 9 to Table 10-6B. |
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-1006, filed 1/8/98, effective 7/1/98. Statutory Authority: Chapters 19.27, 19.27A and 34.05 RCW. 94-05-059, 51-11-1006, filed 2/10/94, effective 4/1/94. Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, 51-11-1006, filed 12/19/90, effective 7/1/91.]
1007.1 General: Table 10-7 lists heat-loss coefficients for
the opaque portion of exterior ceilings below vented attics,
vaulted ceilings, and roof decks in units of ((Btu/hrF per
square foot)) Btu/hft2F of ceiling.
They are derived from procedures listed in Standard ((RS-1))
RS-27, listed in Chapter 7. Ceiling U-factors are modified for
the buffering effect of the attic, assuming an indoor temperature
of 65 F and an outdoor temperature of 45F.
Metal Framed Ceilings: The nominal R-values in Table 10-5A - EFFECTIVE R-VALUES FOR METAL FRAMING AND CAVITY ONLY may be used for purposes of calculating metal framed ceiling section U-factors in lieu of the ASHRAE zone calculation method as provided in Chapter 24 of Standard RS-27.
1007.2 Component Description: The ((three)) four types of
ceilings are characterized as follows:
Ceilings Below a Vented Attic: Attic insulation is assumed to be blown-in, loose-fill fiberglass with a K-value of 2.6 hrft2F/Btu per inch. Full bag count for specified R-value is assumed in all cases. Ceiling dimensions for flat ceiling calculations are forty-five by thirty feet, with a gabled roof having a 4/12 pitch. The attic is assumed to vent naturally at the rate of three air changes per hour through soffit and ridge vents. A void fraction of 0.002 is assumed for all attics with insulation baffles. Standard-framed, unbaffled attics assume a void fraction of 0.008.
Attic framing is either standard or advanced. Standard framing assumes tapering of insulation depth around the perimeter with resultant decrease in thermal resistance. An increased R-value is assumed in the center of the ceiling due to the effect of piling leftover insulation. Advanced framing assumes full and even depth of insulation extending to the outside edge of exterior walls. Advanced framing does not change from the default value.
U-factors for flat ceilings below vented attics with standard framing may be modified with the following table:
U-Factor for Standard Framing |
|||
Roof Pitch | R-30 | R-38 | |
4/12 | .036 | .031 | |
5/12 | .035 | .030 | |
6/12 | .034 | .029 | |
7/12 | .034 | .029 | |
8/12 | .034 | .028 | |
9/12 | .034 | .028 | |
10/12 | .033 | .028 | |
11/12 | .033 | .027 | |
12/12 | .033 | .027 |
Vaulted Ceilings: Insulation is assumed to be fiberglass
batts installed in roof joist cavities. In the vented case, at
least 1.5-inches between the top of the batts and the underside
of the roof sheathing is left open for ventilation in each
cavity. A ventilation rate of ((three)) 3.0 air changes per hour
is assumed. In the unvented or dense pack case, the ceiling
cavity is assumed to be fully packed with insulation, leaving no
space for ventilation.
Roof Decks: Rigid insulation is applied to the top of roof decking with no space left for ventilation. Roofing materials are attached directly on top of the insulation. Framing members are often left exposed on the interior side.
Metal Truss Framing: Overall system tested values for the roof/ceiling Uo for metal framed truss assemblies from approved laboratories shall be used, when such data is acceptable to the building official.
Alternatively, the Uo for roof/ceiling assemblies using metal truss framing may be obtained from Tables 10-7A, 10-7B, 10-7C, 10-7D and 10-7E.
TABLE 10-7
DEFAULT U-FACTORS FOR CEILINGS
Standard Frame | Advanced Frame | ||||
Flat Ceiling | Baffled | ||||
R-19 | 0.049 | 0.047 | |||
R-30 | 0.036 | 0.032 | |||
R-38 | 0.031 | 0.026 | |||
R-49 | 0.027 | 0.020 | |||
R-60 | 0.025 | 0.017 | |||
Scissors Truss | |||||
R-30 (4/12 roof pitch) | 0.043 | 0.031 | |||
R-38 (4/12 roof pitch) | 0.040 | 0.025 | |||
R-49 (4/12 roof pitch) | 0.038 | 0.020 | |||
R-30 (5/12 roof pitch) | 0.039 | 0.032 | |||
R-38 (5/12 roof pitch) | 0.035 | 0.026 | |||
R-49 (5/12 roof pitch) | 0.032 | 0.020 | |||
Vaulted Ceilings | |||||
16" O.C. | 24" O.C. | ||||
Vented | |||||
R-19 2x10 joist | 0.049 | 0.048 | |||
R-30 2x12 joist | 0.034 | 0.033 | |||
R-38 2x14 joist | 0.027 | 0.027 | |||
Unvented | |||||
R-30 2x10 joist | 0.034 | 0.033 | |||
R-38 2x12 joist | 0.029 | 0.027 | |||
R-21 + R-21 2x12 joist | 0.026 | 0.025 | |||
Roof Deck | |||||
4x Beams, 48" O.C. | |||||
R-12.5 | 2" | Rigid insulation | 0.064 | ||
R-21.9 | 3.5" | Rigid insulation | 0.040 | ||
R-37.5 | 6" | Rigid insulation | 0.025 | ||
R-50 | 8" | Rigid insulation | 0.019 |
Table 10-7A Steel Truss1 Framed Ceiling UO |
|||||||||||||
Cavity | Truss Span (ft) | ||||||||||||
R-value | 12 | 14 | 16 | 18 | 20 | 22 | 24 | 26 | 28 | 30 | 32 | 34 | 36 |
19 | 0.1075 | 0.0991 | 0.0928 | 0.0878 | 0.0839 | 0.0807 | 0.0780 | 0.0757 | 0.0737 | 0.0720 | 0.0706 | 0.0693 | 0.0681 |
30 | 0.0907 | 0.0823 | 0.0760 | 0.0710 | 0.0671 | 0.0638 | 0.0612 | 0.0589 | 0.0569 | 0.0552 | 0.0538 | 0.0525 | 0.0513 |
38 | 0.0844 | 0.0759 | 0.0696 | 0.0647 | 0.0607 | 0.0575 | 0.0548 | 0.0525 | 0.0506 | 0.0489 | 0.0474 | 0.0461 | 0.0449 |
49 | 0.0789 | 0.0704 | 0.0641 | 0.0592 | 0.0552 | 0.0520 | 0.0493 | 0.0470 | 0.0451 | 0.0434 | 0.0419 | 0.0406 | 0.0395 |
Table 10-7B Steel Truss1 Framed Ceiling UO with R-3 Sheathing2 |
|||||||||||||
Cavity | Truss Span (ft) | ||||||||||||
R-value | 12 | 14 | 16 | 18 | 20 | 22 | 24 | 26 | 28 | 30 | 32 | 34 | 36 |
19 | 0.0809 | 0.0763 | 0.0728 | 0.0701 | 0.0679 | 0.0661 | 0.0647 | 0.0634 | 0.0623 | 0.0614 | 0.0606 | 0.0599 | 0.0592 |
30 | 0.0641 | 0.0595 | 0.0560 | 0.0533 | 0.0511 | 0.0493 | 0.0478 | 0.0466 | 0.0455 | 0.0446 | 0.0438 | 0.0431 | 0.0424 |
38 | 0.0577 | 0.0531 | 0.0496 | 0.0469 | 0.0447 | 0.0430 | 0.0415 | 0.0402 | 0.0392 | 0.0382 | 0.0374 | 0.0367 | 0.0361 |
49 | 0.0523 | 0.0476 | 0.0441 | 0.0414 | 0.0393 | 0.0375 | 0.0360 | 0.0348 | 0.0337 | 0.0328 | 0.0319 | 0.0312 | 0.0306 |
Table 10-7C Steel Truss1 Framed Ceiling UO with R-5 Sheathing2 |
|||||||||||||
Cavity | Truss Span (ft) | ||||||||||||
R-value | 12 | 14 | 16 | 18 | 20 | 22 | 24 | 26 | 28 | 30 | 32 | 34 | 36 |
19 | 0.0732 | 0.0697 | 0.0670 | 0.0649 | 0.0633 | 0.0619 | 0.0608 | 0.0598 | 0.0590 | 0.0583 | 0.0577 | 0.0571 | 0.0567 |
30 | 0.0564 | 0.0529 | 0.0502 | 0.0481 | 0.0465 | 0.0451 | 0.0440 | 0.0430 | 0.0422 | 0.0415 | 0.0409 | 0.0403 | 0.0399 |
38 | 0.0501 | 0.0465 | 0.0438 | 0.0418 | 0.0401 | 0.0388 | 0.0376 | 0.0367 | 0.0359 | 0.0351 | 0.0345 | 0.0340 | 0.0335 |
49 | 0.0446 | 0.0410 | 0.0384 | 0.0363 | 0.0346 | 0.0333 | 0.0322 | 0.0312 | 0.0304 | 0.0297 | 0.0291 | 0.0285 | 0.0280 |
Table 10-7D Steel Truss1 Framed Ceiling UO with R-10 Sheathing2 |
|||||||||||||
Cavity | Truss Span (ft) | ||||||||||||
R-value | 12 | 14 | 16 | 18 | 20 | 22 | 24 | 26 | 28 | 30 | 32 | 34 | 36 |
19 | 0.0626 | 0.0606 | 0.0590 | 0.0578 | 0.0569 | 0.0561 | 0.0555 | 0.0549 | 0.0545 | 0.0541 | 0.0537 | 0.0534 | 0.0531 |
30 | 0.0458 | 0.0437 | 0.0422 | 0.0410 | 0.0401 | 0.0393 | 0.0387 | 0.0381 | 0.0377 | 0.0373 | 0.0369 | 0.0366 | 0.0363 |
38 | 0.0394 | 0.0374 | 0.0359 | 0.0347 | 0.0337 | 0.0330 | 0.0323 | 0.0318 | 0.0313 | 0.0309 | 0.0305 | 0.0302 | 0.0299 |
49 | 0.0339 | 0.0319 | 0.0304 | 0.0292 | 0.0283 | 0.0275 | 0.0268 | 0.0263 | 0.0258 | 0.0254 | 0.0251 | 0.0247 | 0.0245 |
Table 10-7E Steel Truss1 Framed Ceiling UO with R-15 Sheathing2 |
|||||||||||||
Cavity | Truss Span (ft) | ||||||||||||
R-value | 12 | 14 | 16 | 18 | 20 | 22 | 24 | 26 | 28 | 30 | 32 | 34 | 36 |
19 | 0.0561 | 0.0550 | 0.0541 | 0.0535 | 0.0530 | 0.0526 | 0.0522 | 0.0519 | 0.0517 | 0.0515 | 0.0513 | 0.0511 | 0.0509 |
30 | 0.0393 | 0.0382 | 0.0373 | 0.0367 | 0.0362 | 0.0358 | 0.0354 | 0.0351 | 0.0349 | 0.0347 | 0.0345 | 0.0343 | 0.0341 |
38 | 0.0329 | 0.0318 | 0.0310 | 0.0303 | 0.0298 | 0.0294 | 0.0291 | 0.0288 | 0.0285 | 0.0283 | 0.0281 | 0.0279 | 0.0278 |
49 | 0.0274 | 0.0263 | 0.0255 | 0.0249 | 0.0244 | 0.0239 | 0.0236 | 0.0233 | 0.0230 | 0.0228 | 0.0226 | 0.0225 | 0.0223 |
1 - Assembly values based on 24 inch on center truss spacing; 11 Truss member connections penetrating insulation (4 at the eaves, 7 in the interior space); inch drywall ceiling; all truss members are 2x4 "C" channels with a solid web. | |
2 - Ceiling sheathing installed between bottom chord and drywall. |
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-1007, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, 51-11-1007, filed 12/19/90, effective 7/1/91.]
1008.1 General: Tables 10-8 and ((10-9)) 10-8A list
effective air change rates and heat capacities for heat loss due
to infiltration for Group R occupancy.
Estimated seasonal average infiltration rate in air changes per hour (ACH) is given for standard air-leakage control (see section 502.4 of this code for air leakage requirements for Group R occupancy). The effective air-change rate shall be used in calculations for compliance under either the Component Performance or Systems Analysis approaches.
Heat loss due to infiltration shall be computed using the following equation:
Qinfil= ACHeff* HCP | |||
where: | Qinfil | = | Heat loss due to air infiltration |
ACHeff | = | the effective air infiltration rate in Table 10-8 | |
HCP | = | the Heat Capacity Density Product for the appropriate elevation or climate zone as given below. |
TABLE 10-8
ASSUMED EFFECTIVE AIR CHANGES
PER HOUR
Air-Leakage | Air Changes per Hour | |
Control Package | Natural Effective | |
Standard | 0.35 0.35 |
TABLE ((10-9)) 10-8A
DEFAULT HEAT CAPACITY/DENSITY PRODUCT FOR AIR
Zone | Average Elevation | Heat Capacity/Density | |
1 | Mean Sea Level | 0.0180 Btu/hF | |
2 | 2000 | 0.0168 Btu/hF | |
3 | 3000 | 0.0162 Btu/hF |
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-1008, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, 51-11-1008, filed 12/19/90, effective 7/1/91.]
1009.1 General: ((Table)) Tables 10-9 and 10-10 list((s))
default ((mass-values)) mass values for ((residential)) concrete
masonry construction ((types)). ((All)) Calculations are based
on standard ASHRAE values for heat-storage capacity as listed in
Standard ((RS-1)) RS-27, Chapter 24.
Thermal capacity of furniture is ignored, as is heat storage
beyond the first four inches of mass thickness. All mass is
assumed to be in direct contact with the conditioned space.
Concrete separated from the heated volume by other materials must
multiply the listed concrete mass value by the result of the
following formula:
Ln(R-value) x (-.221)+ 0.5
Where:
Ln= Natural log
R-value= R-value of material covering concrete
Note: | All default values for covered concrete slabs have been adjusted according to this procedure. |
Structural Mass: Includes heat-storage capacity of all standard building components of a typical residential structure, including floors, ceilings, and interior and exterior walls in Btu/ft2F of floor area. It also assumes exterior wall, interior wall and ceiling surface area approximately equals three times the floor area.
Additional Mass: Includes any additional building material
not part of the normal structure, which is added specifically to
increase the building's thermal-storage capability. This
category includes masonry fireplaces, water or trombe walls, and
extra layers of sheetrock. Coefficients are in Btu/ft2F of
surface area of material exposed to conditioned space. The
coefficient for water is Btu/Fgallon.
1009.3 Component Description: Light frame assumes one inch
thick wood flooring with five-eighths inch sheetrock on ceilings
and interior walls, and walls consisting of either five-eighths
inch sheetrock or solid logs. Slab assumes a four-inch concrete
slab on or below grade, with five-eighths inch sheetrock on
exterior and interior walls and ceiling, and with separate values
for interior or exterior wall insulation. Adjustments for slab
covering is based on R-value of material. Additional mass values
are based on the density multiplied by the specific heat of the
material adjusted for listed thickness.
TABLE 10-9
HEAT CAPACITY
Partial Grout | Solid Grout | |
8" CMU | 9.65 | 15.0 |
12" CMU | 14.5 | 23.6 |
8" Brick | 10.9 | 16.4 |
6" Concrete | NA | 14.4 |
TABLE 10-10
DEFAULT MASS VALUES
Structural Mass M-value | Btu/ft2F floor area | |||
Light Frame: | ||||
Joisted/post & beam floor, sheetrock | ||||
walls and ceilings | 3.0 | |||
Joisted/post & beam floor, log walls, | ||||
sheetrock ceilings | 4.0 | |||
Slab With Interior Wall Insulation: | ||||
Slab, no covering or tile, sheetrock walls and ceilings | 10.0 | |||
Slab, hardwood floor covering, sheetrock walls and ceilings | 7.0 | |||
Slab, carpet and pad, sheetrock walls and ceilings | 5.0 | |||
Slab With Exterior Wall Insulation: | ||||
Slab, no covering or tile, sheetrock walls and ceilings | 12.0 | |||
Slab, hardwood floor covering, sheetrock walls and ceilings | 9.0 | |||
Slab, carpet and pad, sheetrock walls and ceilings | 7.0 | |||
Additional Mass M-Value: | Btu/ft2F surface area | |||
Gypsum wallboard, 1/2 inch thickness | 0.54 | |||
Gypsum wallboard, 5/8 inch thickness | 0.68 | |||
Hardwood floor | 1.40 | |||
Concrete/Brick, 4 inch-thickness | 10.30 | |||
Concrete/Brick, 6 inch-thickness | 15.40 | |||
Btu/Fgallon | ||||
Water, 1 gallon | 8.0 |
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-1009, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.020 and 1990 c 2. 91-01-112, 51-11-1009, filed 12/19/90, effective 7/1/91.]
1132.1 Building Envelope: Alterations or repairs shall comply
with nominal R-values and glazing requirements in Table 13-1 or
13-2.
EXCEPTIONS:
1. Storm windows installed over existing glazing.
2. Glass replaced in existing sash and frame provided that glazing is of equal or lower U-factor.
3. For solar heat gain coefficient compliance, glazing with a solar heat gain coefficient equal to or lower than
that of the other existing glazing.
4. Existing roof/ceiling, wall or floor cavities exposed during construction provided that these cavities are
insulated to full depth with insulation having a minimum nominal value of R-3.0 per inch installed per Sections
1311 and 1313.
5. Existing walls and floors without framing cavities, provided that any new cavities added to existing walls
and floors comply with Exception 4.
6. Existing roofs where the roof membrane is being replaced and
a. The roof sheathing or roof insulation is not exposed; or
b. If there is existing roof insulation below the deck.
In no case shall the energy efficiency of the building be decreased.
1132.2 Building Mechanical Systems: Those parts of systems which
are altered or replaced shall comply with Chapter 14 of this
Code.
1132.3 Lighting and Motors: Tenant improvements, alterations or
repairs where 60 percent or more of the fixtures in a use (as
defined in Table 15-1) within a tenant space or in an entire
floor (whichever is smaller) are new shall comply with Sections
1531 and 1532. Where less than 60 percent of the fixtures are
new, the installed lighting wattage shall be maintained or
reduced. Where 60 percent or more of the lighting fixtures in a
suspended ceiling are new, and the existing insulation is on the
suspended ceiling, the roof/ceiling assembly shall be insulated
according to the provisions of Chapter 13 Section 1311.2.
Where new wiring is being installed to serve added fixtures
and/or fixtures are being relocated to a new circuit, controls
shall comply with Sections 1513.1 through 1513.5. Where a new
lighting panel (or a moved lighting panel) with all new raceway
and conductor wiring from the panel to the fixtures is being
installed, controls shall comply with Section 1513.6.
Those motors which are altered or replaced shall comply with
Section 1511.
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-1132, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1132, filed 10/18/93, effective 4/1/94.]
CHAPTER 12DEFINITIONS
Note: | For nonresidential definitions, see Chapter 2. |
AMENDATORY SECTION(Amending WSR 98-03-003, filed 1/8/98,
effective 7/1/98)
WAC 51-11-1312
Glazing and doors.
1312.1 Standard Procedure for Determination of Glazing and Door
U-Factors: U-Factors for glazing and doors shall be determined,
certified and labeled in accordance with Standard RS-31 by a
certified independent agency licensed by the National
Fenestration Rating Council (NFRC). Compliance shall be based on
the Residential or the Nonresidential Model Size. Product
samples used for U-factor determinations shall be production line
units or representative of units as purchased by the consumer or
contractor. Unlabeled glazing and doors shall be assigned the
default U-factor in ((Section 2006)) Table 10-6.
