WSR 97-01-042
EMERGENCY RULES
BUILDING CODE COUNCIL
[Filed December 11, 1996, 11:08 a.m.]
Date of Adoption: December 4, 1996.
Purpose: Emergency adoption of amendments to the 1994 Editions of the Uniform Mechanical Code, Sections 1118 and 1119, and the Uniform Fire Code, Sections 6308 and 6309, relating to the discharge of ammonia refrigerant.
Citation of Existing Rules Affected by this Order: Amending chapters 51-32 and 51-34 WAC.
Statutory Authority for Adoption: RCW 19.27.074.
Under RCW 34.05.350 the agency for good cause finds that immediate adoption, amendment, or repeal of a rule is necessary for the preservation of the public health, safety, or general welfare, and that observing the time requirements of notice and opportunity to comment upon adoption of a permanent rule would be contrary to the public interest.
Reasons for this Finding: The State Building Code Council (council), based on the following good cause, finds that an emergency affecting the general welfare of the state of Washington exists. The council further finds that immediate amendment of certain council rules is necessary for the public welfare and that observing the time requirements of notice and opportunity to comment would be contrary to the public interest.
The declaration of emergency affecting the general welfare of the state of Washington is based on the following findings:
The Washington state amendments to the Uniform Mechanical Code (UMC) and Uniform Fire Code (UFC) contained herein as adopted by the council under emergency rule making pursuant to RCW 34.05.350, will provide economic relief to the agricultural industry by allowing alternative methods of ammonia discharge treatment in cold storage facilities. Immediate adoption of this amendment is necessary so as to not delay the construction of cold storage facilities, and so as not to adversely affect the position of the state's agricultural industry in the marketplace.
Under rules contained in the 1994 UMC and 1994 UFC, mechanical system requirements for ammonia discharge treatment would result in undue expense. The council finds this to be an economic burden on the agricultural industry, which will result in an increase in cost of fruits, vegetables and other products which are dependent upon cold storage. This increased cost would inhibit the ability of the state's agricultural industry to compete in the national and international markets, and would create higher food costs for this state's consumers, and would put this season's crop at risk.
The council appointed a technical advisory group (TAG) comprised of building officials, fire officials, members of the agricultural industry, mechanical systems engineers, cold storage facility owners and operators, and chaired by the council's fire chief representative. The TAG developed the language in the amendment contained herein. This amendment takes into consideration the health and safety of the public. In order to provide immediate relief, the council finds it necessary to adopt the amendment as an emergency rule. The council also has taken the necessary steps to adopt a permanent rule. The permanent rule will not be effective until the end of the 1997 legislative session as per RCW 19.27.074.
The council process for amendment of this rule was initiated by the action of the 1996 legislature and Governor Mike Lowry. The 1996 legislature passed by unanimous vote SHB 2936. The language of the bill is as follows:
"AN ACT Relating to fruit and vegetable storage; adding a new
section to chapter 19.27 RCW.
BE IT ENACTED BY THE LEGISLATURE OF THE STATE OF WASHINGTON:
NEW SECTION. Sec. 1. A new section is added to chapter 19.27 RCW
to read as follows:
(1) Cold storage warehouses and controlled atmosphere storage warehouses used to store fruit or vegetables are not required to comply with any requirements of sections 1118 and 1119 of the uniform mechanical code, as adopted by the state building code council, or sections 6308 and 6309 of the uniform fire code, as adopted by the state building code council, or with any requirements of local amendments adopted to these sections of the uniform mechanical code and uniform fire code.
(2) The state building code council shall adopt rules consistent
with this section."
Governor Mike Lowry, on March 30, 1996, vetoed the bill, with the provision that the council "take appropriate action immediately" to resolve this issue. The veto message reads as follows:
"I am returning herewith, without my approval, Substitute House Bill No. 2936 entitled:
'AN ACT Relating to fruit and vegetable storage;'
Substitute House Bill No. 2936 attempts to resolve a highly complex and technical issue regarding regulation of ammonia refrigerants. It would exempt refrigeration systems using ammonia in cold storage and controlled atmosphere warehouses used to store fruit and vegetables from certain portions of the Uniform Mechanical Code and the Uniform Fire Code, as adopted by the Building Code Council.