1312.2 Solar Heat Gain Coefficient and Shading Coefficient:
Solar Heat Gain Coefficient (SHGC), shall be determined,
certified and labelled in accordance with the National
Fenestration Rating Council (NFRC) Standard by a certified,
independent agency, licensed by the NFRC.
EXCEPTION: | Shading coefficients (SC) shall be an acceptable alternate for compliance with solar heat gain coefficient requirements. Shading coefficients for glazing shall be taken from Chapter 29 of RS-27 or from the manufacturer's test data. |
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-1312, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1312, filed 10/18/93, effective 4/1/94.]
1313.1 Vapor Retarders: Vapor retarders shall be installed on
the warm side (in winter) of insulation as required by this
section.
EXCEPTION:
Vapor retarder installed with not more than 1/3 of the nominal R-value between it and the conditioned space.
1313.2 Roof/Ceiling Assemblies: Roof/ceiling assemblies where
the ventilation space above the insulation is less than an
average of twelve inches shall be provided with a vapor retarder.
(For enclosed attics and enclosed rafter spaces see Section
1505.3 of the Washington State Building Code.) Roof/ceiling
assemblies without a vented airspace, allowed only where neither
the roof deck nor the roof structure are made of wood, shall
provide a continuous vapor retarder with taped seams.
EXCEPTION:
Vapor retarders need not be provided where all of the insulation is installed between the roof membrane and the
structural roof deck.
1313.3 Walls: Walls separating conditioned space from
unconditioned space shall be provided with a vapor retarder.
1313.4 Floors: Floors separating conditioned space from
unconditioned space shall be provided with a vapor retarder.
1313.5 Crawl Spaces: A ground cover of six mil (0.006 inch
thick) black polyethylene or approved equal shall be laid over
the ground within crawl spaces. The ground cover shall be
overlapped twelve inches minimum at the joints and shall extend
to the foundation wall.
EXCEPTION:
The ground cover may be omitted in crawl spaces if the crawl space has a concrete slab floor with a minimum
thickness of three and one-half inches.
[Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1313, filed 10/18/93, effective 4/1/94.]
For metal frame assemblies used in spaces with electric
resistance space heat, compliance shall be demonstrated with the
component U-factor for the overall assembly based on the
assemblies in Chapter 10.
EXCEPTIONS:
1. Opaque smoke vents are not required to meet insulation requirements.
2. The perimeter edge of an above grade floor slab which penetrates the exterior wall may be left uninsulated
provided that the wall insulation is increased by R-2 above that required in Tables 13-1 and 13-2.
[Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1322, filed 10/18/93, effective 4/1/94.]
EXCEPTIONS:
1. Vertical glazing located on the display side of the street level story of a retail occupancy provided the glazing
((
is double-glazed with a minimum 1/2 inch airspace and))
a. is double-glazed with a minimum 1/2 inch airspace and with a low-e coating having a maximum emittance
of e-0.40 or has an area weighted U-factor of 0.60 or less. (When this exception is used, there are no SHGC
requirements) and,
b. does not exceed 75 percent of the gross exterior wall area of the ((
street level story which does not exceed 20
feet in height.)) display side of the street level story. However, if the display side of the street level story
exceeds 20 feet in height, then this exception may only be used for the first 20 feet of that story.
When this exception is utilized, separate calculations shall be performed for these sections of the building
envelope and these values shall not be averaged with any others for compliance purposes. The 75 percent area
may be exceeded on the street level, if the additional glass area is provided from allowances from other areas of
the building.
2. Single glazing for ornamental, security, or architectural purposes shall be included in the percentage of the
total glazing area, U-factor calculation and SHGC as allowed in the Tables 13-1 or 13-2. The maximum area
allowed for the total of all single glazing is one percent of the gross exterior wall floor area.
1323.1 Area: The percentage of total glazing (vertical and
overhead) area relative to the gross exterior wall area shall not
be greater than the appropriate value from Tables 13-1 or 13-2
for the vertical glazing U-factor, overhead glazing U-factor and
solar heat gain coefficient selected.
1323.2 U-Factor: The area-weighted average U-factor of vertical
glazing shall not be greater than that specified in Tables 13-1
or 13-2 for the appropriate area and solar heat gain coefficient.
The area-weighted average U-factor of overhead glazing shall not
be greater than that specified in Tables 13-1 or 13-2 for the
appropriate area and solar heat gain coefficient. U-factors for
glazing shall be determined in accordance with Section 1312.
1323.3 Solar Heat Gain Coefficient: The area-weighted average
solar heat gain coefficient of all glazing shall not be greater
than that specified in Tables 13-1 or 13-2 for the appropriate
area and U-factor.
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-1323, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1323, filed 10/18/93, effective 4/1/94.]
EXCEPTION:
For buildings or structures utilizing the other space heat type (including heat pumps and VAV) compliance
path, for the gross opaque wall, opaque door and glazing (vertical and overhead) area only, compliance may
also be shown using the ENVSTD diskette version 2.1 ((
or later of Standard RS-9)) of ASHRAE/IESNA
Standard 90.1-1989, or an approved alternative, with the following additional requirements:
1. Only the Exterior Wall Requirements portion of the ENVSTD computer program may be used under this
exception.
2. Overhead glazing shall be added to vertical glazing, and shall be input as 1/4 north, 1/4 east, 1/4 south and
1/4 west facing.
3. Lighting loads shall be determined according to Table 15-1.
4. Equipment loads shall be determined from Table 3-1 of Standard RS-29.
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-1331, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1331, filed 10/18/93, effective 4/1/94.]
Equation 13-1:
Target UA[t]
UAt | = | UratArat + UogratAograt + UortAort + UogortAogort + UwtAwt + UvgtAvgt + UdtAdt + UftAft + FstPst + UbgwtAbgwt |
UAt | = | The target combined specific heat transfer of the gross roof/ceiling assembly, exterior wall and
floor area. |
Where: |
||
Urat | = | The thermal transmittance value for roofs over attics found in Table 13-1 or 13-2. |
Uograt | = | The thermal transmittance for overhead glazing found in Table 13-1 or 13-2 which corresponds
to the proposed total glazing area as a percent of gross exterior wall area. |
Uort | = | The thermal transmittance value for other roofs found in Table 13-1 or 13-2. |
Uogort | = | The thermal transmittance for overhead glazing found in Table 13-1 or 13-2 which corresponds
to the proposed total glazing area as a percent of gross exterior wall area. |
Uwt | = | The thermal transmittance value for opaque walls found in Table 13-1 or 13-2. |
Uvgt | = | The thermal transmittance value for vertical glazing found in Table 13-1 or 13-2 which
corresponds to the proposed total glazing area as a percent of gross exterior wall area. |
Udt | = | The thermal transmittance value for opaque doors found in Table 13-1 or 13-2. |
Uft | = | The thermal transmittance value for floors over unconditioned space found in Table 13-1 or
13-2. |
Fst | = | The F-factor for slab-on-grade and radiant slab floors found in Table 13-1 or 13-2. |
Ubgwt | = | The thermal transmittance value for opaque walls found in Table 13-1 or 13-2. |
Adt | = | The proposed opaque door area, Ad. |
Aft | = | The proposed floor over unconditioned space area, Af. |
Pst | = | The proposed lineal feet of slab-on-grade and radiant slab floor perimeter, Ps. |
Abgwt | = | The proposed below grade wall area, Abgw. |
and; | ||
if the total amount of glazing area as a percent of gross exterior wall area does not exceed the maximum allowed
in Table 13-1 or 13-2: |
||
Arat | = | The proposed roof over attic area, Ara. |
Aograt | = | The proposed overhead glazing area in roofs over attics, Aogra. |
Aort | = | The proposed other roof area, Aor. |
Aogort | = | The proposed overhead glazing area in other roofs, Aogor. |
Awt | = | The proposed opaque above grade wall area, Aw. |
Avgt | = | The proposed vertical glazing area, Avg. |
or; |
||
if the total amount of glazing area as a percent of gross exterior wall area exceeds the maximum allowed in Table
13-1 or 13-2: |
||
Arat | = | The greater of: the proposed roof over attic area, and the gross roof over attic area minus Aograt. |
Aograt | = | The lesser of: proposed overhead glazing area in roofs over attics, and the maximum allowed glazing area from Table 13-1 or 13-2. |
Aort | = | The greater of: the proposed other roof area, and the gross other roof area minus Aogort. |
Aogort | = | The lesser of: the proposed overhead glazing area in other roofs, and the maximum allowed glazing area from Table 13-1 or 13-2 minus Aograt. |
Awt | = | The greater of: proposed opaque above grade wall area, and the gross exterior above grade wall area minus Adt minus Avgt. |
Avgt | = | The lesser of: the proposed vertical glazing area, and the maximum allowed glazing area from Table 13-1 or 13-2 minus Aograt minus Aogort. |
EQUATION 13-2
Proposed UAp
UAp | = | UraAra+UorAor+UogAog+UwAw+UdAd+UvgAvg+UfAf+FsPs+UbgwAbgw |
||
Where: |
||||
UAp | = | The combined proposed specific heat transfer of the gross exterior wall, floor and
roof/ceiling assembly area. |
||
Ura | = | The thermal transmittance of the roof over attic area. | ||
Ara | = | Opaque roof over attic area. |
||
Uor | = | The thermal transmittance of the other roof area. | ||
Aor | = | Opaque other roof area. |
||
Uog | = | The thermal transmittance for the overhead glazing | ||
Aog | = | Overhead glazing area. |
||
Uw | = | The thermal transmittance of the opaque wall area. | ||
Aw | = | Opaque above grade wall area (not including opaque doors). |
||
Uvg | = | The thermal transmittance of the vertical glazing area. | ||
Avg | = | Vertical glazing area. |
||
Ud | = | The thermal transmittance value of the opaque door area. | ||
Ad | = | Opaque door area. |
||
Uf | = | The thermal transmittance of the floor over unconditioned space area. | ||
Af | = | Floor area over unconditioned space. |
||
Fs | = | Slab-on-grade or radiant floor component F-factor. | ||
Ps | = | Lineal feet of slab-on-grade or radiant floor perimeter. |
||
Ubgw | = | The thermal transmittance value of the below grade wall area. | ||
Abgw | = | Below grade wall area as defined in Tables 13-1 or 13-2. |
||
NOTE: Where more than one type of wall, window, roof/ceiling, door and skylight is used, the U and A terms
for those items shall be expanded into sub-elements as: |
||||
Uw1Aw1+Uw2Aw2+Uw3Aw3+...etc. |
EQUATION 13-3
Target SHGCAt
SHGCAt | = | SHGCt (Aograt + Aogort + Avgt) |
||
Where: | ||||
SHGCAt | = | The target combined specific heat gain of the target glazing area. |
||
SHGCt | = | The solar heat gain coefficient for glazing found in Table 13-1 or 13-2 which corresponds to
the proposed total glazing area as a percent of gross exterior wall area, and |
||
Aograt , Aogort , and Avgt are defined under Equation 13-1. |
EQUATION 13-4
Proposed SHGCAp
SHGCAp | = | SHGCogAog + SHGCvgAvg |
Where: |
||
SHGCAt | = | The combined proposed specific heat gain of the proposed glazing area. |
SHGCog | = | The solar heat gain coefficient of the overhead glazing. |
Aog | = | The overhead glazing area. |
SHGCvg | = | The solar heat gain coefficient of the vertical glazing. |
Avg | = | The vertical glazing area. |
BUILDING ENVELOPE REQUIREMENTS FOR CLIMATE ZONE 1
MINIMUM INSULATION R-VALUES OR
MAXIMUM COMPONENT U-FACTORS FOR ZONE 1
Space Heat Type | Components | |||||
Roofs Over Attic |
All Other Roofs | Opaque Walls1,2 | Opaque Doors | Floor Over Uncond Space |
Slab On Grade5 | |
1. Electric resistance heat** | R-38 or U=0.031 | R-30 or U=0.034 | R-19 or
U=0.062(( |
U=0.60 | R-30 or U=0.029 | R-10 or F=0.54 |
2. All others including Heat pumps and VAV | R-30 or U=0.036 | R-21 or U=0.050 | R-11 or U=0.14 | U=0.60 | R-19 or U=0.056 | R-10 or F=0.54 |
** | Compliance with nominal prescriptive R-values requires wood framing. |
MAXIMUM GLAZING SOLAR HEAT GAIN COEFFICIENTS
FOR ZONE 1
Maximum Glazing Area as % of Wall |
0% to 15% | >15% to 20% | >20% to 30% | >30% to 40% | ||||||||
Maximum U-Factor |
Max. SHGC4 | Maximum U-Factor |
Max. SHGC4 | Maximum U-Factor |
Max. SHGC4 | Maximum U-Factor |
Max. SHGC4 | |||||
VG | OG | VG | OG | VG | OG | VG | OG | |||||
1. Electric resistance heat | 0.40 | 0.80 | 1.0 | 0.40 | 0.80 | 1.0 | PRESCRIPTIVE PATH NOT ALLOWED | |||||
2. All others including Heat pumps and VAV | 0.90 | 1.45 | 1.0 | 0.75 | 1.40 | 1.0 | 0.60 | 1.30 | 0.65 | 0.50 | 1.25 | 0.45 |
Footnotes | |
1. | Below Grade Walls: |
When complying by the prescriptive approach, Section 1322: |
a) | walls insulated on the interior shall use opaque wall values, |
b) | walls insulated on the exterior shall use a minimum of R-10 insulation, |
c) | those portions of below grade walls and footings that are more than 10 feet below grade, and not included in the gross exterior wall area, may be left uninsulated. |
When complying by the component performance approach, Section 1331: |
a) | walls insulated on the interior shall use the opaque wall values when determining Ubgwt, |
b) | walls insulated on the exterior shall use a target U-factor of U=0.070 for Ubgwt, |
c) | those portions of below grade walls and footings that are more than 10 feet below grade, and not included in the gross exterior wall area, need not be included when determining Abgwt and Abgw. |
2. | Concrete Masonry Walls: If the area weighted heat capacity of the total opaque above grade wall is a minimum of 9.0 Btu/ft2 F,
then the U-factor may be increased to 0.19 for interior insulation and 0.25 for integral and exterior insulation for insulation position
as defined in Chapter (( |
Maximum Glazing Area as % of Wall |
0 to 10 % | >10 to 15 % | >15% to 20 % | >20% to 25 % | ||||||||
Maximum U-Factor |
Max. SHGC4 | Maximum U-Factor |
Max. SHGC4 | Maximum U-Factor |
Max. SHGC4 | Maximum U-Factor |
Max. SHGC4 | |||||
VG | OG | VG | OG | VG | OG | VG | OG | |||||
1. Electric resistance heat | 0.40 | 0.80 | 1.0 | 0.40 | 0.80 | 1.0 | 0.40 | 0.80 | 1.0 | NOT ALLOWED | ||
2. All others including Heat pumps and VAV | 0.90 | 1.45 | 1.0 | 0.75 | 1.40 | 1.0 | 0.65 | 1.30 | 0.80 | 0.60 | 1.30 | 0.65 |
3. | (( |
4. | SHGC (Solar Heat Gain Coefficient per Section 1312.2): May substitute Maximum Shading Coefficient (SC) for SHGC (See
(( |
5. | Radiant Floors: Where insulation is required under the entire slab, radiant floors shall use a minimum of R-10 insulation or F=0.55 maximum. Where insulation is not required under the entire slab, radiant floors shall use R-10 perimeter insulation according to Section 1311.6 or F=0.78 maximum. |
BUILDING ENVELOPE REQUIREMENTS
FOR CLIMATE ZONE 2
MINIMUM INSULATION R-VALUES OR
MAXIMUM COMPONENT U-FACTORS FOR ZONE 2
Space Heat Type | Components | |||||
Roofs Over Attic |
All Other Roofs | Opaque Walls1,2 | Opaque Doors | Floor Over Uncond Space |
Slab On Grade | |
1. Electric resistance heat** | R-38 or U=0.031 | R-30 or U=0.034 | R-24 or
U=0.044(( |
U=0.60 | R-30 or U=0.029 | R-10 or F=0.54 |
2. All others including Heat pumps and VAV | R-38 or U=0.031 | R-25 or U=0.040 | R-19 or U=0.11 | U=0.60 | R-21 or U=0.047 | R-10 or F=0.54 |
** | Compliance with nominal prescriptive R-values requires wood framing. |
MAXIMUM GLAZING SOLAR HEAT GAIN COEFFICIENTS
FOR ZONE 2
Maximum Glazing Area as % of Wall |
0% to 15% | >15% to 20% | >20% to 25% | >25% to 30% | ||||||||
Maximum U-Factor |
Max. SHGC4 | Maximum U-Factor |
Max. SHGC4 | Maximum U-Factor |
Max. SHGC4 | Maximum U-Factor |
Max. SHGC4 | |||||
VG | OG | VG | OG | VG | OG | VG | OG | |||||
1. Electric resistance heat | 0.40 | 0.80 | 1.0 | 0.40 | 0.80 | 1.0 | PRESCRIPTIVE PATH NOT ALLOWED | |||||
2. All others including Heat pumps and VAV | 0.90 | 1.45 | 1.0 | 0.75 | 1.40 | 1.0 | 0.60 | 1.30 | 0.60 | 0.50 | 1.25 | 0.50 |
Footnotes | |
1. | Below Grade Walls: |
When complying by the prescriptive approach, Section 1322: |
a) | walls insulated on the interior shall use opaque wall values, |
b) | walls insulated on the exterior shall use a minimum of R-12 insulation, |
c) | those portions of below grade walls and footings that are more than 10 feet below grade, and not included in the gross exterior wall area, may be left uninsulated. |
When complying by the component performance approach, Section 1331: |
a) | walls insulated on the interior shall use the opaque wall values when determining Ubgwt, |
b) | walls insulated on the exterior shall use a target U-factor of U=0.061 for Ubgwt, |
c) | those portions of below grade walls and footings that are more than 10 feet below grade, and not included in the gross exterior wall area, need not be included when determining Abgwt and Abgw. |
2. | Concrete Masonry Walls: If the area weighted heat capacity of the total opaque above grade wall is a minimum of 9.0 Btu/ft2 F,
then the U-factor may be increased to 0.19 for interior insulation and 0.25 for integral and exterior insulation for insulation position
as defined in Chapter (( |
Maximum Glazing Area as % of Wall |
0 to 5 % | >5 to 7 % | >7% to 10 % | >10% to 15 % | ||||||||
Maximum U-Factor |
Max. SHGC4 | Maximum U-Factor |
Max. SHGC4 | Maximum U-Factor |
Max. SHGC4 | Maximum U-Factor |
Max. SHGC4 | |||||
VG | OG | VG | OG | VG | OG | VG | OG | |||||
1. Electric resistance heat | 0.40 | 0.80 | 1.0 | 0.40 | 0.80 | 1.0 | 0.40 | 0.80 | 1.0 | NOT ALLOWED | ||
2. All others including Heat pumps and VAV | 0.90 | 1.45 | 1.0 | 0.60 | 1.30 | 0.70 | 0.50 | 1.25 | 0.50 | 0.40 | 0.80 | 0.40 |
3. | (( |
4. | SHGC (Solar Heat Gain Coefficient per Section 1312.2): May substitute Maximum Shading Coefficient (SC) for SHGC (See
(( |
5. | Radiant Floors: Where insulation is required under the entire slab, radiant floors shall use a minimum of R-10 insulation or F=0.55 maximum. Where insulation is not required under the entire slab, radiant floors shall use R-10 perimeter insulation according to Section 1311.6 or F=0.78 maximum. |
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-1334, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1334, filed 10/18/93, effective 4/1/94.]