In general, I believe the interests of the public and of the legislature are best served if these issues are handled through the Building Code Council. The council has a grasp of the technical issues associated with code policies that neither the legislature nor the governor possess. The Building Code Council was, in fact, created to minimize the need to address highly technical building code issues in the legislative arena. The existing process should be used.
Process notwithstanding, I am not convinced that the health and safety of the public will be adequately protected if Substitute House Bill No. 2936 become law. If these types of refrigeration systems are exempt from code requirements, densely populated areas could be exposed to an unacceptable risk of ammonia gas releases in case of fire or other mishap.
However, I do not believe the specific mitigation that has been required in some instances under the 1994 Building Code is necessary to protect the health and safety of the public. In rural, sparsely populated areas of the state, sparsely populated by definition, a release of ammonia into the atmosphere would not seem to pose a hazard in many instances.
I believe that an opportunity exists to address the concerns which resulted in this bill and to ensure that public safety issues receive adequate attention in the state building code. Therefore, I am directing the Building Code Council to examine the issues raised in this legislation and to take appropriate action immediately to include drafting amendments to the current state mechanical and fire codes.
I am impressed by the fruit and vegetable storage industry's 95 year record of safe use of ammonia as a refrigerant. This record should be considered as the Building Code Council and other interested parties proceed to examine this issue.
For these reasons, I have vetoed Substitute House Bill No. 2936 in its entirety."
The Washington state amendments adopted by this emergency rule will allow for other viable alternatives to be submitted to the building and fire officials for consideration when new cold storage systems are being constructed.
The council therefore adopts emergency rules under RCW 34.05.350 Emergency rules and amendments, which are proposed below.
Number of Sections Adopted in Order to Comply with Federal Statute: New 0, amended 0, repealed 0; Federal Rules or Standards: New 0, amended 0, repealed 0; or Recently Enacted State Statutes: New 0, amended 0, repealed 0.
Number of Sections Adopted at Request of a Nongovernmental Entity: New 0, amended 0, repealed 0.
Number of Sections Adopted on the Agency's own Initiative: New 0, amended 0, repealed 0.
Number of Sections Adopted in Order to Clarify, Streamline, or Reform Agency Procedures: New 0, amended 0, repealed 0.
Number of Sections Adopted using Negotiated Rule Making: New 0, amended 0, repealed 0; Pilot Rule Making: New 0, amended 0, repealed 0; or Other Alternative Rule Making: New 4, amended 0, repealed 0.
Effective Date of Rule: Immediately.
December 4, 1996
James R. Beaver
Chair
[NEW SECTION]
WAC 51-32-1118 Special Discharge Requirements
1118.1 General. Systems containing other than Group A1 or B1
refrigerants shall discharge to atmosphere only through an approved
flaring device. For treatment system requirements, see also the Fire
Code.
Exceptions:
1. Ammonia systems complying with Section 1119.
2. Ammonia absorption systems serving a single dwelling unit.
3. When the building official determines upon review of a rational engineering analysis that significant fire, health or environmental hazard would not result from the proposed atmospheric release.
4. Lithium bromide absorption system using water as the refrigerant.
1118.2 Design Requirements. Flaring devices shall be designed to
incinerate the entire discharge. The products of refrigerant
incineration shall not pose health or environmental hazards.
Incineration shall be automatic upon initiation of discharge, shall be
designed to prevent blowback and shall not expose structures or materials
to threat of fire. Standby fuel, such as LP-gas, and standby power shall
have the capacity to operate for one and one half the required time for
complete incineration of the charge.
1118.3 Testing. Flaring systems shall be tested to demonstrate their
safety and effectiveness. A report from an approved agency shall be
submitted detailing the emission products from the system as installed.
[]
Reviser's note: The bracketed material preceding the section above
was supplied by the code reviser's office.
[NEW SECTION]
WAC 51-32-1119 Ammonia Discharge
Emergency discharge for ammonia refrigeration systems shall be in
accordance with either Section 1119.1 or Section 1119.2.