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040.
AMENDATORY SECTION(Amending WSR 93-21-052, filed 10/18/93,
effective 4/1/94)
WAC 51-11-1410
General requirements.
The building
mechanical system shall comply with Sections 1411 through
((1415)) 1416, Sections 1440 through ((1442)) 1443 and Sections
1450 through 1454, and with one of the following paths:
a. Simple Systems (Packaged Unitary Equipment) Sections 1420
through 1424.
b. Complex Systems Sections 1430 through ((1438)) 1439.
c. Systems Analysis. See Section 1141.4.
Section Number |
Subject | Simple Systems Path |
Complex Systems Path |
Systems Analysis Option |
1410 | General Requirements | X | X | X |
1411 | HVAC Equipment Performance Requirements | X | X | X |
1412 | Controls | X | X | X |
1413 | Air Economizers | X | X | X |
1414 | Ducting Systems | X | X | X |
1415 | Piping Systems | X | X | X |
1416 | Completion Requirements | X | X | X |
1420 | Simple Systems (Packaged Unitary Equipment) | X | ||
1421 | System Type | X | ||
1422 | Controls | X | ||
1423 | Economizers | X | ||
1424 | Separate Air Distribution Systems | X | ||
1430 | Complex Systems | X | ||
1431 | System Type | X | ||
1432 | Controls | X | ||
1433 | Economizers | X | ||
1434 | Separate Air Distribution Systems | X | ||
1435 | Simultaneous Heating and Cooling | X | ||
1436 | Heat Recovery | X | ||
1437 | Electric Motor Efficiency | X | ||
1438 | Variable Flow Systems | X | ||
1439 | Exhaust Hoods | X | ||
RS-29 | Systems Analysis | X | ||
1440 | Service Water Heating | X | X | X |
1441 | Water Heater Installation | X | X | X |
1442 | Shut Off Controls | X | X | X |
1443 | Pipe Insulation | X | X | X |
1450 | Heated Pools | X | X | X |
1451 | General | X | X | X |
1452 | Pool Water Heaters | X | X | X |
1453 | Controls | X | X | X |
1454 | Pool Covers | X | X | X |
[Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1410, filed 10/18/93, effective 4/1/94.]
1411.1 General: Equipment shall have a minimum performance at
the specified rating conditions not less than the values shown in
Tables 14-1 through 14-3. If a nationally recognized
certification program exists for a product covered in Tables 14-1
through 14-3, and it includes provisions for verification and
challenge of equipment efficiency ratings, then the product shall
be listed in the certification program.
1411.2 Rating Conditions: Cooling equipment shall be rated at
ARI test conditions and procedures when available. Where no
applicable procedures exist, data shall be furnished by the
equipment manufacturer.
1411.3 Combination Space and Service Water Heating: For
combination space and service water heaters with a principal
function of providing space heat, the Combined Annual Efficiency
(CAE) may be calculated by using ASHRAE Standard 124-1991. Storage water heaters used in combination space heat and water
heat applications shall have either an Energy Factor (EF) or a
Combined Annual Efficiency (CAE) of not less than the following:
Energy Factor (EF) |
Combined Annual Efficiency (CAE) | |
< 50 gallon storage | 0.58 | 0.71 |
50 to 70 gallon storage | 0.57 | 0.71 |
> 70 gallon storage | 0.55 | 0.70 |
EXCEPTION:
Unstaffed equipment shelters or cabinets used solely for personal wireless service facilities.
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-1411, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1411, filed 10/18/93, effective 4/1/94.]
1412.1 Temperature Controls: Each system shall be provided with
at least one temperature control device. Each zone shall be
controlled by individual thermostatic controls responding to
temperature within the zone. At a minimum, each floor of a
building shall be considered as a separate zone.
1412.2 Deadband Controls: When used to control both comfort
heating and cooling, zone thermostatic controls shall be capable
of a deadband of at least 5 degrees F within which the supply of
heating and cooling energy to the zone is shut off or reduced to
a minimum.
1412.3 Humidity Controls: If a system is equipped with a means
for adding moisture, a humidistat shall be provided.EXCEPTIONS:
1. Special occupancy, special usage, or code requirements where deadband controls are not appropriate.
2. Buildings complying with Section 1141.4, if in the proposed building energy analysis, heating and cooling
thermostat setpoints are set to the same temperature between 70 degrees F and 75 degrees F inclusive, and
assumed to be constant throughout the year.
3. Thermostats that require manual changeover between heating and cooling modes.
1412.4 Setback and Shut-Off: HVAC systems shall be equipped with
automatic controls capable of accomplishing a reduction of energy
use through control setback or equipment shutdown during periods
of non-use or alternate use of the spaces served by the system. The automatic controls shall have a minimum seven-day clock and
be capable of being set for seven different day types per week.
1412.4.1 Dampers: Outside air intakes, exhaust outlets and
relief outlets serving conditioned spaces shall be equipped with
dampers which close automatically when the system is off or upon
power failure.EXCEPTIONS:
1. Systems serving areas which require continuous operation at the same temperature setpoint.
2. Equipment with full load demands of 2 Kw (6,826 Btu/h) or less may be controlled by readily accessible
manual off-hour controls.
EXCEPTIONS:
1. Systems serving areas which require continuous operation.
2. Combustion air intakes.
1412.4.2 Optimum Start Controls: Heating and cooling systems
with design supply air capacities exceeding 10,000 cfm shall have
optimum start controls. Optimum start controls shall be designed
to automatically adjust the start time of an HVAC system each day
to bring the space to desired occupied temperature levels
immediately before scheduled occupancy. The control algorithm
shall, as a minimum, be a function of the difference between
space temperature and occupied setpoint and the amount of time
prior to scheduled occupancy.
1412.5 Heat Pump Controls: Unitary air cooled heat pumps shall
include microprocessor controls that minimize supplemental heat
usage during start-up, set-up, and defrost conditions. These
controls shall anticipate need for heat and use compression
heating as the first stage of heat. Controls shall indicate when
supplemental heating is being used through visual means (e.g.,
LED indicators).
1412.6 Combustion Heating Equipment Controls: Combustion heating
equipment with a capacity over 225,000 Btu/h shall have
modulating or staged combustion control.
1412.7 Balancing: Each air supply outlet or air or water
terminal device shall have a means for balancing, including but
not limited to, dampers, temperature and pressure test
connections and balancing valves.EXCEPTIONS:
Boilers.
Radiant heaters.
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-1412, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1412, filed 10/18/93, effective 4/1/94.]
1414.1 Sealing: Duct work which is designed to operate at
pressures above 1/2 inch water column static pressure shall be
sealed in accordance with Standard RS-18. Extent of sealing
required is as follows:
1. | Static pressure: 1/2 inch to 2 inches; seal transverse joints. |
2. | Static pressure: 2 inches to 3 inches; seal all transverse joints and longitudinal seams. |
3. | Static pressure: Above 3 inches; seal all transverse joints, longitudinal seams and duct wall penetrations. |
1414.2 Insulation: Ducts and plenums that are constructed and
function as part of the building envelope, by separating interior
space from exterior space, shall meet all applicable requirements
of Chapter 13. These requirements include insulation
installation, moisture control, air leakage, and building
envelope insulation levels. Unheated equipment rooms with
combustion air louvers must be isolated from the conditioned
space by insulating interior surfaces to a minimum of R-11 and
any exterior envelope surfaces per Chapter 13. Outside air ducts
serving individual supply air units with less than 2,800 cfm of
total supply air capacity shall be insulated to a minimum of R-7
and are not considered building envelope. Other outside air duct
runs are considered building envelope until they,
1. connect to the heating or cooling equipment, or
2. are isolated from the exterior with an automatic shut-off damper complying with Section 1412.4.1.
Once outside air ducts meet the above listed requirements,
any runs within conditioned space ((must)) shall comply with
Table 14-5 requirements.
Other ducts and plenums shall be thermally insulated per Table 14-5.
EXCEPTIONS: | 1. Within the HVAC equipment. |
2. Exhaust air ducts not subject to condensation. |
3. Exposed ductwork within a (( |
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-1414, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1414, filed 10/18/93, effective 4/1/94.]
1415.1 Insulation: Piping shall be thermally insulated in
accordance with Table 14-6.
EXCEPTION: | Piping installed within unitary HVAC equipment. |
[Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1415, filed 10/18/93, effective 4/1/94.]
1416.1 Drawings: Construction documents shall require that
within 90 days after the date of system acceptance, record
drawings of the actual installation be provided to the building
owner. Record drawings shall include as a minimum the location
and performance data on each piece of equipment, general
configuration of duct and pipe distribution system, including
sizes, and the terminal air and water design flow rates.
1416.2 Manuals: Construction documents shall require an
operating manual and maintenance manual be provided to the
building owner. The manual shall be in accordance with industry
accepted standards and shall include, at a minimum, the
following:
1. Submittal data stating equipment size and selected
options for each piece of equipment requiring maintenance.
2. Operation and maintenance manuals for each piece of
equipment requiring maintenance, except equipment not furnished
as part of the project. Required routine maintenance actions
shall be clearly identified.
3. Names and addresses of at least one service agency.
4. HVAC controls system maintenance and calibration
information, including wiring diagrams, schematics, and control
sequence descriptions. Desired or field determined set points
shall be permanently recorded on control drawings at control
devices, or, for digital control systems, in programming
comments.
5. A complete narrative of how each system is intended to
operate including suggested set points.
1416.3 System Balancing
1416.3.1 General: Construction documents shall require that all
HVAC systems be balanced in accordance with generally accepted
engineering standards. Air and water flow rates shall be
measured and adjusted to deliver final flow rates within 10% of
design rates, except variable flow distribution systems need not
be balanced upstream of the controlling device (for example, VAV
box or control valve). Construction documents shall require a
written balance report be provided to the owner.
1416.3.2 Air System Balancing: Air systems shall be balanced in
a manner to first minimize throttling losses then, for fans with
system power of greater than 1 hp, fan speed shall be adjusted to
meet design flow conditions.
1416.3.3 Hydronic System Balancing: Hydronic systems shall be
proportionately balanced in a manner to first minimize throttling
losses, then the pump impeller shall be trimmed or pump speed
shall be adjusted to meet design flow conditions. Each hydronic
system shall have either the ability to measure pressure across
the pump, or test ports at each side of each pump.
EXCEPTIONS: | 1. Pumps with pump motors of 10 hp or less. |
2. When throttling results in no greater than 5% of the nameplate horsepower draw above that required if the impeller were trimmed. |
1416.4.1 Simple Systems: For simple systems, as defined in
Section 1421, and for warehouses and semi-heated spaces, HVAC
control systems shall be tested to ensure that control devices,
components, equipment and systems are calibrated, adjusted and
operate in accordance with approved plans and specifications.
Sequences of operation shall be functionally tested to ensure
they operate in accordance with approved plans and
specifications. A complete report of test procedures and results
shall be prepared and filed with the owner. Drawing notes shall
require commissioning in accordance with this paragraph.
1416.4.2 Other Systems: All other HVAC control systems, and
other automatically controlled systems for which energy
consumption, performance, or mode of operation are regulated by
this code, shall be tested to ensure that control devices,
equipment and systems are calibrated, adjusted and operate in
accordance with approved plans and specifications. Sequences of
operation shall be functionally tested to ensure they operate in
accordance with approved plans and specifications.
1416.4.2.1 Documentation: Drawing notes shall require
commissioning in accordance with this section. Drawing notes may
refer to specifications for further commissioning requirements.
Plans and specifications shall require tests mandated by this
section be performed and the results recorded. Plans and
specifications shall require preparation of preliminary and final
reports of test procedures and results as described in Section
1416.4.2.2. Plans and specifications shall identify the
following for each test:
1. Equipment and systems to be tested, including the extent
of sampling tests,
2. Functions to be tested (for example calibration,
economizer control, etc.),
3. Conditions under which the test shall be performed (for
example winter design conditions, full outside air, etc.),
4. Measurable criteria for acceptable performance.
1416.4.2.2 Commissioning Reports
1416.4.2.2.1 Preliminary Commissioning Report: A preliminary
commissioning report of test procedures and results shall be
prepared. The preliminary report shall identify:
1. Deficiencies found during testing required by this
section which have not been corrected at the time of report
preparation and the anticipated date of correction.
2. Deferred tests which cannot be performed at the time of
report preparation due to climatic conditions.
3. Climatic conditions required for performance of the
deferred tests, and the anticipated date of each deferred test.
1416.4.2.2.2 Final Commissioning Report: A complete report of
test procedures and results shall be prepared and filed with the
owner.
1416.4.2.3 Acceptance: Buildings or portions thereof, required
by this code to comply with this section, shall not be issued a
final certificate of occupancy until such time that the building
official determines that the preliminary commissioning report
required by this section has been completed.
[]
The total capacity of all units without economizers shall
not exceed 240,000 Btu/h per building, or 10% of its aggregate
cooling (economizer) capacity, whichever is greater. That
portion of the equipment serving Group R occupancy is not
included in determining the total capacity of all units without
economizers in a building.
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-1423, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1423, filed 10/18/93, effective 4/1/94.]
a. | Single package unitary fan-cooling units with a supply capacity of greater than 1,900 cfm or a total cooling capacity greater than 54,000 Btu/h. |
b. | Other individual fan-cooling units with a supply capacity of greater than 2,800 cfm or a total cooling capacity greater than 84,000 Btu/h. |
EXCEPTIONS: | 1. Systems with air or evaporatively cooled condensers and that either one of the following can be demonstrated to the satisfaction of the enforcing agency: |
a. Special outside air filtration and treatment, for the reduction and treatment of unusual outdoor contaminants, makes an air economizer infeasible. | |
b. The use of outdoor air cooling affects the operation of other systems (such as humidification, dehumidification, and supermarket refrigeration systems) so as to increase the overall building energy consumption. | |
2. Systems for which at least 75 percent of the annual energy used for mechanical cooling is provided from site-recovery or site-solar energy source. | |
3. A water economizer system, which is capable of cooling supply air by indirect evaporation. Such a system shall be designed and capable of being controlled to provide 100 percent of the expected system cooling load at outside air temperatures of 50 degrees F dry-bulb/45 degrees F wet-bulb and below. For this calculation, all factors including solar and internal load shall be the same as those used for peak load calculations, except for the outside air temperatures. |
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-1433, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1433, filed 10/18/93, effective 4/1/94.]
a. | Reheating for temperature control. |
b. | Recooling for temperature control. |
c. | Mixing or simultaneous supply of air that has been
previously mechanically heated and air that has been
previously cooled, either by economizer systems(( |
d. | Other simultaneous operation of heating and cooling systems to the same zone. |
e. | Reheating for humidity control. |
EXCEPTIONS: | (( |
1. Zones for which the volume of air that is reheated, recooled, or mixed is no greater than the larger of the following: | |
i. The volume of air required to meet the ventilation requirements of the Washington State Ventilation and Indoor Air Quality Code for the zone. | |
ii. 0.4 cfm/ft2 of the zone conditioned floor area, provided that the temperature of the primary system air is, by design or through reset controls, 0-12F below the design space heating temperature when outside air temperatures are below 60F for reheat systems and the cold deck of mixing systems and 0-12F above design space temperature when outside air temperatures are above 60F for recooling systems and the hot deck of mixing systems. For multiple zone systems, each zone need not comply with this exception provided the average of all zones served by the system that have both heating and cooling ability comply. | |
iii. 300 cfm. This exception is for zones whose peak flow rate totals no more than 10% of the total fan system flow rate. | |
iv. Any higher rate that can be demonstrated, to the satisfaction of the building official, to reduce overall system annual energy usage by offsetting reheat/recool energy losses through a reduction in outdoor air intake in accordance with the multiple space requirements defined in ASHRAE Standard 62. | |
2. Zones where special pressurization relationships, cross-contamination requirements, or code-required minimum circulation rates are such that variable air volume systems are impractical. | |
3. Zones where at least 75% of the energy for reheating or for providing warm air in mixing systems is provided from a site-recovered (including condenser heat) or site solar energy source. | |
4. Zones where specific humidity levels are required to satisfy process needs, such as computer rooms, museums, surgical suites, and buildings with refrigerating systems, such as supermarkets, refrigerated warehouses, and ice arenas. |
[Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1435, filed 10/18/93, effective 4/1/94.]
[Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1438, filed 10/18/93, effective 4/1/94.]
1439.1 Kitchen Hoods. Individual kitchen exhaust hoods larger
than 5000 cfm shall be provided with make-up air sized so that at
least 50% of exhaust air volume be (a) unheated or heated to no
more than 60F and (b) uncooled or cooled without the use of
mechanical cooling.
EXCEPTIONS: | 1. Where hoods are used to exhaust ventilation air which would otherwise exfiltrate or be exhausted by other fan systems. |
2. Certified grease extractor hoods that require a face velocity no greater than 60 fpm. |
(a) Variable air volume hood exhaust and room supply systems capable of reducing exhaust and make-up air volume to 50% or less of design values.
(b) Direct make-up (auxiliary) air supply equal to at least 75% of the exhaust rate, heated no warmer than 2F below room set point, cooled to no cooler than 3F above room set point, no humidification added, and no simultaneous heating and cooling used for dehumidification control.
(c) Heat recovery systems to precondition make-up air in accordance with Section 1436, without using any exception.
(d) Constant volume fume hood designed and installed to operate at less than 50 fpm face velocity.