1119.1 Ammonia systems shall be provided with an emergency discharge
into a tank of water provided exclusively for ammonia absorption. Such
systems shall meet national standards.
Exception: An emergency discharge is not required for ammonia-water
absorption unit systems installed outdoors provided that the
discharge is shielded and dispersed.
1119.2 Ammonia discharge to atmosphere without a flaring device is
allowed unless the Building Official, upon review of the permit
application and submittals, finds that such a discharge method may
reasonably result in discharge of concentrations exceeding 500 ppm at
grade level and present a significant life hazard to exposed occupancies.
The Building Official may require an approved engineering analysis
showing that:
Concentrations exceeding 500 ppm at grade level do not present a
significant life hazard to exposed occupancies.
The engineering analysis may include the following:
1. Quantity and rate of material expected to be discharged.
2. Weather conditions such as wind speed, wind direction,
humidity, and temperature inversion.
3. Emergency response planning.
4. Design benefits limiting discharge.
[]
Reviser's note: The bracketed material preceding the section above
was supplied by the code reviser's office.
[NEW SECTION]
WAC 51-34-6308 Special Discharge Requirements
6308.1 General.
6308.1.1 Applicability. Refrigeration systems which are designed to
discharge refrigerant vapor to atmosphere shall be provided with an
approved treatment or flaring system when required by Section 6308.1.
Also see Section 6314.1.
Exceptions: 1. Ammonia systems complying with Section 6309.
2. Ammonia absorption systems serving a single dwelling unit.
3. When the building official determines upon review of a rational engineering analysis that significant fire, health or environmental hazard would not result from the proposed atmospheric release.
4. Lithium bromide absorption system using water as the refrigerant.
6308.1.2 Toxic and highly toxic refrigerants. Systems containing
refrigerants which are toxic or highly toxic shall discharge vapor to
atmosphere only through an approved treatment system. Treatment systems
shall be in accordance with Sections 8003.3.1.3.5.1, 8003.3.1.3.5.2 and
8003.3.1.3.5.3.
6308.1.3 Flammable refrigerants. Systems containing refrigerants which
are flammable shall discharge vapor to the atmosphere only through an
approved treatment or flaring system. Flaring systems shall be in
accordance with Section 6308.2.
6308.2 Flaring System Design Requirements. Flaring systems for
incineration of flammable refrigerants shall be designed to incinerate
the entire discharge. The products of refrigerant incineration shall not
pose health or environmental hazards. Incineration shall be automatic
upon initiation of discharge, shall be designed to prevent blowback, and
shall not expose structures or materials to threat of fire. Standby
fuel, such as LP-gas, and standby power shall have the capacity to
operate for one and one half the required time for complete incineration
of refrigerant in the system.
[]
Reviser's note: The bracketed material preceding the section above
was supplied by the code reviser's office.
[NEW SECTION]
WAC 51-34-6309 Ammonia Discharge
Emergency discharge for ammonia refrigeration systems shall be in
accordance with either Section 6309.1 or Section 6309.2.
6309.1 Ammonia refrigeration systems shall be provided with an emergency
discharge into a tank of water provided exclusively for ammonia
absorption. Such systems shall meet national standards.
Exception: An emergency discharge is not required for ammonia-water
absorption unit systems installed outdoors provided that the discharge
is shielded and dispersed.
6309.2 Ammonia discharge to atmosphere without a flaring device is
allowed unless the Chief, upon review of the permit application and
submittals, finds that such a discharge method may reasonably result in
discharge of concentrations exceeding 500 ppm at grade level and present
a significant life hazard to exposed occupancies. The Chief may require
an approved engineering analysis showing that:
Concentrations exceeding 500 ppm at grade level do not present a
significant life hazard to exposed occupancies.
The engineering analysis may include the following:
1. Quantity and rate of material expected to be discharged.
2. Weather conditions such as wind speed, wind direction,
humidity, and temperature inversion.
3. Emergency response planning.
4. Design benefits limiting discharge.
[]
Reviser's note: The bracketed material preceding the section above was supplied by the code reviser's office.