[]
[]
TABLE 14-1
Standard Rating Conditions and Minimum Performance for
Air Cooled Unitary Air Conditioners, Heat Pumps, Packaged Terminal Air Conditioners,
Warm Air Furnaces, Duct Furnaces and Unit Heaters
Equipment Type & Rating |
Category | Sub-category & Rating Conditions |
Minimum Rating | Standard | |
Steady State | Seasonal or Part Load |
||||
Air Conditioners and Heat Pumps Cooling Ratings |
≤65,000 Btu/h Cooling Capacity |
Split Systems Single Package |
NA NA |
10.0 SEER 9.7 SEER |
ARI 210/240 -1989 |
>65,000 and ≤135,000 Btu/h Cooling Capacity |
All Unitary Standard Ratings: |
8.9 EER 95F db |
8.3 IPLV 80F db |
||
>135,000 and ≤760,000 Btu/h1 Cooling Capacity |
Air Conditioners Heat Pumps |
8.5 EER 8.5 EER |
7.5 IPLV 7.5 IPLV |
ARI 360 -1986 |
|
>760,000 Btu/h1 Cooling Capacity |
Air Conditioners Heat Pumps |
8.2 EER 8.7 EER |
7.5 IPLV 7.5 IPLV |
||
Packaged Term. Air Conditioners & Heat Pumps Cooling Ratings |
All Capacities | Air Conditioners and Heat Pumps Standard/Low Temp[:] |
10.0 - (0.16 x Cap/1000)3 EER 95F` |
12.2 - (0.20 x Cap/1000)2,3 EER 82F |
ARI 310 -1990 |
Heat Pump Heating Ratings |
≤65,000 Btu/h Cooling Capacity |
Split Systems Single Package |
6.8 HSPF 6.6 HSPF |
ARI 210/240 -1989 |
|
>65,000 and ≤135,000 Btu/h Cooling Capacity |
All Unitary Standard Ratings: |
3.0 COP 47F db/43F wb |
2.0 COP 17F db/15F wb |
||
>135,000 Btu/h Cooling Capacity |
Standard Ratings[:] |
2.9 COP 47F |
2.0 COP 17F |
ARI 365 -1986 |
|
Packaged Term. Heat Pumps Heating Ratings |
All Capacities | Heat Pumps Standard Ratings[:] |
2.9 - (0.026 x Cap/1000)3 (( 47F db/ 43F wb |
ARI 380 -1990 |
|
Warm Air Furnaces & Combination Furnace/A.C. |
<225,000 Btu/h | Gas and Oil Fired Seasonal Ratings[:] |
80% Et4 | 78% AFUE5 | DOE 10 CFR Part430 AppN |
≥225,000 Btu/h | Gas, Max Rating6 Gas, Min Rating6 |
80% Et4 78% Et4 |
NA NA |
ANSI Z21.47 -1983 |
|
≥225,000 Btu/h | Oil, Max Rating6 Oil, Min Rating6 |
81% Et4 81% Et4 |
NA NA |
UL 727 -1986 |
|
Warm-Air Duct Furnaces and Unit Heaters |
All Size Gas Duct Furnaces |
Max Rated Capacity6 Min Rated Capacity6 |
78% Et4 75% Et4 |
NA NA |
ANSI Z83.9 -1986 |
All Size Gas Unit Heaters |
Max Rated Capacity6 Min Rated Capacity6 |
78% Et4 74% Et4 |
NA NA |
ANSI Z83.8 -1985 |
|
All Size Oil Unit Heaters |
Max Rated Capacity6 Min Rated Capacity6 |
81% Et4 81% Et4 |
NA NA |
UL 731 -1988 |
1. | For units that have a heating section, deduct 0.2 from all required EER's and IPLV's. |
2. | For multi-capacity equipment the minimum performance shall apply to each step provided Multi-capacity refers to manufacturer published rating for more than one capacity mode allowed by the product's controls. |
3. | Capacity (Cap) means the rated cooling capacity of the product in Btu/h in accordance with the cited ARI standard. If the unit's capacity is less than 7,000 Btu/h, use 7,000 Btu/h in the calculation. If the unit's capacity is greater than 15,000 Btu/h, use 15,000 Btu/h in the calculation. |
4. | These values apply to non-NAECA equipment. See referenced standard for definition of Thermal efficiency (Et), (100% flue losses). |
TABLE 14-2
Standard Rating Conditions and Minimum Performance for
Water and Evaporatively Cooled Unitary Air Conditioners, Heat Pumps, Water Source and Ground Source
Heat Pumps, Condensing Units, and Water Chilling Packages
Equipment Type & Rating |
Category | Sub-category & Rating Conditions |
Minimum Rating | Standard | |
Steady State | Seasonal or Part Load |
||||
Evaporatively Cooled A/Cs & Heat Pumps Cooling Ratings |
≤65,000 Btu/h Cooling Capacity |
Standard Conditions1: Outdoor Conditions: 95F db/75F wb |
9.3 EER | 8.5 IPLV | ARI 210/240 -1989 CTI 201 -1986 |
>65,000 and ≤135,000 Btu/h Cooling Capacity |
10.5 EER | 9.7 IPLV | |||
Water Source Heat Pump Cooling Ratings |
≤65,000 Btu/h Cooling Capacity |
Standard Conditions1: Entering Water[:] |
9.3 EER 85F ewt2 |
10.2 EER 75F ewt2 |
ARI 320 -1986 CTI 201 -1986 |
>65,000 and ≤135,000 Btu/h Cooling Capacity |
Standard Conditions1: Entering Water[:] |
10.5 EER 85F ewt2 |
NA | ||
Ground Water Heat Pump Cooling Ratings |
<135,000 Btu/h Cooling Capacity |
Standard Conditions1: Entering Water[:] |
11.0 EER 70F ewt2 |
11.5 EER 50F ewt2 |
ARI 325 -1985 |
Water Cooled Unitary Air Conditioners Cooling Ratings |
≤65,000 Btu/h Cooling Capacity |
Standard Conditions1: Entering Water[:] |
9.3 EER 85F ewt2 |
8.3 IPLV 75F ewt2 |
ARI 210/240 -1989 CTI 201 -1986 |
>65,000 and ≤135,000 Btu/h Cooling Capacity |
Standard Conditions1: Entering Water[:] |
10.5 EER 85F ewt2 |
NA | ||
Water/Evap Cooled Air Cond. and Heat Pumps Cooling Ratings |
>135,000 Btu/h Cooling Capacity |
Standard Conditions1: | 9.6 EER | 9.0 IPLV | ARI 360 -1986 CTI 201 -1986 |
Air and Water/Evap Cooled Condensing Units Cooling Ratings3 | >135,000 Btu/h Cooling Capacity |
Air Cooled Water/Evap Cooled |
9.9 EER 12.9 EER |
11.0 IPLV 12.9 IPLV |
ARI 365 -1987 CTI 201 -1986 |
Air and Water Cooled Water Chilling Packages Cooling Ratings | <150 Tons ≥150 and <300 Tons ≥300 Tons |
Water Cooled | 3.8 COP 4.2 COP 5.2 COP4 |
3.9 IPLV 4.5 IPLV 5.3 IPLV4 |
ARI 550-90 ARI 590-86pN CTI 201 -1986 |
<150 Tons ≥150 Tons |
Air Cooled with Condenser |
2.7 COP 2.5 COP |
2.8 IPLV 2.5 IPLV |
||
All Capacities | Air Cooled Condenserless |
3.1 COP | 3.2 IPLV | ||
Water & Ground-Water Source Heat Pumps Heating Ratings | <135,000 Btu/h Cooling Capacity |
Water Source Standard Conditions1: |
3.8 COP 70F ewt2 |
NA NA |
ARI 320 -1986 |
Ground Water Source Standard Conditions1: | 3.4 COP 70F ewt2 |
3.0 COP 50F ewt2 |
ARI 325 -1985 |
1. | Standard Indoor Conditions: 80F dry bulb and 67F wet bulb. |
2. | ewt: Entering Water Temperature for water cooled heat pumps and air conditioners. |
3. | Condensing unit requirements are based on single - number rating defined in paragraph 5.1.3.2 of ARI Standard 365. |
4. | These requirements are reduced to 4.7 COP and 4.8 IPLV, where refrigerants with ozone depletion factors of 0.05 or less are used. No reduction is allowed for standard design systems analyzed under RS-29. |
TABLE 14-3
Standard Rating Conditions and Minimum Performance,
Gas- and Oil-Fired Boilers
Reference | Category | Rating Condition | Minimum Performance |
DOE Test Procedure 10 CFR, Part 430 AppN |
Gas-Fired <300,000 Btu/h |
Seasonal Rating |
AFUE 80%1,3 |
Oil-Fired <300,000 Btu/h |
Seasonal Rating |
AFUE 80%1 |
|
ANSI Z21.13-87 H.I. Htg. Boiler Std. 86 ASME PTC4.1-64 U.L. 795-73 |
Gas-Fired ≥300,000 Btu/h |
1. Max. Rated Capacity2 Steady-State |
Ec4 80% |
2. Min. Rated Capacity2 Steady-State | Ec4 80% |
||
U.L. 726-75 H.I. Htg. Boiler Std. 86 ASME PTC4.1-64 |
Oil-Fired ≥300,000 Btu/h |
1. Max. Rated Capacity2 Steady-State |
Ec4 83% |
2. Min. Rated Capacity2 Steady-State | Ec4 83% |
||
H.I. Htg. Boiler Std. 86 ASME PTC4.1-64 |
Oil-Fired (Residual) ≥300,000 Btu/h |
1. Max. Rated Capacity2 Steady-State |
Ec4 83% |
2. Min. Rated Capacity2 Steady-State | Ec4 83% |
1. | To be consistent with National Appliance Energy Conservation Act of 1987 (P.L. 100-12). |
2. | Provided and allowed by the controls. |
3. | Except for gas-fired steam boilers for which minimum AFUE is 75%. |
4. | Ec= combustion efficiency, 100% - flue losses. See reference document for detailed information. |
TABLE 14-4
Energy Efficient Electric Motors
Minimum Nominal Full-Load Efficiency
Open Motors | Closed Motors | |||||
Synchronous Speed (RPM) |
3,600 | 1,800 | 1,200 | 3,600 | 1,800 | 1,200 |
HP | Efficiency | Efficiency | Efficiency | Efficiency | Efficiency | Efficiency |
1.0 | - | 82.5 | 80.0 | 75.5 | 82.5 | 80.0 |
1.5 | 82.5 | 84.0 | 84.0 | 82.5 | 84.0 | 85.5 |
2.0 | 84.0 | 84.0 | 85.5 | 84.0 | 84.0 | 86.5 |
3.0 | 84.0 | 86.5 | 86.5 | 85.5 | 87.5 | 87.5 |
5.0 | 85.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 |
7.5 | 87.5 | 88.5 | 88.5 | 88.5 | 89.5 | 89.5 |
10.0 | 88.5 | 89.5 | 90.2 | 89.5 | 89.5 | 89.5 |
15.0 | 89.5 | 91.0 | 90.2 | 90.2 | 91.0 | 90.2 |
20.0 | 90.2 | 91.0 | 91.0 | 90.2 | 91.0 | 90.2 |
25.0 | 91.0 | 91.7 | 91.7 | 91.0 | 92.4 | 91.7 |
30.0 | 91.0 | 92.4 | 92.4 | 91.0 | 92.4 | 91.7 |
40.0 | 91.7 | 93.0 | 93.0 | 91.7 | 93.0 | 93.0 |
50.0 | 92.4 | 93.0 | 93.0 | 92.4 | 93.0 | 93.0 |
60.0 | 93.0 | 93.6 | 93.6 | 93.0 | 93.6 | 93.6 |
75.0 | 93.0 | 94.1 | 93.6 | 93.0 | 94.1 | 93.6 |
100.0 | 93.0 | 94.1 | 94.1 | 93.6 | 94.5 | 94.1 |
125.0 | 93.6 | 94.5 | 94.1 | 94.5 | 94.5 | 94.1 |
150.0 | 93.6 | 95.0 | 94.5 | 94.5 | 95.0 | 95.0 |
200.0 | 94.5 | 95.0 | 94.5 | 95.0 | 95.0 | 95.0 |
TABLE 14-5
Duct Insulation
Duct Type | Duct (( |
Insulation R-Value |
Other Requirements |
Supply, Return | Not within conditioned space: On exterior of building, on roof, in attic, in enclosed ceiling space, in walls, in garage, in crawl spaces | R-7 | Approved weather proof barrier |
Outside air intake | Within conditioned space | R-7 | See Section 1414.2 |
Supply, Return, Outside air intake | Not within conditioned space: in concrete, in ground | R-5.3 | |
Supply with supply air temperature <55F or >105F | Within conditioned space | R-3.3 |
Note: | Requirements apply to (( |
TABLE 14-6
Minimum Pipe Insulation (inches)1
Fluid Design Operating Temp. Range, F |
Insulation Conductivity | Nominal Pipe Diameter (in.) | ||||||
Conductivity Range Btu in. / (h ft2 F) |
Mean Rating Temp. F |
Runouts2 up to 2 |
1 and less |
>1 to 2 | >2 to 4 | >4 to 6 | >6 | |
Heating systems (Steam, Steam Condensate[,] and Hot water) | Nominal Insulation Thickness | |||||||
Above 350 251-350 201-250 141-200 105-140 |
0.32-0.34 0.29-0.31 0.27-0.30 0.25-0.29 0.24-0.28 |
250 200 150 125 100 |
1.5 1.5 1.0 0.5 0.5 |
2.5 2.0 1.5 1.5 1.0 |
2.5 2.5 1.5 1.5 1.0 |
3.0 2.5 2.0 1.5 1.0 |
3.5 3.5 2.0 1.5 1.5 |
3.5 3.5 3.5 1.5 1.5 |
Domestic and Service Hot Water Systems | ||||||||
105 and Greater | 0.24-0.28 | 100 | 0.5 | 1.0 | 1.0 | 1.5 | 1.5 | 1.5 |
Cooling Systems (Chilled Water, Brine[,] and Refrigerant) | ||||||||
40-55 Below 40 |
0.23-0.27 0.23-0.27 |
75 75 |
0.5 1.0 |
0.5 1.0 |
0.75 1.5 |
1.0 1.5 |
1.0 1.5 |
1.0 1.5 |
1. | Alternative Insulation Types. Insulation thicknesses in Table 14-6 are based on insulation with thermal conductivities within the range listed in Table14-6 for each fluid operating temperature range, rated in accordance with ASTM C 335-84 at the mean temperature listed in the table. For insulation that has a conductivity outside the range shown in Table 14-6 for the applicable fluid operating temperature range at the mean rating temperature shown (when rounded to the nearest 0.01 Btu in./(hft2F)), the minimum thickness shall be determined in accordance with the following equation: |
T= PR[[(]1+ t/PR)K/k - 1] |
Where |
T= | Minimum insulation thickness for material with conductivity K, inches. |
PR= | Pipe actual outside radius, inches[.] |
t= | Insulation thickness from Table 14-6, inches |
K= | conductivity of alternate material at the mean rating temperature indicated in Table 14-6 for the applicable fluid temperature range, Btu in[.]/(hft2 F) |
k= | the lower value of the conductivity range listed in Table 14-6 for the applicable fluid temperature range, Btu in[.]/(h ft2 F) |
2. | Runouts to individual terminal units not exceeding 12 ft. in length. |
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-1454, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1454, filed 10/18/93, effective 4/1/94.]
Reviser's note: The brackets and enclosed material in the text of the above section occurred in the copy filed by the agency and appear in the Register pursuant to the requirements of RCW 34.08.040.
AMENDATORY SECTION(Amending WSR 98-03-003, filed 1/8/98,
effective 7/1/98)
WAC 51-11-1512
Exempt lighting.
1512.1 Exempt Spaces: The following rooms, spaces, and areas, are
exempt from the lighting power requirements in Sections 1520 and
1530 but shall comply with all other requirements of this
chapter.
1. | Areas in which medical or dental tasks are performed. |
2. | High risk security areas or any area identified by building officials as requiring additional lighting. |
3. | Spaces designed for primary use by the visually impaired, hard of hearing (lip-reading) or by senior citizens. |
4. | Food preparation areas. |
5. | Outdoor manufacturing, greenhouses, and processing areas. |
6. | Electrical/mechanical equipment rooms. |
7. | Outdoor athletic facilities. |
8. | Inspection and restoration areas in galleries and museums. |
9. | The sanctuary portion of a house of worship, defined as the space or room where the worship service takes place. Classrooms, meeting rooms, offices and multipurpose rooms that are part of the same facility are not exempt. |
1. | Special lighting needs for research. |
2. | Emergency lighting that is automatically OFF during normal building operation. |
3. | Lighting integral to signs, and permanently ballasted lighting fixtures for walkways and pathways. |
4. | Lighting that is part of machines, equipment or furniture. |
5. | Lighting that is used solely for indoor plant growth during the hours of 10:00 p.m. to 6:00 a.m. |
6. | Lighting for theatrical productions, television broadcasting (including sports facilities), audio-visual presentations, and special effects lighting for stage areas and dance floors in entertainment facilities. |
7. | Lighting for art exhibits, non-retail displays, portable plug in display fixtures, and show case lighting. |
8. | Exterior lighting for public monuments. |
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-1512, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1512, filed 10/18/93, effective 4/1/94.]
1513.1 Local Control and Accessibility: Each space, enclosed by
walls or ceiling-height partitions, shall be provided with
lighting controls located within that space. The lighting
controls, whether one or more, shall be capable of turning off
all lights within the space. The controls shall be readily
accessible, at the point of entry/exit, to personnel occupying or
using the space.
EXCEPTIONS: | The following lighting controls may be centralized in remote locations: |
1. Lighting controls for spaces which must be used as a whole. | |
2. Automatic controls. | |
3. Controls requiring trained operators. | |
4. Controls for safety hazards and security. |
EXCEPTIONS:
1. Industrial or manufacturing process areas, as may be required for production.
2. Areas less than five percent of footprint for footprints over 100,000 square feet.
1513.3 Daylight Zone Control: All daylighted zones, as defined
in Chapter ((12)) 2, both under overhead glazing and adjacent to
vertical glazing, shall be provided with individual controls, or
daylight-or occupant-sensing automatic controls, which control
the lights independent of general area lighting.
Contiguous daylight zones adjacent to vertical glazing are allowed to be controlled by a single controlling device provided that they do not include zones facing more than two adjacent cardinal orientations (i.e. north, east, south, west). Daylight zones under overhead glazing more than 15 feet from the perimeter shall be controlled separately from daylight zones adjacent to vertical glazing.
EXCEPTION: | Daylight spaces enclosed by walls or ceiling height partitions and containing 2 or fewer light fixtures are not required to have a separate switch for general area lighting. |
1513.5 Automatic Shut-Off Controls, Exterior: Exterior lighting
not intended for 24-hour continuous use shall be automatically
switched by timer, photocell, or a combination of timer and
photocell. Automatic time switches must also have program
back-up capabilities, which prevent the loss of program and time
settings for at least 10 hours, if power is interrupted.
1513.6 Automatic Shut-Off Controls, Interior: Office buildings
greater than ((25,000)) 5,000 sq. ft. and all school classrooms
shall be equipped with separate automatic controls to shut off
the lighting during unoccupied hours. Automatic controls may be
an occupancy sensor, time switch, or other device capable of
automatically shutting off lighting.
EXCEPTIONS: | 1. Areas that must be continuously illuminated, or illuminated in a manner requiring manual operation of the lighting. |
2. Emergency lighting systems. | |
3. Switching for industrial or manufacturing process facilities as may be required for production. |
1513.6.2 Automatic Time Switches: Automatic time switches shall
have a minimum 7 day clock and be capable of being set for 7
different day types per week and incorporate an automatic holiday
"shut-off" feature, which turns off all loads for at least 24
hours and then resumes normally scheduled operations. Automatic
time switches shall also have program back-up capabilities, which
prevent the loss of program and time settings for at least 10
hours, if power is interrupted.
Automatic time switches shall incorporate an over-ride switching device which:
a. | is readily accessible; |
b. | is located so that a person using the device can see the lights or the areas controlled by the switch, or so that the area being illuminated is annunciated; and |
c. | is manually operated; |
d. | allows the lighting to remain on for no more than two hours when an over-ride is initiated; and |
e. | controls an area not exceeding 5,000 square feet or 5 percent of footprint for footprints over 100,000 square feet, whichever is greater. |
[Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1513, filed 10/18/93, effective 4/1/94.]
a. one- or two-lamp (but not three-or more lamp);
b. non-lensed, fluorescent fixtures;
c. fitted with type T-1, T-2, T-4, T-5, T-6, T-8 ((or PL
type)) or compact fluorescent lamps from 5 to 50 watts (but not
T-10 or T-12 lamps); and
d. electronic ballasts (electronic ballasts that screw into medium base sockets do not comply with this section).
EXCEPTIONS:
1. Up to a total of 5 percent of installed lighting fixtures need not be ballasted and may use any type of lamp.
2. Clear safety lenses are allowed in food prep and serving areas and patient care areas in otherwise compliant
fixtures.
3. Exit lights are not included in the count of fixtures provided that they do not exceed 5 watts per fixture and
are light emitting diode (LED) type or T-1 fluorescent type only. (See the Uniform Fire Code for face
illumination footcandle requirements and other requirements.)
[Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1521, filed 10/18/93, effective 4/1/94.]
The wattage used for any unballasted fixture shall be the
maximum UL listed wattage for that fixture regardless of the lamp
installed. The wattage used for track lighting shall be:
a. for line voltage track, 50 watts per lineal foot of track or actual luminare wattage, whichever is greater
b. for low voltage track, 25 watts per lineal foot of track or the VA rating of the transformer, whichever is greater.
No credit towards compliance with the lighting power
allowances shall be given for the use of any controls, automatic
or otherwise.
Exit lights that are 5 watts or less per fixture shall not
be included in the lighting power allowance calculations. Other
exit lights shall be included in the lighting power allowance
calculations.
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-1530, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1530, filed 10/18/93, effective 4/1/94.]
((If multiple uses are intended,)) The lighting power
allowance for each ((type of)) use shall be separately calculated
and summed to obtain the interior lighting power allowance.
In cases where a lighting plan for only a portion of a
building is submitted, the interior lighting power allowance
shall be based on the gross interior floor area covered by the
plan. Plans submitted for common areas only, including
corridors, lobbies and toilet facilities shall use the lighting
power allowance for common areas in Table 15-1.
When insufficient information is known about the specific
use of the space, the allowance shall be based on the apparent
intended use of the space.
[Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1531, filed 10/18/93, effective 4/1/94.]
EXCEPTIONS:
1. Group ((
M)) U occupancy accessory to Group R-3 occupancy.
2. For covered parking, 0.30 w/sf may be used for the lighting provided that the ceilings and walls are painted
or stained with a reflectance value of 0.70 or higher.
TABLE 15-1
Unit Lighting Power Allowance (LPA)
Use1 | LPA2 (watts/sq. ft.) |
Painting, welding, carpentry, machine shops | 2.3 |
Barber shops, beauty shops | 2.0 |
Hotel banquet/conference/exhibition hall3,4 | 2.0 |
Laboratories | 2.0 |
Aircraft repair hangars | 1.5 |
Cafeterias, fast food establishments5 | 1.5 |
Factories, workshops, handling areas | 1.5 |
Gas stations, auto repair shops6 | 1.5 |
Institutions | 1.5 |
Libraries5 | 1.5 |
Nursing homes and hotel/motel guest rooms | 1.5 |
Retail10, retail banking | 1.5 |
Wholesale stores (pallet rack shelving) | 1.5 |
Mall concourses | 1.4 |
Schools buildings (Group E occupancy only), school classrooms, day care centers | 1.35 |
Laundries | 1.3 |
Office buildings, office/administrative areas in facilities of other use types (including but not limited to schools, hospitals, institutions, museums, banks, churches)5,7,11 | 1.2 |
Police and fire stations8 | 1.2 |
Atria (atriums) | 1.0 |
Assembly spaces9, auditoriums, gymnasia9, theaters | 1.0 |
Group R-1 common areas | 1.0 |
Process plants | 1.0 |
Restaurants/bars5 | 1.0 |
1.5)) | |
Locker and/or shower facilities | 0.8 |
Warehouses11, storage areas | 0.5 |
Aircraft storage hangars | 0.4 |
Parking garages | See Section 1532 |
Plans Submitted for Common Areas Only7 | |
(( |
(( 1.2 |
Common areas, corridors, toilet facilities and washrooms, elevator lobbies | 0.8 |
2. The watts per square foot may be increased, by two percent per foot of ceiling height above twenty feet, unless specifically directed otherwise by subsequent footnotes.
3. Watts per square foot of room may be increased by two percent per foot of ceiling height above twelve feet.
4. For all other spaces, such as seating and common areas, use the Unit Light Power Allowance for assembly.
5. Watts per square foot of room may be increased by two percent per foot of ceiling height above nine feet.
6. Includes pump area under canopy.
7. In cases in which a lighting plan is submitted for only a portion of a floor, a Unit Lighting Power Allowance of 1.35 may be used for usable office floor area and 0.80 watts per square foot shall be used for the common areas, which may include elevator space, lobby area and rest rooms. Common areas, as herein defined do not include mall concourses.
8. For the fire engine room, the Unit Lighting Power Allowance is 1.0 watts per square foot.
9. For indoor sport tournament courts with adjacent spectator seating, the Unit Lighting Power Allowance for the court area is 2.6 watts per square foot.
10. ((For both Retail A and Retail B, light)) Display window
illumination installed within 2 feet of the window, lighting
for free-standing display where the lighting moves with the
display, and building showcase illumination ((and display
window illumination installed within two feet of the window
are exempt.
Retail A allows a Unit Lighting Power Allowance of 1.0 watts per square foot. Ceiling mounted adjustable tungsten halogen and HID merchandise display illuminaries are exempt.
Retail B allows a Unit Lighting Power Allowance of 1.5 watts per square foot, including all ceiling mounted merchandise display luminaries)) where the lighting is enclosed within the showcase are exempt.
An additional 1.5 w/ft2 of merchandise display luminaires are exempt provided that they comply with all three of the following:
(a) located on ceiling-mounted track or directly on or
recessed into the ceiling itself (not on the wall).
(b) adjustable in both the horizontal and vertical axes
(vertical axis only is acceptable for fluorescent and other
fixtures with two points of track attachment).
(c) fitted with tungsten halogen, fluorescent, or high
intensity discharge lamps.
This additional lighting power is allowed only if the
lighting is actually installed.
11. Provided that a floor plan, indicating rack location and height, is submitted, the square footage for a warehouse may be defined, for computing the interior Unit Lighting Power Allowance, as the floor area not covered by racks plus the vertical face area (access side only) of the racks. The height allowance defined in footnote 2 applies only to the floor area not covered by racks.
[Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-1532, filed 10/18/93, effective 4/1/94.]
CHAPTER 17STANDARDS
Note: | For nonresidential standards, see chapter 7. |
CHAPTER 20
DEFAULT HEAT-LOSS COEFFICIENTS
Note: | For nonresidential defaults, see chapter 10. |
REFERENCE STANDARD ((COMMERCIAL)) NONRESIDENTIAL
BUILDING DESIGN BY SYSTEMS ANALYSIS
AMENDATORY SECTION(Amending WSR 93-21-052, filed 10/18/93,
effective 4/1/94)
WAC 51-11-99902
Section 2 -- General principles and
requirements.
2.1 Energy Analysis: Compliance with this Standard will require
an analysis of the annual energy usage, hereinafter called an
annual energy analysis.
A building designed in accordance with this Standard will be
deemed as complying with this Code, if
a. The calculated annual energy consumption is not greater
than that of a corresponding "standard design," as defined below
and in Section 3,
and;
b. Whose enclosure elements and energy-consuming systems
comply with Sections 1310 through 1314, 1410 through ((1415))
1416, 1440 through ((1442)) 1443, 1450 through 1454 and 1510
through 1513. Buildings shall only vary from those requirements
in Sections 1330 through 1334, 1432 through ((1438)) 1439 and
1530 through 1532 where those variations have been accurately and
completely modeled. Where variations are not specifically
analyzed, the building shall comply with these requirements.
For a proposed building design to be considered similar to a "standard design," it shall utilize the same energy source(s) for the same functions and have equal floor area and the same ratio of envelope area to floor area, environmental requirements, occupancy, climate data and usage operational schedule. Inputs to the energy analysis relating to occupancy and usage shall correspond to the expected occupancy and usage of the building.
Except as noted below, the systems identified, and, to the
extent possible, the assumptions made in assigning energy inputs
to each system, shall be the same for the standard design and the
proposed design. When electrically driven heat pumps, other than
multiple units connected to a common water loop, are employed to
provide all or part of the heat for the proposed design, the
standard design shall also, for the purposes of the analysis,
assume that electrically driven heat pump, in conformance with
Chapter 14 of the Code and having capacity at least as great as
those used in the proposed design are employed.
2.2 Design: The standard design and the proposed design shall be
designed on a common basis as specified herein:
a. The comparison shall be expressed as kBtu input per square foot of conditioned floor area per year at the building site. Buildings which use electricity as the only fuel source, comparisons may be expressed in kWh. When converting electricity in kWh to kBtu a multiplier of 3.413 kWh/kBtu shall be used.
b. If the proposed design results in an increase in consumption of one energy source and a decrease in another energy source, even though similar sources are used for similar purposes, the difference in each energy source shall be converted to equivalent energy units for purposes of comparing the total energy used.
2.3 Analysis Procedure: The analysis of the annual energy usage
of the standard and the proposed building and system design shall
meet the following criteria:
a. The building heating/cooling load calculation procedure used for annual energy consumption analysis shall be detailed to permit the evaluation of effect of factors specified in Section 2.4.
b. The calculation procedure used to simulate the operation
of the building and its service systems through a full-year
operating period shall be detailed to permit the evaluation of
the effect of system design, climatic factors, operational
characteristics and mechanical equipment on annual energy usage. Manufacturer's data or comparable field test data shall be used
when available in the simulation of systems and equipment. The
calculation procedure shall be based upon 8,760 hours of
operation of the building and its service systems and shall
utilize the design methods, specified in Standards RS-27, -11,
-12 and -13 listed in Chapter 7 ((and 17)) of the Code or in
other programs approved by the building official.
2.4 Calculation Procedure: The calculation procedure shall cover
the following items:
a. Design requirements--Design heating conditions and design
cooling conditions as defined in Chapter ((12)) 2 of the Code.
b. Climatic data--Coincident hourly data for temperatures, solar radiation, wind and humidity of typical days in the year representing seasonal variation.
c. Building data--Orientation, size, shape, mass, air and heat transfer characteristics.
d. Operational characteristics--Temperature, humidity, ventilation, illumination and control mode for occupied and unoccupied hours.
e. Mechanical equipment--Design capacity and part load profile.
f. Building loads--Internal heat generation, lighting, equipment and number of people during occupied and unoccupied periods.
((
EXCEPTION:Proposed designs having an area of 25,000 square feet or less are exempt from the full-year energy analysis
described in section 2.3(b). However, comparison of energy consumption between the proposed design and the
standard design shall be provided based on one of the programs suggested in Section 4.2 for these buildings.))
2.5 Documentation: All analyses submitted shall be accompanied
by an energy analysis comparison report. The report shall
provide technical detail on the two building and system designs
and on the data used in and resulting from the comparative
analysis to verify that both the analysis and the designs meet
the criteria of Section 1.
The calculation procedure for the standard design and the
proposed design shall separately identify the calculated annual
energy consumption for each different occupancy type, if
possible, for each of the following end uses:
a. Interior lighting;
b. Parking lighting;
c. Exterior lighting;
d. Space heating;
e. Space cooling;
f. Interior ventilation/fans;
g. Parking ventilation/fans;
h. Exhaust fans;
i. Service water heating;
j. Elevators;
k. Appliances.
Energy consumption of the following items shall be included
but is not required to be separated out by each individual item.
a. Office equipment;
b. Refrigeration other than comfort cooling;
c. Cooking; and
d. Any other energy-consuming equipment.
The specifications of the proposed building project used in
the analysis shall be as similar as is reasonably practical to
those in the plans submitted for a building permit.
[Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-99902, filed 10/18/93, effective 4/1/94.]
The specific modeling assumptions consist of methods and
assumptions for calculating the standard energy consumption for
the standard building and the proposed energy consumption of the
proposed design. In order to maintain consistency between the
standard and the proposed design energy consumptions, the input
assumptions in this section shall be used.
"Prescribed" assumptions shall be used without variation. "Default" assumptions shall be used unless the designer can
demonstrate that a different assumption better characterizes the
building's use over its expected life. Any modification of a
default assumption shall be used in modeling both the standard
building and the proposed design unless the designer demonstrates
a clear cause to do otherwise.
3.1 Orientation and Shape: The standard building shall consist
of the same number of stories and gross floor area for each story
as the proposed design. Each floor shall be oriented exactly as
the proposed design. The geometric form shall be the same as the
proposed design.
3.2 Internal Loads: Internal loads shall be modeled as noted in
the following parts of Section 3.2. The systems specified for
calculating the standard energy consumption in Section 3.2 are
intended only as constraints in calculating the consumption. They are not intended as requirements or recommendations for
systems to be used in the proposed building or for the
calculation of the proposed energy consumption.
3.2.1 Occupancy: Occupancy schedules shall be default
assumptions. The same assumptions shall be made in computing
proposed energy consumption as were used in calculating the
standard energy consumption. Occupancy levels vary by building
type and time of day. Table 3-1 establishes the density
presented as ft2/person of conditioned floor area that will be
used by each building type. Table 3-2 establishes the percentage
of the people that are in the building by hours of the day for
each building type.
3.2.2 Lighting: The interior and exterior lighting power
allowance for calculating the standard energy consumption shall
be determined from Sections 1531 and 1532. The lighting power
used to calculate the proposed energy consumption shall be the
actual lighting power of the proposed lighting design. Exempt
lighting in the standard design shall be equal to the exempt
lighting in the proposed design.
Lighting levels in buildings vary based on the type of uses within buildings, by area and by time of day. Table 3-2 contains the lighting energy profiles which establish the percentage of the lighting load that is switched ON in each prototype or reference building by hour of the day. These profiles are default assumptions and can be changed if required when calculating the standard energy consumption to provide, for example, a 12 hour rather than an 8 hour work day or to reflect the use of automatic lighting controls. The lighting schedules used in the standard and proposed designs shall be identical and shall reflect the type of controls to be installed in the proposed design. The controls in the proposed design shall comply with the requirements in Section 1513 and no credit shall be given for the use of any additional controls, automatic or otherwise.
3.2.3 Receptacle: Receptacle loads and profiles are default
assumptions. The same assumptions shall be made in calculating
proposed energy consumption as were used in calculating the
standard energy consumption. Receptacle loads include all
general service loads that are typical in a building. These
loads should include additional process electrical usage but
exclude HVAC primary or auxiliary electrical usage. Table 3-1
establishes the density in W/ft2 to be used. The receptacle
energy profiles shall be the same as the lighting energy profiles
in Table 3-2. This profile establishes the percentage of the
receptacle load that is switched ON by hour of the day and by
building type.
3.3 Envelope
3.3.1 Insulation and Glazing: Glazing area and U-factor of the
standard building envelope shall be determined by using the
Target UA requirements of Equation 13-1 and U-factor values in
Table 13-1 or 13-2. The glazing solar heat gain coefficient
(SHGC) or shading coefficient of the standard building shall be
the lesser of 0.65 and the SHGC required by Table 13-1 or 13-2
for the vertical or overhead glazing area for the appropriate
wall type. The opaque area U-factors of the standard building
shall be determined by using the Target UA requirements from
Equation 13-1 including the appropriate mass for walls. The
insulation characteristics and glazing area are prescribed
assumptions for the standard building for calculating the
standard energy consumption. In the calculation of the proposed
energy consumption of the proposed design, the envelope
characteristics of the proposed design shall be used. The
standard design shall use the maximum glazing areas listed in
Tables 13-1 or 13-2 for the appropriate use. The distribution of
vertical glazing in the gross wall area of the standard design
shall be equal to the distribution of vertical glazing in the
proposed design or shall constitute an equal percentage of gross
wall area on all sides of the standard building. The
distribution of overhead glazing in the gross roof/ceiling area
of the standard design shall be equal to the distribution of
overhead glazing in the proposed design. The distribution of
doors in the gross opaque wall area of the standard design shall
be identical to the distribution of doors in the proposed design.
3.3.2 Infiltration: For standard and proposed buildings,
infiltration assumptions shall be equal.
3.3.3 Envelope and Ground Absorptivities: For the standard
building, absorptivity assumptions shall be default assumptions
for computing the standard energy consumption and default
assumptions for computing the proposed energy consumption. The
solar absorptivity of opaque elements of the building envelope
shall be assumed to be 70 percent. The solar absorptivity of
ground surfaces shall be assumed to be 80 percent (20 percent
reflectivity).
3.3.4 Window Treatment: No draperies or blinds shall be modeled
for the standard or proposed building.
3.3.5 Shading: For standard building and the proposed design,
shading by permanent structures and terrain shall be taken into
account for computing energy consumption whether or not these
features are located on the building site. A permanent fixture
is one that is likely to remain for the life of the proposed
design. Credit may be taken for external shading devices that
are part of the proposed design.
3.4 HVAC Systems and Equipment: For the standard building, the
HVAC system used shall be the system type used in the proposed
design. If the proposed HVAC system type does not comply with
Sections 1432 through ((1438)) 1439, the standard design system
shall comply in all respects with those sections.
Exception: | When approved by the building official, a prototype HVAC system may be used, if the proposed design system
cannot be modified to comply with Sections 1422 and 1432 through (( |
1. assembly | 6. restaurant |
2. health/institutional | 7. retail (mercantile) |
3. hotel/motel | 8. school (educational) |
4. light manufacturing | 9. warehouse (storage) |
5. office (business) |
EXCEPTIONS: | 1. Building types such as assembly or warehouse may be modeled as a single zone if there is only one space. |
2. Thermally similar zones, such as those facing one orientation on different floors, may be grouped together for the purposes of either the standard or proposed building simulation. |
3.4.3 HVAC Equipment Sizing: The equipment shall be sized to
include the capacity to meet the process loads. For calculating
the proposed energy consumption, actual air flow rates and
installed equipment size shall be used in the simulation. Equipment sizing in the simulation of the proposed design shall
correspond to the equipment intended to be selected for the
design and the designer shall not use equipment sized
automatically by the simulation tool.
Equipment sizing for the standard design shall be based on
the same as the proposed design or lesser sizing ratio of
installed system capacity to the design load for heating and for
cooling.
Chilled water systems for the standard building shall be
modeled using a reciprocating chiller for systems with total
cooling capacities less than 175 tons, and centrifugal chillers
for systems with cooling capacities of 175 tons or greater. For
systems with cooling capacities of 600 tons or more the standard
energy consumption shall be calculated using two centrifugal
chillers, lead/lag controlled. Chilled water shall be assumed to
be controlled at a constant 44 degree F temperature rise, from 44
degrees F to 56 degrees F, operating at 65 percent combined
impeller and motor efficiency. Condenser water pumps shall be
sized using a 10 degree F temperature rise, operating at 60
percent combined impeller and motor efficiency. The cooling
tower shall be an open circuit, centrifugal blower type sized for
the larger of 85 degrees F leaving water temperature or 10
degrees F approach to design wetbulb temperature. The tower
shall be controlled to provide a 65 degrees F leaving water
temperature whenever weather conditions permit, floating up to
design leaving water temperature at design conditions.
3.4.4 ((Variable Speed:)) Fans: The ((energy)) power of the
combined fan system per air volume at design conditions (w/cfm)
of the proposed design shall be equal to that of the standard
design.
Variable air volume fan systems in the standard building shall be variable speed.
3.5 Service Water Heating: The service water heating loads for
prototype buildings are defined in terms of Btu/person-hour in
Table 3-1. The values in the table refer to energy content of
the heated water. The service water heating loads from Table 3-1
are default for all buildings. The same service-water-heating
load assumptions shall be made in calculating proposed energy
consumption as were used in calculating the standard energy
consumption. The service water heating system for the standard
building shall be modeled as closely as possible as if it were
designed in accordance with ((the ASHRAE Handbook, 1995 HVAC
Systems and Applications Volume)) RS-11 and meeting all the
requirements of Sections 1440 through ((1442)) 1443.
3.6 Controls
3.6.1: All occupied conditioned spaces in standard and proposed
design buildings in all climates shall be simulated as being both
heated and cooled.
EXCEPTIONS: | 1. If a building or portion of a building is to be provided with only heating or cooling, both the standard building and the proposed design shall be simulated using the same assumptions. |
2. If warehouses are not intended to be mechanically cooled, both the standard and proposed energy consumption shall be modeled assuming no mechanical cooling. |
EXCEPTIONS: | 1. Setback shall not be modeled in determining either the standard or proposed energy consumption if setback is not realistic for the proposed design such as a facility being operated 24 hours/day. For instance, health facilities need not have night setback during the heating season. |
2. If deadband controls are not to be installed, the proposed energy consumption shall be calculated with both heating and cooling thermostat setpoints set to the same value between 70 degrees F and 75 degrees F inclusive, assumed to be constant for the year. |
3.6.4: If humidification is to be used in the proposed design,
the same level of humidification and system type shall be used in
the standard building.
TABLE 3-1
Acceptable Occupancy Densities, Receptacle Power Densities and
Service Hot Water Consumption1
Building Type | Occupancy Density2 Sq. Ft./Person (Btu/hft2) |
Receptacle Power Density3 Watts/Sq. Ft. (Btu/hft2) |
Service Hot
Water Quantities4 Btu/hperson |
Assembly | 50 (4.60) | 0.25 (0.85) | 215 |
Health/Institutional | 200 (1.15) | 1.00 (3.41) | 135 |
Hotel/Motel | 250 (0.92) | 0.25 (0.85) | 1,110 |
Light Manufacturing | 750 (0.31) | 0.20 (0.68) | 225 |
Office | 275 (0.84) | 0.75 (2.56) | 175 |
Parking Garage | N.A. | N.A. | N.A. |
Restaurant | 100 (2.30) | 0.10 (0.34) | 390 |
Retail | 300 (0.77) | 0.25 (0.85) | 135 |
School | 75 (3.07) | 0.50 (1.71) | 215 |
Warehouse | 15,000 (0.02) | 0.10 (0.34) | 225 |
1. | The occupancy densities, receptacle power densities and service hot water consumption values are from ASHRAE Standard 90.1-1989 and addenda. |
2. | Values are in square feet of conditioned floor area per person. Heat generation in Btu per person per hour is 230 sensible and 190 latent. Figures in parentheses are equivalent Btu per hour per square foot. |
3. | Values are in Watts per square foot of conditioned floor area. Figures in parentheses are equivalent Btu per hour per square foot. These values are the minimum acceptable. If other process loads are not input (such as for computers, cooking, refrigeration, etc.), it is recommended that receptacle power densities be increased until total process energy consumption is equivalent to 25% of the total. |
4. | Values are in Btu per person per hour. |
TABLE 3-2A
Assembly Occupancy1
Hour of Day | Schedule for Occupancy Percent of Maximum Load |
Schedule for Lighting Receptacle Percent of Maximum Load |
Schedule for HVAC System |
Schedule for Service Hot Water Percent of Maximum Load |
Schedule for Elevator Percent of Maximum Load |
|||||||||||
(time) | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | |
1 | (12-1am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 0 | 0 | 0 | 0 | 0 | 0 |
2 | (1-2am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 0 | 0 | 0 | 0 | 0 | 0 |
3 | (2-3am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 0 | 0 | 0 | 0 | 0 | 0 |
4 | (3-4am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 0 | 0 | 0 | 0 | 0 | 0 |
5 | (4-5am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 0 | 0 | 0 | 0 | 0 | 0 |
6 | (5-6am) | 0 | 0 | 0 | 5 | 5 | 5 | on | off | off | 0 | 0 | 0 | 0 | 0 | 0 |
7 | (6-7am) | 0 | 0 | 0 | 40 | 5 | 5 | on | on | on | 0 | 0 | 0 | 0 | 0 | 0 |
8 | (7-8am) | 0 | 0 | 0 | 40 | 30 | 30 | on | on | on | 0 | 0 | 0 | 0 | 0 | 0 |
9 | (8-9am) | 20 | 20 | 10 | 40 | 30 | 30 | on | on | on | 0 | 0 | 0 | 0 | 0 | 0 |
10 | (9-10am) | 20 | 20 | 10 | 75 | 50 | 30 | on | on | on | 5 | 5 | 5 | 0 | 0 | 0 |
11 | (10-11am) | 20 | 20 | 10 | 75 | 50 | 30 | on | on | on | 5 | 5 | 5 | 0 | 0 | 0 |
12 | (11-12pm) | 80 | 60 | 10 | 75 | 50 | 30 | on | on | on | 35 | 20 | 10 | 0 | 0 | 0 |
13 | (12-1pm) | 80 | 60 | 10 | 75 | 50 | 65 | on | on | on | 5 | 0 | 0 | 0 | 0 | 0 |
14 | (1-2pm) | 80 | 60 | 70 | 75 | 50 | 65 | on | on | on | 5 | 0 | 0 | 0 | 0 | 0 |
15 | (2-3pm) | 80 | 60 | 70 | 75 | 50 | 65 | on | on | on | 5 | 0 | 0 | 0 | 0 | 0 |
16 | (3-4pm) | 80 | 60 | 70 | 75 | 50 | 65 | on | on | on | 5 | 0 | 0 | 0 | 0 | 0 |
17 | (4-5pm) | 80 | 60 | 70 | 75 | 50 | 65 | on | on | on | 5 | 0 | 0 | 0 | 0 | 0 |
18 | (5-6pm) | 80 | 60 | 70 | 75 | 50 | 65 | on | on | on | 0 | 0 | 0 | 0 | 0 | 0 |
19 | (6-7pm) | 20 | 60 | 70 | 75 | 50 | 65 | on | on | on | 0 | 0 | 0 | 0 | 0 | 0 |
20 | (7-8pm) | 20 | 60 | 70 | 75 | 50 | 65 | on | on | on | 0 | 65 | 65 | 0 | 0 | 0 |
21 | (8-9pm) | 20 | 60 | 70 | 75 | 50 | 65 | on | on | on | 0 | 30 | 30 | 0 | 0 | 0 |
22 | (9-10pm) | 20 | 80 | 70 | 75 | 50 | 65 | on | on | on | 0 | 0 | 0 | 0 | 0 | 0 |
23 | (10-11pm) | 10 | 10 | 20 | 25 | 50 | 5 | on | on | on | 0 | 0 | 0 | 0 | 0 | 0 |
24 | (11-12am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 0 | 0 | 0 | 0 | 0 | 0 |
Total/Day | 710 | 750 | 700 | 1155 | 800 | 845 | 1800 | 1700 | 1700 | 70 | 125 | 115 | 0 | 0 | 0 | |
Total/Week | 50.50 | hours | 74.20 | hours | 124 | hours | 5.9 | hours | 0 | hours | ||||||
Total/Year | 2633 | hours | 3869 | hours | 6465 | hours | 308 | hours | 0 | hours |
Wk= Weekday |
1. | Schedules for occupancy, lighting, receptacle, HVAC system and service hot water are from ASHRAE Standard 90.1-1989 and addendums, except that 5% emergency lighting has been added for all off hours. Elevator schedules, except for restaurants, are from the U.S. Department of Energy Standard Evaluation Techniques except changed to 0% when occupancy is 0%. THESE VALUES MAY BE USED ONLY IF ACTUAL SCHEDULES ARE NOT KNOWN. |
TABLE 3-2B
Health Occupancy1
Hour of Day (time) |
Schedule for Occupancy Percent of Maximum Load |
Schedule for Lighting Receptacle Percent of Maximum Load |
Schedule for HVAC System | Schedule for Service Hot Water Percent of Maximum Load |
Schedule for Elevator Percent of Maximum Load |
|||||||||||
Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | ||
1 | (12-1am) | 0 | 0 | 0 | 10 | 10 | 5 | on | on | on | 1 | 1 | 1 | 0 | 0 | 0 |
2 | (1-2am) | 0 | 0 | 0 | 10 | 10 | 5 | on | on | on | 1 | 1 | 1 | 0 | 0 | 0 |
3 | (2-3am) | 0 | 0 | 0 | 10 | 10 | 5 | on | on | on | 1 | 1 | 1 | 0 | 0 | 0 |
4 | (3-4am) | 0 | 0 | 0 | 10 | 10 | 5 | on | on | on | 1 | 1 | 1 | 0 | 0 | 0 |
5 | (4-5am) | 0 | 0 | 0 | 10 | 10 | 5 | on | on | on | 1 | 1 | 1 | 0 | 0 | 0 |
6 | (5-6am) | 0 | 0 | 0 | 10 | 10 | 5 | on | on | on | 1 | 1 | 1 | 0 | 0 | 0 |
7 | (6-7am) | 0 | 0 | 0 | 10 | 10 | 5 | on | on | on | 1 | 1 | 1 | 0 | 0 | 0 |
8 | (7-8am) | 10 | 10 | 0 | 50 | 20 | 5 | on | on | on | 17 | 1 | 1 | 2 | 2 | 0 |
9 | (8-9am) | 50 | 30 | 5 | 90 | 40 | 10 | on | on | on | 58 | 20 | 1 | 75 | 46 | 2 |
10 | (9-10am) | 80 | 40 | 5 | 90 | 40 | 10 | on | on | on | 66 | 28 | 1 | 100 | 70 | 2 |
11 | (10-11am) | 80 | 40 | 5 | 90 | 40 | 10 | on | on | on | 78 | 30 | 1 | 100 | 70 | 2 |
12 | (11-12pm) | 80 | 40 | 5 | 90 | 40 | 10 | on | on | on | 82 | 30 | 1 | 100 | 70 | 2 |
13 | (12-1pm) | 80 | 40 | 5 | 90 | 40 | 10 | on | on | on | 71 | 24 | 1 | 75 | 51 | 2 |
14 | (1-2pm) | 80 | 40 | 5 | 90 | 40 | 10 | on | on | on | 82 | 24 | 1 | 100 | 51 | 2 |
15 | (2-3pm) | 80 | 40 | 5 | 90 | 40 | 10 | on | on | on | 78 | 23 | 1 | 100 | 51 | 2 |
16 | (3-4pm) | 80 | 40 | 5 | 90 | 40 | 10 | on | on | on | 74 | 23 | 1 | 100 | 51 | 2 |
17 | (4-5pm) | 80 | 40 | 0 | 30 | 40 | 5 | on | on | on | 63 | 23 | 1 | 100 | 51 | 0 |
18 | (5-6pm) | 50 | 10 | 0 | 30 | 40 | 5 | on | on | on | 41 | 10 | 1 | 100 | 25 | 0 |
19 | (6-7pm) | 30 | 10 | 0 | 30 | 10 | 5 | on | on | on | 18 | 1 | 1 | 52 | 2 | 0 |
20 | (7-8pm) | 30 | 0 | 0 | 30 | 10 | 5 | on | on | on | 18 | 1 | 1 | 52 | 0 | 0 |
21 | (8-9pm) | 20 | 0 | 0 | 30 | 10 | 5 | on | on | on | 18 | 1 | 1 | 52 | 0 | 0 |
22 | (9-10pm) | 20 | 0 | 0 | 30 | 10 | 5 | on | on | on | 10 | 1 | 1 | 28 | 0 | 0 |
23 | (10-11pm) | 0 | 0 | 0 | 30 | 10 | 5 | on | on | on | 1 | 1 | 1 | 0 | 0 | 0 |
24 | (11-12am) | 0 | 0 | 0 | 10 | 10 | 5 | on | on | on | 1 | 1 | 1 | 0 | 0 | 0 |
Total/Day | 850 | 380 | 40 | 1060 | 550 | 160 | 2400 | 2400 | 2400 | 783 | 249 | 24 | 1136 | 540 | 16 | |
Total/Week | 46.70 | hours | 60.10 | hours | 168 | hours | 41.88 | hours | 62.36 | hours | ||||||
Total/Year | 2435 | hours | 3134 | hours | 8760 | hours | 2148 | hours | 3251 | hours |
Wk= Weekday |
1. | Schedules for occupancy, lighting, receptacle, HVAC system and service hot water are from ASHRAE Standard 90.1-1989 and addendums, except that 5% emergency lighting has been added for all off hours. Elevator schedules, except for restaurants, are from the U.S. Department of Energy Standard Evaluation Techniques except changed to 0% when occupancy is 0%. THESE VALUES MAY BE USED ONLY IF ACTUAL SCHEDULES ARE NOT KNOWN. |
TABLE 3-2C
Hotel/Motel Occupancy1
Hour of Day | Schedule for Occupancy Percent of Maximum Load |
Schedule for Lighting Receptacle Percent of Maximum Load |
Schedule for HVAC System |
Schedule for Service Hot Water Percent of Maximum Load |
Schedule for Elevator Percent of Maximum Load |
|||||||||||
(time) | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | |
1 | (12-1am) | 90 | 90 | 70 | 20 | 20 | 30 | on | on | on | 20 | 20 | 25 | 40 | 44 | 55 |
2 | (1-2am) | 90 | 90 | 70 | 15 | 20 | 30 | on | on | on | 15 | 15 | 20 | 33 | 35 | 55 |
3 | (2-3am) | 90 | 90 | 70 | 10 | 10 | 20 | on | on | on | 15 | 15 | 20 | 33 | 35 | 43 |
4 | (3-4am) | 90 | 90 | 70 | 10 | 10 | 20 | on | on | on | 15 | 15 | 20 | 33 | 35 | 43 |
5 | (4-5am) | 90 | 90 | 70 | 10 | 10 | 20 | on | on | on | 20 | 20 | 20 | 33 | 35 | 43 |
6 | (5-6am) | 90 | 90 | 70 | 20 | 10 | 20 | on | on | on | 25 | 25 | 30 | 33 | 35 | 43 |
7 | (6-7am) | 70 | 70 | 70 | 40 | 30 | 30 | on | on | on | 50 | 40 | 50 | 42 | 40 | 52 |
8 | (7-8am) | 40 | 50 | 70 | 50 | 30 | 40 | on | on | on | 60 | 50 | 50 | 42 | 32 | 52 |
9 | (8-9am) | 40 | 50 | 50 | 40 | 40 | 40 | on | on | on | 55 | 50 | 50 | 52 | 45 | 65 |
10 | (9-10am) | 20 | 30 | 50 | 40 | 40 | 30 | on | on | on | 45 | 50 | 55 | 52 | 45 | 65 |
11 | (10-11am) | 20 | 30 | 50 | 25 | 30 | 30 | on | on | on | 40 | 45 | 50 | 40 | 42 | 53 |
12 | (11-12pm) | 20 | 30 | 30 | 25 | 25 | 30 | on | on | on | 45 | 50 | 50 | 51 | 60 | 60 |
13 | (12-1pm) | 20 | 30 | 30 | 25 | 25 | 30 | on | on | on | 40 | 50 | 40 | 51 | 65 | 53 |
14 | (1-2pm) | 20 | 30 | 20 | 25 | 25 | 20 | on | on | on | 35 | 45 | 40 | 51 | 65 | 51 |
15 | (2-3pm) | 20 | 30 | 20 | 25 | 25 | 20 | on | on | on | 30 | 40 | 30 | 51 | 65 | 50 |
16 | (3-4pm) | 30 | 30 | 20 | 25 | 25 | 20 | on | on | on | 30 | 40 | 30 | 51 | 65 | 44 |
17 | (4-5pm) | 50 | 30 | 30 | 25 | 25 | 20 | on | on | on | 30 | 35 | 30 | 63 | 65 | 64 |
18 | (5-6pm) | 50 | 50 | 40 | 25 | 25 | 20 | on | on | on | 40 | 40 | 40 | 80 | 75 | 62 |
19 | (6-7pm) | 50 | 60 | 40 | 60 | 60 | 50 | on | on | on | 55 | 55 | 50 | 86 | 80 | 65 |
20 | (7-8pm) | 70 | 60 | 60 | 80 | 70 | 70 | on | on | on | 60 | 55 | 50 | 70 | 80 | 63 |
21 | (8-9pm) | 70 | 60 | 60 | 90 | 70 | 80 | on | on | on | 50 | 50 | 40 | 70 | 75 | 63 |
22 | (9-10pm) | 80 | 70 | 80 | 80 | 70 | 60 | on | on | on | 55 | 55 | 50 | 70 | 75 | 63 |
23 | (10-11pm) | 90 | 70 | 80 | 60 | 60 | 50 | on | on | on | 45 | 40 | 40 | 45 | 55 | 40 |
24 | (11-12am) | 90 | 70 | 80 | 30 | 30 | 30 | on | on | on | 25 | 30 | 20 | 45 | 55 | 40 |
Total/Day | 1390 | 1390 | 1300 | 855 | 785 | 810 | 2400 | 2400 | 2400 | 915 | 930 | 900 | 1217 | 1303 | 1287 | |
Total/Week | 96.40 | hours | 58.70 | hours | 168.0 | hours | 64.05 | hours | 86.75 | hours | ||||||
Total/Year | 5026 | hours | 3061 | hours | 8760 | hours | 3340 | hours | 4523 | hours |
Wk= Weekday |
1. | Schedules for occupancy, lighting, receptacle, HVAC system and service hot water are from ASHRAE Standard 90.1-1989 and addendums, except that 5% emergency lighting has been added for all off hours. Elevator schedules, except for restaurants, are from the U.S. Department of Energy Standard Evaluation Techniques except changed to 0% when occupancy is 0%. THESE VALUES MAY BE USED ONLY IF ACTUAL SCHEDULES ARE NOT KNOWN. |
TABLE 3-2D
Light Manufacturing Occupancy1
Hour of Day | Schedule for Occupancy Percent of Maximum Load |
Schedule for Lighting Receptacle Percent of Maximum Load |
Schedule for HVAC System |
Schedule for Service Hot Water Percent of Maximum Load |
Schedule for Elevator Percent of Maximum Load |
|||||||||||
(time) | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | |
1 | (12-1am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 5 | 5 | 4 | 0 | 0 | 0 |
2 | (1-2am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 5 | 5 | 4 | 0 | 0 | 0 |
3 | (2-3am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 5 | 5 | 4 | 0 | 0 | 0 |
4 | (3-4am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 5 | 5 | 4 | 0 | 0 | 0 |
5 | (4-5am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 5 | 5 | 4 | 0 | 0 | 0 |
6 | (5-6am) | 0 | 0 | 0 | 10 | 5 | 5 | off | off | off | 8 | 8 | 7 | 0 | 0 | 0 |
7 | (6-7am) | 10 | 10 | 5 | 10 | 10 | 5 | on | on | off | 7 | 7 | 4 | 0 | 0 | 0 |
8 | (7-8am) | 20 | 10 | 5 | 30 | 10 | 5 | on | on | off | 19 | 11 | 4 | 35 | 16 | 0 |
9 | (8-9am) | 95 | 30 | 5 | 90 | 30 | 5 | on | on | off | 35 | 15 | 4 | 69 | 14 | 0 |
10 | (9-10am) | 95 | 30 | 5 | 90 | 30 | 5 | on | on | off | 38 | 21 | 4 | 43 | 21 | 0 |
11 | (10-11am) | 95 | 30 | 5 | 90 | 30 | 5 | on | on | off | 39 | 19 | 4 | 37 | 18 | 0 |
12 | (11-12pm) | 95 | 30 | 5 | 90 | 30 | 5 | on | on | off | 47 | 23 | 6 | 43 | 25 | 0 |
13 | (12-1pm) | 50 | 10 | 5 | 80 | 15 | 5 | on | on | off | 57 | 20 | 6 | 58 | 21 | 0 |
14 | (1-2pm) | 95 | 10 | 5 | 90 | 15 | 5 | on | on | off | 54 | 19 | 9 | 48 | 13 | 0 |
15 | (2-3pm) | 95 | 10 | 5 | 90 | 15 | 5 | on | on | off | 34 | 15 | 6 | 37 | 8 | 0 |
16 | (3-4pm) | 95 | 10 | 5 | 90 | 15 | 5 | on | on | off | 33 | 12 | 4 | 37 | 4 | 0 |
17 | (4-5pm) | 95 | 10 | 5 | 90 | 15 | 5 | on | on | off | 44 | 14 | 4 | 46 | 5 | 0 |
18 | (5-6pm) | 30 | 5 | 5 | 50 | 5 | 5 | on | on | off | 26 | 7 | 4 | 62 | 6 | 0 |
19 | (6-7pm) | 10 | 5 | 0 | 30 | 5 | 5 | on | off | off | 21 | 7 | 4 | 20 | 0 | 0 |
20 | (7-8pm) | 10 | 0 | 0 | 30 | 5 | 5 | on | off | off | 15 | 7 | 4 | 12 | 0 | 0 |
21 | (8-9pm) | 10 | 0 | 0 | 20 | 5 | 5 | on | off | off | 17 | 7 | 4 | 4 | 0 | 0 |
22 | (9-10pm) | 10 | 0 | 0 | 20 | 5 | 5 | on | off | off | 8 | 9 | 7 | 4 | 0 | 0 |
23 | (10-11pm) | 5 | 0 | 0 | 10 | 5 | 5 | off | off | off | 5 | 5 | 4 | 0 | 0 | 0 |
24 | (11-12am) | 5 | 0 | 0 | 5 | 5 | 5 | off | off | off | 5 | 5 | 4 | 0 | 0 | 0 |
Total/Day | 920 | 200 | 60 | 1040 | 280 | 120 | 1600 | 1200 | 0 | 537 | 256 | 113 | 555 | 151 | 0 | |
Total/Week | 48.60 | hours | 56.00 | hours | 92.00 | hours | 30.54 | hours | 29.26 | hours | ||||||
Total/Year | 2534 | hours | 2920 | hours | 4797 | hours | 1592 | hours | 1526 | hours |
Wk= Weekday | |
1. | Schedules for occupancy, lighting, receptacle, HVAC system and service hot water are from ASHRAE Standard 90.1-1989 and addendums, except that 5% emergency lighting has been added for all off hours. Elevator schedules, except for restaurants, are from the U.S. Department of Energy Standard Evaluation Techniques except changed to 0% when occupancy is 0%. THESE VALUES MAY BE USED ONLY IF ACTUAL SCHEDULES ARE NOT KNOWN. |
TABLE 3-2E
Office Occupancy1
Hour of Day | Schedule for Occupancy Percent of Maximum Load |
Schedule for Lighting Receptacle Percent of Maximum Load |
Schedule for HVAC System |
Schedule for Service Hot Water Percent of Maximum Load |
Schedule for Elevator Percent of Maximum Load |
|||||||||||
(time) | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | |
1 | (12-1am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 5 | 5 | 4 | 0 | 0 | 0 |
2 | (1-2am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 5 | 5 | 4 | 0 | 0 | 0 |
3 | (2-3am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 5 | 5 | 4 | 0 | 0 | 0 |
4 | (3-4am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 5 | 5 | 4 | 0 | 0 | 0 |
5 | (4-5am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 5 | 5 | 4 | 0 | 0 | 0 |
6 | (5-6am) | 0 | 0 | 0 | 10 | 5 | 5 | off | off | off | 8 | 8 | 7 | 0 | 0 | 0 |
7 | (6-7am) | 10 | 10 | 5 | 10 | 10 | 5 | on | on | off | 7 | 7 | 4 | 0 | 0 | 0 |
8 | (7-8am) | 20 | 10 | 5 | 30 | 10 | 5 | on | on | off | 19 | 11 | 4 | 35 | 16 | 0 |
9 | (8-9am) | 95 | 30 | 5 | 90 | 30 | 5 | on | on | off | 35 | 15 | 4 | 69 | 14 | 0 |
10 | (9-10am) | 95 | 30 | 5 | 90 | 30 | 5 | on | on | off | 38 | 21 | 4 | 43 | 21 | 0 |
11 | (10-11am) | 95 | 30 | 5 | 90 | 30 | 5 | on | on | off | 39 | 19 | 4 | 37 | 18 | 0 |
12 | (11-12pm) | 95 | 30 | 5 | 90 | 30 | 5 | on | on | off | 47 | 23 | 6 | 43 | 25 | 0 |
13 | (12-1pm) | 50 | 10 | 5 | 80 | 15 | 5 | on | on | off | 57 | 20 | 6 | 58 | 21 | 0 |
14 | (1-2pm) | 95 | 10 | 5 | 90 | 15 | 5 | on | on | off | 54 | 19 | 9 | 48 | 13 | 0 |
15 | (2-3pm) | 95 | 10 | 5 | 90 | 15 | 5 | on | on | off | 34 | 15 | 6 | 37 | 8 | 0 |
16 | (3-4pm) | 95 | 10 | 5 | 90 | 15 | 5 | on | on | off | 33 | 12 | 4 | 37 | 4 | 0 |
17 | (4-5pm) | 95 | 10 | 5 | 90 | 15 | 5 | on | on | off | 44 | 14 | 4 | 46 | 5 | 0 |
18 | (5-6pm) | 30 | 5 | 5 | 50 | 5 | 5 | on | on | off | 26 | 7 | 4 | 62 | 6 | 0 |
19 | (6-7pm) | 10 | 5 | 0 | 30 | 5 | 5 | on | off | off | 21 | 7 | 4 | 20 | 0 | 0 |
20 | (7-8pm) | 10 | 0 | 0 | 30 | 5 | 5 | on | off | off | 15 | 7 | 4 | 12 | 0 | 0 |
21 | (8-9pm) | 10 | 0 | 0 | 20 | 5 | 5 | on | off | off | 17 | 7 | 4 | 4 | 0 | 0 |
22 | (9-10pm) | 10 | 0 | 0 | 20 | 5 | 5 | on | off | off | 8 | 9 | 7 | 4 | 0 | 0 |
23 | (10-11pm) | 5 | 0 | 0 | 10 | 5 | 5 | off | off | off | 5 | 5 | 4 | 0 | 0 | 0 |
24 | (11-12am) | 5 | 0 | 0 | 5 | 5 | 5 | off | off | off | 5 | 5 | 4 | 0 | 0 | 0 |
Total/Day | 920 | 200 | 60 | 1040 | 280 | 120 | 1600 | 1200 | 0 | 537 | 256 | 113 | 555 | 151 | 0 | |
Total/Week | 48.60 | hours | 56.00 | hours | 92.00 | hours | 30.54 | hours | 29.26 | hours | ||||||
Total/Year | 2534 | hours | 2920 | hours | 4797 | hours | 1592 | hours | 1526 | hours |
Wk= Weekday | |
1. | Schedules for occupancy, lighting, receptacle, HVAC system and service hot water are from ASHRAE Standard 90.1-1989 and addendums, except that 5% emergency lighting has been added for all off hours. Elevator schedules, except for restaurants, are from the U.S. Department of Energy Standard Evaluation Techniques except changed to 0% when occupancy is 0%. THESE VALUES MAY BE USED ONLY IF ACTUAL SCHEDULES ARE NOT KNOWN. |
TABLE 3-2F
Parking Garage Occupancy1
Hour of Day | Schedule for Occupancy Percent of Maximum Load |
Schedule for Lighting Receptacle Percent of Maximum Load |
Schedule for HVAC System |
Schedule for Service Hot Water Percent of Maximum Load |
Schedule for Elevator Percent of Maximum Load |
|||||||||||
(time) | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | |
1 | (12-1am) | 100 | 100 | 100 | ||||||||||||
2 | (1-2am) | 100 | 100 | 100 | ||||||||||||
3 | (2-3am) | 100 | 100 | 100 | ||||||||||||
4 | (3-4am) | 100 | 100 | 100 | ||||||||||||
5 | (4-5am) | 100 | 100 | 100 | ||||||||||||
6 | (5-6am) | 100 | 100 | 100 | ||||||||||||
7 | (6-7am) | 100 | 100 | 100 | ||||||||||||
8 | (7-8am) | 100 | 100 | 100 | ||||||||||||
9 | (8-9am) | 100 | 100 | 100 | ||||||||||||
10 | (9-10am) | 100 | 100 | 100 | Based | Included | ||||||||||
11 | (10-11am) | 100 | 100 | 100 | on | with | ||||||||||
12 | (11-12pm) | N/A | 100 | 100 | 100 | likely | N/A | other | ||||||||
13 | (12-1pm) | 100 | 100 | 100 | use | occupancies | ||||||||||
14 | (1-2pm) | 100 | 100 | 100 | ||||||||||||
15 | (2-3pm) | 100 | 100 | 100 | ||||||||||||
16 | (3-4pm) | 100 | 100 | 100 | ||||||||||||
17 | (4-5pm) | 100 | 100 | 100 | ||||||||||||
18 | (5-6pm) | 100 | 100 | 100 | ||||||||||||
19 | (6-7pm) | 100 | 100 | 100 | ||||||||||||
20 | (7-8pm) | 100 | 100 | 100 | ||||||||||||
21 | (8-9pm) | 100 | 100 | 100 | ||||||||||||
22 | (9-10pm) | 100 | 100 | 100 | ||||||||||||
23 | (10-11pm) | 100 | 100 | 100 | ||||||||||||
24 | (11-12am) | 100 | 100 | 100 | ||||||||||||
Total/Day | 2400 | 2400 | 2400 | |||||||||||||
Total/Week | 168 | hours | ||||||||||||||
Total/Year | 8760 | hours |
Wk= Weekday | |
1. | Schedules for occupancy, lighting, receptacle, HVAC system and service hot water are from ASHRAE Standard 90.1-1989 and addendums, except that 5% emergency lighting has been added for all off hours. Elevator schedules, except for restaurants, are from the U.S. Department of Energy Standard Evaluation Techniques except changed to 0% when occupancy is 0%. THESE VALUES MAY BE USED ONLY IF ACTUAL SCHEDULES ARE NOT KNOWN. |
TABLE 3-2G
Restaurant Occupancy1
Hour of Day | Schedule for Occupancy Percent of Maximum Load |
Schedule for Lighting Receptacle Percent of Maximum Load |
Schedule for HVAC System |
Schedule for Service Hot Water Percent of Maximum Load |
Schedule for Elevator Percent of Maximum Load |
|||||||||||
(time) | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | |
1 | (12-1am) | 15 | 30 | 20 | 15 | 20 | 20 | on | on | on | 20 | 20 | 25 | 0 | 0 | 0 |
2 | (1-2am) | 15 | 25 | 20 | 15 | 15 | 15 | on | on | on | 15 | 15 | 20 | 0 | 0 | 0 |
3 | (2-3am) | 5 | 5 | 5 | 15 | 15 | 15 | on | on | on | 15 | 15 | 20 | 0 | 0 | 0 |
4 | (3-4am) | 0 | 0 | 0 | 15 | 15 | 15 | off | off | off | 0 | 0 | 0 | 0 | 0 | 0 |
5 | (4-5am) | 0 | 0 | 0 | 15 | 15 | 15 | off | off | off | 0 | 0 | 0 | 0 | 0 | 0 |
6 | (5-6am) | 0 | 0 | 0 | 20 | 15 | 15 | off | off | off | 0 | 0 | 0 | 0 | 0 | 0 |
7 | (6-7am) | 0 | 0 | 0 | 40 | 30 | 30 | off | off | off | 0 | 0 | 0 | 0 | 0 | 0 |
8 | (7-8am) | 5 | 0 | 0 | 40 | 30 | 30 | on | off | off | 60 | 0 | 0 | 0 | 0 | 0 |
9 | (8-9am) | 5 | 0 | 0 | 60 | 60 | 50 | on | off | off | 55 | 0 | 0 | 0 | 0 | 0 |
10 | (9-10am) | 5 | 5 | 0 | 60 | 60 | 50 | on | on | off | 45 | 50 | 0 | 0 | 0 | 0 |
11 | (10-11am) | 20 | 20 | 10 | 90 | 80 | 70 | on | on | on | 40 | 45 | 50 | 0 | 0 | 0 |
12 | (11-12pm) | 50 | 45 | 20 | 90 | 80 | 70 | on | on | on | 45 | 50 | 50 | 0 | 0 | 0 |
13 | (12-1pm) | 80 | 50 | 25 | 90 | 80 | 70 | on | on | on | 40 | 50 | 40 | 0 | 0 | 0 |
14 | (1-2pm) | 70 | 50 | 25 | 90 | 80 | 70 | on | on | on | 35 | 45 | 40 | 0 | 0 | 0 |
15 | (2-3pm) | 40 | 35 | 15 | 90 | 80 | 70 | on | on | on | 30 | 40 | 30 | 0 | 0 | 0 |
16 | (3-4pm) | 20 | 30 | 20 | 90 | 80 | 70 | on | on | on | 30 | 40 | 30 | 0 | 0 | 0 |
17 | (4-5pm) | 25 | 30 | 25 | 90 | 80 | 60 | on | on | on | 30 | 35 | 30 | 0 | 0 | 0 |
18 | (5-6pm) | 50 | 30 | 35 | 90 | 90 | 60 | on | on | on | 40 | 40 | 40 | 0 | 0 | 0 |
19 | (6-7pm) | 80 | 70 | 55 | 90 | 90 | 60 | on | on | on | 55 | 55 | 50 | 0 | 0 | 0 |
20 | (7-8pm) | 80 | 90 | 65 | 90 | 90 | 60 | on | on | on | 60 | 55 | 50 | 0 | 0 | 0 |
21 | (8-9pm) | 80 | 70 | 70 | 90 | 90 | 60 | on | on | on | 50 | 50 | 40 | 0 | 0 | 0 |
22 | (9-10pm) | 50 | 65 | 35 | 90 | 90 | 60 | on | on | on | 55 | 55 | 50 | 0 | 0 | 0 |
23 | (10-11pm) | 35 | 55 | 20 | 50 | 50 | 50 | on | on | on | 45 | 40 | 40 | 0 | 0 | 0 |
24 | (11-12am) | 20 | 35 | 20 | 30 | 30 | 30 | on | on | on | 25 | 30 | 20 | 0 | 0 | 0 |
Total/Day | 750 | 740 | 485 | 1455 | 1365 | 1115 | 2000 | 1800 | 1700 | 790 | 730 | 625 | 0 | 0 | 0 | |
Total/Week | 49.75 | hours | 97.55 | hours | 135 | hours | 53.05 | hours | 0 | hours | ||||||
Total/Year | 2594 | hours | 5086 | hours | 7039 | hours | 2766 | hours | 0 | hours |
Wk= Weekday | |
1. | Schedules for occupancy, lighting, receptacle, HVAC system and service hot water are from ASHRAE Standard 90.1-1989 and addendums, except that 5% emergency lighting has been added for all off hours. Elevator schedules, except for restaurants, are from the U.S. Department of Energy Standard Evaluation Techniques except changed to 0% when occupancy is 0%. THESE VALUES MAY BE USED ONLY IF ACTUAL SCHEDULES ARE NOT KNOWN. |
TABLE 3-2H
Retail Occupancy1
Hour of Day | Schedule for Occupancy Percent of Maximum Load |
Schedule for Lighting Receptacle Percent of Maximum Load |
Schedule for HVAC System |
Schedule for Service Hot Water Percent of Maximum Load |
Schedule for Elevator Percent of Maximum Load |
|||||||||||
(time) | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | |
1 | (12-1am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 4 | 11 | 7 | 0 | 0 | 0 |
2 | (1-2am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 5 | 10 | 7 | 0 | 0 | 0 |
3 | (2-3am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 5 | 8 | 7 | 0 | 0 | 0 |
4 | (3-4am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 4 | 6 | 6 | 0 | 0 | 0 |
5 | (4-5am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 4 | 6 | 6 | 0 | 0 | 0 |
6 | (5-6am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 4 | 6 | 6 | 0 | 0 | 0 |
7 | (6-7am) | 0 | 0 | 0 | 5 | 5 | 5 | on | on | off | 4 | 7 | 7 | 0 | 0 | 0 |
8 | (7-8am) | 10 | 10 | 0 | 20 | 10 | 5 | on | on | off | 15 | 20 | 10 | 12 | 9 | 0 |
9 | (8-9am) | 20 | 20 | 0 | 50 | 30 | 10 | on | on | on | 23 | 24 | 12 | 22 | 21 | 0 |
10 | (9-10am) | 50 | 50 | 10 | 90 | 60 | 10 | on | on | on | 32 | 27 | 14 | 64 | 56 | 11 |
11 | (10-11am) | 50 | 60 | 20 | 90 | 90 | 40 | on | on | on | 41 | 42 | 29 | 74 | 66 | 13 |
12 | (11-12pm) | 70 | 80 | 20 | 90 | 90 | 40 | on | on | on | 57 | 54 | 31 | 68 | 68 | 35 |
13 | (12-1pm) | 70 | 80 | 40 | 90 | 90 | 60 | on | on | on | 62 | 59 | 36 | 68 | 68 | 37 |
14 | (1-2pm) | 70 | 80 | 40 | 90 | 90 | 60 | on | on | on | 61 | 60 | 36 | 71 | 69 | 37 |
15 | (2-3pm) | 70 | 80 | 40 | 90 | 90 | 60 | on | on | on | 50 | 49 | 34 | 72 | 70 | 39 |
16 | (3-4pm) | 80 | 80 | 40 | 90 | 90 | 60 | on | on | on | 45 | 48 | 35 | 72 | 69 | 41 |
17 | (4-5pm) | 70 | 80 | 40 | 90 | 90 | 60 | on | on | on | 46 | 47 | 37 | 73 | 66 | 38 |
18 | (5-6pm) | 50 | 60 | 20 | 90 | 90 | 40 | on | on | off | 47 | 46 | 34 | 68 | 58 | 34 |
19 | (6-7pm) | 50 | 20 | 10 | 60 | 50 | 20 | on | on | off | 42 | 44 | 25 | 68 | 47 | 3 |
20 | (7-8pm) | 30 | 20 | 0 | 60 | 30 | 5 | on | on | off | 34 | 36 | 27 | 58 | 43 | 0 |
21 | (8-9pm) | 30 | 20 | 0 | 50 | 30 | 5 | on | on | off | 33 | 29 | 21 | 54 | 43 | 0 |
22 | (9-10pm) | 0 | 10 | 0 | 20 | 10 | 5 | off | on | off | 23 | 22 | 16 | 0 | 8 | 0 |
23 | (10-11pm) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 13 | 16 | 10 | 0 | 0 | 0 |
24 | (11-12am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 8 | 13 | 6 | 0 | 0 | 0 |
Total/Day | 720 | 750 | 280 | 1115 | 985 | 525 | 1500 | 1600 | 900 | 662 | 690 | 459 | 844 | 761 | 288 | |
Total/Week | 46.30 | hours | 70.85 | hours | 100 | hours | 44.59 | hours | 52.69 | hours | ||||||
Total/Year | 2414 | hours | 3694 | hours | 5214 | hours | 2325 | hours | 2747 | hours |
Wk= Weekday | |
1. | Schedules for occupancy, lighting, receptacle, HVAC system and service hot water are from ASHRAE Standard 90.1-1989 and addendums, except that 5% emergency lighting has been added for all off hours. Elevator schedules, except for restaurants, are from the U.S. Department of Energy Standard Evaluation Techniques except changed to 0% when occupancy is 0%. THESE VALUES MAY BE USED ONLY IF ACTUAL SCHEDULES ARE NOT KNOWN. |
TABLE 3-2I
School Occupancy1
Hour of Day | Schedule for Occupancy Percent of Maximum Load |
Schedule for Lighting Receptacle Percent of Maximum Load |
Schedule for HVAC System |
Schedule for Service Hot Water Percent of Maximum Load |
Schedule for Elevator Percent of Maximum Load |
|||||||||||
(time) | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | |
1 | (12-1am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 5 | 3 | 3 | 0 | 0 | 0 |
2 | (1-2am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 5 | 3 | 3 | 0 | 0 | 0 |
3 | (2-3am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 5 | 3 | 3 | 0 | 0 | 0 |
4 | (3-4am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 5 | 3 | 3 | 0 | 0 | 0 |
5 | (4-5am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 5 | 3 | 3 | 0 | 0 | 0 |
6 | (5-6am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 5 | 3 | 3 | 0 | 0 | 0 |
7 | (6-7am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 5 | 3 | 3 | 0 | 0 | 0 |
8 | (7-8am) | 5 | 0 | 0 | 30 | 5 | 5 | on | off | off | 10 | 3 | 3 | 0 | 0 | 0 |
9 | (8-9am) | 75 | 10 | 0 | 85 | 15 | 5 | on | on | off | 34 | 3 | 5 | 30 | 0 | 0 |
10 | (9-10am) | 90 | 10 | 0 | 95 | 15 | 5 | on | on | off | 60 | 5 | 5 | 30 | 0 | 0 |
11 | (10-11am) | 90 | 10 | 0 | 95 | 15 | 5 | on | on | off | 63 | 5 | 5 | 30 | 0 | 0 |
12 | (11-12pm) | 80 | 10 | 0 | 95 | 15 | 5 | on | on | off | 72 | 5 | 5 | 30 | 0 | 0 |
13 | (12-1pm) | 80 | 10 | 0 | 80 | 15 | 5 | on | on | off | 79 | 5 | 5 | 30 | 0 | 0 |
14 | (1-2pm) | 80 | 0 | 0 | 80 | 5 | 5 | on | off | off | 83 | 3 | 5 | 30 | 0 | 0 |
15 | (2-3pm) | 80 | 0 | 0 | 80 | 5 | 5 | on | off | off | 61 | 3 | 3 | 30 | 0 | 0 |
16 | (3-4pm) | 45 | 0 | 0 | 70 | 5 | 5 | on | off | off | 65 | 3 | 3 | 15 | 0 | 0 |
17 | (4-5pm) | 15 | 0 | 0 | 50 | 5 | 5 | on | off | off | 10 | 3 | 3 | 0 | 0 | 0 |
18 | (5-6pm) | 5 | 0 | 0 | 50 | 5 | 5 | on | off | off | 10 | 3 | 3 | 0 | 0 | 0 |
19 | (6-7pm) | 15 | 0 | 0 | 35 | 5 | 5 | on | off | off | 19 | 3 | 3 | 0 | 0 | 0 |
20 | (7-8pm) | 20 | 0 | 0 | 35 | 5 | 5 | on | off | off | 25 | 3 | 3 | 0 | 0 | 0 |
21 | (8-9pm) | 20 | 0 | 0 | 35 | 5 | 5 | on | off | off | 22 | 3 | 3 | 0 | 0 | 0 |
22 | (9-10pm) | 10 | 0 | 0 | 30 | 5 | 5 | on | off | off | 22 | 3 | 3 | 0 | 0 | 0 |
23 | (10-11pm) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 12 | 3 | 3 | 0 | 0 | 0 |
24 | (11-12am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 9 | 3 | 3 | 0 | 0 | 0 |
Total/Day | 710 | 50 | 0 | 990 | 170 | 120 | 1500 | 500 | 0 | 691 | 80 | 84 | 285 | 0 | 0 | |
Total/Week | 36.00 | hours | 52.40 | hours | 80.00 | hours | 36.19 | hours | 14.25 | hours | ||||||
Total/Year | 1877 | hours | 2732 | hours | 4171 | hours | 1887 | hours | 743 | hours |
Wk= Weekday | |
1. | Schedules for occupancy, lighting, receptacle, HVAC system and service hot water are from ASHRAE Standard 90.1-1989 and addendums, except that 5% emergency lighting has been added for all off hours. Elevator schedules, except for restaurants, are from the U.S. Department of Energy Standard Evaluation Techniques except changed to 0% when occupancy is 0%. THESE VALUES MAY BE USED ONLY IF ACTUAL SCHEDULES ARE NOT KNOWN. |
TABLE 3-2J
Warehouse Occupancy1
Hour of Day | Schedule for Occupancy Percent of Maximum Load |
Schedule for Lighting Receptacle Percent of Maximum Load |
Schedule for HVAC System |
Schedule for Service Hot Water Percent of Maximum Load |
Schedule for Elevator Percent of Maximum Load |
|||||||||||
(time) | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | Wk | Sat | Sun | |
1 | (12-1am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 2 | 2 | 2 | 0 | 0 | 0 |
2 | (1-2am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 2 | 2 | 2 | 0 | 0 | 0 |
3 | (2-3am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 2 | 2 | 2 | 0 | 0 | 0 |
4 | (3-4am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 2 | 2 | 2 | 0 | 0 | 0 |
5 | (4-5am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 5 | 2 | 2 | 0 | 0 | 0 |
6 | (5-6am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 7 | 2 | 2 | 0 | 0 | 0 |
7 | (6-7am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 7 | 2 | 2 | 0 | 0 | 0 |
8 | (7-8am) | 15 | 0 | 0 | 40 | 5 | 5 | on | off | off | 10 | 2 | 2 | 0 | 0 | 0 |
9 | (8-9am) | 70 | 20 | 0 | 70 | 8 | 5 | on | on | off | 30 | 6 | 2 | 0 | 0 | 0 |
10 | (9-10am) | 90 | 20 | 0 | 90 | 24 | 5 | on | on | off | 36 | 12 | 2 | 0 | 0 | 0 |
11 | (10-11am) | 90 | 20 | 0 | 90 | 24 | 5 | on | on | off | 36 | 12 | 2 | 30 | 0 | 0 |
12 | (11-12pm) | 90 | 20 | 0 | 90 | 24 | 5 | on | on | off | 46 | 17 | 2 | 0 | 0 | 0 |
13 | (12-1pm) | 50 | 10 | 0 | 80 | 5 | 5 | on | on | off | 57 | 4 | 4 | 0 | 0 | 0 |
14 | (1-2pm) | 85 | 10 | 0 | 90 | 5 | 5 | on | on | off | 43 | 4 | 4 | 0 | 0 | 0 |
15 | (2-3pm) | 85 | 10 | 0 | 90 | 5 | 5 | on | on | off | 38 | 2 | 2 | 0 | 0 | 0 |
16 | (3-4pm) | 85 | 10 | 0 | 90 | 5 | 5 | on | on | off | 40 | 2 | 2 | 40 | 0 | 0 |
17 | (4-5pm) | 20 | 0 | 0 | 90 | 5 | 5 | on | off | off | 30 | 2 | 2 | 0 | 0 | 0 |
18 | (5-6pm) | 0 | 0 | 0 | 30 | 5 | 5 | off | off | off | 18 | 2 | 2 | 0 | 0 | 0 |
19 | (6-7pm) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 3 | 2 | 2 | 0 | 0 | 0 |
20 | (7-8pm) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 3 | 2 | 2 | 0 | 0 | 0 |
21 | (8-9pm) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 3 | 2 | 2 | 0 | 0 | 0 |
22 | (9-10pm) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 3 | 2 | 2 | 0 | 0 | 0 |
23 | (10-11pm) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 3 | 2 | 2 | 0 | 0 | 0 |
24 | (11-12am) | 0 | 0 | 0 | 5 | 5 | 5 | off | off | off | 3 | 2 | 2 | 0 | 0 | 0 |
Total/Day | 680 | 120 | 0 | 915 | 180 | 120 | 1000 | 800 | 0 | 429 | 91 | 52 | 70 | 0 | 0 | |
Total/Week | 35.20 | hours | 48.75 | hours | 58.00 | hours | 22.88 | hours | 3.50 | hours | ||||||
Total/Year | 1835 | hours | 2542 | hours | 3024 | hours | 1193 | hours | 182 | hours |
Wk= Weekday | |
1. | Schedules for occupancy, lighting, receptacle, HVAC system and service hot water are from ASHRAE Standard 90.1-1989 and addendums, except that 5% emergency lighting has been added for all off hours. Elevator schedules, except for restaurants, are from the U.S. Department of Energy Standard Evaluation Techniques except changed to 0% when occupancy is 0%. THESE VALUES MAY BE USED ONLY IF ACTUAL SCHEDULES ARE NOT KNOWN. |
TABLE 3-3
HVAC Systems of Prototype Buildings3
Use | System # | Remarks |
1. Assembly | ||
a. Churches (any size) | 1 | |
b. ≤ 50,000 ft2 or ≤ 3 floors | 1 or 3 | Note 2 |
c. > 50,000 ft2 or > 3 floors | 3 | |
2. Health | ||
a. Nursing Home (any size) | 2 | |
b. ≤ 15,000 ft2 | 1 | |
c. > 15,000 ft2 and ≤ 50,000 ft2 | 4 | Note 3 |
d. > 50,000 ft2 | 5 | Note 3,4 |
3. Hotel/Motel | ||
a. ≤ 3 Stories | 2 | Note 6 |
b. > 3 Stories | 6 | Note 7 |
4. Light Manufacturing | 1 or 3 | |
5. Office | ||
a. ≤ 20,000 ft2 | 1 | |
b. > 20,000 ft2 and either ≤ 3 floors or ≤ 75,000 ft2 |
4 | |
c. > 75,000 ft2 or > 3 floors | 5 | |
6. Restaurant | 1 or 3 | Note 2 |
7. Retail | ||
a. ≤ 50,000 ft2 | 1 or 3 | Note 2 |
b. > 50,000 ft2 | 4 or 5 | Note 2 |
8. Schools | ||
a. ≤ 75,000 ft2 or ≤ 3 floors | 1 | |
b. > 75,000 ft2 or > 3 floors | 3 | |
9. Warehouse | Note 5 |
TABLE 3-3 (cont.)
HVAC System Descriptions for Prototype Buildings1
HVAC Component | System #1 | System #2 | |
System Description | Packaged rooftop single zone, one unit per zone. | Packaged terminal air conditioner with space heater or heat pump, heating or cooling unit per zone. | |
Fan System | |||
Design Supply | Note 10 | Note 11 | |
Circulation Rate | |||
Supply Fan Control | Constant volume. | Fan cycles with call for heating or cooling. | |
Return Fan Control | N.A. | N.A. | |
Cooling System | Direct expansion air cooled | Direct expansion air cooled. | |
Heating System | Furnace, heat pump, or electric resistance. | Heat pump with electric resistance auxiliary or air conditioner with space heater. | |
Remarks | Drybulb economizer per Section 1433, heat recovery if required by Section 1436. | No economizer, if not required by Section 1433. |
TABLE 3-3 (cont.)
HVAC Systems Descriptions for Prototype Buildings1
HVAC Component | System #3 | System #4 | |
System Description | Air handler per zone with central plant. | Packaged rooftop VAV with perimeter reheat and fan-powered terminal units. | |
Fan System | |||
Design Supply | Note 10 | Note 10 | |
Circulation Rate | |||
Supply Fan Control | Constant volume. | VAV with forward curved centrifugal fan and variable inlet fans. | |
Return Fan Control | Constant volume. | VAV with forward curved centrifugal fan and discharge dampers. | |
Cooling System | Chilled water (Note 12) | Direct expansion air cooled. | |
Heating System | Hot water (Note 13) | Hot water (Note 13) or electric resistance. | |
Remarks | Drybulb economizer per Section 1433, heat recovery if required by Section 1436. | Drybulb economizer per Section 1433. Minimum VAV setting per Section 1435 Exception 1, Supply air reset by zone of greatest cooling demand, heat recovery if required by Section 1436. |
TABLE 3-3 (cont.)
HVAC System Descriptions for Prototype Buildings1
HVAC Component | System #5 | System #6 | |
System Description | Built-up central VAV with perimeter reheat and fan-powered terminal units | Four-pipe fan coil per zone with central plant. | |
Fan System | |||
Design Supply | Note 10 | Note 10 | |
Circulation Rate | |||
Supply Fan Control | VAV with air-foil centrifugal fan and AC frequency variable speed drive. | Fan cycles with call for heating or cooling. | |
Return Fan Control | VAV with air-foil centrifugal fan and AC frequency variable speed drive. | NA | |
Cooling System | Chilled water (Note 12) | Chilled water (Note 12) | |
Heating System | Hot water (Note 13) or electric resistance. | Hot water (Note 13) or electric resistance. | |
Remarks | Drybulb economizer per Section 1433. Minimum VAV setting per Section 1435 Exception 1, Supply air rest by zone of greatest cooling demand, heat recovery if required by Section 1436. | No economizer, if not required by Section 1433. |
HVAC System Descriptions for Prototype Buildings
1. | The systems and energy types presented in this Table are not intended as requirements or recommendations for the proposed design. |
2. | For occupancies such as restaurants, assembly and retail that are part of a mixed use building which, according to Table 3-3, includes a central chilled water plant (systems 3, 5, or 6), chilled water system type 3 or 5 shall be used as indicated in the table. |
3. | Constant volume may be used in zones where pressurization relationships must be maintained by code.
Where constant volume is used, the system shall have heat recovery if required by Section 1436. VAV
shall be used in all other areas, in accordance with Sections 1432 through (( |
4. | Provide run-around heat recovery systems for all fan systems with a minimum outside air intake greater than 70%. Recovery effectiveness shall be 0.50. |
5. | If a warehouse is not intended to be mechanically cooled, both the standard and proposed designs shall be calculated assuming no mechanical cooling. |
6. | The system listed is for guest rooms only. Areas such as public areas and back-of-house areas shall be served by system 4. Other areas such as offices and retail shall be served by systems listed in Table 3-3 for these occupancy types. |
7. | The system listed is for guest rooms only. Areas such as public areas and back-of-house areas shall be served by system 5. Other areas such as offices and retail shall be served by systems listed in Table 3-3 for these occupancy types. |
8. | Reserved. |
9. | Reserved. |
10. | Design supply air circulation rate shall be based on a supply-air-to-room air temperature difference of 20F. A higher supply air temperature may be used if required to maintain a minimum circulation rate of 4.5 air changes per hour or 15 cfm per person to each zone served by the system, at design conditions. If return fans are specified, they shall be sized for the supply fan capacity less the required minimum ventilation with outside air, or 75% of the supply fan capacity, whichever is larger. Except where noted, supply and return fans shall be operated continuously during occupied hours. |
11. | Fan energy when included in the efficiency rating of the unit as defined in Section 1411, need not be modeled explicitly for this system. The fan shall cycle with calls for heating or cooling. |
12. | Chilled water systems shall be modeled using a reciprocating chiller for systems with total cooling capacities less than 175 tons, and centrifugal chillers for systems with cooling capacities of 175 tons or greater. For systems with cooling capacities of 600 tons or more, the standard design energy consumption shall be calculated using two centrifugal chillers, lead/lag controlled. Chilled water shall be assumed to be controlled at a constant 44F. Chiller water pumps shall be sized using a 12F temperature rise, from 44F to 56F, operating at 65% combined impeller and motor efficiency. Condenser water pumps shall be sized using a 10F temperature rise, operating at 60% combined impeller and motor efficiency. The cooling tower shall be an open circuit, centrifugal blower type sized for the larger of 85F leaving water temperature or 10F approach to design wetbulb temperature. The tower shall be controlled to provide a 65F leaving water temperature whenever weather conditions permit, floating up to design leaving water temperatures at design conditions. Chilled water supply temperature shall be reset in accordance with Section 1432.2.2. |
13. | Hot water system shall include a natural draft fossil fuel or electric boiler. The hot water pump shall be sized based on a 30F temperature drop, from 180F to 150F, operating at a combined impeller and motor efficiency of 60%. Hot water supply temperature shall be reset in accordance with Section 1432.2.2. |
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-99903, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-99903, filed 10/18/93, effective 4/1/94.]
((4.1 Programs Acceptable for Projects for Full-Year Hourly
Analysis))
Program Name | Source |
ADM Associates 3239 Ramos Circle Sacramento, CA 95827 916-363-8383)) |
|
Blast 3.0 (Level (( |
Blast Support Office University of Illinois Dept. of Mechanical and Industrial Engineering 1206 W. Green Street, Room (( Urbana, IL 61801 (( (217) 244-8182 |
DOE 2.1E | Energy Science and Technology Software Center (ESTSC) PO Box 1220 Oakridge, TN 37831-1020 423-576-2606 |
DOE 2.1E or DOE 2.2 | James J. Hirsch & Associates Building Performance Analysis Software & Consulting 12185 Presilla Road Camarillo, CA 93012-9243 (805) 532-1045 |
EnergyPlus | Kathy Ellington Lawrence Berkeley National Laboratory (LBNL) Building 90, Room 3147 Berkeley, CA 94720-0001 (510) 486-5711 |
ESAS | Ross Meriweather Consulting, Engineering 3315 Outrider San Antonio, TX 78247-4405 210-490-7081 |
ESP-II | Automated Procedures for
Engineering Consultants, Inc. 40 W. 4th Centre, Suite 2100 Dayton, OH 45402 937-228-2602 |
HAP (( |
Carrier Building Systems and Services 3215 South 116th St., Suite 133 Tukwila, WA 98168 (206)-439-0097 |
ACROSOFT/CAER 1204-1/2 Washington Avenue Golden, CO 80401 303-279-8136)) |
|
Trace 600 Version
(( |
The Trane Co. 3600 Pammel Creek Rd. Lacrosse, WI 54601 608-787-3926 |
3239 Ramos Circle Sacramento, CA 95827 916-363-8383 |
|
Clearinghouse 1(800) DOE-EREC (363-3732) |
|
Analysis and Easy DOE |
PO Drawer 1194 Bryan, TX 77806 409-846-2340 |
5100 W. 82nd St., Suite 204 Bloomington, MN 55437 612-844-8000 |
|
2855 Telegraph Ave., Suite 410 Berkeley, CA 94705 510-848-8400 |
|
XENERGY 492 9th Street, Suite 220 Oakland, CA 94607 510-891-0446)) |
[Statutory Authority: RCW 19.27A.025 and 19.27A.045. 98-03-003, 51-11-99904, filed 1/8/98, effective 7/1/98. Statutory Authority: RCW 19.27A.025. 93-21-052, 51-11-99904, filed 10/18/93, effective 4/1/94.]
The following sections of the Washington Administrative Code are repealed:
WAC 51-11-1201 | Scope. |
WAC 51-11-1210 | Application of terms. |
WAC 51-11-1701 | Scope. |
WAC 51-11-2000 | Default heat-loss coefficients. |
WAC 51-11-2001 | General. |
WAC 51-11-2002 | Below grade walls and slabs. |
WAC 51-11-2003 | On-grade slab floors. |
WAC 51-11-2004 | Floors over unconditioned space. |
WAC 51-11-2005 | Above grade walls. |
WAC 51-11-2006 | Default U-factors for glazing and doors. |
WAC 51-11-2007 | Ceilings. |
WAC 51-11-2008 | Reserved. |
WAC 51-11-2009 | Mass. |